Академический Документы
Профессиональный Документы
Культура Документы
TAMM &
SANJAY VIJAYARAGHAVAN
PETER E. JENKINS (1st
EDITION MANUAL)
Chapter 2 W sin
D=
Fundamentals of Solar Radiation tan 12
At winter solstice, the solar declination is its lowest
2.1 at s = -23.45, which can be confirmed by solving
Given: L = 40.77N, Solar Time = 2:00 PM Eq. (2.23). The hour angle at solar noon is hs = 0.
Find: s , z, as From Eq. (2.28),
sin 12 = sin L sin s + cos L cos s
From Eq. (2.23), with n = 274, 12 = 36.87
s = 23.45 sin 360 ( 284 + 274 ) 365 With the tilt angle fixed, the distance separating the
s = 4.22 two rows is now fixed at
sin 30 2
From Eq. (2.25), D =W = W
hs = 15 ( 2) = 30 tan 36.87 3
At 9 AM on Dec 21, the hour angle is hs = -45 and
From Eq. (2.28),
from Eq. (2.28),
sin = sin L sin s + cos L cos s cos hs
sin 9 = sin L sin s + cos L cos s cos hs ,9
= 37.3
From Eq. (2.24), 9 = 21.5
z = 90 = 52.7 As the sun is not due south, the angle as shown in
From Eq. (2.29), the diagram is
sin as = cos s sin hs cos tan 9 = tan 9 cos as ,9
as = 38.8 With the solar azimuth angle from Eq. (2.29) as
sin as ,9 = cos s sin hs ,9 cos 9
as ,9 = 44.2
2.2 which gives the south projected altitude angle at 9
Given: L = 29.68N Gainesville, south facing east- AM as
west collectors, tilt = 30, Dec 21 9 = 28.8
Find: Minimum distance between rows at solar As before, but with a 9 AM sun, the geometry gives
noon for no shading and % shading at W sin
9 AM with same separation. D+x =
tan 9
such that x is given as
1 1
x = W sin
tan 9 tan 12
From the tangent rule,
x + Ws 180 180 2 9
= tan tan
x Ws 2 2
Combining the last two relations,
Ws 1 1
= sin
W tan 9 tan 12
180 180 2 9
tan 2 tan
From the above geometry,
b 2
tan 12 = g
D 180 180 2 9
tan 2 + tan
b 2
sin =
W The percent shaded is therefore 13.7%.
Combining, the minimum distance for no shading is Notes:
This assumes that the rows are very long, so that at The unit directional for the sun can be written in
9 AM although the easternmost part of the back row terms of an East-North-Vertical coordinate system.
is not shaded, this changes the overall shading s = cos sin as E + cos cos as N sin V
percentage very little.
Similarly for the panel normal,
p = cos ( 90 ) sin ( aw ) E
2.3 cos ( 90 ) cos ( aw ) N
Given: Sep 1
Find: Sunrise and sunset time for a selected + sin ( 90 ) V
location p = sin sin aw E sin cos aw N + cos V
The scalar product of the two is
With n = 244, the declination is given by Eq. (2.23)
cos i = s n
s = 23.45 sin 360 ( 284 + 244 ) 365
= cos sin as sin sin aw
s = 7.72
+ cos cos as sin cos aw
With the latitude of the location known, Eq. (2.30)
gives the sunrise and sunset times as + sin cos
hss or hsr = cos 1 [ tan L tan s ] Combining terms and using an identity, Eq. (2.44)
results as
These are hour angles, so the corresponding solar
cos i = cos sin cos ( as aw ) + sin cos
times for sunrise and sunset are
Sunrise time = 12 : 00 Noon + hsr ( 4min/degree ) Notes:
The identity used was
Sunset time = 12 : 00 Noon + hss ( 4min/degree )
cos ( x y ) = cos x cos y m sin x sin y
The local standard time is found from Eq. (2.26) as
LST = Solar Time ET ( lst llocal ) 4min degree
where the equation of time is from Eq. (2.27) as 2.6
ET = 9.87 sin 2 B 7.53cos B 1.5sin B Given: L = 29.68N, llocal = 82.27W, Sep 21, solar
B = 360 ( n 81) 364 noon, surface with = 30 and aw = 0
which for Sep 1 yields ET = 0.63 min. Find: z, i, Ib,c, Id,c, Ir,c, Ic, and EST
2.9
Draw: Shadow map for geometry (c) in 2-8 in
40N latitudes, but rotated 90 such that
point P is now on west wall
2.11 A
Given: Same as 2.10, with panel facing S 45E
Find: i for same dates/times as 2.10
2.13 2
s ,max hs ,min
cos i dhs d s
Derive an eqn. for lines of constant declination. cos i avg =
2 ( s ,max s ,min )( hs ,max hs ,min )
In order to plot lines of constant declination on a The factor of 2 is there as the declination range is
plot similar to Fig. 2.10, we must write the seen twice a year. With the minimum values as
declination in terms of two polar coordinates, simply the negative of the maximum values,
namely the solar azimuth and altitude angles. The integration with respect to the hour angle yields
solar altitude angle is from Eq. (2.28), and can be s ,max
1
written in terms of the hour angle as cos i avg = sin ( L ) sin s
sin sin L sin s 4 s ,max hs ,max s ,max
cos hs =
cos L cos s +2 cos ( L ) cos s sin hs ,max
The solar azimuth is given by Eq. (2.29), Completing the second integration,
sin as cos 1
sin hs = cos i avg =
cos s 4 s ,max hs ,max
{
Using the identity,
sin 2 hs + cos 2 hs = 1 sin ( L ) cos ( s ,max ) cos ( s ,max )
the hour angle is removed as a variable. The answer
is then written as
+2 cos ( L ) sin hs ,max 2 sin ( s ,max ) }
simplifying,
( cos L cos s ) ( sin sin L sin s )
2 2
2.16 2.19
Given: L = 23N Given: Hamburg, Germany
Find: sunset time for May 1 and Dec 1 Find: Average horizontal insolation with PS =
From Eq. (2.23), 40 in May and PS = 60 in October.
May 1, n = 121, s = 14.9
Hamburg is at a latitude of 53.63 N, according to
Dec 1, n = 335, s = 22.1 Table A2.3a. For each month, Table A2.2 gives the
From Eq. (2.30), average daily extraterrestrial horizontal insolation
hss = cos 1 [ tan L tan s ] as
May 1, hss = 96.49 kWh MJ
May, H o ,h = 10.42 2 = 37.51 2
m day m day
Dec 1, hss = 80.07
kWh MJ
With 15 per hour, sunsets are at Oct, H o , h = 3.99 2 = 14.36 2
96.49 m day m day
May 1, Sunset time = = +6.43hrs = 6 : 26 PM Using the Angstrm-Page method, Table 2.5 gives a
15
= 0.22 and b = 0.57 for Hamburg. Then from Eq.
80.07
Dec 1, Sunset time = = +5.34hrs = 5 : 20 PM (2.48),
15
40 MJ
May, H h = 37.51 0.22 + 0.57 = 16.8 2
100 m day
2.17 60 MJ
Oct, H h = 14.36 0.22 + 0.57 = 8.07 2
Given: llocal = 107W 100 m day
Find: Solar Time at 10:00 AM MDT on June 1
Solar Time at 10:00 AM MST on Jan 1
2.20 For the horizontal surface, the hourly beam
Modify Eq. (2.51) to work with a solar constant component is given as
of 1353 W/m2. W
I b ,h = I b , N sin = 571.3 2
m
Eq. (2.51) is given as and the diffuse component from Eq. (2.78) as the
Dh balance:
1.390 4.027 KT + 5.531KT2 3.108 KT3
Hh W
I d ,h = I h I b ,h = 104.9 2
Where from Eq. (2.50), m
Hh
KT =
1394W m 2
2.22
Introduce a modified monthly clearness index to be
Find: Minimum distance between east-west
Hh
KT = rows of solar collectors
1353W m 2
Thus,
1353
KT = KT = 0.971KT
1394
and with the new parameter, Eq. (2.51) becomes
Dh
1.390 3.909 KT + 5.210 KT2 2.842 KT3
Hh
2.21
Given: L = 40N Denver, clear sky, horizontal
surface, Sep 9, 9:30 AM
Find: hourly beam and diffuse radiation From the law of sines,
D b
The hourly horizontal extraterrestrial radiation is =
given as Eq. (2.74). For Sep 9, n = 252. With the sin sin
solar declination from Eq. (2.23) as 4.61 and the Further reduce with
hour angle at 9:30 AM solar time from Eq. (2.25) as b = L sin
37.5, Eq. (2.74) yields: to obtain the result:
L ( sin )
2
W
I o ,h = 1353 ( 0.988 )( 0.656 ) = 876.2 2 D=
m sin
The air mass ratio is found from Eq. (2.38) as:
1
m=
sin
where from Eq. (2.28), the solar altitude angle is
41.1 such that m = 1.52. For clear skies, Eq. (2.77)
gives the total horizontal terrestrial radiation as
I W
I h = o ,h ( 83.02 3.847 m ) = 676.2 2
100 m
From Eq. (2.73),
I
kt = h = 0.772
I o,h
Therefore the hourly beam normal component is
given by Eq. (2.75) as
W
I b , N = 520 + 1800kt = 869.1 2
m
Chapter 3 The percentage of possible insolation is from Eq.
Methods of Solar Collection and (2.73) as
I
Thermal Conversion kt = h = 0.498
I o,h
3.1 The direct normal beam portion follows then from
Given: Uc = 6 W/m2K, l = 0.15 m, t = 0.0005 m, D Eq. (2.75) as
= 0.012 m, hc,i = 1200 W/m2K, = 0.9, = W
I b , N = 520 + 1800kt = 375.9 2
0.9, A = 1 m x 3 m, m& = 0.02 kg/s, Tf,i = m
330 K, aluminum The solar altitude angle is from Eq. (2.28) to be
Find: heat removal factor FR 41.2, such that the beam horizontal radiation is
W
The parameter m is determined as I b ,h = I b , N sin ( 41.2 ) = 247.6 2
m
Uc 6W m2 K The balance is the beam diffuse component,
m= = = 7.66m 1
kt 204.4 W mK 0.0005m W
I d ,h = I h I b ,h = 202.4 2
The conductivity for aluminum is interpolated from m
Table A3.4 to be 118.1 Btu/hrftF or 204.4 W/mK. The tilt angle is not specified in the problem
Therefore, the fin efficiency is determined as statement, but is taken here as 40. Therefore the tilt
tanh ( mw ) factor is
f = = 0.916 cos i
mw Rb =
Where the length sin
l D sin ( L ) sin s + cos ( L ) cos s cos hs
w= = 0.069m =
2 sin ( 41.2 )
From Eq. (3.37), the collector efficiency factor is cos s cos hs
= = 1.49
F =
1 Uc
= 0.906 sin ( 41.2 )
( )
l 1 U c ( D + 2w f ) + 1 ( hc ,i P )
Thus the radiation in the collector is
where the tube perimeter is simply P = D . Then I c = Rb I b , h + I d , h cos 2 ( 2) + I h sin 2 ( 2 )
from Eq. (3.43), W
= 368.79 + 178.72 + 10.53 = 558.04
( m& Ac ) c p Uc F m2
FR = 1 exp
( m& Ac ) c p
Finally from Eq. (3.46),
Uc
U c (T f ,i Ta )
= 0.823 c = FR
where the specific heat for water is 4179 J/kgC as Ic
given in Table A3.2.
6 ( 330 280 )
= 0.823 ( 0.9 )( 0.9 )
558.04
3.2 = 0.224
Given: collector in problem 3.1, Mar 1, L = 40N, The heat removal factor was taken from 3.1.
Ih = 450 W/m2, Ta = 280 K, aw = 0
Find: c between 11 AM and 12 PM
3.3
From Eq. (2.23) with n = 60, the declination is Given: collector in example 3.2, 10 AM, s I s = 0,
s = 8.29 150, 270 W/m2 in first 3 hours, Ta = 285 K
The average hour angle, hs = -7.5. From Eq. (2.74), Find: Tp at 10 AM
for the hourly horizontal extraterrestrial radiation,
W Values of the collector heat capacity are found in
I o ,h = 1353 (1.017 )( 0.657 ) = 904.1 2
m example 3.2 to be
J where N = 2 for two glass covers. From the
( mc ) p + (U c U )( mc ) g = 15,500 definition in Eq. (3.13),
K
Then from Eq. (3.52), qtop
U top =
I I Ac ( Tc Ta )
Tp ,9 am = Ta + s s s s (Tp ,8 am Ta )
Uc Uc and so combining with Eq. (3.23),
1
U At U top =
exp c c N ( Tc C ) (Tc Ta ) ( N + f )
0.33
+ hc,1
15,500
For one hour, t = 3600 s. The collector area in (Tc2 + Ta2 ) (Tc + Ta )
example 3.2 is given as 2 m2. Therefore, at 9 AM, +
1 p + 0.05 N (1 p ) + ( 2 N + f 1) g N
150 150 6 ( 2 ) 3600
Tp ,9 am = 285 + exp with the Stefan-Boltzman constant as 5.67x10-8
6 6 15,500 W/m2K4,
= 308.46 K W
Note that during the first hour, 8-9 AM, there was no U top = 1.038 + 1.362 = 2.4 2
m K
collector temperature rise as there was no absorbed
and finally,
insolation. Following the same method for the next
W
hour, U c = 0.8 + 2.4 = 3.2 2
270 270 m K
Tp ,9 am = 285 + ( 308.46 285 ) Clearly, as the bottom is better insulated, 75% of
6 6 the losses are from the top.
6 ( 2 ) 3600
exp
15,500
3.5
= 328.67 K
Given: Fig. 3.18, s = 0.9, s = 0.92, Ic = 600
W/m2, Ta = 5 C, Tf,i = 15 C, Tf,o = 60 C
3.4 Find: FR, Uc, qu/Ac, m& w
Given: double glass collector, Ta = 275 K, p =
From Fig. 3.18, the intercept is at 0.69. Thus the
0.9, ki = 0.04 W/mK, t = 3 cm, g = 0.88, ti
heat removal factor follows as
= 5 cm, Tc = 340 K, = 45, V = 3 m/s 0.69 = FR s s FR = 0.833
Find: Uc The slope is determined from Fig 3.18 to be
0.69 0.2 W
Neglecting edge losses, the total heat losses are FRU c = U c = 8.2 2
from the top and bottom as 0 0.072 m K
Combining Eq. (3.66) with Eq. (3.46),
1
U c = U bot + U top = + U top
= I c FR s s FRU c (T f ,i Ta ) = 345.5 2
qu W
Rbot
Ac m
where the thermal resistance through the bottom is
only according to the insulation conductivity. The efficiency of the collector for the noted fluid
inlet temperature and ambient temperature is
1 k W
= i = 0.8 2
Rbot ti m K
( q A ) 345.5 = 57.6%
c = u c =
Ic 600
From Eq. (3.23), the top surface convection
coefficient and other parameters are found as From Eq. (3.66), the maximum flow rate for the
W given fluid exit temperature is then
hc , = 5.7 + 3.8V = 17.1 2 c Ac I c 0.576 (10 )( 600 )
m K m& = =
C = 250 1 0.0044 ( 90 ) = 299.5 c p ( T f ,o T f ,i ) 4.18 ( 60 15 )
,c g = 70.3 W m 2
qrad
, g a = 111.2 W m 2
qconv 3.7
Given: normal = 0.7512 0.138 (T f ,in Ta ) I c
, g a = 31.1 W m 2
qrad
To handle the bottom surface, the thermal resistance K = 1 0.15 (1 cos i 1)
due to conduction is readily found as Sep 15, Ac = 6 m2, = 30, south facing,
t 0.03 m2 K = 0.3 m3 (water), Ts,0 = 30 C
Rbot = i = = 0.75 Find: qu of each hour and whole day
ki 0.04 W
Ts for each hour
There is no convective cooling at the bottom as the
collector is assumed here to be on a roof. Therefore
From Eq. (2.23), the solar declination is taken as
the overall heat loss coefficient is found as
constant through the day at 2.217. From Eq. (2.30),
1 1
Uc = + the hour angle at sunrise and sunset are
Rbot Rtop ,c g + Rtop , g a hsr = 91.26 = 5 : 55AM
=
1
+
1 hss = +91.26 = 6 : 05PM
Rbot 1 ( hc + hr )c g + 1 ( hc + hr ) g a Determine the angle of incidence for Gainesville (L
W = 29.68 N) as a function of the hour angle. For
= 3.84 south facing surface,
m2 K
In comparison, Eq. (3.23) yields for the top of the cos i = sin ( L ) sin s + cos ( L ) cos s cos hs
single cover collector = C1 + C2 cos hs
W Assume a profile for the ambient temperature
hc , = 5.7 + 3.8V = 17.1 2
m K between 6 AM and 6 PM as
C = 250 1 0.0044 ( 90 ) = 299.5
Ta = 30C + 5C sin ( hs + 90 )
90
120
f = (1 0.04hc , + 0.005hc2, ) (1 + 0.091N ) = 1.94
This profile will have the hottest temperature at 2 PM
1 solar time, and a daily average of 30 C. For the
U top = 0.33
N ( Tc C ) (Tc Ta ) ( N + f ) + hc,1 incident radiation, use Eqs. (2.42), (2.43), (2.45)
and (2.47).
(Tc2 + Ta2 ) (Tc + Ta ) I c = I b ,c + I d ,c + I r ,c
+
1 p + 0.05 N (1 p ) + ( 2 N + f 1) g N = I b , N cos i + C cos 2 ( 2 )
= 2.061 + 1.074 + ( sin + C ) sin 2 ( 2 )
= 3.14 The reflectivity is taken as 0.2, and from Eq. (2.39),
Finally, adding the top and bottom loss coefficients,
I b , N = Cn Ie k sin
1
U c = U bot + U top = + 3.14 Cn = 1 assuming clear, and from Eq. (2.35)
0.75
W I = I 0 1 + 0.034 cos ( 360n 356.25 )
= 4.47 2
m K W
= 1340.5
This is 17 % higher than the value determined by m2
the previous method.
Values from Table 2.4 are found to be The figure above shows the rise in the storage tank
k = 0.1816 temperature, determined with the above method for
C = 0.0978 1 hour angle increments. The useful energy
The solar altitude angle is taken from Eq. (2.28) as collection over the entire day was
sin = sin L sin s + cos L cos s cos hs qutotal = 131, 261 kJ
= C3 + C4 cos hs Over each hour, the totals are given below.
Although nearly symmetric over solar noon, it is not
The collector efficiency is measured for normal
exactly as the ambient temperature profile is not
angles of incidence. Thus for other angles, the
symmetric over solar noon nor is the fluid inlet
collector efficiency includes the incidence angle
(storage) temperature.
modifier as
c = 0.7512 K 0.138 (T f ,in Ta ) I c usuful energy collection per hour
useful energy kJ
25000
angle and fluid inlet temperature only. However, the 20000
fluid inlet temperature, assumed to be the average 15000
10000
storage tank temperature, depends on the collector 5000
efficiency. Thus a numerical solution is used, taken 0
over small hour angle steps. 1 2 3 4 5 6 7 8 9 10 11 12
1. The initial condition is at sunrise, with the fluid hour
inlet temperature equal to the ambient temperature
of 30 C, ie.
T f0,i = Ta ( sunrise ) = 30C
The useful energy at this step is: 3.8
qu0 = Acc0 I c0 = 0.7512 Ac K0 I c0 Given: T0 = 10 C, c = 50%
2. Assume this useful energy delivery is constant Find: 2 for Tc = 70 C, 200 C, 2500 C
over the step.
3. Assuming a small hour angle (or equivalently) The second law efficiency can be defined as the
time step, hs , the storage tank temperature rise is first law efficiency over the maximum efficiency
found as for a device between the high (sun) and low
(ambient) temperatures. That maximum efficiency
= water water C p , water (T f1,i T f0,i )
3600 s
qu0 hs is the Carnot efficiency as:
15
T
With this new fluid temperature, increase the hour max,sun = 1 0
angle by the step size and repeat until the desired Tsun
hour angle is reached. The best first law efficiency for a device operating
4. Add up the useful energy over the full duration of at the collector temperature is likewise
interest. T0
max,collector = 1
storage and ambient temperatures Tcollector
Therefore, for a perfect collector, the second law
efficiency of the combined collector and device to
130
convert the energy to useful work is:
temperature (C)
110
2perfect = max,collector
90 max,sun
70 As the collector is specified as not perfect, it has a
certain collector efficiency such that the overall
50
second law efficiency becomes
30
time (6am to 6pm )
2 = c
max,collector FR U c (T f ,o Ta )
c =
max,sun exp ( U c F Gc p ) Ic
1 T0 Tc
= 0.5
1 T0 Tsun
Tsun = 5762 K, such that for collector temperatures 3.11
of 343 K, 473 K and 2773 K, 2nd law efficiencies Derive Eq. (3.43) without the exponent term,
are 9.2%, 21.1% and 47.2%, respectively. using Taylor series expansion. Find range so new
equation agrees to within 1%.
Ra (T1 + T2 ) 2
2
Uc =
2 g (T1 T2 ) L Pr
3
the stagnation temperature occurs when the
collector efficiency is zero, Take the average temperature of the air in the gap as
900 335.5 K. With properties from Table A3.1 as
Tc ,max = ( 0.75 0 ) + 20 = 170C
4.5 335.5 K = 2.048 x10 5 kg m s
Pr 335.5 K = 0.700
3.13 335.5 K = 1.050 kg m3
Given: Same as 3.12, except CR = 2.0, 0 = 70% the density is solved to be
Find: Tc,max = 0.371kg m3
In going from the density at atmospheric pressure
Using the same method, and 335.5 K to the required density at the same
900 temperature, the required pressure is approximated
Tc ,max = ( 0.70 0 ) CR + 20 = 300C ideally as
4.5
Patm P 14.7
= P= ( 0.371) = 5.19 psia
atm 1.050
3.14
Given: Fig. 3.19, c = 50%, Ic = 800 W/m2
Find: Tc 3.17
Given: Example 3.3, with m& air
new
= 2m& air
From Fig. 3.19, Find: FRnew , and % increase
W
FRU c = 1.4 ; FRopt = 0.54
m2 K In example 3.3, Re = 7066. Doubling the flow rate,
Assume the ambient temperature is 20 C. Then
Re new = 14,132
From Eq. (3.46),
From Eq. (3.53),
Tc = ( FRopt c ) c + Ta = 42.86C
I
FRU c
0.0192 ( Re new ) W
34
Pr I eff = I b ,c cos it + cos ic
Nu new
= = 34.00 D
1 + 1.22 ( Re new )
1 8
( Pr 2 )
+ I d ,c FTS (1 + F )
The old Nusselt number was 22, such that
For tubes spaced one diameter apart, the shape
Nu new kJ
hcnew = hc = 1.55hc = 102.8 2 factors above are
Nu m hr C
F 0.34
and
FTS 0.43
h new 102.8
F new = newc = = 0.851 Another shape factor, , is in the range 0.6-0.7 for
hc + U c 102.8 + 18 tubes spaced one diameter apart, so is taken as 0.65.
Finally solving Eq. (3.56), Thus the effective radiation is
( 0.0256 )(1) 1 exp ( 0.851)18 3600 I eff = 600 ( cos it + 0.39 cos ic ) + 162.646 W/m2
FRnew =
18 3600 ( 0.0256 )(1) The optical efficiency is from Eq. (4.51) <1st ed> as
e r I eff
= 0.784 0 =
The % increase is simply I b ,c + I d , c
F new FR or upon substitution,
% increase = R x100
FR 0 = 0.001I eff
0.784 0.677 Therefore, the optical efficiency is only in terms of
= x100 the hour angle. For the two specified hour angles,
0.677
= 15.8%
hs = 0 hs = 30
it ( ) 2.75 4.65
3.18 ic ( ) 2.75 28.88
Given: evacuated tube collector, Nov 13, L = 30,
= 45, Ib,c = 600 W/m2, Id,c = 100 W/m2, I eff (W m2 ) 995.69 965.56
e r = 0.70, W = D, = 0.60 0 0.996 0.966
Find: 0
The sun temperature is 5760 K. The receiver where the reflectance for the silver mirror is taken
temperature is a maximum when the collector from Table 3.4 as 0.88, and 0.82 for anodized
efficiency is zero. Solving, aluminum. Therefore,
Tr ,max = 3025.8 K R.L. = 1 0.880.3 = 0.0376 silver
R.L. = 1 0.820.3 = 0.0578 anodized aluminum
3.21
Given: CR = 5, full CPC 3.23
Find: Depth for Aa = 1 m, 0.01 m Given: = 9
Find: n for full and 50% truncated CPC
From the geometry in Fig. 3.40,
A 2 + Aa 2 From Figs. 3.44 and 3.45, for the full CPC,
D= r n = 1.08
tan max
refector
The tangent term is eliminated by using the identity = 6.4
aperture
1 1
= 1 Assuming the reflector area varies directly with the
tan max sin max
2
height, the 50% CPC will have
and further from section 3.7.3, refector 6.4
1 A = = 3.2
CR = = a aperture 2
sin max Ar and from Fig. 3.45, CR = 5.75. Then from Fig. 3.44,
Combining equations, for the 50% CPC,
A + Aa n = 0.8
D= r CR 2 1
2
A 1
= a + 1 CR 2 1 3.24
2 CR
Given: = 7, CPC
For the 1 m aperture, D = 2.94 m. For the 1 cm Find: CR for 25%, 33% and 50% truncated
aperture, D = 2.94 cm.
From Fig. 3.45 for the full CPC,
refector
3.22 = 8.3
aperture
Given: 50% truncated CPC, = 36
Find: reflectance loss for silver and anodized With the truncation, this value is reduced. Then
aluminum mirror surfaces from Fig. 3.45, the new CR is found. The results are
3.26
Given: PTC, i = 30, perfect optics and tracking,
no end supports, r r = 0.75, m = 0.80,
5% shaded
Find: optical efficiency
3.27
Given: PTC, La = 0.5 m, = 50, slope accuracy
= 2 mrad, = 0.92
Find: CR, Dr
Chapter 4 Vsalt 125, 700
= = 0.26
Thermal Energy Storage and Transport Vwater 483, 670
Clearly, the salt has the highest energy storage per
4.1 volume owing to its phase change.
Given: Tlow = 30C, Thigh = 60C
Find: Q/V for water, rock and Glaubers salt;
compare volumes 4.2
Given: Ac = 100 m2, Pc = 7 kPa, flat plate, L =
Properties are from Table 4.1, and the volumetric 40 m
energy storage is computed as
Find: Ptot , D
Q
= c p T = cp 30C
V Some more information is needed. In this solution,
water rock it is assumed that
c p ( kJ / kgK ) 4.19 0.880 1) flow rate is 0.03 gpm per ft2 of collector
( kg / m ) 3 1000 1600 2) pipe velocity is 3 ft/s
3) fittings add 200 equivalent feet of pipe
Q V ( kJ m ) 3 125,700 42,240 4) actual pipe length is 2.5 times the distance L
The flow rate is then determined as
10.76 ftc2 gpm
m& = (100m2c )
For Glaubers salt, there will be a phase change as
the melting point is 32.4 C. The volumetric energy 2 0.03 2
mc ftc
storage is then
= 32.3gpm
= avg c p , s (Tm Tlow ) + fg + c p ,l (Thigh Tm )
Q
Distance is 40 m = 131.2 ft. The pipe distance is
V
where the density is an average of the solid and assumed to be 2.5 times this, or 328 ft. Adding the
liquid densities equivalent pipe length due to fittings, the total pipe
length is then 528 ft. From Fig A4.3, the friction
+ l
avg = s loss is found as 3.5 ft head / 100 ft pipe. Thus,
2
3.5 ft water 62.4 lb ft 3
Ptot = Pc + 528 ft pipe
100 ft 144 in 2 ft 2
With the properties for Glaubers salt taken from
Table 4.3, pipe
= 7 kPa + 8.008 psi
Tm ( C ) 32.4
= 9.023 psi
c p,s ( kJ / kgK ) 1.76 Also from Table A4.3, the required pipe diameter is
c p ,l ( kJ / kgK ) 3.32 read as 2.5 in. This should match approximately to
the pipe diameter calculated by continuity for the
s ( kg / m ) 3 1460 assumed flow rate and pipe velocity.
l ( kg / m ) 3 1330
fg ( kJ kg ) 251 4.3
QV ( kJ m3 ) 483,670 Given: Collector as in 4.2, cylindrical storage
tank with D = H, Tst = 70 C, Ta = 16 C, t
= 0.15 m
For the same energy storage, the volume of rock Find: heat loss rate qcyl
needed relative to water is
Vrock 125, 700 Typical storage is 50-75 kg mc2 , so assume here a
= = 2.98
Vwater 42, 240 value of 60. The mass of storage is then
The volume of Glaubers salt needed relative to mst = ( 60 kg mc2 )(100mc2 ) = 6000kg
water is
For water at 70 C, Table A3.2 lists the density as
978 kg/m3. Therefore the volume is
D3 m P = 9.5MPa = 93.9atm = 1380.6 psi
Vst = = st = 6.136m3 D = 1.984m
4 water
The insulation property is approximated from Table
4.8 as k = 0.4 W/mK. The heat loss rate is given by 4.6
Eq. (4.28) as Given: Vmax = 4 ft/s, m& = 500 gpm, L = 500 ft
2 kL Find: D, P
qcyl = (Tst Ta ) = 1912 W
ln ( ( D + 2t ) D ) From Fig. 4.7, with the given flow rate and fluid
This assumed no losses from the top or bottom of velocity,
the cylinder. D = 7 in
1.5 ftloss
loss =
100 ft pipe
4.4
The pressure drop is then
Given: Load = 1.5 GJ, Tst = 20 C
1.5 ftloss
Find: Vst, cost if 4 m3 carbon steel tank costs P = ( 500 ft pipe ) = 7.5 ftloss
100 ft
$1000 pipe
4.13
Given: condenser shell and 2 tubes, m& s = 0.8
kg/min, Ps = 80 kPa, Tcw,i = 290 K, Tcw,f =
320 K, U = 3000 W/m2K
Find: Ahx
=
q
=
(Tcw, f Tcw,i ) = 0.391
( mc
& p ) (Ts Tcw,i )
cw
(Ts Tcw,i )
Chapter 5 5.3
Solar Heating Systems Given: Denver, q = 150,000 Btuh for T = 75 F,
qi = 20,000 Btuh, Ti = 70 F
Find: Energy demand
5.1
Given: Eq. (5.6)
The peak load gives
Find: Modify to include losses through a slab
150, 000 Btu
which are independent of the ambient q = UAT UA = = 2000
75 hr F
Eq. (5.5) gives the internal generation as balancing From Eq. (5.6), the generation gives the no-load
the losses due to ventilation and infiltration as temperature as
qi = UA ( Ti Tnl ) Tnl = 70 F
20, 000 Btuh
= 60 F
2000 Btuh / F
If there is an ambient temperature independent loss
From Table 5.3 for the given no-load temperature
through a slab, that can be modeled as
and Denver as the location,
qslab = U slab
*
Aslab C days = 2622
Then the balanced equation becomes or conversion to Fahrenheit,
qi qslab = UA (Ti Tnl ) F days = 4720
or in terms of the no-load temperature, the modified Therefore the annual energy demand for a 60 F
Eq. (5.6) is difference is
Tnl = Ti
( qi Uslab
*
Aslab ) Q = ( F days ) UA
24h
UA day
= ( 4720 )( 2000 )( 24 )
= 227 x106 Btu
5.2
Given: Garage on building north wall, garage Ar,
Awi, Ad, Awa
5.4
Find: Effective U in terms of other U values
Given: January, Washington DC, water heating
system, Ac = 100 m2, Q = 4 m3/day, Tw,o =
The garage gains heat through the north wall, and
65 C, Tw,i = 12 C
all the heat is lost through the other garage surfaces
Find: solar load fraction
to the ambient at steady state.
q = U nw Anw (Ti Tg ) Ti Tg =
q
The energy input to heat the given volume flow rate
U nw Anw of water for January is
q = UAg (Tg Ta ) Tg Ta = q UAg Load = wQc p (Tw,o Tw,i )
Adding the two equations to remove the garage = (1000 )( 4 x31)( 4.18 )( 65 12 )
temperature,
= 27.47 GJ month
Ti Ta = q (1 U nw Anw + 1 UAg )
For a typical flat plate collector, Fig. 5.20 gives the
UAgU nw slope and y-intercept as
q= Anw (Ti Ta )
UAg + U nw Anw FRU c 4.6 2
W
Thus, the effective U value is m C
UAgU nw FR ( ) n 0.8
U= From Eq. (5.21), the time averaged value is given as
UAg + U nw Anw
FR ( ) = 0.95FR ( ) n = 0.76
where
UAg = ArU r + AwiU wi + AdU d + AwaU wa For no heat exchanger,
Fhx = 1
From Eq. (5.27) for a water system,
Fhx FRU c Ac t H c = 2.28 ( 4.57 ) + 0.883 ( 2.81) + 0.088 ( 7.38 )
PL =
Load MJ
= 13.56
(11.6 + 1.18Tw,o + 3.86Tw,i 2.32Ta ) m 2 day
where the temperatures are in C, and the time Finally, from Eq. (5.19),
period as the total seconds per month. The average A F F ( ) H c ( # days )
ambient temperature for Washington can be looked Ps = c hx R
Load
up in an outside reference for January to be 36.9 F
= 2.72 C. Thus, 100 (1)( 0.76 ) (13.56 x106 ) ( 31)
=
1( 4.6 )(100 )( 31x 24 x3600 ) 27.47 x109
PL =
27.47 x109 = 1.16
(11.6 + 1.18 x65 + 3.86x12 2.32 x 2.72 ) Eq. (5.22), or Fig 5.21, can be used to find the solar
load fraction as
= 5.75
f s = 1.029 (1.16 ) 0.065 ( 5.75 ) 0.245 (1.16 )
2
Monthly averaged daily horizontal insolation values
+ 0.0018 ( 5.75 ) + 0.0215 (1.16 )
2 3
can be looked up for Baltimore in Table A2.3b
(near Washington) for January as
= 0.58
MJ
H h = 7.38 2
m day
From Table A2.2, the average daily horizontal 5.5
extraterrestrial insolation in January at 40 N Given: Same as HW 5.4, but for Albuquerque,
latitude is NM in July, Tw,i = 17 C
Wh MJ
H o , h = 4200 2 = 15.12 2 Find: solar load fraction
m day m day
Using the Liu and Jordan method from Ch. 2.6.1, The hot water load will be less and is given as
assuming a tilt angle of 40 N for optimal collection Load = wQc p (Tw,o Tw,i )
during the year,
= (1000 )( 4 x31)( 4.18 )( 65 17 )
KT = 0.488
MJ = 24.88 GJ month
Dh = 0.38 H h = 2.81 2 Collector parameters will remain the same from Fig.
m day
5.20. The average ambient temperature will be
MJ
Bh = H h Dh = 4.57 2 much higher, and can be found from an outside
m day reference as 78.5 F = 25.8 C in July.
Rd = 0.883 1( 4.6 )(100 )( 31x 24 x3600 )
PL =
Rr = 0.088 24.88 x109
assuming snow covered ground. The beam tilt (11.6 + 1.18 x65 + 3.86 x17 2.32 x 25.8)
factor is found at mid-month, Jan 15. With the = 4.66
declination as -21.27, the hour angle at sunrise is The lower value of the loss parameter is expected
found from Eq. (2.30), taking L = 40, as for the hotter ambient temperatures. The latitude is
hsr = 70.94 = 1.238rad about 35 N, such that Table A2.2 gives
Then the tilt factor from Eq. (2.56) becomes Wh MJ
H o , h = 11,172 2 = 40.22 2
cos s sin hsr m day m day
Rb =
cos L cos s sin hsr + hsr sin L sin s From Table A2.3b, in July,
= 2.28 H h = 27.03 2
MJ
Thus the daily average insolation on the collector is m day
given by Eq. (2.60) as Carrying through the Liu and Jordan method again
with the collector tilt equal to the latitude,
KT = 0.672
MJ
Dh = 0.238H h = 6.44 The loss and solar load parameters are both
m 2 day
proportional to the collector size, according to
MJ
Bh = H h Dh = 20.59 2 PL = K L Ac
m day
Ps = K s Ac
Rd = 0.910
Thus for the original collector area, the two can be
Rr = 0.018 combined to obtain
assuming dry grass cover in July. With the K
declination as 21.52, the hour angle at sunrise is PL = L Ps
Ks
found from Eq. (2.30), taking L = 35, as
which is a straight line passing through the origin
hsr = 106.0 = 1.85rad
and point (Ps, PL). Note that if the collector area is
Then the tilt factor from Eq. (2.56) becomes changed while keeping the K values the same, the
cos s sin hsr above relationship will hold for the new collector
Rb =
cos L cos s sin hsr + hsr sin L sin s area as well. The modified loss parameter will be
= 0.797 PL' = K L Ac'
Thus the daily average insolation on the collector is which can be combined with a previous expression
given by Eq. (2.60) as for the loss parameter to get
H c = 0.797 ( 20.59 ) + 0.91( 6.44 ) + 0.018 ( 27.03) PL' Ac' A'
= PL' = PL c
MJ PL Ac Ac
= 22.76
m2 day The value of the solar load fraction is then at the
Finally, from Eq. (5.19), intersection of the two equations,
A F F ( ) H c ( # days ) K
PL = L Ps and PL' = PL c
A'
Ps = c hx R Ks Ac
Load
100 (1)( 0.76 ) ( 22.76 x106 ) ( 31)
Shown graphically, the intersection is located on a
= contour for the solar load fraction, at about fs =
24.88 x109 0.65, while the original collector area with point
= 2.16 (Ps, PL) gave fs = 0.8.
The higher solar parameter indicates there is more
sunshine. Eq. (5.22), or Fig 5.21, can be used to find
the solar load fraction as
f s = 1.029 ( 2.16 ) 0.065 ( 4.66 ) 0.245 ( 2.16 )
2
= 1.03
Since the solar load fraction is greater than unity,
then it is expected that all of the monthly load can
be supplied by solar energy.
Notes:
If the collector area was reduced to 80 m2, for
example, then the solar load fraction would drop to
0.94. Hence with a reduction in the collector size,
the supplied solar energy will drop faster than the
collector losses and all of the load would not be 5.8
covered by solar energy. Given: Shell and tube Ash = 10 m2, Ush = 2000
W/m2K, Ac,sh = 100 m2; Tube coil Dtc =
1.27 cm, copper; storage 50 kg water per
5.6 m2 collector, Tst = 60 C, Tc = 70 C
Explain the graphical use of the f-chart for a Find: Ltc for same UA, tube % volume of
range of collector sizes, for an original Ps and PL storage tank
Eq. (3.71) is a relation for free convection from a 5.9
cylinder, from the 1st edition, but can be looked up Given: qu = 2500 MJ/m2yr, 30 kg/m2hr, F = 0.93,
from a heat transfer text. U = 4 W/m2K
hD
NuD = c tc = 0.53 ( GrD Pr ) Find: qu if flow rate is doubled
0.25
k
The Grashof number based on the tube diameter can From Eq. (3.43), assuming Tf,in = 20 C to get cp,
also be looked up in another text as
Gc p U F
2 g T ( Tw Tst ) Dtc3 FR1 = 1 exp c
GrD = U c
2 Gc p
and the Prandtl number as
=
( 30 3600 )( 4180 ) 1 exp 4 ( 0.93) 3600
c
Pr = p 4 ( 30 )( 4180 )
k
Combining, = 0.882
0.25
If the flow rate is doubled, keeping the same F,
2 g T c p
hc = 0.53
k
(Tw Tst ) Dtc3 FR 2 =
( 60 3600 )( 4180 ) 1 exp 4 ( 0.93) 3600
k
( 60 )( 4180 )
Dtc 4
Properties are found at the average film temperature
of 65 C from Table A3.2 as = 0.906
From Eq. (3.44),
2 g T c p
= 7.62 x1010 m3 K 1 qu
= Ac s I s U c (T f ,in Ta )
k FR
W
k = 0.659 Since nothing on the right hand side changes, we
mK can write
Thus, qu1 qu 2 F MJ
0.659 = qu 2 = R 2 qu1 = 2567 2
7.62 x1010 ( 70 60 ) 0.01273
0.25
hc = 0.53 FR1 FR 2 FR1 m yr
0.0127
W
= 972 2
m K 5.10
For having equivalent energy storage as with the Given: Denver, Aug 21, Ac = 1000 m2, Tc = 100
shell and tube heat exchanger, C, Ta = 35 C
Q& st = U sh Ash T = hc Dtc Ltc T Find: Heat rejection
Ltc =
( 2000W m 2 K )(10m 2 )
= 515.7 m From the hourly data in Table A2.6c for 40 N
( 972W m 2 K ) ( )( 0.0127 ) latitude and Aug 21, the highest hourly insolation is
The storage mass is for 50 kg per sq. meter of 311 Btuh/ft2 for the noon hour, and 30 tilt. Thus,
collector area, or 5000 kg total. For the listed assuming the sky is clear,
density in Table A3.2, the volume of water is Btuh W
I c = 311 2 = 981.2 2
5000kg ft m
Vst = 3
= 5.085m3
983.3 kg m The parameter needed to use Fig. 5.20 is
Tin Ta 100 35 W
The tube volume is = = 6.6 x102 2
Ic 981.2 m K
Vtc = Dtc2 Ltc = 0.065m3
4 Then Fig. 5.20 gives
Thus, the volume percentage of the storage tank = 0.44
occupied by the tubular collector is Therefore, the amount of heat rejection is the
0.065 amount of collected heat, which is
%V = x100 = 1.27%
0.065 + 5.085
J Using the Liu and Jordan method from Ch. 2.6.1,
qu = I c Ac = 0.44 ( 981.2 )(1000 ) = 431, 728 assuming a tilt angle of 55 N for optimal collection
s
MJ during the year,
= 1554 KT = 0.501
hr
MJ
Dh = 0.37 H h = 3.36 2
m day
5.11 MJ
Given: Little Rock, January, Load = 40 x 106 Bh = H h Dh = 5.73 2
m day
Btu/month, L = 35 N, = 55, aw = 0, Ac
Rd = 0.787
= 1000 ft2, Ta = 40.6 F, collector efficiency
from Fig. 5.20, Fhx = 1 Rr = 0.160
Find: solar load fraction using f-chart assuming snow covered ground. The beam tilt
factor is found at mid-month, Jan 15. With the
For a typical flat plate collector, Fig. 5.20 gives the declination as -21.27, the hour angle at sunrise is
slope and y-intercept as found from Eq. (2.30), taking L = 35, as
W hsr = 74.18 = 1.295rad
FRU c 4.6 2
m C Then the tilt factor from Eq. (2.56) becomes
FR ( ) n 0.8 Rb = 2.16
From Eq. (5.21), the time averaged value is given as Thus the daily average insolation on the collector is
FR ( ) = 0.95FR ( ) n = 0.76 given by Eq. (2.60) as
For no heat exchanger, H c = 2.16 ( 5.73) + 0.787 ( 3.36 ) + 0.160 ( 9.09 )
Fhx = 1 MJ
= 16.48
From Eq. (5.27) for a water system, m 2 day
F F U A t Finally, from Eq. (5.19),
PL = hx R c c
Load A F F ( ) H c ( # days )
Ps = c hx R
(11.6 + 1.18Tw,o + 3.86Tw,i 2.32Ta ) Load
where the temperatures are in C, and the time 92.9 (1)( 0.76 ) (16.48 x106 ) ( 31)
period as the total seconds per month. Assume the =
4.22 x1010
collector gives water at 65 C and water enters the
= 0.855
collector at 15 C. In SI units, the area is 92.9 m2,
Eq. (5.22), or Fig 5.21, can be used to find the solar
the load is 4.22 x 1010 J/month, and the average
load fraction as
ambient temperature is 4.78 C.
f s = 1.029 ( 0.855 ) 0.065 ( 3.66 ) 0.245 ( 0.855 )
2
1( 4.6 )( 92.9 )( 31x 24 x3600 )
PL =
+ 0.0018 ( 3.66 ) + 0.0215 ( 0.855 )
2 3
4.22 x1010
(11.6 + 1.18 x65 + 3.86x15 2.32 x 4.78) = 0.50
= 3.66
Monthly averaged daily horizontal insolation values
can be looked up for Little Rock in Table A2.3b for 5.12
January as Given: same as Problem 5.11, with storage
MJ doubled and halved
H h = 9.09 2 Find: solar load fraction
m day
From Table A2.2, the average daily horizontal
From Eq. (5.25) in Table 5.8,
extraterrestrial insolation in January at 35 N 0.25
0.25
latitude is V V
PL = PL, nom s = PL ,nom s
Wh MJ 75 V
H o , h = 5039 2 = 18.14 2 s ,nom
m day m day
The nominal value of the load parameter is 3.66,
found in Problem 5.11. If the volume is doubled, 5.14
PL ,doubled = 3.66 ( 2 )
0.25 Given: same as Problem 5.13, with collector flow
= 3.08
rate doubled
and if halved, Find: solar load fraction
PL ,halved = 3.66 ( 0.5 )
0.25
= 4.35
With the solar parameter unchanged as 0.855, Eq. From Table 5.9, the modified loss parameter is
(5.22) or Fig. 5.21 yields given by
f s ,doubled = 0.531
0.28
Q
0.28
Q
PL = PL, nom c = PL ,nom c
f s ,halved = 0.465 10.1 Q
c ,nom
Thus with an increase in the storage volume, more Doubling the flow rate, and taking the nominal loss
of the heating load can be covered with solar. parameter value from Problem 5.13,
PL = 2.89 ( 2 ) = 3.51
0.28
= 0.22
= 0.34
As the horizontal collector faces the sun less than a
This is less than the solar load fraction found in
tilted collector in January, the solar load fraction is
Problem 5.11, indicating that water systems deliver
less than in Problem 5.11. It was also shown that
more energy.
MJ The Hottel-Whillier-Bliss is Eq. (3.46), as
Dh = 0.37 H h = 3.36
m 2 day c = FR s s U c (T f ,in Ta ) I c
MJ
Bh = H h Dh = 5.73 2 Combining the last two equations and rewriting,
FU
= 0.49 = intercept R c
This is not a large change from that found in slope
Problem 5.11 for the 55 tilted collector. intercept
=
1 + slope 2Gc p
For the second case (b), the fluid inlet temperature
5.16 is written as
Explain how FR ( ) and FRU c can be I
T f ,in = T f ,out c c
determined from plots of efficiency versus Gc p
(a) (T f Ta ) I c or (b) (T f ,out Ta ) I c , in terms of Substitution into the Hottel-Whillier-Bliss equation,
slopes, intercepts, and fluid capacitance rates
c =
FR
s s U c
(T f Ta )
1 FRU c Gc p Ic
For the first case (a), the average fluid temperature
is given as and thus,
T + T f ,in FR s s
T f = f ,out T f ,out = 2T f T f ,in intercept =
2 1 FRU c Gc p
An energy balance for the collector gives FRU c
slope =
= c I c = Gc p (T f ,out T f ,in )
qu 1 FRU c Gc p
Ac This is similar to before, save for the factor of 2
Combining the above two equations, removed from the fluid capacitance term. Thus, the
I rewritten terms become
T f ,in = T f c c
2Gc p
slope
FRU c =
1 + slope Gc p
intercept
FR ( ) =
1 + slope Gc p
5.17
Discuss a solar-assisted heat pump system and a
solar augmented heat pump system with respect
to different climates.
Chapter 6
Solar Cooling and Dehumidification From table A6.1b, the refrigerant properties leaving
the condenser at saturated liquid at the system high
pressure are
6.1
Tc = 36.11C
Given: Houston, July 30, solar noon, tabulated
data hlc = 100.42 kJ kg
Find: cooling load Q& cool Leaving the evaporator, assuming saturated vapor,
the same table gives at the system low pressure
For July 30, n = 211, and Eq. (2.23) yields the Te = 0.3C
declination as 18.42. The latitude of Houston is hle = 247.06 kJ kg
29.44N. From Eq. (6.8), the angle of incidence for
sve = 0.9192 kJ kgK
the vertical wall is found as
With the cooling load from 6.1, the mass flow rate
cos i = sin sin ( L s ) = 0.191
of refrigerant is found from an energy balance at the
From Eq. (2.28), the solar altitude is found as evaporator, assuming the throttling is isenthalpic, as
sin = cos ( L s ) = 0.9816 Q& cool 14.05
m& r = = = 0.0958 kg s
Assuming no shading, the load for the south facing hve hlc 247.06 100.42
window is given as Eq. (6.1) From Table A6.2, the properties of the superheated
0.191
Q& wi = ( 8 ) (1)( 0.6 )( 580 ) + ( 0.80 )( 250 ) vapor leaving the compressor assuming isentropic
0.9816 expansion are found through a double interpolation
+ ( 0.55)( 200 ) + ( 6.2 )( 37 24 )} of the table. First, for the two listed pressures
encompassing the high pressure,
= 3666.5W 0.9MPa hvds = 270.47 kJ kg
The shaded window load is given by Eq. (6.2) as
1.0MPa hvds = 272.69 kJ kg
Q& wi , sh = ( 8 + 20 + 25 )( 6.2 )( 37 24 ) = 4271.8W
And interpolating the enthalpy at 0.915 MPa from
Assuming white paint with s , wa = 0.12 , the south these values,
facing wall load is given by Eq. (6.3) as 0.915MPa hvds = 270.80 kJ kg
0.191
Q& wa = ( 30 ) ( 012 ) 200 + 250 + 580
From the definition of the compressor efficiency,
0.9816 hs h
c = vd ve hvd = 273.44 kJ kg
+ (1.08)( 37 24 ) hvd hve
= 2447.5W Then from Eq. (6.16),
The shaded wall load is given by Eq. (6.4) as Q& cool
COP = = 6.18
Q& wa , sh = ( 30 + 75 + 75)(1.08 )( 37 24 ) = 2527.2W m& r ( hvd hve )
The roof load, assuming it is shaded, is given by Eq.
(6.5) as
Q& rf = ( 250 )( 0.35 )( 37 24 ) = 1137.5W 6.3
Neglect loads associated with infiltration and Given: Absorption-Refrigeration, LiBr-H2O, 1
ventilation. Therefore the total cooling load is kW cooling
Find: Q& a , Q& c , Q& e , COP, then Ac for Arizona,
Q& cool = 3666.5 + 4271.8 + 2447.5 + 2527.2 + 1137.5
= 14.05kW noon, August, FR ( ) = 0.81, FRU c = 3
W/m2K, 3 ton cooling
D=
Area
=
( 20 )( 40 ) = 6.67m Q&
W&electrical = cool =
332
= 110.7 kW
Perimeter 2 ( 20 + 40 ) COP 3
This was calculated on a hot day with high
and the air properties are determined at the film
insolation. Thus, this work input can provide the
temperature. Assume a midday average temperature
peak cooling demand for the ice rink.
of 28 C on June 21 (taken from Climatic data).
Notes:
T f = (Ta + Ts ) 2 = 287 K Energy transfer due to mass transfer between the ice
The heat transfer coefficient therefore becomes and air was neglected.
k k W
hconv ,nat = Nu D = 0.27 RaD0.25 = 1.005 2
D D m K
where the thermal conductivity k = 0.0253 W/mK. 6.5
Here, the Nusselt number is Given: Desiccant heat pump, Tcond = 150 F
Nu D = 265 Find: COP
It should be noted that the range of applicability for
the Nusselt number relation is up to about During daytime operation, let the solar collector
temperature be 95 C and assume the room
RaD 1010
temperature is 20 C, such that from Table A3.8,
So there will be some error but this is only a first
approximation. The convective heating then is
h368
fg
K
= 2270.2 kJ kg m& w = m& s m& r
h 293
fg
K
= 2451.1 kJ kg m& s = m& r
( X r X w ) = 20m& = 0.2848 kg
The daytime COP is the heating provided to the ( Xs Xw) r
s
house over the heat input to the collector. This is Assuming saturated vapor, the refrigerant leaving
approximately equal to the ratio of latent heats, the generator/rectifier is at
neglecting sensible heat changes. T1 ( P = 15bar , X r = 0.98 ) = 85.1C
2454.1
COPday = = 1.081 Assume the heat source is to be 5 C hotter,
2270.2 Tcollector 90C
Similarly at night, assume the outside air to be 10
Assuming that the heat input to the system is
C and the condensing temperature was specified as
required 24 hours a day, the daily load is
150 F = 65 C. From table A3.8,
Qgday = Q& g ( 24 hr day )( 3600 s hr ) = 5063 MJ day
h338
fg
K
= 2346.2 kJ kg
Assuming there is storage, this amount must be
h 283
fg
K
= 2477.7 kJ kg delivered by the collector each day of the year (for a
The desired effect is heating the house, and the constant 5 ton cooling requirement). A limiting case
energy supply is from the outside air. will be for a day with the least insolation. Using
2346.2 Jacksonville (L = 30.5 N) as the example, Table
COPnight = = 0.947 A2.3b gives the lowest average daily insolation in
2477.7
Thus, the overall COP is December as
COPavg 1
MJ
H h = 9.65 2
m day
Table A2.2 gives the maximum on the horizontal
surface for 30 N latitude in December as
6.6
Whr MJ
Given: 5 ton cooling, NH3-H2O, Fig. 6.9, Plow = 3 H o , h = 5463 2 = 19.67 2
bar, Phigh = 15 bar, Xr = 0.98, Xs = 0.6, Xw m day m day
= 0.58, COP = 0.3 From Eq. (2.50)
Find: Ac, Tc 9.65
KT = = 0.49
19.67
From the saturated ammonia Table A6.3 and water For the middle of the month (Dec 16), Eq. (2.23)
Table A3.8, the properties are added in the indicated and (2.30) give
proportion (0.98) to get s = 23.37
h2 ( P = 15bar , X r = 0.98 ) = 179.44 kJ kg hsr = 75.25 = 1.313rad
h4 ( P = 3bar , X r = 0.98 ) = 1413.74 kJ kg hss = +75.25 = +1.313rad
This assumes saturated liquid leaving the condenser From Eq. (2.52), the diffuse component is given as
and saturated vapor leaving the evaporator. With the Dh
cooling at 5 ton = 17.58 kW, the mass flow rate of = 0.775 + 0.347 hss
refrigerant is
Hh 2
Q& e
m& r = = 0.01424
kg 0.505 + 0.0261 hss cos ( 2 KT 1.8 )
( h4 h3 ) s 2
With the COP indicated as 0.3, the heat input to the = 0.345
generator is or
Q& 17.58 MJ
H D = 0.345 ( 9.65) = 3.33
Q& g = e = = 58.6kW m 2 day
COP 0.3
A total solution and ammonia mass balance at the and the horizontal beam component is thus
absorber allows the determination of the strong MJ
Bh = H h H D = 6.32 2
solution flow rate as m day
m& s X s = m& w X w + m& r X r
The best collector tilt for the winter season, when with the ambient temperature. So the winter cooling
the solar altitude is low, is taken as load would be lower and so would the required
= L + 15 = 45.5 collector area.
Then from Eq. (2.56),
cos ( 15 ) cos ( 23.37 ) sin ( 75.25 )
6.7
1.313sin ( 15 ) sin ( 23.37 )
Given: LiCl packed tower, m& dehum ,i = mreg ,o , eqn.
Rb =
sol
& sol
cos ( 30.5 ) cos ( 23.37 ) sin ( 75.25)
for m& reg
sol
, w , given properties
W Yoair = 0.01138
FRU c = 3
m2 K Thus, the condensed amount of water from the air in
Collection occurs for 10 hours per day in December the dehumidifier is found as
(based on the sunrise and sunset times), the ambient
m& w = (Yi Yo ) m& a ,i =
air air air air ( Yi air Yoair ) air
m&
was assumed to be 15 C, and the rectifier exit
temperature of 85.1 C was used as the heat source (1 + Yi air ) i
fluid inlet temperature. Thus the minimum collector kg
area is = 1.78
h
Qgday 5063 This of course assumes the mass flow of dry air is
Ac = = = 805m 2 constant in the process. This condensed amount is
Hc 6.29
added to the desiccant solution, such that the new
Notes:
mass flow rate of solution is
The refrigeration load was assumed to be constant
throughout the year. In reality, the load would vary
kg
m& dehum ,o = mdehum ,i + mw = 850 + 1.78 = 851.78
sol
& sol & air
h
The mass flow of dry desiccant is assumed to be
constant, and is
kg
m& dsol = X dehum ,i mdehum ,i = ( 0.35 )( 850 ) = 297.5
sol
& sol
h
Therefore, with the added water to the desiccant
solution, the concentration at the dehumidifier
outlet and thus regenerator inlet is
m& dsol 297.5
X dehum ,o = X reg ,i = sol
sol sol
= = 0.3493
m& dehum ,o 851.78
The problem statement says to assume constant
flow rate of desiccant solution, such that the
regenerator will evaporate enough of the water to
bring the solution concentration back to 35%.
kg g
m& reg
sol
, w = mw = 1.78
& air = 0.494
h s
The equation for this amount of water evaporated
from the desiccant solution in the regenerator is
given in the problem statement in terms of the
regenerator temperature and the inlet desiccant
solution concentration.
m& reg , w = f ( Treg , X reg ,i )
sol sol
7.2
Given: Passive solar system
Find: Equation for calculating cost and savings
life-cycle economics
Here,
Cs ,tot is the extra cost of using passive features over
(c)
an equivalent conventional facility
CRF is the capital recovery factor
Tprop is the assessed tax rate for the property
Cs ,ass is the marginal assessed value of the passive
features
M is the annual maintenance cost
ES ann is the annual energy savings
CE is the cost of energy. Another factor can be
7.4
added to account for the change in energy Given: 200 m2 Denver residence
prices annually. Find: Aux. Heating required, solar projected
area and concrete storage mass for 10 C
Note that the maintanence cost can be negligibly temperature swing. Use rules of thumb
small in a well designed passive system. Operating
costs are neglected, tax credits are also neglected. For aux. heating energy required, use Eq. (7.5).
Assume
NLC Floor area = 120 ( kJ / C day.m 2 )
NLC = 24, 000 ( kJ / C day ) 7.5
Given: 2000 ft2 house in Boston, MA. NLC=
Good LCR (cold climate) = 410 (kJ/m2. C-day)
12,000 Btu/F-day, Ap=150 ft2. Direct gain
Table 5.3 has degree data for Denver.
system, double glazing, night-time
Qnet = NLC ( No. of degree days ) insulation, and 30 Btu/ft2F thermal
storage capacity. Use LCR method.
Total DD in the year = 2622 Find: annual aux. heating energy requirement,
Q storage mass and dimensions
SSF = 1 aux
Qnet
Qaux = (1 SSF ) NLC ( No. of degree days ) LCR = NLC Ap = 12, 000 ( Btu / F day ) 150 ft 2 ( )
(
LCR = 80 Btu / ft 2 .F .day )
From Fig. 7.5, a reasonable value of SSF for Denver
= 0.7
From Table A7.1 in Appendix 7, system
classification is A3
Qaux = (1 SSF ) NLC ( No. of degree days )
= (1 0.7 ) 24, 000(kJ / C day )2622( Deg .C days ) Using Table A7.2 (LCR tables for Boston)
DD=5621
= 18,878, 400(kJ )
SSF=0.1653
Ap =
24, 000
410
= 58.5 m2( ) (b) For heat capacity of 30 Btu/ft2-F, using the
To find the concrete storage mass required, assume data for masonry
direct absorption of radiation by the storage mass, Required mass density is
thermal swing of storage temperature for 10 C (
30 Btu / ft .F
2
)
room air-temperature swing is 20 C.
t
=
0.2 ( Btu / lb.F )
( )
= 150 lb / ft 2
Heat capacity required based on rule of thumb This corresponds to 1 ft thick walls.
613 ( kJ / o C ) per m2 of projected glazing area.
Assuming Trombe wall area same as the projected
Therefore area,
mc p T = Ap 613 T
Ap 613 Mass = 22,500 lbs.
m=
cp
m=
( ) (
58.5 m 2 613 kJ / m 2 o C ) 7.6
Given: house in P 7.5
kJ kg .o C
( o
)
0.2 Btu lbm. F 4.187 o Find: Annual SSF for different types of passive
Btu lbm. F systems
= 42,824 ( kg )
Use appropriate table from Appendix 7
Thermal capacity of concrete from Table A3.5.
Type Classification SSF
direct gain DGA3 0.165
vented Trombe wall TWD4 0.172
Unvented Trombe wall TW14 0.145
waterwall WWB4 0.179 For Boston, Heating degree days in March = 846 F-
sunspace SSB4 0.193 deg.day,
Use table A7.1(b) to find system classification
DGB3 system.
7.7
Given: 200 ft2 vented 12 thick Trombe wall 12, 000 ( Btu/F-day )
LCR = (
= 80 Btu/ft 2 .F-day )
added to house in P 7.5, similar storage.
Find: Annual aux. Heating requirement,
( )
150 ft 2
Trombe wall dimensions From table A7.3 for DGB3 system, A=0.5601,
B=0.9839, C=1.3520, D=1.1510, R=0.8879,
For more than one reference system, determine G=2.38, H=0.00, LCRs=0.0, STDV=0.032
individual reference system SSF using total area.
The determine aperture area weighted SSF for the Using Eq.(7.8) in book,
combination. K = 1 + G LCR = 1 + 2.38 80 = 1.03
Total projected area = 200 + 150 = 350 ft2 Calculate S, the monthly insolation absorbed by a
vertical surface per unit of projected solar area.
(
LCR = NLC Ap = 12,000 350 = 34.3 Btu / ft 2 .F .day ) Insolation = 961 Btu/ft2.day, from weather data in
Passive Solar Design Handbook. This can also be
Use Table A7.1C to determine classification as calculated by correlations from Horizontal surface
TWA3 data.
Using LCR tables in A7.2for Boston
S = 961( Btu / ft 2 .day ) 31( days ) 0.8 0.96
SSF=0.226
Similarly for the reference system in Problem 7.5
SSF = 0.294 (
= 22,879.5 Btu / ft 2 .month )
Calculate aperture weighted SSF.
Eq. (7.10) gives
150 0.294 + 200 0.226
SSF = = 0.255 22,879.5 846 0.0 0.00
350 X=
80 1.03
= 0.328
(a) Annual Aux. Energy Requirement
Since X R
= (1 SSF ) NLC DD F = AX
= (1 0.255 ) 12, 000 ( Btu / F day ) 5621( F day ) = 0.5601 0.328
= 0.184
= 50.25 106 ( Btus )
(b) For Trombe wall of 12 inch thickness, the From Eq. (7.7)
storage capacity per unit area is 30 Btu/ft2-F SSF = 1 1.03 (1 0.184 )
The Trombe wall mass, assuming a face area same = 0.159
as Ap is (refer P7.5) 52,500 lbs
Qaux = (1 0.159 )12, 000 ( Btu / F .day ) 846 ( F .deg.day )
= 8.54 106 ( Btu / month )
7.8
Given: 2000 ft2 house in Boston. NLC=12,000
Btu/F-day, Ap=150 ft2, direct gain system
Find: Use SLR method, find Aux. Energy
7.9
required in March
Given: Boston House of P 7.8
Find: Heating season Aux. Energy Requirement
Use the LCR method. From tables in Appendix enough, it is reasonable to assume that comfort
A7.2 conditions exist.
SSF=0.169
DD for heating season in Boston = 5621 7.12
Qaux = (1 0.169 )12, 000 ( Btu / F .day ) 5621( F .deg.day ) Given: 4m 5m 3m room
= 56.05 106 ( Btu / year ) Find: Design a stack effect solar chimney
For 80 F and 82.5 fpm velocity, and the Based on the average temperatures, the radiative
information given in page 309, using a linear heat transfer per unit area can be calculated as
interpolation, 80 F and 86 fpm velocity would be
at comfort conditions. Since the numbers are close
(
qrc = Tbody
4
Tsky
4
) 7.16
(
= 0.9 5.67 108 303.154 291.84 ) Given: An office space with dimmer control
( )
system
= 61 W / m 2 Find: payback period for dimmer control system
Convective heat transfer The lighting control system would cost $600.00 to
For quiescent air, the free convection coefficient install for this given space at $1 / ft2
would be expected to be around 5-10 W/m2.K. Assume that the office operates 50 hours a week
throughout the year. The lighting energy saving is
Assuming a value of 10, the convection heat
transfer would be around 10(30-24.2) = 58 W/m2. (
ES L = 50 ( hr/week ) 52 ( weeks/yr ) 2 W/ft 2 )
600(ft 2 )0.3/1000
= 936 (kWh)
7.14 Using Eq. (7.24)
Given: Buried Pipe Example (7.4) f
Find: Which flow rate leads to least expensive EST = ES L 1 + c
installation? COP
0.5
= ES L 1 +
Case #pipes Length/pipe Total 2.5
= 1.2 ES L
length
250 cfm 8 200 ft 1600
750 cfm 2 250 ft 500 Total energy savings (annual) is 1123.2 kWh
1250 cfm 2 286 ft 572 Annual saving is $112.30
A simple payback period of 5.34 years is then
calculated. Considering interest rates, the actual
Of the cases considered, the best option is to use the
payback period would be longer.
750 cfm case, since the total length of pipe required
is the smallest, to meet the design conditions. The
pressure drop and the cost of a blower should also
factor in the calculations, but are not considered 7.17
here. Given: Vertical, south facing windoe at solar
noon. 36N
Find: Illuminances (sun, sky and ground
reflected) on clear and overcast days on June 21st
7.15
and Dec 21st.
Given: Data from Fig. 7.9
Find: Design, 9 ft deep ground pipe, in Dallas
For June 21st.
(June) for 1000 cfm @ 75F, when outside
Julian day = 172
temp = 90F
Hour angle hs = 0
Calculate declination angle from Eq. (2.23) as
The year round average temperature for Dallas is
about 66F. Factoring in a phase lag of 75 days for s = 23.45sin 360 ( 284 + n ) 365
The temperature in the ground, a temperature of = 23.45o
about 65F (value chosen for convenience) is a Altitude angle from Eq. (2.28)
reasonable assumption. From Fig. 7.9, for that sin = cos L cos s cos hs + sin L sin s
flowrate, the temperature drop per 100 ft at 1000
cfm is about 5F. = 77.45o
The temperature drop is linear in the pipe, upto The sun-window azimuth angle difference (asw)can
about 250 feet. Assume it holds upto 300 feet. be easily shown to be zero.
Then we need around 3000 feet of pipe.
Using Figs. 7.13 and 7.14, the various illuminances
can be calculated. The table below summarizes the Cs Ks Esp
results.
Max 0.0206 0.145 456 fc
June 21st Dec. 21st
Mid 0.0153 0.110 257 fc
Min 0.0106 0.105 170 fc
Solar Altitude 77.45 Solar Altitude 30.55
Direct Sunlight 2000 fc Direct sunlight 6800 fc
E gp = C g K g K m Esg Aw
Clear Summer Skylight Clear Winter Skylight
1300 fc 1100 fc Ground reflected: Table 7.4 c
Overcast 1200 fc Overcast 400 fc Cg Kg E gp
Horizontal Surface Horizontal Surface Max 0.0147 0.124 21 fc
Clear sky + direct Clear sky + direct = Mid 0.0128 0.123 18 fc
=10800 fc 5500 fc Min 0.0106 0.0994 12 fc
Overcast Sky = 1900 fc Overcast sky = 1000 fc
Reflectivity = 0.10 Reflectivity 0.10
Reflected component Reflected component
Clear sky + direct - Clear sky + direct -
7.19
540 fc 275 fc
Given: Room, dimensions, and window position,
Overcast sky - 95 fc Overcast sky - 50 fc
date and time.
Find: Clear sky day and cloudy day illuminances
Cs Ks Esp
Max 0.0188 0.122 262 fc 7.21
Given: Skylight dimensions, properties
Mid 0.0054 0.0939 58 fc
Find: Net transmittance
Min 0.0029 0.101 33 fc
Determine effective dome transmittance using Eq.
E gp = C g K g K m Esg Aw (7.32)
Ground reflected: Table 7.4 c TD1 = 1.25 0.8 (1.18 0.416 0.8 )
Cg Kg E gp
= 0.85
Max 0.0098 0.140 4.3 fc
Mid 0.0062 0.107 3.6 fc TD2 = 1.25 0.7 (1.18 0.416 0.7 )
Min 0.0041 0.0984 2.4 fc
= 0.78
Note that the ground reflected values do not
contribute much in the overcast situation. Use Eq. (7.33) to combine the single dome
transmittances
0.85 0.78
7.20 TD =
Given: 5 cities 0.85 + 0.78 0.85 0.78
Find: Determine clear and cloudy day horizontal = 0.68
illuminances on skylights on Dec 21st
The well index is calculated as Eq. (7.34)
2 ( 3 + 5) K u = Tn ( RCU )
WI =
235 = 0.45 0.9536
= 0.533 = 0.43
Using Fig. 7.16, for 80 % reflective wall The required work-plane illuminance is known.
N w = 0.75 Use Eq. (7.39) to determine number of skylights
Given, needed.
RA = 0.9
Tc = 1 A
ETWP = EH T K u K m
AWP
Using Eq. (7.35), the net skylight transmittance can
10 4 n
be calculated as 100 = 6000 0.429 0.70
Tn = TD N w RATc 2500
= 0.682 0.75 0.9 1 Where n is the number of skylights.
= 0.46
This gives a value for n=3.44
5 7 ( 50 + 50 )
RCR =
( 50 50 )
= 1.4
= 0.9536
=
( 285.3 + 782.1 5.55 ) = 0.329
2870.65
T p h s 8.2
(C) (Mpa) (kJ/kg) (kJ/kg.K) Given: Regenerative Rankine cycle conditions,
3 350 5 3068 6.449 s.h. vap. 90% turbine and pump efficiencies
4 188 1.2 2751 6.449 wet vap. Find: Work and Heat inputs/outputs, efficiency
4 188 1.2 2782.7 6.519 wet vap.
8.4
This is easily shown to be Given: Engine efficiency, load and collection
V4
Wnet = mR ln (TH TL ) conditions
V3 Find: Collector area required
The heat added is the sum of the heat required to
preheat the gas from the regenerator temperature to The efficiencies and the heat input are calculated
the temperature of isothermal heat addition and the according to
heat input in the isothermal expansion process.
273 + 5 net = e c
carnot = 1 = 0.244
273 + 95 U r (Tr T ) T
0.244 ( ) ( )
engine = = 0.122 I c CR Tr
2 =k
Ur T2
4kW +
T
Qinput = = 32.79kW I c CR Tr
0.122
Assuming that the pump operates only during the Differentiate with respect to Tr and equate to zero.
day, the required collector area is d net U r T2 T
32.79 3600 =k 2 1 + ( ) 2 = 0
Ac =
0.5 2800
= 84.3m 2 dTr I c CR Tr Tr
Solving for Tr
( ) I c CR
Tr = T + T
8.5
UR
Given: Rankine cycle efficiency vs. max cycle
temperature, various working fluids Use the following ambient temperature values of
Find: Preliminary analysis of three different 13.8 C (287 K) for both locations, based on
collector types and corresponding suitable weather data. For the linear-focus collector, assume
working fluid for Washington D.C. and collector characteristics of
Albuquerque, NM U r = 5W / m2 K , ( ) = 0.8, = 0.9, CR = 1.5
For Washington, assuming 8 hours of sunlight,
The key is to match the receiver temperature, which I c = 3000 / 8 = 375 W/m2.
will be closely related to the maximum working
0.8 0.9 375 1.5
fluid temperature, to the choice of working fluid at Tr = 287 + 287
each location. Solar data for each location obtained 5
from: = 325K
For Albuquerque, use I c = 5000 / 8 = 625 W/m2.
http://rredc.nrel.gov/solar/old_data/nsrdb/redbook/at
las/ 0.8 0.9 625 1.5
Tr = 287 + 287
5
Refer to the footnote on pg. 586, for Table A2.3b.
= 348K
The average annual radiation is
For the paraboloid disk collector,
kWh/m2.day Washington Albuquerque
Concentrator (single 3-4 5-6 U r = 2W / m 2 K , ( ) = 0.8, = 0.9, CR = 30
axis track) For Washington, assuming 8 hours sunlight
2-Axis tracking 4-5 6-7 I c = 4000 / 8 = 500
2-Axis tracking flat 6-7 8-10
0.8 0.9 500 30
plate Tr = 287 + 287
2
To estimate the receiver temperature, determine the = 1278K
collector efficiency first as For Albuquerque, use I c = 6000 / 8 = 750 W/m2.
U (T T )
c = ( ) r r Tr = 287
0.8 0.9 750 30
+ 287
I c CR
2
The cycle/engine efficiency can be expressed as a
fraction of the Carnot efficiency as = 1550K
For the CPC
T
e = k 1 U r = 2W / m 2 K , ( ) = 0.8, = 0.9, CR = 3
Tr It is reasonable to assume that 2-axis tracking CPC
The total efficiency is would see all of the direct and a good fraction of the
diffuse radiation. Hence, the 2 axis tracking flat
plate collector radiation data is used, although the
estimate could be a little high. For Washington, 305
assuming 8 hours sunlight e = 0.6 1
423
I c = 6000 / 8 = 750
net = e c
0.8 0.9 750 3 = 0.17 0.61 = 0.10 = 10%
Tr = 287 + 287
2 The pump power input is 37.3 kW (50 hp). Thus,
= 561K the required collector area is
For Albuquerque, use I c = 8000 / 8 = 1000 W/m2. 37,300
Ac = = 504 m2
740 0.10
0.8 0.9 1000 3
Tr = 287 + 287
2
= 626K 8.7
From the temperature values, converting to Given: Energy delivery eqn for solar collector
Fahrenheit and using the supplied efficiency chart, Find: Expression for work output for solar
In both Washington and Albuquerque, use R-12 powered heat engine
for line-focus collectors.
Use multistage steam plants with Paraboloidal The useful energy or energy delivered is given as
concentrators for both Washington and T f4
qu = ( )eff I c
Albuquerque. CR
Toluene is a good choice using CPCs For the Carnot cycle case,
Albuquerque has much better clear sky conditions W = c qu
as compared to Washington D.C., so the storage
T T f4
( eff ) I c
requirements would be substantially lower there. = 1
Tf
Notes: CR
This is only a preliminary analysis. There are
T T f3 T f4
several other factors that affect the choice of = ( eff ) I c ( eff ) I c TT f
1
+
working fluids and operating temperature for any CR CR
location and collection system. Differentiate with respect to T f and equate to zero.
T T f2 T f3
= ( eff ) I cTT f2 + 3
dW
4
8.6 dT f CR CR
Given: Solar powered ORC pumping water T T f4 T f5
Find: Collector area needed in Albuquerque 0 = ( eff ) I cT + 3 4
CR CR
Assume a heat rejection temperature of 305 K and For the Brayton cycle case,
that the ORC engine works at 60% of the Carnot W = B qu
efficiency. Then the engine efficiency is CT T f4
T = 1 B
( eff ) I c
e = 0.6 1 Tf CR
Tr
with Tr = 423 K, T8 = 305 K. = ( eff ) I c CB ( eff ) I c TT f1
U (T T ) CBT T f3 T f4
c = ( ) r r +
I c CR CR CR
Assuming some values for these factors Differentiate with respect to T f and equate to zero.
( ) = 0.8, = 0.9, CR = 3,U r = 2W / m2 K C T T f T f 2 3
= CB ( eff ) I cTT f2 + 3 B
dW
Assume the solar intensity of direct radiation is 4
dT f CR CR
about 740 W/m2K from the previous problem.
2 ( 423 305 ) CBT T f4 T f5
c = 0.8 0.9 = 0.61 0 = CB ( eff ) I cT + 3 4
740 3 CR CR
Chapter 9 0.36 1068 5.34 0.41 2.17
Photovoltaics 0.365 1132 5.66 0.41 2.33
0.37 1181 5.91 0.42 2.46
0.375 1157 5.79 0.42 2.45
0.38 1120 5.60 0.43 2.40
0.385 1098 5.49 0.43 2.38
9.1 0.39 1098 5.49 0.44 2.41
Given: GaAs 0.395 1189 5.95 0.45 2.65
Find: Wavelength corresponding to bandgap 0.4 1429 7.15 0.45 3.22
From table 9.2, bandgap of GaAs is 1.40 eV 0.405 1644 8.22 0.46 3.75
=
hc
=
( ) (
6.625 1034 3 108 ) 0.41 1751 8.76 0.46 4.05
0.415 1774 8.87 0.47 4.15
E 1.40 1.6 1019 0.42 1747 8.74 0.47 4.14
= 8.87 107 m = 0.887 m 0.425 1693 8.47 0.48 4.06
0.43 1639 8.20 0.48 3.97
9.2 0.435 1663 8.32 0.49 4.08
Given: Blue light incident on GaAs 0.44 1810 9.05 0.50 4.49
Find: Theoretical max efficiency 0.445 1922 9.61 0.50 4.82
E 0.45 2006 10.03 0.51 5.09
max = BG 0.455 2057 10.29 0.51 5.28
E photon 0.46 2066 10.33 0.52 5.36
1.40 1.6 1019 0.465 2048 10.24 0.52 5.37
=
( )
6.625 1034 3 108 0.45 106
0.47
0.475
2033
2044
10.17
10.22
0.53
0.54
5.39
5.47
= 0.507 = 50.7% 0.48 2074 10.37 0.54 5.61
0.485 1976 9.88 0.55 5.40
0.49 1950 9.75 0.55 5.39
9.3 0.495 1960 9.80 0.56 5.47
Given: GaAs cell 0.5 1942 9.71 0.56 5.47
Find: Theoretical maximum efficiency 0.505 1920 9.60 0.57 5.47
Use the zero air mass spectrum from appendix 2 0.51 1882 9.41 0.57 5.41
Only radiation of wavelength smaller than 0.887 m 0.515 1833 9.17 0.58 5.32
has sufficient energy to excite the material 0.52 1833 9.17 0.59 5.37
0.525 1852 9.26 0.59 5.48
Calculate efficiency at all wavelengths and 0.53 1842 9.21 0.60 5.50
0.535 1818 9.09 0.60 5.48
numerically integrate
0.54 1783 8.92 0.61 5.43
Wavelength energy in band efficiency output
2 2 2 0.545 1754 8.77 0.61 5.39
(m) W/m .m (W/m ) (W/m )
0.55 1725 8.63 0.62 5.35
0.29 482 36.15 0.33 1.58
0.555 1720 8.60 0.63 5.38
0.295 584 2.92 0.33 0.97
0.56 1695 8.48 0.63 5.35
0.3 514 2.57 0.34 0.87
0.565 1705 8.53 0.64 5.43
0.305 603 3.02 0.34 1.04
0.57 1712 8.56 0.64 5.50
0.31 689 3.45 0.35 1.20
0.575 1719 8.60 0.65 5.57
0.315 764 3.82 0.36 1.36
0.58 1715 8.58 0.65 5.61
0.32 830 4.15 0.36 1.50
0.585 1712 8.56 0.66 5.65
0.325 975 4.88 0.37 1.79
0.59 1700 8.50 0.67 5.65
0.33 1059 5.30 0.37 1.97
0.595 1682 8.41 0.67 5.64
0.335 1081 5.41 0.38 2.04
0.6 1660 8.30 0.68 5.61
0.34 1074 5.37 0.38 2.06
0.605 1647 8.24 0.68 5.62
0.345 1069 5.35 0.39 2.08
0.61 1635 12.26 0.69 8.43
0.35 1093 5.47 0.39 2.16
0.62 1602 16.02 0.70 11.20
0.355 1083 5.42 0.40 2.17
0.63 1570 15.70 0.71 11.15
0.64 1544 15.44 0.72 11.14 e V e V I
0.65 1511 15.11 0.73 11.07 exp o m 1 + o m = 1 + s
kT kT Io
0.66 1486 14.86 0.74 11.06
eoVm
0.67 1456 14.56 0.76 11.00 = 37.044
0.68 1427 14.27 0.77 10.94 kT
0.69 1402 12.62 0.78 9.82 Solve by trial and error to get
0.698 1374.6 6.87 0.79 5.41 Vm = 0.389 V
0.7 1369 8.21 0.79 6.48
0.71 1344 13.44 0.80 10.76 Determine current at max power point from Eq.
0.72 1314 11.83 0.81 9.60 (9.14)
0.728 1295.5 6.48 0.82 5.32 eoVm
0.73 1290 7.74 0.82 6.37
I L ,m =
kT
0.74 1260 12.60 0.83 10.51 ( I s + Io )
eoVm
0.75 1235 13.59 0.85 11.49 1+
0.762 1205.5 12.06 0.86 10.36 kT
0.77 1185 10.67 0.87 9.26
0.78 1159 11.59 0.88 10.19 =
37.044
(
(1 + 37.044 )
)
5 + 1.8 10 7
0.79 1134 11.34 0.89 10.10
0.8 1109 8.87 0.90 8.00 = 4.675 A
0.806 1095.1 13.69 0.91 12.44 PL , m = I L ,mVm
0.825 1048 12.58 0.93 11.70
= 1.819W
0.83 1036 5.18 0.94 4.85
(c) To obtain 100 W output,
0.835 1024.5 8.20 0.94 7.72
0.846 998.1 12.48 0.95 11.90
100/1.819 = 55 cells are needed.
0.86 968 11.62 0.97 11.26
To obtain 12 V output,
0.87 947 7.10 0.98 6.97
12/0.389 = 30.84 = 31 cells are needed
0.875 436.5 3.71 0.99 3.66
0.887 912.5 11.41 1.00 11.41
total 548.79
To meet the load, use 62 cells with two sets of
31 cells in series in parallel with each other.
Efficiency = 548.79/1353 = 40.6%
9.5
9.4
Given: Insolation, collection area, V and I
Given: Si cell, Io, Isc
Find: Array efficiency
Find: OCV, Pmax, and No. of cells to supply a
load
Array power output:
(a) Voc : Use Eq. (9.10)
Pout = V I
kT J s
Voc = ln + 1 = 50 15
eo J o
= 750W
Js Is
=
Jo Io Efficiency
23 750
1.381 10 313.15 5 =
Voc = 19
ln 7
+ 1 650 10
1.602 10 1.8 10
= 11.54%
= 0.463Volts
(b) Max power output
Using Eq. (9.12) to determine Vm
9.6
Given: Pmax, Insolation
Find: Insolation for increased power output
Assuming that the efficiency of the array does not Find: PV output required
change with increasing illumination intensity: Since the average PV output is 200 W, the battery
would not be required, assuming clear sky
600 17 conditions. Then the PV output requirement is
Intensity = = 1020W / m 2
10 Load inverter = 480 0.85
= 564.7Wh / day
9.9
Given: System from P 9.7
Find: Sunlight for batt. Charging
Assume that the battery is at 100 % charge level and
depleted by the load at night.
________________________________________________________________________________________
9.17
Given: Pumping application
Find: Design system
=
( VgH
& )
p
=
( )
1( kg/l ) 5000 ( gal ) 3.78 ( l/gal ) 9.81 ms -2 50 ( m )
0.30
= 30.9 ( MJ/day )
= 8,584 ( Wh/day )
case (a), 10 ppb Use Eq. 10.20 to determine the required intensity.
ln (10 300 ) I k
t= I= o
0.0128 a ko
= 265.7 ( min ) =
35 0.210
1.14 0.283
case(b) 99.9 % destruction = 22.8(W/m 2 )
10.2
Short answer questions
a. Illumination Intensity: Photocatalytic reaction
rates increase with higher illumination intensity.
However, the increase is not linear. The
generally observed dependence shows a
x
I
k = ko
function of the form
Io
x <1
Area =
(119.05MJ / s 3600 24 365) air with products coming out at 1000 K would be
calculated by substituting values into Eq. (11.12),
(17.33MJ / kg 7200kg / ha.) and using data from Table 11.6 for enthalpies at
Area = 30, 089hectares different temperatures
Notes: 1( 42, 769 9364 ) + 2 ( 35,882 9,904 )
The assumption of the power plant operating at full
capacity 24/7/365 is not really valid. +5.643 ( 30,129 8, 669 )
595, 400 12 ( 0 ) + 32 ( 0 ) + 12 ( 0 ) + 5.643 ( 0 )
capacity =
( 2.19 108 kg / year 490liters / ton ) Since the overall thermodynamic efficiency is 55 %,
907.185kg / ton the methane requirement can be calculated from the
heat of reaction of the oxidation of methane.
capacity = 11.83 106 liters / year Assuming that the reactants are at 298 K
CH 4 + 2O2 CO2 + 2 H 2O (l )
H R = 393,520 + 2 285,830 + 74,850
11.7
= 890,330 kJ / kmol Given: 2000 bpd ethanol plant using Jerusalem
= 55, 645.6 kJ / kg artichokes
Hence, it is an exothermic reaction. The kg/h of Find: Feedstock and crop area requirement
methane required can be calculated as
2, 000 3600(kJ / h) 2,000 bpd ethanol plant, using Jerusalem artichokes.
m& methane (kg / h) =
( 0.55 55, 645.6(kJ / kg ) ) From Table 11.4, yield is 45,000 kg/ha. Ethanol
yield from Jerusalem artichokes is 90 liters/ton
= 235.25(kg / h) (section 11.4.1).
2000 barrels = 317,940 litres
Therefore, quantity of Jerusalem artichokes required
11.5 is
Given: Coal plant considering co-firing, alkali 317,940 /90 = 3533 tons.= 3,204,765 kg.
limit in ash The annual land area needed to cultivate feedstock
Find: Max. switchgrass content in feedstock, therefore is
expected sulfur emissions 3, 204, 765 365
= 26, 000ha.
45, 000
Switchgrass has a heating value of 18.4 MJ/kg, with
15.1 % Alkali in ash, and 10.1 % ash in fuel.
Assuming all of the alkali content comes from 11.8
switchgrass and using the limit of 0.34 kg alkali/GJ Given: 10 MW power plant, cycles
fuel heating value, the quantity of switchgrass Find: annual fuel cost
required for 0.34 kg alkali content is
0.34
= 22.294kg 10 MW power plant fueled with Hybrid Poplar
0.101 0.151 ($48/ton). For a conventional steam plant with a
The mass of coal required with 22.294 kg heat rate of 14,000 Btu/kWh, the thermodynamic
switchgrass to bring heating value up to 1 GJ is efficiency of the steam plant can be calculated as
6
( 6
)
1, 000 10 22.294 18.64 10 = 20.873kg th =
1
3
=
1
HR 0.2931 10 14, 000 0.2931 103
28 106
The maximum percentage of switchgrass is 51.6 %. 1
= = 0.2437
Then the expected sulfur emission is 4.1034
20.873 0.04kg / GJ = 0.835kg / GJ Annual energy input for the 10 MW plant operating
365/24 is
11.6
( 10
0.2437) 365 24 3600MJ = 1.294 109 MJ
Given: Base plant capacity and cost Using heating value of hybrid poplar from the text
Find: Predicted cost for twice capacity as 19 MJ/kg, the fuel requirement is
6.81 107 kg
Base plant 5000 bpd @ $60 million. or approximately 75,067 tons of hybrid poplar
Cb = 60, 000, 000 annually. At $48/ton, the fuel cost is $3.6 million
per year. By gasifying, the net thermal efficiency of
Sb = 5000
biomass to electricity conversion is
Using Eq. (11.24), using n= 0.6
th = 0.5 0.85 = 0.425
( )
0.6
C = 60, 000, 000 10, 000 Following the calculations above, the biomass
s 5, 000
requirements would be calculated to be 43,040 tons
= 90,900, 000 annually. The fuel cost at $48/ton is $2.07 million.
The predicted cost for a plant of twice the capacity
is about $91 million.
11.9
Given: coal and switchgrass costs
Find: tax required don CO2 emissions to make
biomass (switchgrass) competitive
12.1
Given: Initial cost, interest rate, mortgage term
Find: Annual payment
12.2
Given: Solar system cost, energy delivered, interest rate, backup fuel cost, inflation
Find: Total cost curve, cost-optimal system size
cf = 7 = $511.74 / GJ
0.08
600000
500000
400000
cost($)
300000
200000
100000
0
0 100 200 300 400 500 600 700
collector area
12.3
Given: payment, discount rate
Find: present worth
12.4
Given: p 12.3, new discount rate
Find: present worth
The costs involved are the mortgage costs (principal and interest), tax savings on interest,
power cost, maintenance cost, scrap value, and fuel savings.
Year Ann. payment M&P Tax credit Ann. Salvage Fuel saving Cash flow
1 934.92 90 172.80 197.25 550.00 -104.87
2 934.92 99 161.43 197.25 605.00 -79.24
3 934.92 108.90 149.03 197.25 665.50 -32.04
4 934.92 119.79 135.52 197.25 732.05 10.11
5 934.92 131.77 120.79 197.25 805.26 56.61
6 934.92 144.95 104.73 197.25 885.78 107.81
7 934.92 159.44 87.23 197.25 974.36 164.48
8 934.92 173.38 68.16 197.25 1071.79 226.90
9 934.92 192.92 47.37 197.25 1178.97 275.75
10 934.92 212.22 24.70 197.25 1296.87 371.68
10
Cash flow
Present worth = = $425.20
(1.09 )
n
n =1
12.6
Given: 8 %, 20 year loan
Find: Difference in CRF for monthly and annualized payments
On an annual scale
CRF(8,20) = 0.10185
The monthly time scale would require an annual payment of 1.45% less than the annual
time scale.
12.7
Given: Collector data, P 12.2
Find: Production function
1000
900
y = 332.39x - 1214.2
800
R2 = 0.9963
700
600
Qs (GJ)
500
400
300
200
100
0
3 3.5 4 4.5 5 5.5 6 6.5 7
ln(Ac)
Using the data in a spreadsheet program such as Microsoft Excel, the production function
can be easily computed. See plot above
Qs = 1214.2 + 332.39 ln ( Ac )
12.8
Given: Production function for a solar water heating system and costs
Find: cost-optimal collector area
(
CT = 20 Ac + 9 140 12 Ac0.6 )
Differentiating and equating to zero
dCT
= 20 64.8 Ac0.4 = 0
dAc
Solving for optimal collector area
Ac ,opt = 18.9 m2
12.9
Given: Building heat demand data for January
Find: Compare proposed solar system and energy conservation measures