Uninterruptible Power Supply Unitfor Universal Use

QUINT-DC-UPS/24DC/20

1. Short Description
Uninterruptible Power Supply Units for Buffering
Long-Term Power Interruptions
Saves space thanks to the compact, uniform design
Integrated diode saves money through isolation of
loads
Maximum system availability through optimum
battery management and reliable signaling
Minimum installation time due to ready-to-use
plug-in bridges and integrated timeout
QUINT-DC-UPS uninterruptible power supply units
with long-life lead-acid batteries provide long buffer
times at high currents. Even in the event of a longer
supply voltage failure, the units ensure that all
connected devices continue to operate without
interruption.
The devices have a narrow and uniform design,
which makes them ideal for use on the DIN rail where
space is limited. In addition, short wiring paths ensure
order and clarity in the control cabinet.
The high level of availability and the particularly long
service life of the battery modules are achieved
through professional battery management. An
automatic presence check (every minute), automatic
quality test (once a week), temperature-determined
charging, and electronic overcurrent protection ensure
the battery modules are ready to operate at all times.
Power is therefore available in the event of an error and No additional installation is required for shutdown. In
the service life of the battery module is maximized. addition, ready-to-use plug-in bridges minimize the
The actual state must be determined quickly so that installation time.
the right decision can be made in an emergency. The connected devices can be divided into buffered
Optimum signaling is thus required for maximum and unbuffered loads using the isolated input. This
system availability. Three floating PDT contacts and extends the buffer time, which depends on the output
three LEDs are provided for function monitoring, which current. If only critical devices are protected using
indicate all the operating states clearly. fuses, smaller battery modules can be used that save
So that relay signaling is more reliable and more money and space in the control cabinet. In addition, the
durable than before, an additional positive supply isolated input protects the connected devices against
output has been provided. The contact, which is errors in the internal network.
current-limited and resistant to continued short circuits,
is located next to the relay connections and enables
easy bridging. In the event of wiring errors, the short-
circuit protection prevents any welding of the relay
contacts. This ensures that the user can rely on an OK
signal. Even in the event of connection errors, currents
remain below 100 mA, which prevents damage to the
relay contacts.
A system is switched off after a specific time that can
be set on the device or by an external signal.

Headquarters: Phoenix Contact GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg Germany
Phone +49 - 52 35 - 30 0 Fax +49 - 52 35 - 34 12 00 www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

2. Technical Data

125 mm
(4.921 in.)

t...[m in ] 1 1
J

R e m o te
R 1

O n /O ff

A la r m
B a t.-S e le c t [A h ] 1 2
1 3
+ R 2

(5.118 in.)
2 1

B a t. M o d e

130 mm
2 x 1 2 V
- 2 2
B a tte ry + 2 4 V
2 0 0 m A 2 3

In p u t O u tp u t 3 1

C h a rg e
D C 2 4 V 0 -2 0 A D C
3 2
3 3

66 mm
(2.598 in.)

QUINT-DC-UPS/24DC/20

DC UPS Module UuF


Solid Stranded Torque
[mm2] AWG [Nm][ lb in]

Input 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 10.6 - 13.3


Output 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 10.6 - 13.3 7 mm (0.28 in.)
Signal 0.2 - 2.5 0.2 - 2.5 25 - 14 0.5 - 0.6 4.5 - 5.3

Pcs.
Description Type Order No. Pkt.
Uninterruptible power supply unit QUINT-DC-UPS/24DC/20 28 66 23 9 1
3.4 Ah battery module QUINT-BAT/24DC/3,4Ah 28 66 34 9
7.2 Ah battery module QUINT-BAT/24DC/7,2Ah 28 66 35 2
12 Ah battery module QUINT-BAT/24DC/12Ah 28 66 36 5

Technical Data

Input Data
Nominal input voltage 24 V DC
Input voltage range 22.5 - 30 V DC
Current consumption (no load/charging/maximum) 0.1 A/2.0 A/22.0 A
Switching threshold Ua< 22 V; dynamic Uin - 1 V/0.1s
Buffer time Can be configured 0.5; 1; 2; 3; 5; 10; 15; 20; 30; continuous
Input fuse Internal, 25 A
Maximum power dissipation (Ready/buffer mode) 15 W/20 W
Output Data
Can be connected in parallel (battery module) Yes, to increase the buffer time
Output Data in Normal Operation
Nominal output voltage 24 V DC
Output voltage Uin
Output current 20 A
Current limit None
Overload fuse Internal, 25 A
Output Data in Buffer Mode
Nominal output voltage 24 V DC
Output voltage Maximum 27.9 V DC
Output current 20 A
Current limit 27 A
Overload fuse Electronic
Level of efficiency (Typical) 95%
Remote shutdown Yes
Charging
Charge characteristic curve I/U characteristic curve
End-of-charge voltage Temperature compensated
Charge current < 2.5 A
Battery presence check/time interval 60 seconds
Battery quality test/time interval 180 hours
Memory Medium External
Nominal voltage 24 V DC
Nominal capacity 3.4 Ah, 7.2 Ah, 12 Ah
Charge current < 2.5 A

PHOENIX CONTACT page 2 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

Signaling
Power In OK Green LED
Alarm Red LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Battery Mode Yellow LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Battery Charge Yellow LED, flashing, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Approvals/Standards
Electrical equipment of machines EN 60 204
Electrical safety (of IT equipment) EN 60950/VDE 0805,
UL/C-UL Recognized UL 60 950
Industrial control equipment UL/C-UL Listed UL 508
Shipbuilding Germanischer Lloyd
Electronic equipment for use in electrical power installations EN 50 178/VDE 0160

General Data
Insulation voltage
Input/output to housing: 1 kV AC type test
1 kV AC routine test
Mounting position On a horizontal 35 mm (1.378 in.) DIN rail
EN 60 715
1 kV/1 kV
Degree of protection IP20
Class of protection II
MTBF According to IEC 1709 (SN 29 500) > 500,000 h
Housing version AluNox (AlMg1), closed
Dimensions (W x H x D) default upon delivery (66 x 130 x 125 mm [2.598 x 5.118 x 4.921 in.])
Dimensions (W x H x D) rotated 90 (122 x 130 x 69 mm [4.803 x 5.118 x 2.717 in.])
Weight Approximately 0.8 kg
Climatic Data
Ambient temperature Operation/storage -25C to +70C (-13F to +158F)/-40C to +85C (-40F to +185F)
Humidity At +25C (+77F) 95%, no condensation
Vibration According to IEC 68-2-6 15 Hz - 150 Hz, 2.3 g, 90 minutes

Shock (in all space directions) According to IEC 68-2-27 30 g


Pollution degree According to EN 50 178 2
Climatic category According to EN 60 721 3K3

c
Conformance With EMC Directive 89/336/EEC
and Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility) QUINT-DC-UPS/24DC/20
Noise Immunity Acc. to EN 61000-6-2 Housing Level 4
EN 61000-4-22) Contact discharge: 8 kV
Electrostatic discharge (ESD) Air discharge: 15 kV

EN 61000-4-31) Housing Level 3


Electromagnetic HF field Frequency/Field strength: 80 - 1000 MHz/10 V/m

EN 61000-4-42) Input, output: 2 kV (Level 3)4)


Fast transients (burst): Signal: 1 kV (Level 2)4)

EN 61000-4-52) Input, output, signal: 0.5 kV4)/0.5 kV3)/(Level 1)


Surge current loads (surge):

EN 61000-4-61) I/O/S: Level 3


Conducted interference Frequency/U0: 0.15 - 80 MHz/10 V

Noise Emission According to EN 50081-2


Radio interference emission EN 55011 (EN 55022) Class B5)
Radio interference voltage EN 55011 (EN 55022) Class B5)
EN 55011 corresponds to CISPR11/EN 55022 corresponds to
CISPR22/EN 61000 corresponds to IEC 1000
1)
Criterion A: Normal operating characteristics within the
specified limits.
2)
Criterion B: Temporary adverse effects on the operating
characteristics that the device corrects
automatically.
3)
Symmetrical: Cable to cable.
4)
Asymmetrical: Cable to ground.
5)
Class B: Industrial and domestic applications.

PHOENIX CONTACT page 3 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

3. Device View, Connections, and Control Elements

8
7

13
3 14 D
14O DC
OK C
K ++
++
9
+2
4V
0,2 13
A 3 14 D

www.interface.phoenixcontact.com
11 14 O DC
21OK C
QUINT DC-UPS 20 A
K +
31 + +
R1 + /20 A
1 DC /22 C
4 2

11
13
22
23
R2
R1 C-U8 6
T-D 2
/24 9 DC VD
PS 23 24V -30 0A
6
e: V
.5 /2
22 DC
Ala 32 Re U IN No.: lt ag 24
m R2 Q er- o C
rm 33 ote lV
21 Ordut: ona 70 F -2
Ba 3 OF
Inperati + 58 0-6
00
Mo t.- 1 ONF
Optput: 5+1 61 81-1
de Ba -2 EN 500
Ou 3
Ch t.- -1 EN
5 ar
ge 2
5

B
Ala

Ba at.-M
rm
Ala
rm
AL
S TR
US OL T
IA
L
F
t.-C o de OV INDNTRMEN
ha de Mo e PR COUIP
rg t.- arg AP EQKA
Po
e Ba -Ch 43

U
t.
6 t
we
r In
OK
Ba
we
r In
OK
LIS
TE
D

m Po
[m ax 0,5 1
in] 2 ns
io
ct
3
ru
D Ba
t.-S
30
st
In C 24
5
ele
20 in
pu c
15 10 n
io
+ t V [A t Ser at
h] vice
a ll g

20
O A
u
+ tput
3
7,
1 2
2
,4 s t tin
in nec
a d con
0
R e re
fo
Ba
t
+ ter
be
!
y
"
1
2 $
3

Figure 04

1 DC input: 24 V unbuffered 4. Safety Notes and Warning


Input voltage 24 V DC
(0.5 mm2 to 16 mm2 solid)
Instructions
(0.5 mm2 to 10 mm2 stranded)
(20 - 6 AWG) To ensure that the device can be operated safely
Internal fuse 25 AT and all functions can be used, please read these
2 DC output: 24 V buffered instructions carefully.
Output voltage 24 V DC
(0.5 mm2 to 16 mm2 solid) Caution: Never carry out work when the
(0.5 mm2 to 10 mm2 stranded) (20 - 6 AWG) power is turned on, this is highly
The device is idling-proof and short-circuit-proof. dangerous.
3 24 V battery module connection
4 Floating PDT (11,12,13): Alarm
5 Floating PDT (21,22,23): Battery Mode
6 Floating PDT (31,32,33) The QUINT-DC-UPS is a built-in device. Installation
7 24 V supply voltage, and startup must only be carried out by qualified
maximum current limit 0.2 A for grouped contacts personnel. The relevant country-specific regulations
11, 21, 31 (e.g., VDE, DIN) must also be observed.
8 Remote shutdown (R1, R2) Before startup it is particularly important to ensure
9 Universal DIN rail adapter UTA 107 that:
0 Red LED: Alarm All supply lines have sufficient fuse protection and
! Yellow LED: Battery Mode/Battery Charge
" Green LED: Power In OK are the correct size.
Buffer time setting 0.5 - 30 minutes All output cables are the correct size for the maximum
$ Battery module/Service setting selection device output current or have separate fuse
protection.
Sufficient convection is ensured.

PHOENIX CONTACT page 4 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

5. Installation

5.1. Mounting
The uninterruptible power supply unit together with
the battery module can be snapped onto all DIN rails
according to EN 60715 and should be mounted
horizontally (input terminal blocks facing downwards). 13
3 14 D
14O DC
OK C
K ++
++
+2
4V
0,2 13

Installation Dimensions A 3 14 D

www.interface.phoenixcontact.com
11 14 O DC
21OK C

QUINT DC-UPS 20 A
K +
31 + +
R1 + /20 A
12 DC /22 C
13 R2 /24 9 DC VD
PS 23 24V -30 0A
22 6
C-U8 6 2.5 C/2
11 23 R1 T-D 2 :2 D
Re IN No.: ge 24V
Ala 32
m R2 QU er- lta
rm 21 33 ote rd l Vo 0 C
O ut: ona 7 -2
Ba 3 OF
Inperati + 58 F 0-6
00
Mo t.- 1 ONF
Optput: 5+1 61 81-1
-2

No minimum spacing to other modules is de Ba


Ch t.-
arg
e
Ou
2
5 -1
3 EN 500
EN

required for proper operation of the B


Ala

Ba at.-M
rm
Ala
rm
AL
S TR
US OL T
IA
L
F
t.-C o od e
e OV INDNTRMEN
ha de PR COUIP
rg t.-M arg AP EQKA
e Ba -Ch
device. Po

t
m
we
r In
OK
Ba

Po
t.

we
r In
OK
U LI
STE
D
43

[m ax 0,5 1 ns
in] ti o
2
3 uc
D Ba
t.-S
30
s tr
In C 24
5
ele
20 in
15 10 n
pu
t V
c
[A t ti o
+ 20 h]
Se
rvice ll a g
s ta tin
in nec
3
O A ,4
ut 7,2
a d con
1
pu 2
+ t R e re
fo
e
Ba b
tte
+ r y

Figure 05

5.2. Narrow Mounting Position


The device is supplied ex works for a narrow
mounting position.

Mounting:
Place the module with the DIN rail guideway on the
Mounting
top edge of the DIN rail and then snap it downwards.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the bottom edge of the
DIN rail.

5.3. Flat Mounting Position


A flat mounting position can be achieved by
mounting the module onto the DIN rail at a 90 angle. Removal
To do this, mount the DIN rail adapter (UTA 107) 7 as
shown in Figure 7. No additional assembly material is
required. Mounting screws: Torx T10
(torque 0.8 - 0.9 Nm).
Figure 06

Figure 07

PHOENIX CONTACT page 5 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

QUINT-DC-UPS
QUINT-BAT/24DC
Power
AC Supply Input Output Battery + Unbuffered
+ + + + Load


DC +

Buffered
Load


DC +

Figure 08

3
5.4. Connection 14OD
DC
OK C
K ++
++
+2
The following cable cross sections can be connected: 4V
0,2
A
13
3 14 D
11 14 O DC
Solid Stranded AWG Torque 21OK C

QUINT DC-UPS 20 A
K +
31 + +
[mm2] [mm2] [Nm] 12
R1 +
R2 24
DC
/20
22
C/ D
13 S/ 3 9 VD 0V
UP66 2 24.5-3 /20
1 Input: 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 11
22
23 R1 T :-
-
DC 28
e : 22VDC
IN No. ag 24
2 Output: 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 Al
ar
m 21
32
33
Re
m R2
ot
e
QUder-
Or ut: iona
lV
olt
70
+ 58
3 Battery: 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 Ba 3
t
Mo .- 1
OF
ONF
Inperat
p
O tpu t : 5+1
de Ba -2
4-8
-- Signal: 0.2 - 4 0.2 - 2.5 25 - 12 0.5 - 0.6 Ch t.-
ar
O u
2
5 -1
3

ge

l
B
Al
ar
m
Al
a rm LS
R
ST L
IA
L
F
For reliable and safe-to-touch Ba at.-
t.-CMo
ha de
de
Mo e P RO
VA NDUTROENT
I N M
COUIP
rg t.- arg AP
connections: Strip 10 mm (0.39 in.) Po
e Ba -Ch
t.
EQKA
43

U
we
B a K
r In nO
from the input and output side t
m
OK
Po
we
rI LIS
TE
D

[m ax 0,5 1
connector ends and 7 mm (0.28 in.) Ba
in] 2
3
D 30

from the signal connector ends. In C 24


pu
t.-S
ele 0
c
[A t
2
15 10
5

+ t V Se

To maintain UL approvals, use copper cables, which h] rvic


20 a
st
e

O A
ut 7
1 ,2
3
,4 in n
a d con
are designed for operating temperatures > 75C pu 2
+ t R e ore
f
be
(167F). To meet GL requirements, unused terminal +
Ba
tte
ry
compartments should be closed.

5.5. Input (1, Figure 4, Figure 8) Figure 09


The QUINT-DC-UPS is connected to the 24 V DC
output of the power supply via the "Input +" and
"Input -" terminal blocks. The output is isolated from the
input by the internal diode. The stored power is only
supplied to the output. The device is protected against
overcurrent and short circuit by an internal input fuse.

Fuse
Additional device protection is not required, as an
internal fuse is present.

If the internal fuse is blown, this is


most probably due to a device fault.
In this case, the device should be
checked in the factory.

PHOENIX CONTACT page 6 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

5.6. Output
All devices that must be supplied without interruption
in the event of a supply voltage failure ("Buffered
Load"), are connected to the "Output +" and "Output -"
terminal blocks of the DC output (Fig. 8). It is 20 12 Ah

Current [A]
recommended that all other loads, which do not require 15 7.2 Ah
buffering ("Unbuffered Load"), are connected to the 10 3.4 Ah
24 V DC output of the power supply. 5
This increases the buffer time, as this time depends 0
on the output current (see Fig. 10). The internal diode 30 60 90 120
ensures that the buffered loads are isolated from the
Time [min.]
unbuffered loads. Figure 10

5.7. Battery Module


The battery module is connected to the
QUINT-DC-UPS via the "Battery +" and "Battery -" t.-CMo
ha de Mo e
terminal blocks. To interrupt the charge/discharge rg
e a t.- harg AP
B -C
current of the battery module, the "Battery module Po t.
Ba OK
U
we
selection" selector switch $ must be set to "Service". r In
OK r In
t we L
m
[m ax 0,5 1 Po
The fuse on the battery module in] 2

must be removed when installing or DC Ba 30


3

replacing the battery module. t.-S 2


5
ele 0 $
pu 24 V
15 10
c
t [A t Se
20 h] rvic
e

The QUINT-DC-UPS is optimized for use with


O A
u
3
7,2
,4

+ tput
1
2

QUINT-BAT/24DC type battery modules.


The following battery modules are recommended: Ba
tte
QUINT-BAT/24DC/3,4AH (Order No. 2866349) + ry
QUINT-BAT/24DC/7,2AH (Order No. 2866352)
QUINT-BAT/24DC/12AH (Order No. 2866365)
Figure 11
Following successful installation, the capacity of the
connected battery module must be selected using the
"Battery module selection" rotary switch $.

5.8. Signaling Outputs


The signal outputs are connected via terminal blocks
11/12/13 4, 21/22/23 5 or 31/32/33 6. The contacts
are floating contacts. The plug-in bridge provided can
be used to supply +24 V to grouped contacts 11,21,31.
This means that N/C contacts 12,22,32 and N/O
contacts 13,23,33 can be evaluated as switching
outputs with 0 V and +24 V voltage levels.

PHOENIX CONTACT page 7 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

5.9. Remote Shutdown ("Remote", Fig. 12)


The device has a UPS remote shutdown function for
specific shutdown.
Remote shutdown must be deactivated for the device 13
3 14 D
14O DC
to switch to buffer mode in the event of a supply voltage OK C
K ++
failure. ++

Remote Shutdown Off V


0,2 13
A 3 14 D
11 14 O DC
The "Remote shutdown R1" and "Remote 21OK C
K +
31 + +
shutdown R2" terminal points are short circuited R1 +
1 8
(e.g., with a plug-in bridge) OR 2
13 R2
22
The "Remote shutdown R2" terminal point is 11 23 R1
I
supplied with a 24 V DC voltage Al
ar
m
32
33
Re
m R2
ot QUde
21 e Or u
The QUINT-DC-UPS switches to buffer mode in the Ba 3 OF p
In e
Mo t.- 1 ONF
Optp
event of a supply voltage failure de Ba Ou
Ch t.-
ar
ge
Remote Shutdown On Al
ar
The "Remote shutdown R1" and "Remote shutdown Ba
m
ar
m
Ba t.- Al e
R2" terminal points are not connected t.-CMo od
ha ed
rg t. -M arge AP
P
All LEDs are off e Ba C h
The QUINT-DC-UPS does not switch to buffer mode
in the event of a supply voltage failure, instead the
Figure 12
U
device is shut down. When the supply voltage is
reapplied, the battery module is charged and the
device remains off until remote shutdown is
deactivated.
Connected loads are supplied as long as the supply
voltage is present

6. Setting Options on the Device


B a
(Fig. 13) Ba at.- Al e
t.-CMo od
ha de
rg t . -M arge
Po
e Ba -Ch
6.1. Buffer Time Setting t.
Ba OK
we
r In
Buffer mode can be exited after a predefined time OK r In
has elapsed or by external shutdown (see 6.9). t we
m
[m ax 0,5 1 Po
If the device is to be shut down after a specific time in] 2
3
has elapsed, the time can be set via the selector switch Ba 30
t.-S 5
on the front of the device. ele 0
2
15 10
c
When the supply voltage is reapplied, the device can [A t Se
20 h] rvic
e
switch to buffer mode again. O A 3
,4
u 7,2 $
+ tput
1
2

6.2. Battery Module Setting


Before startup, the capacity of the battery module Ba
tte
used must be set on the device via the selector + ry
switch $. When replacing the battery, the selector
switch must be set to "Service" (see also 6.7).
Figure 13

PHOENIX CONTACT page 8 of 9


Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20

7. Method of Operation

In the event of a power failure at the output, the QUINT-DC-UPS supplies all connected devices with a 24 V DC
voltage without interruption at a load current up to 20 A. When the 24 V supply voltage is applied, the connected
battery module is charged. In the event of a supply voltage failure, the battery module is connected to the output,
and the stored power ensures that all connected devices continue to operate without interruption. The professional
signaling via function LEDs and floating PDT contacts enables reliable evaluation of all the main operating states.

7.1. Output Voltage


In normal operation, the QUINT-DC-UPS output voltage corresponds to the usual supply voltage. If the supply
voltage drops more than 1 V in the space of 0.1 seconds or falls below the minimum threshold of 22 V, the device
switches to buffer mode.
If the output voltage drops below 20.4 V in buffer mode, this is indicated by the Alarm indicator.
If the output voltage drops to 19.2 V because the battery module is flat, the device is shut down completely. When
the supply voltage is reapplied, the device automatically switches on again. The device is electronically short-
circuit-proof and idling-proof.

7.2. Signaling
Three floating PDT contacts and three indicators are provided for function monitoring.

Key/Indicators Green " Yellow ! Red 0


Power IN OK Bat. Mode/Charge Alarm
Supply voltage OK, ON Flashing OFF
battery module charging
Supply voltage OK, ON OFF OFF
battery module charged (normal operation)
Buffer mode OFF ON OFF

Battery module flat OFF OFF ON

- Battery module quality test negative ON OFF ON


- No battery module
- Service
- Buffer time elapsed OFF OFF OFF
- Remote shutdown activated

xx - xx: Contact closed,

http://www.phoenixcontact.com
1x Alarm, 2x Battery Mode, 3x Battery Charge
x1 group contact, x2 N/C contact, x3 N/O contact

Key/Output Bat. Charge Bat. Mode Alarm


6 5 4
Supply voltage OK, 31 - 33 21 - 22
battery module charging
Supply voltage OK, 31 - 32 21 - 22
battery module charged (normal operation)
Buffer mode 31 - 32 21 - 23
TNR: 102034-00

Battery module flat 31 - 32 21 - 22 11 - 13

- Battery module quality test negative 31 - 32 21 - 22 11 - 13


- No battery module
- Service
- Buffer time elapsed 21 - 22 11 - 13
- Remote shutdown activated
05/01/05

7.3. Temperature Response


The charging rate of the connected battery module depends on the temperature.
PHOENIX CONTACT

7.4. Testing the Battery Module


A quality test is carried out on the battery module once a week and its presence is verified every minute. A
negative test result is indicated by the Alarm indicator.

PHOENIX CONTACT page 9 of 9