Вы находитесь на странице: 1из 12

DADOS...

M T T
C..
5 22OV 2 plos 220V
38OV 4 plos 380V
POTNCIA MECNICA 44OV 6 plos 440V
APLICADA AO EIXO
8 plos 480V

Funcion.:Horas/Dia e Dias/Ms COS Y Desejado


100 8 22 0.95

DIMENSIONAMENTOS : Tarifa kvarh 0.1000 R$

Dados do Motor sem a Correo:


Rendimento 0.846
Fator de Potncia Atual 0.83
Potncia Absorvida da Rede 4.37 kW
Consumo de Energia Ativa 769.74 kWh
Cons. de Energia Reativa Excedente Atual 8.35 R$ DESPERDCIO !!!
Corrente Aparente Atual 13.83 A
Potncia Reativa Real Necessria 1.50 kvar

ESCOLHA SOMENTE UM DOS MODELOS DE CAPACITORES TRIFSICOS


UCW-T MCW BCW

1.5 nenhum

Insero do Capacitor (Cor. Localizada):


Potncia Nominal do Capacitor Escolhido kvar
Nova Corrente Aparente no Circuito A
Fator de Potncia Alcanado
Consumo de Energia Reativa Excedente 0.00 R$ FIM DO DESPERDCIO!!!

Manobra e Proteo do Capacitor WEG:


Modelo do Contator Tripolar A
Fusveis contra Curto-Circuito A

CLCULO DO RETORNO DO INVESTIMENTO:


Informe o Valor do Oramento da Correo R$1,500.00
Retorno do Capital Investido 179.7 Meses

A WEG TEM AS SOLUES PARA O MELHORAMENTO DA EFICINCIA


ENERGTICA DE SUA INSTALAO. CONSULTE-NOS !
Vnculos Resultados Resultados Finais
Potncia (cv) 11
Tenso da Rede 1
Polaridade 2
Tenso Nom. Capacitor 1
Carga Aplicada ao Eixo (%) 2
CosF Desejado 4
Nr. De Horas por Dia 18
Dias de Func. no Ms 22
Fator de Potncia Atual 0.830
Rendimento 0.846
Potncia Absorvida (kW) 4.374
Cons. kWh/ms 769.74
Fat. kvarh Exc. Atual 83.47
Corrente do Motor (A) 13.83
Pot. Reativa p/elevar o Fator 1.50
Pot. Nom. Capacitor (UCW-T) 5 1.5
Pot. Nom. Capacitor (MCW) 20
Pot. Nom. Capacitor (BCW) 1 1
Potncia em kvar escolhida 1
Fator de Pot. Alcanado 0.950
Nova Ie do Circuito (A)
Nova FER 0.00
Corrente Nominal do Capacitor
Contator
Fusvel (A)
WEG ACIONAMENTOS - MOTORES W21 - 60Hz

MOTORES Fator de carga 75%


II plos IV plos VI plos VIII plos
cv kW FP h FP h FP h FP h
0.16 0.12 0.65 0.530 0.58 0.500 0.52 0.420 0.50 0.452
0.25 0.18 0.68 0.580 0.58 0.560 0.54 0.500 0.46 0.448
0.33 0.25 0.72 0.590 0.59 0.620 0.55 0.563 0.50 0.475
0.5 0.37 0.73 0.655 0.59 0.640 0.53 0.554 0.54 0.562
0.75 0.55 0.79 0.685 0.60 0.690 0.54 0.633 0.60 0.630
1 0.75 0.75 0.710 0.77 0.740 0.64 0.720 0.60 0.641
1.5 1.1 0.85 0.745 0.76 0.720 0.66 0.722 0.55 0.648
2 1.5 0.82 0.780 0.68 0.775 0.64 0.715 0.61 0.740
3 2.2 0.77 0.800 0.80 0.790 0.64 0.738 0.68 0.781
4 3 0.80 0.825 0.75 0.800 0.69 0.790 0.65 0.802
5 3.7 0.82 0.820 0.80 0.833 0.68 0.819 0.67 0.815
6 4.5 0.84 0.842 0.81 0.840 0.70 0.835 0.64 0.853
7.5 5.5 0.80 0.865 0.77 0.880 0.73 0.842 0.63 0.859
10 7.5 0.85 0.865 0.78 0.870 0.70 0.852 0.64 0.866
12.5 9.2 0.86 0.872 0.78 0.875 0.77 0.870 0.77 0.849
15 11 0.85 0.895 0.81 0.882 0.71 0.890 0.78 0.870
20 15 0.84 0.907 0.79 0.893 0.71 0.890 0.82 0.870
25 18.5 0.85 0.905 0.77 0.900 0.87 0.893 0.69 0.883
30 22 0.86 0.910 0.84 0.902 0.84 0.900 0.74 0.892
40 30 0.85 0.900 0.82 0.905 0.81 0.904 0.82 0.902
50 37 0.85 0.911 0.83 0.917 0.81 0.900 0.80 0.905
60 45 0.89 0.900 0.87 0.912 0.85 0.912 0.79 0.905
75 55 0.88 0.913 0.84 0.917 0.80 0.915 0.78 0.922
100 75 0.90 0.921 0.80 0.920 0.78 0.922 0.75 0.915
125 90 0.85 0.895 0.85 0.910 0.80 0.928 0.75 0.920
150 110 0.86 0.914 0.87 0.913 0.79 0.923 0.74 0.922
175 132 0.86 0.916 0.83 0.920 0.78 0.925 0.75 0.931
200 150 0.87 0.924 0.85 0.925 0.79 0.933 0.70 0.938
250 185 0.90 0.929 0.86 0.938 0.76 0.937 0.75 0.929
300 220 0.92 0.927 0.85 0.945 0.76 0.945 0.74 0.938
350 260 0.92 0.938 0.85 0.946 0.73 0.947 0.72 0.930
400 300 0.85 0.947 0.79 0.945
450 330 0.85 0.948 0.78 0.947
500 370 0.85 0.950

Dados de Motores Eltricos do Manual 050.03/102000.


Fator de carga 100%
II plos IV plos VI plos VIII plos
FP h FP h FP h FP h
0.70 0.581 0.66 0.560 0.58 0.463 0.54 0.502
0.75 0.619 0.66 0.640 0.61 0.574 0.50 0.505
0.78 0.629 0.69 0.670 0.61 0.581 0.54 0.520
0.83 0.684 0.69 0.680 0.62 0.623 0.62 0.623
0.85 0.710 0.70 0.710 0.63 0.656 0.68 0.645
0.83 0.745 0.82 0.780 0.72 0.725 0.68 0.651
0.87 0.757 0.83 0.727 0.72 0.732 0.62 0.677
0.89 0.805 0.76 0.800 0.72 0.735 0.68 0.747
0.84 0.815 0.85 0.793 0.72 0.766 0.74 0.781
0.86 0.840 0.82 0.827 0.76 0.794 0.72 0.813
0.88 0.845 0.83 0.846 0.75 0.825 0.73 0.827
0.87 0.843 0.86 0.842 0.75 0.840 0.72 0.858
0.87 0.865 0.82 0.885 0.78 0.844 0.71 0.863
0.88 0.870 0.84 0.890 0.75 0.858 0.72 0.868
0.89 0.875 0.86 0.877 0.82 0.875 0.82 0.866
0.89 0.895 0.86 0.883 0.78 0.890 0.83 0.873
0.86 0.910 0.83 0.898 0.78 0.890 0.85 0.874
0.88 0.905 0.82 0.901 0.90 0.894 0.75 0.888
0.88 0.910 0.87 0.910 0.86 0.902 0.82 0.894
0.88 0.910 0.85 0.910 0.84 0.906 0.85 0.909
0.87 0.922 0.86 0.917 0.84 0.912 0.85 0.910
0.91 0.910 0.90 0.916 0.87 0.917 0.81 0.917
0.90 0.925 0.88 0.919 0.85 0.921 0.81 0.927
0.91 0.931 0.87 0.925 0.84 0.927 0.79 0.926
0.88 0.914 0.87 0.918 0.84 0.929 0.79 0.926
0.88 0.927 0.89 0.920 0.83 0.930 0.79 0.928
0.87 0.929 0.85 0.927 0.83 0.937 0.81 0.938
0.90 0.933 0.88 0.934 0.82 0.935 0.75 0.947
0.92 0.938 0.89 0.941 0.80 0.940 0.80 0.939
0.93 0.938 0.88 0.950 0.81 0.945 0.80 0.940
0.93 0.940 0.88 0.951 0.79 0.949 0.80 0.947
0.88 0.953 0.83 0.947
0.88 0.954 0.82 0.950
0.88 0.954
Carga Aplicada ao Eixo do Motor (%)

75
100
Valores do Fator de Potncia Indutivo Desejado
0.92
0.93
0.94
0.95
0.96
0.97
0.98
LINHA WEG DE FUSVEIS TIPO D e NH
Corrente (A)Fusvel (A)
0 2
2 2
2.2 4
4.3 4
4.4 6
6.5 6
6.6 10
11 10
11 16
16.5 16
17 20
21 20
21.5 25
26 25
26.5 35
37.5 35
38 50
51 50
51.5 63
65 63
65.1 80
81 80
81.5 100
100 100
101 125
125 125
126 160
162.5 160
163 200
200 200
201 224
224 224
225 250
250 250
260 300
300 300
301 315
315 315
320 355
355 355
360 400
400 400
405 425
425 425
430 500
500 500
510 630
630 630
CONTATORES CONVENCIONAIS PARA REGIME AC-6b

VALORES DE POTNCIAS EM kvar


Valores Determinados Ith kvar Contator
220V 380V 440V Contator CWM* 220V
3.0 5.0 5.0 25 9 0.1 CWM 9
4.5 9.5 9.5 25 12 3 CWM 9
6.5 11.0 11.0 32 18 3.1 CWM 12
7.5 12.5 12.5 45 25 4.5 CWM 12
12.5 21.0 21.0 60 32 4.6 CWM 18
15.0 25.0 25.0 60 40 6.5 CWM 18
22.0 40.0 40.0 90 50 6.6 CWM 25
25.0 45.0 45.0 110 65 7.5 CWM 25
27.5 50.0 50.0 110 80 7.6 CWM 32
35.0 60.0 65.0 140 95 12.5 CWM 32
37.5 62.5 75.0 140 105 12.6 CWM 40
35.0 60.0 60.0 180 112 CWM 112 15 CWM 40
50.0 90.0 100.0 225 180 CWM 180 15.1 CWM 50
80.0 140.0 160.0 350 250 CWM 250 22 CWM 50
22.1 CWM 65
*INSERIR INDUTNCIA MNIMA DE 6mH ENTRE CAPACITORES 25 CWM 65
SE HOUVER ACIONAMENTO EM PARALELO DOS MESMOS 25.1 CWM 80
27.5 CWM 80
27.6 CWM 95
35 CWM 95
35.1 CWM 105
37.5 CWM 105
37.6 CWM 180
50 CWM 180
50.1 CWM 250
80 CWM 250
kvar Contator kvar Contator
380V 440V
0.1 CWM 9 0.1 CWM 9
5 CWM 9 5 CWM 9
5.1 CWM 12 5.1 CWM 12
9.5 CWM 12 9.5 CWM 12
9.6 CWM 18 9.6 CWM 18
11 CWM 18 11 CWM 18
11.1 CWM 25 11.1 CWM 25
12.5 CWM 25 12.5 CWM 25
12.6 CWM 32 12.6 CWM 32
21 CWM 32 21 CWM 32
21.1 CWM 40 21.1 CWM 40
25 CWM 40 25 CWM 40
25.1 CWM 50 25.1 CWM 50
40 CWM 50 40 CWM 50
40.1 CWM 65 40.1 CWM 65
45 CWM 65 45 CWM 65
45.1 CWM 80 45.1 CWM 80
50 CWM 80 50 CWM 80
50.1 CWM 95 50.1 CWM 95
60 CWM 95 65 CWM 95
60.1 CWM 105 65.1 CWM 105
62.5 CWM 105 75 CWM 105
62.6 CWM 180 75.1 CWM 180
90 CWM 180 100 CWM 180
90.1 CWM 250 100.1 CWM 250
140 CWM 250 160 CWM 250
UCW-T MCW BCW
V V V
nenhum nenhum nenhum
0.5 2.5 10
0.75 5 12.5
1 7.5 15
1.5 10 17.5
2 12.5 20
2.5 15 22.5
3 17.5 25
20 27.5
22.5 30
25 35
27.5 37.5
30
Tenses Nominais da Rede
220
380
440

Tenses Nominais dos Capacitores


220
380
440
480
Nr. Dias no Ms Nr. Horas por Dia
1 0.25
2 0.5
3 0.75
4 1
5 1.5
6 2
7 2.5
8 3
9 3.5
10 4
11 4.5
12 5
13 5.5
14 6
15 6.5
16 7
17 7.5
18 8
19 8.5
20 9
21 9.5
22 10
23 11
24 12
25 13
26 14
27 15
28 16
29 17
30 18
31 19
20
21
22
23
24

Вам также может понравиться