Your ref : ES20150331-96563 Building Engineering Group (#12-00)

Our ref : E2501-00024-2014-ST01 Tel : 68044581


Date : 23/06/2015 Fax : 63342561
E-mail : lim_meng_may@bca.gov.sg

Developer :
MINISTRY OF EDUCATION
1 NORTH BUONA VISTA DRIVE
LEVEL 1
SINGAPORE 138675

Dear Sir

WRITTEN DIRECTION

PROPOSED CONVERSION OF THE TEMPORARY STRUCTURE TO PERMANENT


STRUCTURE OF A 2-STOREY CONTAINER CLASSROOMS WITH SHELTERED LINKWAY
TO EXISTING EAST VIEW PRIMARY SCHOOL ON LOT ON LOT06126N MK 28 AT 4
TAMPINES STREET 91 SINGAPORE 528907 (TAMPINES PLANNING AREA) ON LOT (S)
06126N MK28 AT 4 TAMPINES STREET 91 SINGAPORE 528907

I refer to your *application / resubmission for approval of structural plans which was received on
23/06/2015.

2 Please comply with the requirements specified in the attached Schedule. If you are unable to
comply with all the requirements by 07/07/2015, you may apply for an extension of time. Any application
for extension of time is to reach this Division at least 5 days before this expiry date.

3 Please note that if you are unable to comply with all the requirements by the date specified or such
other period as may be extended, the structural plans shall, by virtue of Section 5(4) of the Building
Control Act (Cap 29), be DEEMED TO HAVE BEEN DISAPPROVED.

Yours faithfully

LIM MENG MAY


For COMMISSIONER OF BUILDING CONTROL

Qualified Person: Accredited Checker :


ER. TAN BIN KEONG
B K TAN CONSULTANTS
510 GEYLANG ROAD
#02-04 THE SUNFLOWER
SINGAPORE 389466

Qualified Person (Geotechnical): Specialist Accredited Checker:

PABE01300: ST Written Direction


52 Jurong Gateway Road, #11-01, Singapore 608550
Tel: 1800-34252222 Fax: 63344287 email: bca_enquiry@bca.gov.sg
www.bca.gov.sg An MND Statutory Board
Project Ref No.: E2501-00024-2014

THE SCHEDULE

Please note that if compliance by the Accredited Checker (AC) (or the Specialist Accredited Checker,
where appropriate) is necessary, the Qualified Person (QP) for structural works (or Qualified Person for
geotechnical works, where appropriate) is required to collate and resubmit together with the ACs
compliance/certificate.

Item Description Compliance


No. By
1 Refer to item 1 of our WD issued 13 April 2015. Please comply. QP

2 We refer to our reply on item 2 of our WD, please note that the matter is not QP
addressed to. We are referring to the following:
i) Reinforced Concrete
(a) Dimensional check of all footings, pilecaps, beams and columns
-Please follow Direction: all footings, beams, columns need to be
checked for the size.

(b) Verification of steel reinforcement through ferro-sensing or visual


confirmation.
-Verify the reinforcement through visual confirmation (Destructive
Test) : 2 samples

(c) Confirmation of concrete strength through examination and crushing of


cores, ultrasonic pulse velocity, rebound hammer, etc.
-Confirmation of concrete strength through destructive test : 2 test on
7 days and 2 test on 28 days

(d) Confirmation of strength of steel reinforcements through laboratory


tests on extracted samples
-Confirmation of strength of steel reinforcement through laboratory
test: 2 samples.

ii) Steel
(a) Dimensions of all steel sections used as beams and columns,
-Please follow Direction: all footings, beams, columns need to be
checked for the size.

(b) Determination of steel grades by physical tests


-To test by laboratory (Cast laboratory)

(c) Bolt and welded connections by appropriate tests, e.g. magnetic-


particle inspection, ultrasonics, etc.
-Welded connection to be tested by magnetic particle inspection : 5
PABE01300: ST Written Direction
52 Jurong Gateway Road, #11-01, Singapore 608550
Tel: 1800-34252222 Fax: 63344287 email: bca_enquiry@bca.gov.sg
www.bca.gov.sg An MND Statutory Board
areas
- Bolt connection by physical examination at the site

3 Please withdraw the submission if you are unable to comply by 7 July 2015. QP

(This letter is generated through electronic means and is a computer printout. No signature is required)

PABE01300: ST Written Direction


52 Jurong Gateway Road, #11-01, Singapore 608550
Tel: 1800-34252222 Fax: 63344287 email: bca_enquiry@bca.gov.sg