Address No.

Parameter Settings Options Settings


Differential Protection settings
112 DIFF.PROTECTION Enabled/Disabled Enabled
143 TRANSFORMER NO/YES YES
149 charge I comp. Enabled/Disabled Disabled
201 CT Starpoint towards line/ towards busbar Towards Busbar
205 CT Rated Primary Current 10.10000 A 250 A
206 CT Rated Secondary Current 1 A/ 5 A 1A
207 System Star point - Solid Earthed
208 1-1/2 CB NO/YES NO
251 K_ALF/K_ALF_N 1.0010.00 1.50
253 CT E % at K_ALF/K_ALF_N 0.550.0 % 13 %
254 CT E % at K_ALF_N 0.550.0 % 20 %
1111 X' 0.0050 .. 9.5000 /km 0.1459 /km
1112 C' 0.000 .. 100.000 F/km 0.1580 F/km
1113 Line Length 0.1 .. 1000.0 km 0.50 km
1114 Tot. Line length 0.1 .. 1000.0 km 0.50 km
1140 I-CTsat. Thres. 0.2 .. 50.0 A;
1161 VECTOR GROUP U 011 0
1162 VECTOR GROUP I 011 0
1163 TRANS STP IS - Solid Earthed
1201 STATE OF DIFF. OFF/ON ON
1210 I-DIFF> 0.10 .. 20.00 A 0.11 A
1213 I-DIF>SWITCH ON 0.10 .. 20.00 A 0.11 A
1217 T-DELAY I-DIFF> 0.00 .. 60.00 sec; 0.00 sec
1218 T3I0 1PHAS 0.00 .. 0.50 sec; 0.00 sec
1219 I> RELEASE DIFF 0.10 .. 20.00 A; 0 0
1221 Ic-comp. OFF/ON OFF
1224 IcSTAB/IcN 2.0.4.0 2.0
1233 I-DIFF>> 0.8 .. 100.0 A; 1.9 A
1235 I-DIF>>SWITCHON 0.8 .. 100.0 A; 1.9 A
2301 INRUSH REST. OFF/ON ON
2302 2nd HARMONIC 10 .. 45 % 15 %
2303 CROSS BLOCK OFF/ON OFF
2305 MAX INRUSH PEAK 1.1 .. 25.0 A 9.40 A
2310 CROSSB 2HM 0.00 .. 60.00 sec;
Distance Protection settings
Power System Data 2 (Secondary Values) - -
1103 Measurement: Full Scale Voltage (100%) - -
1104 Measurement: Full Scale Current (100%) - -
1105 Line Angle - -
1511 Angle of inclination - -
1107 P,Q operational measured values sign - -
1116 Zero seq. comp. factor RE/RL for Z1 - -
1117 Zero seq. comp. factor XE/XL for Z1 - -
1118 Zero seq. comp.factor RE/RL(> Z1) - -
1119 Zero seq. comp.factor XE/XL(> Z1) - -
Distance protection - -
1501 Distance protection - -
1502 Phase Current threshold for dist. meas. - -
1511 Angle of inclination - -
1508 Series compensated line - -
1532 Instantaneous trip after SwitchOnToFault - -
1533 Zone Z1 blocked by diff. active - -
1541 R load, minimum load impedance (ph-e) - -
1542 PHI load, maximum load angle (ph-e) - -
1543 R load, minimum load impedance (ph-ph) - -
1544 PHI load, maximum load angle (ph-ph) - -
1617A Single pole trip for faults in Z2 - -
1657 Z1B enabled before 1st AR (int. or ext.) - -
1503 3I0 threshold for neutral current pickup - -

SB401H01
1504 3U0 threshold zero seq. voltage pickup - -
1507A 3I0>-pickup-stabilisation (3I0> /Iphmax) - -
1509A criterion of earth fault recognition - -
1521A Loop selection with 2Ph-E faults - -
1510 Condition for zone timer start - -
1605 T1-1phase, delay for single phase faults - -
1606 T1multi-ph, delay for multi phase faults - -
1615 T2-1phase, delay for single phase faults - -
1616 T2multi-ph, delay for multi phase faults - -
1625 T3 delay - -
1635 T4 delay - -
1645 T5 delay - -
1665 T6 delay - -
1655 T1B-1phase - -
1656 T1B-multi-ph - -
Distance zones (quadrilateral) (Secondary Values) - -
1601 Operating mode Z1 - -
1602 R(Z1), Resistance for ph-ph-faults - -
1603 X(Z1), Reactance - -
1604 RE(Z1), Resistance for ph-e faults - -
1605 T1-1phase, delay for single phase faults - -
1606 T1multi-ph, delay for multi phase faults - -
1607 Zone Reduction Angle (load compensation), - -
1651 Operating mode Z1B (overrreach zone), - -
1652 R(Z1B), Resistance for ph-ph-faults - -
1653 X(Z1B), Reactance - -
1654 RE(Z1B), Resistance for ph-e faults - -
1655 T1B-1phase, delay for single ph. faults - -
1656 T1B-multi-ph, delay for multi ph. faults - -
1657 Z1B enabled before 1st AR (int. or ext.), - -
1611 Operating mode Z2, - -
1612 R(Z2), Resistance for ph-ph-faults - -
1613 X(Z2), Reactance - -
1614 RE(Z2), Resistance for ph-e faults - -
1615 T2-1phase, delay for single phase faults - -
1616 T2multi-ph, delay for multi phase faults - -
1621 Operating mode Z3 - -
1622 R(Z3), Resistance for ph-ph-faults - -
1623 X(Z3), Reactance - -
1624 RE(Z3), Resistance for ph-e faults - -
1625 T3 delay, - -
1631 Operating mode Z4, - -
1632 R(Z4), Resistance for ph-ph-faults - -
1633 X(Z4), Reactance - -
1634 RE(Z4), Resistance for ph-e faults - -
1635 T4 delay, - -
1641 Operating mode Z5, - -
1642 R(Z5), Resistance for ph-ph-faults - -
1643 X(Z5)+, Reactance for Forward direction - -
1644 RE(Z5), Resistance for ph-e faults - -
1645 T5 delay, - -
1646 X(Z5)-, Reactance for Reverse direction - -
1661 Operating mode Z6, - -
1662 R(Z6), Resistance for ph-ph-faults - -
1663 X(Z6)+, Reactance for Forward direction - -
1664 RE(Z6), Resistance for ph-e faults - -
1665 T6 delay, - -
1666 X(Z6)-, Reactance for Reverse direction - -