QUINT-DC-UPS/24DC/20
1. Short Description
Uninterruptible Power Supply Units for Buffering
Long-Term Power Interruptions
Saves space thanks to the compact, uniform design
Integrated diode saves money through isolation of
loads
Maximum system availability through optimum
battery management and reliable signaling
Minimum installation time due to ready-to-use
plug-in bridges and integrated timeout
QUINT-DC-UPS uninterruptible power supply units
with long-life lead-acid batteries provide long buffer
times at high currents. Even in the event of a longer
supply voltage failure, the units ensure that all
connected devices continue to operate without
interruption.
The devices have a narrow and uniform design,
which makes them ideal for use on the DIN rail where
space is limited. In addition, short wiring paths ensure
order and clarity in the control cabinet.
The high level of availability and the particularly long
service life of the battery modules are achieved
through professional battery management. An
automatic presence check (every minute), automatic
quality test (once a week), temperature-determined
charging, and electronic overcurrent protection ensure
the battery modules are ready to operate at all times.
Power is therefore available in the event of an error and No additional installation is required for shutdown. In
the service life of the battery module is maximized. addition, ready-to-use plug-in bridges minimize the
The actual state must be determined quickly so that installation time.
the right decision can be made in an emergency. The connected devices can be divided into buffered
Optimum signaling is thus required for maximum and unbuffered loads using the isolated input. This
system availability. Three floating PDT contacts and extends the buffer time, which depends on the output
three LEDs are provided for function monitoring, which current. If only critical devices are protected using
indicate all the operating states clearly. fuses, smaller battery modules can be used that save
So that relay signaling is more reliable and more money and space in the control cabinet. In addition, the
durable than before, an additional positive supply isolated input protects the connected devices against
output has been provided. The contact, which is errors in the internal network.
current-limited and resistant to continued short circuits,
is located next to the relay connections and enables
easy bridging. In the event of wiring errors, the short-
circuit protection prevents any welding of the relay
contacts. This ensures that the user can rely on an OK
signal. Even in the event of connection errors, currents
remain below 100 mA, which prevents damage to the
relay contacts.
A system is switched off after a specific time that can
be set on the device or by an external signal.
Headquarters: Phoenix Contact GmbH & Co. KG Flachsmarktstrae 8 32825 Blomberg Germany
Phone +49 - 52 35 - 30 0 Fax +49 - 52 35 - 34 12 00 www.phoenixcontact.com
Local Contact: www.phoenixcontact.com/salesnetwork
Uninterruptible Power Supply Unit for Universal Use QUINT-DC-UPS/24DC/20
2. Technical Data
125 mm
(4.921 in.)
t...[m in ] 1 1
J
R e m o te
R 1
O n /O ff
A la r m
B a t.-S e le c t [A h ] 1 2
1 3
+ R 2
(5.118 in.)
2 1
B a t. M o d e
130 mm
2 x 1 2 V
- 2 2
B a tte ry + 2 4 V
2 0 0 m A 2 3
In p u t O u tp u t 3 1
C h a rg e
D C 2 4 V 0 -2 0 A D C
3 2
3 3
66 mm
(2.598 in.)
QUINT-DC-UPS/24DC/20
Pcs.
Description Type Order No. Pkt.
Uninterruptible power supply unit QUINT-DC-UPS/24DC/20 28 66 23 9 1
3.4 Ah battery module QUINT-BAT/24DC/3,4Ah 28 66 34 9
7.2 Ah battery module QUINT-BAT/24DC/7,2Ah 28 66 35 2
12 Ah battery module QUINT-BAT/24DC/12Ah 28 66 36 5
Technical Data
Input Data
Nominal input voltage 24 V DC
Input voltage range 22.5 - 30 V DC
Current consumption (no load/charging/maximum) 0.1 A/2.0 A/22.0 A
Switching threshold Ua< 22 V; dynamic Uin - 1 V/0.1s
Buffer time Can be configured 0.5; 1; 2; 3; 5; 10; 15; 20; 30; continuous
Input fuse Internal, 25 A
Maximum power dissipation (Ready/buffer mode) 15 W/20 W
Output Data
Can be connected in parallel (battery module) Yes, to increase the buffer time
Output Data in Normal Operation
Nominal output voltage 24 V DC
Output voltage Uin
Output current 20 A
Current limit None
Overload fuse Internal, 25 A
Output Data in Buffer Mode
Nominal output voltage 24 V DC
Output voltage Maximum 27.9 V DC
Output current 20 A
Current limit 27 A
Overload fuse Electronic
Level of efficiency (Typical) 95%
Remote shutdown Yes
Charging
Charge characteristic curve I/U characteristic curve
End-of-charge voltage Temperature compensated
Charge current < 2.5 A
Battery presence check/time interval 60 seconds
Battery quality test/time interval 180 hours
Memory Medium External
Nominal voltage 24 V DC
Nominal capacity 3.4 Ah, 7.2 Ah, 12 Ah
Charge current < 2.5 A
Signaling
Power In OK Green LED
Alarm Red LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Battery Mode Yellow LED, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Battery Charge Yellow LED, flashing, floating PDT,
30 V AC/DC, maximum; 1 A, maximum
Approvals/Standards
Electrical equipment of machines EN 60 204
Electrical safety (of IT equipment) EN 60950/VDE 0805,
UL/C-UL Recognized UL 60 950
Industrial control equipment UL/C-UL Listed UL 508
Shipbuilding Germanischer Lloyd
Electronic equipment for use in electrical power installations EN 50 178/VDE 0160
General Data
Insulation voltage
Input/output to housing: 1 kV AC type test
1 kV AC routine test
Mounting position On a horizontal 35 mm (1.378 in.) DIN rail
EN 60 715
1 kV/1 kV
Degree of protection IP20
Class of protection II
MTBF According to IEC 1709 (SN 29 500) > 500,000 h
Housing version AluNox (AlMg1), closed
Dimensions (W x H x D) default upon delivery (66 x 130 x 125 mm [2.598 x 5.118 x 4.921 in.])
Dimensions (W x H x D) rotated 90 (122 x 130 x 69 mm [4.803 x 5.118 x 2.717 in.])
Weight Approximately 0.8 kg
Climatic Data
Ambient temperature Operation/storage -25C to +70C (-13F to +158F)/-40C to +85C (-40F to +185F)
Humidity At +25C (+77F) 95%, no condensation
Vibration According to IEC 68-2-6 15 Hz - 150 Hz, 2.3 g, 90 minutes
c
Conformance With EMC Directive 89/336/EEC
and Low Voltage Directive 73/23/EEC
EMC (Electromagnetic Compatibility) QUINT-DC-UPS/24DC/20
Noise Immunity Acc. to EN 61000-6-2 Housing Level 4
EN 61000-4-22) Contact discharge: 8 kV
Electrostatic discharge (ESD) Air discharge: 15 kV
8
7
13
3 14 D
14O DC
OK C
K ++
++
9
+2
4V
0,2 13
A 3 14 D
www.interface.phoenixcontact.com
11 14 O DC
21OK C
QUINT DC-UPS 20 A
K +
31 + +
R1 + /20 A
1 DC /22 C
4 2
11
13
22
23
R2
R1 C-U8 6
T-D 2
/24 9 DC VD
PS 23 24V -30 0A
6
e: V
.5 /2
22 DC
Ala 32 Re U IN No.: lt ag 24
m R2 Q er- o C
rm 33 ote lV
21 Ordut: ona 70 F -2
Ba 3 OF
Inperati + 58 0-6
00
Mo t.- 1 ONF
Optput: 5+1 61 81-1
de Ba -2 EN 500
Ou 3
Ch t.- -1 EN
5 ar
ge 2
5
B
Ala
Ba at.-M
rm
Ala
rm
AL
S TR
US OL T
IA
L
F
t.-C o de OV INDNTRMEN
ha de Mo e PR COUIP
rg t.- arg AP EQKA
Po
e Ba -Ch 43
U
t.
6 t
we
r In
OK
Ba
we
r In
OK
LIS
TE
D
m Po
[m ax 0,5 1
in] 2 ns
io
ct
3
ru
D Ba
t.-S
30
st
In C 24
5
ele
20 in
pu c
15 10 n
io
+ t V [A t Ser at
h] vice
a ll g
20
O A
u
+ tput
3
7,
1 2
2
,4 s t tin
in nec
a d con
0
R e re
fo
Ba
t
+ ter
be
!
y
"
1
2 $
3
Figure 04
5. Installation
5.1. Mounting
The uninterruptible power supply unit together with
the battery module can be snapped onto all DIN rails
according to EN 60715 and should be mounted
horizontally (input terminal blocks facing downwards). 13
3 14 D
14O DC
OK C
K ++
++
+2
4V
0,2 13
Installation Dimensions A 3 14 D
www.interface.phoenixcontact.com
11 14 O DC
21OK C
QUINT DC-UPS 20 A
K +
31 + +
R1 + /20 A
12 DC /22 C
13 R2 /24 9 DC VD
PS 23 24V -30 0A
22 6
C-U8 6 2.5 C/2
11 23 R1 T-D 2 :2 D
Re IN No.: ge 24V
Ala 32
m R2 QU er- lta
rm 21 33 ote rd l Vo 0 C
O ut: ona 7 -2
Ba 3 OF
Inperati + 58 F 0-6
00
Mo t.- 1 ONF
Optput: 5+1 61 81-1
-2
Ba at.-M
rm
Ala
rm
AL
S TR
US OL T
IA
L
F
t.-C o od e
e OV INDNTRMEN
ha de PR COUIP
rg t.-M arg AP EQKA
e Ba -Ch
device. Po
t
m
we
r In
OK
Ba
Po
t.
we
r In
OK
U LI
STE
D
43
[m ax 0,5 1 ns
in] ti o
2
3 uc
D Ba
t.-S
30
s tr
In C 24
5
ele
20 in
15 10 n
pu
t V
c
[A t ti o
+ 20 h]
Se
rvice ll a g
s ta tin
in nec
3
O A ,4
ut 7,2
a d con
1
pu 2
+ t R e re
fo
e
Ba b
tte
+ r y
Figure 05
Mounting:
Place the module with the DIN rail guideway on the
Mounting
top edge of the DIN rail and then snap it downwards.
Removal:
Release the snap-on catch using a screwdriver and
then detach the module from the bottom edge of the
DIN rail.
Figure 07
QUINT-DC-UPS
QUINT-BAT/24DC
Power
AC Supply Input Output Battery + Unbuffered
+ + + + Load
DC +
Buffered
Load
DC +
Figure 08
3
5.4. Connection 14OD
DC
OK C
K ++
++
+2
The following cable cross sections can be connected: 4V
0,2
A
13
3 14 D
11 14 O DC
Solid Stranded AWG Torque 21OK C
QUINT DC-UPS 20 A
K +
31 + +
[mm2] [mm2] [Nm] 12
R1 +
R2 24
DC
/20
22
C/ D
13 S/ 3 9 VD 0V
UP66 2 24.5-3 /20
1 Input: 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 11
22
23 R1 T :-
-
DC 28
e : 22VDC
IN No. ag 24
2 Output: 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 Al
ar
m 21
32
33
Re
m R2
ot
e
QUder-
Or ut: iona
lV
olt
70
+ 58
3 Battery: 0.5 - 16 0.5 - 10 20 - 6 1.2 - 1.5 Ba 3
t
Mo .- 1
OF
ONF
Inperat
p
O tpu t : 5+1
de Ba -2
4-8
-- Signal: 0.2 - 4 0.2 - 2.5 25 - 12 0.5 - 0.6 Ch t.-
ar
O u
2
5 -1
3
ge
l
B
Al
ar
m
Al
a rm LS
R
ST L
IA
L
F
For reliable and safe-to-touch Ba at.-
t.-CMo
ha de
de
Mo e P RO
VA NDUTROENT
I N M
COUIP
rg t.- arg AP
connections: Strip 10 mm (0.39 in.) Po
e Ba -Ch
t.
EQKA
43
U
we
B a K
r In nO
from the input and output side t
m
OK
Po
we
rI LIS
TE
D
[m ax 0,5 1
connector ends and 7 mm (0.28 in.) Ba
in] 2
3
D 30
+ t V Se
O A
ut 7
1 ,2
3
,4 in n
a d con
are designed for operating temperatures > 75C pu 2
+ t R e ore
f
be
(167F). To meet GL requirements, unused terminal +
Ba
tte
ry
compartments should be closed.
Fuse
Additional device protection is not required, as an
internal fuse is present.
5.6. Output
All devices that must be supplied without interruption
in the event of a supply voltage failure ("Buffered
Load"), are connected to the "Output +" and "Output -"
terminal blocks of the DC output (Fig. 8). It is 20 12 Ah
Current [A]
recommended that all other loads, which do not require 15 7.2 Ah
buffering ("Unbuffered Load"), are connected to the 10 3.4 Ah
24 V DC output of the power supply. 5
This increases the buffer time, as this time depends 0
on the output current (see Fig. 10). The internal diode 30 60 90 120
ensures that the buffered loads are isolated from the
Time [min.]
unbuffered loads. Figure 10
+ tput
1
2
7. Method of Operation
In the event of a power failure at the output, the QUINT-DC-UPS supplies all connected devices with a 24 V DC
voltage without interruption at a load current up to 20 A. When the 24 V supply voltage is applied, the connected
battery module is charged. In the event of a supply voltage failure, the battery module is connected to the output,
and the stored power ensures that all connected devices continue to operate without interruption. The professional
signaling via function LEDs and floating PDT contacts enables reliable evaluation of all the main operating states.
7.2. Signaling
Three floating PDT contacts and three indicators are provided for function monitoring.
http://www.phoenixcontact.com
1x Alarm, 2x Battery Mode, 3x Battery Charge
x1 group contact, x2 N/C contact, x3 N/O contact