Pipe Support calculation

(Load is at Center of Beam)

Distance Between two support(S) = 6000 mm


Diameter of Pipe(D) = 1000 mm
Density of Steel() = 8000 kg/m (FRP=2000 kg/m)
Pipe Wall thickness(t) = 5 mm
Specific Gravity(g) = 9.81 m/s
Load on Support(W) = .D.t.S..g D

W= 7,399.54 N

Unit Weight of bar = 14.8 kg/m


Length of bar(L) = 2700 mm
Total Weight of bar = L.g W
Wb = 392.01 N

Weight of Media
Density of Water() = 1000 kg/m
Density of air() = 1.23 kg/m d
Load on Support(W) = .D.S..g
L
Wm = 56.88 N F1 F2
Therefore,
Total Force on Vertical support(F1) = W/2+w/2+Wm/2
= 3,924.22 N

Cross section Area of Beam(A) = 1920 mm

Tensile Stree on Vertical Beam = F/A


= 2.04 N/mm

Allowable tensile stress = 172 N/mm

Tensile stress < Allowable tensile stress

Moment of Inertia (I) = 3,440,000.00 mm4

Shear Stress on horizontal beam = F1/A

xy = 2.04 N/mm

Bending Moment due to Load(Mb) = F1 x d

= 5,297,693.25 N.mm

Beam width (y) = 100 mm


Beam Depth(h) = 100 mm

Stress on horizontal Beam (x) = Mb.y/I

= 77.00 N/mm

Combined stress is simplfied formula of Strain Energy Distorsion using Von Mises Theory of
Failure Equition and the bending stress & shear stress for Y-Z and Z-X plane will be zero.
Effective Stress = [2{ (x-y) + (y-z) + (z-x) + 6(xy+yz+zx)}]^0.5/(2)^0.5

= [(2x + 6 xy)]^0.5 /(2)^0.5

= 77.08 N/mm2

Allowable shear stress = 140 N/mm

Effective stress < Allowable shear stress

Modulus of Elascity (E) = 210,000.00 N/mm

Deflection of Horizontal Beam = 5FL3/384 EI

= 3.86201838E+14
2.774016E+14

= 1.39 mm

Allowable deflection of beam = L/240 (assume)

= 11.25 mm

Defelction Due to Weight < Allowable deflection of beam

Therefore, The support is safe.


entry data

calculated data

fixed data
Pipe Support calculation ###
(Load is at Cantilever of Beam) ###

Distance Between two support(S) = 3000 mm (Maximum)


Diameter of Pipe(D) = 1000 mm D
Density of Steel() = 8000 kg/m
Pipe Wall thickness(t) = 5 mm
Specific Gravity(g) = 9.81 m/s2

Load on Support(W) = .D.t.S..g

W = 3,699.77 N

H
Unit Weight of bar = 17.9 kg/m X2
Length of bar(L) = 2000 mm
Total Weight of bar = Unit mass x L x g X1
Wb = 351.20 N
X

Weight of Media
Density of Water() = 1000 kg/m
Density of air() = 1.23 kg/m
Load on Support(W) = .D.S..g

Wm = 23,123.57 N

Total Load on Support(F) = W+Wb+Wm

= 27,174.54 N

Distance from support to F (d) = 1000 mm


Moment due to Load (Mb) = Fxd

= 27,174,541 N.mm

Distance of lowest bolt from base of support


X = 50 mm

Total vertical length of support(H) = 1200 mm

X1 = 600 mm [50+(800-100)/2]

X2 = 1150 mm [800-50]

Force on Bolt per mm Fb = Mb/(X+X1+X2)

= 16.13 N/mm

Force on top bolt F = Fb x (H-X)


= 18,546.42 N

= 18.55 KN
Recommended Force = 30.00 KN (From Hilti Stud Anchor)
Total force on bolt < Recommended Force
Therefore,
The Stud anchor is safe for supporting system.

Cross sectional area of beam (A) = 2,720 mm


Moment of Inertia(I) = 19,500,000 mm4
Beam width (y) = 200 mm (U Channel)
Beam Depth(h) = 80 mm (U Channel)
Shear Stress on horizontal Bar = F/A
xy = 9.99 N/mm

Stress on horizontal Beam (x) = Mb.y/I

x = 139.36 N/mm

Combined stress is simplfied formula of Strain Energy Distorsion using Von Mises Theory of
Failure Equition and the bending stress & shear stress for Y-Z and Z-X plane will be zero.

Effective Stress = [2{ (x-y) + (y-z) + (z-x) + 6(xy+yz+zx)}]^0.5/(2)^0.5

= [(2x + 6 xy)]^0.5 /(2)^0.5

= 140.43 N/mm
Allowable Stress = 172 N/mm

Effective Stress < Allowable Stress

Pipe+Water weight(Fp) = 26,823.34 N

Modulus of Elascity (E) = 210,000.00 N/mm

Deflection due to wt of pipe


and water = Fp d(3L-d)/6 E I

= 1.3411671E+14
2.457E+13

= 5.46 mm

Deflection due to wt of beam


and water = FL/8EI

= 0.09 mm

Total Deflection = 5.54 mm

Allowable Deflection = L/240

= 8.33 mm

Defelction Due to Weight < Allowable deflection of beam

Therefore, The support is safe.