Consider the Fault on 33 kV side of Substation as shown in
figureRefering to the SLD Fault calculations will be done Percentage Reactance and Base KVA Method
Two 50 MVA transformers are loacated in 220/33kv Substation
having Percent Impedance of 12.5% 220/33kv,50 MVA 220/33kv,50 MVA 1 + 1 Transformer For fault calculations consider the base of 100MVA respectively. %Z=12.5 Transformer %Z=12.5 %Xa=25% %Xb=25% Xa Xb %Xeq=12.5%
Input Data FAULT
POINT REACTANCE DIAGRAM AT BASE KVA EQUIVALENT REACTANCE DIAGRAM Transformer Rating/Rated KVA 50000 BUS BAR
Percentage Reactance 12.50 SINGLE LINE DIAGRAM FOR 220/ 33 KV
SUBSTATION
Base kVA 100000
Percentage Reactance % Reactance at Rated KVA X (Base
at base kVA = kVA/Rated kVA)
Therefore Percentage Reactance of 50MVA 25.00
transformer at 100000 kVA=
Percentage Reactance of 50 MVA Transformer at 100MVA base
is 25%
Total Percentage Reactance upto fault 12.50 XA XB=(1/Xa+1/Xb) Point as shown in fig =
Short Circuit KVA = (100 X Base kVA)/ % X
Short Circuit kVA 800000 kVA Short CircuitMVA 800 MVA Input Data Transformer Rating/Rated KVA 8000 Percentage Reactance 8.350 Base kVA 96000
% Reactance at Rated KVA X( Base
Percentage Reactance at base kVA = kVA/Rated kVA)
Therefore Percentage Reactance at Base 96000kVA= 100.20
Percentage Reactance of 8 MVA Transformer at 96MVA base is 100.20
Total Percentage Reactance upto fault Point = XA XB Xc Xd
25.05 Short Circuit KVA = (100 X Base Kva)/%X) Short Circuit kVA 383233.532934132 kVA Short CircuitMVA 383 MVA