Intelligent Process

Cooling Technology Saves


on Water and Energy,
Improves Productivity
Presented at the Society of Plastics Engineers
ANTEC, May 1-5, 2011 in Boston, MA, USA

Lou Zavala, National Sales Manager


Frigel North America
150 Prairie Lake Road Unit A
East Dundee IL 60118

www.frigel.com
Intelligent Process Cooling Technology

Abstract

The concern for the environment in the plastics industry needs to go far beyond
materials where it is typically found. Curbing energy use, water use and chemical
disposal are significant responsibilities of the industry as well and can, to a large
degree, be accomplished through a more streamlined approach to process cooling.
When implementing closed-loop dry cooling, processors see immediate reductions in
energy, water and chemical use, directly impacting the local environment as well as
the bottom line.

Introduction

In the United States and in most industrialized nations, manufacturing is the culprit
of a great deal of resource consumption. So it is our responsibility to continue to
drive innovation and continuous improvement. Some improvements will be
incremental such as motion sensor lighting systems and water saving fixtures for
employee use, and other areas represent an opportunity for much more.

Currently, approximately 92 percent of a manufacturers energy consumption is


attributed to processing machinery and 16 percent of that is used to operate process
cooling systems [1].

Adding to significant energy use, in developed countries industry uses 45 percent of


the available water [2], and one of the top five sources of that waste is in inefficient
and poorly maintained methods for cooling [3].

At the heart of all of these environmental downfalls by industry is technology that


plastics processors have long relied on such as cooling towers and central chillers.
These inefficient methods are responsible for using an estimated 5.3 quadrillion liters
(1.4 quadrillion gallons) of water/year. They also require fans and pumps to be
continuously running to keep up with the water and cooling needs of these systems
and the open looped nature of a tower system creates dirty water leading to scale
accumulation that drives down efficiencies.

Table 1: Effect of scale on heat transfer

Page 2 of 10
Intelligent Process Cooling Technology

Figure 1: Effect of scale on energy consumption of chillers

Statement of Theory

Traditionally processors incorporate open tower systems with centralized chillers,


pumps, multiple insulating piping configurations and move cooled water over long
distances to provide the needed temperatures machine side. The evaporation alone
accounts for significant water consumption. For example, to achieve one ton of
cooling, a tower must evaporate around 0.11 liters (0.03 gallons) of process water
every minute. Extrapolating that into a common scenario, based on 8,760 operating
hours per year (24 hours/day, 365 days/year) with tower operating at full capacity, a
100 ton tower consumes 5,968,838 liters (1,576,800 gallons) per year.

The Ecodry System, or the closed-loop dry cooling system, offers processors
advanced technology with a simplified set up that utilizes a single unit feeding
machine side TCUs and a single set of non-insulated pipes running through the
facility.

The closed-loop nature keeps water clean and eliminates evaporation which means
no continuous water or chemical consumption and the elimination of chemical
emissions into the atmosphere and wastewater dumping into a communitys water
supply. Using the same scenario above, water savings would equal over 97 percent.

Page 3 of 10
Intelligent Process Cooling Technology

Description of Technology

The closed-loop, dry cooling technology operates by pumping water returning from
the process into heat exchangers and cooling it with ambient air flow. This process
provides clean water at the right temperature to process machines year round.
Desired water temperatures are continuously met through control and software that
provides fully-automatic water and energy savings adjustments based on actual
thermal load and outdoor temperatures.

To maintain water below setpoint in hot weather, defined as 29.4C (85F), outside
air passes through an adiabatic chamber before reaching the air-to-water heat
exchanger coils. Adiabatic mode keeps LWT below 35C (95F) even when ambient
temperatures reach 48.9F (120F). In the chamber, a fine mist of water (from a
separate source) is pulsed into the air stream, evaporates immediately and cools the
air before it impinges on the cooling coils. The spray function and volume of water
used is controlled by the microprocessor based on ambient temperatures. Only cool,
dry air makes contact with the heat exchanger coils, creating the concept of dry
cooling. This ensures coils are kept completely dry and free of scale.

Figure 2: Adiabatic cooling diagram

During colder months, this closed-loop dry cooling technology automatically adjusts
so the recirculation pumps turn off and the unit drains fully, providing 100 percent
freeze protection. Non-draining units can be used in non-freezing climates or if
desired, glycol can be used in freezing climates.

In these situations, the technology also provides opportunities for free cooling,
where machine side units are supplied with clean cooling water, replacing the need
for chillers and turning off any chiller compressors, fans and other energy consuming
functions. Depending on process set points and local ambient conditions, free cooling
can benefit many processors.

Page 4 of 10
Intelligent Process Cooling Technology

Figure 3: Chart shows what percentage of the year you can start to take advantage
of free cooling based on Chicago, IL weather data for purpose of example [4].

The limited times of the year when it is necessary, additional air flow is generated by
axial fans with variable DC motors, creating the lowest energy consumption
available. The fans provide extremely high efficiency under partial load conditions
and have an average annual consumption of less than 0.03 kW/ton.

kW / fan 2.00
1.50
1.00
0.50
-
0 20 40 60
O U T D O O R T E M P . ( F)
80 100

Figure 4: Chart shows energy consumption of 0.03 kW/ton based on LWT of 32.2C
(90F) in Los Angeles, CA.

While the above description focused primarily on the substitution of a cooling tower
with a closed-loop, dry cooling unit, the other part of the system involves the
machine side units. Large pumping stations and central chiller systems create
difficulty for a processor to achieve precise water temperature at all process
machines and achieving that means significant energy consumption.

Modern machine side technology can include both chiller and temperature control
unit functionality in one compact unit and adjust for required temperature, flow and
pressure individually. With cooling parameters optimized at each machine, results
are better part quality, cycle time improvements of up to 20 percent and less scrap
that would end up in landfills or require energy to regrind. As an alternative to
central chillers, this method can save up to 80 percent of energy consumption from
reduction of thermal losses and minimal pump horsepower required.

Page 5 of 10
Intelligent Process Cooling Technology

Figure 5: The top illustration represents the flow of water through an injection mold
using a central chiller and flow meter combination, the result is a T of 11.1C
(20F). The bottom illustration represents a dedicated machine side unit showing a
low T of 1.1C (2F). The result of less T is better quality parts, faster cooling and
less scrap.

Results

As a result of the negative impact cooling towers and central chillers have long had
on the environment and companys bottom lines, closed-loop dry cooling provides a
new way to benefit from performance improvements as well as meet sustainability
goals. Those environmental benefits include:
Highest global energy efficiency and lowest energy operating cost
Lowest water consumption
Zero ongoing chemical use and disposal, eliminating costly filtration and
contamination of water supply
Lowest risk of refrigerant gas emission to atmosphere
Reduce production of plastic scrap
Highest productivity (generating additional savings of energy, water, resin
and effort)

Specifically, the following benefits can be seen by an operation:


Energy savings: A typical 100-ton cooling system operates with about 0.8 to
1.2 kWh/ton energy consumption. A comparable-sized closed-loop dry cooling
system uses 0.05 kWh/ton.
Water savings: In addition to pollution prevention and ending contamination
of community water sources, the water volume savings are significant. In a
typical 100-ton cooling system, this technology reduces consumption by over
3.78 million liters (1 million gallons) of water/year.
Maintenance time savings: This technology operates with minimal
maintenance. It can save companies up to 40 hours in maintenance per
month.

Page 6 of 10
Intelligent Process Cooling Technology
In many cases, adding up the energy, maintenance and water savings results in
payback of less than two years, and depending on the climate and system demands,
can be as soon as one year. Additionally, rebates from state and local government,
as well as utilities, are available for manufacturers implementing energy saving
technology and tax incentives such as the American Recovery and Reinvestment Act
of 2009 [5] are also available to those implementing closed-loop dry cooling
technology.

Independent Study

In an independent study lead by researchers at the UC Davis Energy Efficiency


Center and PL Energy LLC, a California-based energy consultancy, a processor
operating 22 injection molding machines was analyzed [6].

The existing system consisted of a 150 ton cooling tower with a central chiller
operating at 6.7C (44F) and providing 60 tons of mold cooling. This set up was
replaced by a closed-loop dry cooling unit and press side units. The ability to
automatically provide ambient cooling in lieu of a chiller for mold cooling created
savings as well as the reduction in pumping and the method of cooling. Potential
energy savings from this measure are shown in Table 2.

Table 2: Annual total energy savings projected during study [6].

Page 7 of 10
Intelligent Process Cooling Technology
Additional analysis found that in addition to environmental and financial benefits,
manufacturing performance including on-time deliveries, inventory turns, machine
hours available and other measures were improving with closed-loop dry cooling as
well. See noted improvements in Figure 6.

Figure 6: This performance chart shows the input/outputs from modeling with
manufacturing changes held to 5 percent in relative improvement or absolute dollars
with the target improvements ranging from 2-15 percentiles from this project [6].

Finally, the savings in dollars were computed on these benefiting production items
that are not customarily included in an analysis of a process cooling system but
proved to be positively affected in the end.

Table 3: Energy and operations savings broken out annually and monthly based on
closed-loop dry cooling system implementation [6].

Page 8 of 10
Intelligent Process Cooling Technology

Figure 7: The annual results above are represented here as a pie chart to see which
savings had the most financial impact on the molder [6].

Conclusion

Energy and water every day become more scarce and more of a concern to the
commercial, government and residential sectors alike. Because of industrys
significant demand on these available resources, it goes beyond the bottom line and
becomes a responsibility of manufacturers to take action to lessen its reliance. As
demonstrated here, great opportunity lies in process cooling technology available
today that can support these initiatives.

With measurable savings available, it is important to first understand the current


process cooling system and its impact on the environment as well as the companys
financial performance.

With that information in hand, it will be easy to see the post-installation results that
many companies have experienced to date including:
Improved productivity
Substantial savings on volume of water and energy use
Eliminated dumping fees associated with chemical treatment
Nearly zero gas emissions due to consistently clean water
Met sustainability goals
Realized less maintenance and associated costs

Page 9 of 10
Intelligent Process Cooling Technology

References

1. Dr. Robin Kent, Energy Management in Plastics Processing Strategies, targets,


techniques and tools (2008).
2. Global water crisis overview. April 2007. www.arlingtoninstitute.org
3. How to save water in the workplace. June 2003. www.waterwise.com
4. National Environmental Satellite, Data, and Information Service (NESDIS).
www.ncdc.noaa.gov/oa/documentlibrary/ewdcd/handbook.pdf
5. U.S. Department of Energy, Business Tax Incentives.
www.energy.gov/business_tax_incentives.htm
6. Church, G. ACEEE Summer Study of Energy Efficiency in Industry, Energy
Financial Project Analysis, What Have We Been Missing? 2009 Summer Study
Program in Industry, American Council for an Energy Efficient Economy,
Washington, DC. www.aceee.org