LIEBERT DSE

CABINET DIMENSIONAL DATA


DOWNFLOW DA080-DA085 MODELS
Secondary Refrigerant
Piping Entrance
80" Opening
2032mm

33"
838mm 24 3/8"
AIR INLET OPENING 619mm Opening
35"
889mm

1 3/4" Handle 5/16" Bezel


44mm 8mm
Secondary Entrance TOP VIEW Secondary Entrance
High Volt Connection(s) Low Volt Connections
Minimum required
100" for filter replacement
2540mm

5"
127mm

76"
1930mm

2" FRONT VIEW 34"


864mm
51mm Shaded area indicates a
99" recommended minimum
2515mm
clearance be provided for
component access.
Approximate Dry Weight
lb. (kg)

DA080 2200 (998)


DA085 2250 (1021)

Notes:
Form No.: DPN001040_REV4

1. Filters are accessible through top of unit only.


2. Downflow electrical connections can be made from top or bottom of unit.

DPN004083 REV : 0
Page :1 /1 REV DATE : 2/17
LIEBERT DSE
DISASSEMBLY DIMENSIONAL DATA
DOWNFLOW DA080-DA085

FILTER & ELECTRIC BOX ASSEMBLY

39"
991mm

COMPRESSOR ASSEMBLY

BLOWER & COIL ASSEMBLY 76"


1930mm
Assembled Height

76"
1930mm
59 7/16"
1510mm

37"
940mm

17" 82"
33" 432mm 2083mm
838mm 99"
Assembled Length 2515mm

APPROXIMATE DRY WEIGHT lb (kg) (Includes Panels)


COMPRESSOR ASSEMBLY 590 (269)
FILTER & ELECTRIC BOX ASSEMBLY 250 (114)
BLOWER & COIL ASSEMBLY 1410 (641)

Notes:
Form No.: DPN001040_REV4

1. Drawing views are simplified with panels removed to show over all dimensions.
2. See disassembly and handling instructions in installation manual.

DPN003140 REV : 3
Page :1 /1 REV DATE : 1/17
LIEBERT DSE
PIPING SCHEMATIC
DA050, DA080 & DA085 MODELS
Differential Differential
Check Valve Optional "EconoPhase" UNIT Check Valve

1-3/8" Liquid from Condenser


Check
2 Valve

7/8" Liquid to Indoor Unit


LIEBERT MC CONDENSER LIEBERT DSE Solenoid
RECEIVER Valve 2

Ball Ball
Valve Valve

HOT GAS DISCHARGE 1-1/8" Hot Gas Discharge


Includes Factory traps. from Indoor Unit
No external trap required. 2

DA050, DA080, & DA085 LIQUID


EVAPORATOR For rises over 25ft. (7.6m),
COIL trap every 20ft. (6m) or
Service
evenly divided
Valve

SUCTION 8

Field installed relief valves


required for 50Hz EU CE
units rated maximum
650 PSIG (45 bar) 8

Check Trap at base


Valve of risers
over 5ft. (1.5m)
8

4 8
Service Isolation Valve
Valve (Fully Ported)

Check
Valve 9 HOT GAS DISCHARGE
2

Electronic LIQUID RETURN


Isolation Valve
Expansion (Fully Ported)
Valve 2
REFRIGERANT PIPING 4 8
SERVICE/SCHRADER (ACCESS) CONNECTION, NO VALVE CORE.
FIELD PIPING
SERVICE/SCHRADER (ACCESS) CONNECTION, WITH VALVE CORE.
Notes:
1. Two refrigeration circuits provided on DA080 & DA085. Single refrigeration circuit provided on DA050. Single refrigeration circuit shown for clarity.

2. Circuit 1 must be maintained between indoor unit, condenser and EconoPhase unit. Circuit 2 must be maintained between indoor unit, condenser and EconoPhase unit.
3. Schematic representation shown. Do not use for specific connection locations.

4. Port in ball must be the same diameter as the piping I.D.


5. Length of piping between condenser and indoor unit shall be no greater than 300 ft (91.4 m) [Maximum equivalent length of 450 ft (137.2 m)].
6. Vertical height of condenser above indoor unit shall be no greater than 60ft (18.3m).
7. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum thickness. All outdoor insulation must be UV and ozone resistant.

8. Components are not supplied by Liebert but are required for proper circuit operation and maintenance. One or more pressure relief valves are required downstream of an and all
field installed isolation valves. Do not isolate any refrigerant circuits from over pressurization protection.
Form No.: DPN001040_REV4

9. Traps must be installed and horizontal lines pitched to ensure proper oil return and to reduce liquid flood back to compressor. Pitch horizontal hot gas piping at a minimum of
1/2" per 10 feet (42mm per 10m) so that gravity will aid in moving oil in the direction of refrigeration flow.

DPN002615 REV : 8
Page :1 /1 REV DATE : 4/17
LIEBERT DS
PRIMARY CONNECTION LOCATIONS
DOWNFLOW AIR COOLED 53-77kW
SCROLL OR DIGITAL SCROLL COMPRESSOR MODELS W/ EC FANS

A A

X
O 1

R
Y
L1 L2 G1 G2
35"
889mm EC Fan EC Fan
Outlet Outlet
4 LV1
3 3
ECS ECR 2 LV2
CD LV3

E1 E2 HUM Section A-A Front of Unit


98"
2489mm

POINT DESCRIPTION X in. (mm) Y in. (mm) CONNECTION SIZE / OPENING


R DS REFRIGERANT ACCESS 81-3/4 (2076) 14-3/4 (375) 12-3/16" (310mm) X 4" (102mm)
53kW (15 TONS) 70 & 77kW (20 & 22 TONS)
L1 LIQUID LINE SYSTEM 1 94-11/16 (2405)
16-3/4 (425) 1/2" O.D. Cu 5/8" O.D. Cu
L2 LIQUID LINE SYSTEM 2 91-7/8 (2334)
G1 HOT GAS DISCHARGE 1 4 88-3/4 (2254)
16-3/8 (416) 7/8" O.D. Cu 1-1/8" O.D. Cu
G2 HOT GAS DISCHARGE 2 4 85-9/16 (2173)
CONDENSATE DRAIN 2
3/4" NPT FEMALE
CD (infrared humidifier or no humidifier) 68-3/8 (1737) 31-3/8 (797)
W/ OPTIONAL PUMP 1/2" O.D. Cu
HUM HUMIDIFIER SUPPLY LINE 76-1/2 (1943) 29 (737) 1/4" O.D. Cu
ECS ECON-O-COIL SUPPLY 3 78-5/8 (1997) 22-1/4 (565)
2-1/8" O.D. Cu
ECR ECON-O-COIL RETURN 3 73-15/16 (1878) 26-9/16 (675)
E1 78-1/2 (1994)
ELECTRICAL CONN. (HIGH VOLT) 31-1/8 (791) 2-1/2"
E2 75-3/8 (1915)
LV1 29 (737)
LV2 ELECTRICAL CONN. (LOW VOLT) 2 (51) 30-7/8 (784) 7/8"
LV3 32 (813)

Notes:

1. Drawing not to scale. All dimensions from rear corner of unit including panels, and have a tolerance of 1/2" (13mm).

2. Field pitch Condensate Drain line a minimum of 1/8" (3.2 mm) per foot (305 mm). All units contain a factory installed condensate trap. Do not trap external to the unit. Drain line may
contain boiling water. Select appropriate drain system materials. The drain line must comply with all local codes.
3. Supplied on Dual Cooling systems only.
Form No.: DPN001040_REV4

4. When piping out the top of the unit, install traps in the discharge lines in the bottom of the unit before running lines to the top.
5. Digital Scroll compressor not available on DS077 models.

DPN002182 REV : 7
Page :1 /1 REV DATE : 1/17
LIEBERT DS
DRAIN SYSTEMS
UPFLOW & DOWNFLOW MODELS
DOWNFLOW DS UNIT UPFLOW DS UNIT
INTERNAL
DRAIN INTERNAL
EXTERNAL DRAIN
UNIT DRAIN

EXTERNAL UNIT
DRAIN

CONTINUOUS DOWNWARD SLOPE CONTINUOUS DOWNWARD SLOPE

CORRECT CORRECT

INTERNAL INTERNAL
DRAIN EXTERNAL DRAIN
DRAIN
UNIT

UNIT

EXTERNAL
DRAIN
DO NOT EXTERNALLY DO NOT EXTERNALLY
TRAP THE UNIT TRAP THE UNIT

INCORRECT INCORRECT
INTERNAL
DRAIN

INTERNAL
UNIT EXTERNAL DRAIN
DRAIN

UNIT

EXTERNAL
DRAIN

THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH


UNINTENTIONAL. LINES MUST BE RIGID ENOUGH THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH
NOT TO BOW OVER TOP OF OTHER OBJECTS. UNINTENTIONAL. LINES MUST BE RIGID ENOUGH
NOT TO BOW OVER TOP OF OTHER OBJECTS.

INCORRECT INCORRECT
Form No.: DPN001040_REV4

DPN001556 REV : 2
Page :1 /1 REV DATE : 1/17
LIEBERT DSE
DRAIN SYSTEMS
UPFLOW & DOWNFLOW MODELS
DOWNFLOW UNIT UPFLOW UNIT
INTERNAL
DRAIN INTERNAL
EXTERNAL DRAIN
UNIT DRAIN

EXTERNAL UNIT
DRAIN

CONTINUOUS DOWNWARD SLOPE CONTINUOUS DOWNWARD SLOPE

CORRECT CORRECT

INTERNAL INTERNAL
DRAIN EXTERNAL DRAIN
DRAIN
UNIT

UNIT

EXTERNAL
DRAIN
DO NOT EXTERNALLY DO NOT EXTERNALLY
TRAP THE UNIT TRAP THE UNIT

INCORRECT INCORRECT
INTERNAL
DRAIN

INTERNAL
UNIT EXTERNAL DRAIN
DRAIN

UNIT

EXTERNAL
DRAIN

THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH


UNINTENTIONAL. LINES MUST BE RIGID ENOUGH THESE ARE EXTERNAL TRAPS ALSO, ALTHOUGH
NOT TO BOW OVER TOP OF OTHER OBJECTS. UNINTENTIONAL. LINES MUST BE RIGID ENOUGH
NOT TO BOW OVER TOP OF OTHER OBJECTS.

INCORRECT INCORRECT
Form No.: DPN001040_REV4

DPN004153 REV : 0
Page :1 /1 REV DATE : 4/17
LIEBERT DS & DSE
ELECTRICAL FIELD CONNECTION DESCRIPTION
DS, DA050 - DA085 UPFLOW AND DOWNFLOW MODELS
STANDARD ELECTRICAL CONNECTIONS
1) Primary high voltage entrance - 2.50 (64mm); 1.75 (44mm); 1.375 (35mm) diameter concentric knockouts located in bottom of box
2) Secondary high voltage entrance - 2.50 (64mm); 1.75 (44mm); 1.375 (35mm) diameter concentric knockouts located in top of box
3) Primary low voltage entrance - Quantity (3) 1.375 (35mm) diameter knockouts located in bottom of unit
4) Secondary low voltage entrance - Quantity (3) 1. 375 (35mm) diameter knockouts located in top of box
5) Three phase electrical service - Terminals are on main fuse block (disregard if unit has optional disconnect switch). Three phase service
not by Liebert.
6) Earth ground - Terminal for field supplied earth grounding wire. Earth grounding required for Liebert units.
7) Remote unit shutdown - Replace existing jumper between terminals 37 & 38 with field supplied normally closed switch having a
minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
8) Customer alarm inputs - Terminals for field supplied, normally open contacts, having a minimum 75VA, 24VAC rating, between
terminals 24 & 50, 51, 55, 56. Use field supplied Class 1 wiring. Terminal availability varies by unit options.
9) Common alarm - On any alarm, normally open dry contact is closed across terminals 75 & 76 for remote indication. 1 AMP, 24VAC max
load. Use Class 1 field supplied wiring.
10) Heat rejection interlock - On any call for compressor operation, normally open dry contact is closed across terminals 70 & 71(circuit 1),
230 (circuit 2) to heat rejection equipment. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring. When DS unit is paired with a
Liebert MC series condenser, remove jumper between terminal 71 and terminal 230. Three wires must connect terminals 70, 71 and 230
of the indoor unit to terminals 70, 71 and 230 of the Liebert MC series condenser. Liebert DSE units must be connected to Liebert MC
series condenser with premium control. It is required that the jumper between terminal 71 and terminal 230 be removed. Three wires
must connect terminals 70, 71, and 230 of the indoor unit to terminals 70, 71 and 230 of the Liebert MC series condenser.

CANBUS ELECTRICAL CONNECTIONS


11) CANbus Connector Terminal block with terminals 49-1 (CAN-H) and 49-3 (CAN-L) + SH (shield connection). The terminals are used to
connect the CANbus communication cable (provided by others) from the indoor unit to the Liebert MC Condenser Optional Econophase
Unit.
12) CANbus Cable CANbus cable provided by others to connect to the outdoor condenser, and optional PRE unit (DA units only). No
special considerations are required when the total external cable connection between the indoor unit and outdoor unit(s) is less than
450FT (137M). For total external cable connections greater than 450FT (137M) but less than 800FT (243M) a CANbus isolator is required.
Contact Factory.
Cable must have the following specifications:
Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
13) Do not run in same conduit, raceway, or chase as high voltage wiring.
14) For CANbus network lengths greater than 450FT (137M) call Factory.
Form No.: DPN001040_REV4

DPN000807 REV : 15
Page :1 /4 REV DATE : 4/17
LIEBERT DS & DSE
ELECTRICAL FIELD CONNECTION DESCRIPTION
DS, DA050 - DA085 UPFLOW AND DOWNFLOW MODELS
OPTIONAL ELECTRICAL CONNECTIONS
15) Unit factory installed disconnect switch, Fuse Block and Main Fuses Two types of disconnect switches are available Non-
Locking and Locking. The Non-Locking Type consists of a non-automatic molded case switch operational from the outside of the unit.
Access to the high voltage electric panel compartment can be obtained with the switch in either the on or off position. The Locking
Type is identical except access to the high voltage electric panel compartment can be obtained only with the switch in the off position.
Units with fused disconnects are provided with a defeater button that allows access to the electrical panel when power is on. The molded
case switch disconnect models contain separate main fuses. Units with fused disconnect have main fuses within the disconnect. Only
fused disconnects are used on dual disconnect options.
16) Secondary disconnect switch and earth ground
17) Three phase electrical service - Terminals are on top of disconnect switch. Three phase service not by Liebert.
18) Smoke sensor alarm - Factory wired dry contacts from smoke sensor are 91-common, 92-NO, and 93-NC. Supervised contacts, 80 &
81, open on sensor trouble indication. This smoke sensor is not intended to function as, or replace, any room smoke detection system that
may be required by local or national codes. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
19) Reheat and humidifier lockout - Remote 24VAC required at terminals 82 & 83 for lockout of reheat and humidifier.
20) Condensate alarm (with condensate pump option) - On pump high water indication, normally open dry contact is closed across terminals
88 & 89 for remote indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
21) Remote humidifier - On any call for humidification, normally open dry contact is closed across terminals 11 & 12 to signal field supplied
remote humidifier. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
22) Auxiliary cool contact - On any call for econ-o-coil operation, normally open dry contact is closed across terminals 72 & 73 on dual cool
units only. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.

OPTIONAL LOW VOLTAGE TERMINAL PACKAGE CONNECTIONS


23) Remote unit shutdown - Two additional contact pairs available for unit shutdown (labeled as 37B & 38B, 37C & 38C). Replace jumpers
with field supplied normally closed switch having a minimum 75VA, 24VAC rating. Use field supplied Class 1 wiring.
24) Common alarm - On any alarm, two additional normally open dry contacts are closed across terminals 94 & 95 and 96 & 97 for remote
indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
25) Main fan auxiliary switch - On closure of main fan contactor, normally open dry contact is closed across terminals 84 & 85 for remote
indication. 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
26) LiquiTect shutdown and dry contact - On LiquiTect activation, normally open dry contact is closed across terminals 58 & 59 for remote
indication (LiquiTect sensor ordered separately). 1 AMP, 24VAC max load. Use Class 1 field supplied wiring.
NOTE: Refer to specification sheet for total unit full load amps, wire size amps, and max overcurrent protective device size.
Form No.: DPN001040_REV4

DPN000807 REV : 15
Page :2 /4 REV DATE : 4/17
LIEBERT DS & DSE
ELECTRICAL FIELD CONNECTION DESCRIPTION Intellislot
Housing
2
DS, DA050 - DA085 UPFLOW AND DOWNFLOW MODELS 4

A B

C D
OVERCURRENT PROTECTION DEVICES
17
Alternate
Location
60 Hz
P64
6
CONTACTORS P67

CONTACTORS, RELAYS, &


15
OVERLOAD PROTECTORS E

3
1 5 6 DS DOWNFLOW
Note: Typical orientation of components shown. Component location varies by option and unit size. DA080/085 UPFLOW AND DOWNFLOW
LOW VOLT SECTION
19 20 9 24 18 21

82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 CAUTION:
Risk of broken or shorted low volt
UPFLOW 3 wiring. Field installed low volt wiring
must be routed with loop as shown
A B to allow electric box to swing.
26 25 23 7 8 10 22

58 59 84 85 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 A B

C D
C D
11
SH
49-1
49-3

12

Item 12 Installation Conditions E E


1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway, or
chase as high voltage wires (120-600V). POINT OF HINGED LOW
3. Separate high volt wires from CAN wires by 12 inches.
Form No.: DPN001040_REV4

VOLT ELECTRIC BOX


DS UPFLOW LOW VOLTSECTION
DPN000807 REV : 15
Page :3 /4 REV DATE : 4/17
LIEBERT DS & DSE
Intellislot
2 ELECTRICAL FIELD CONNECTION DESCRIPTION Housing

DS, DA050 - DA085 UPFLOW AND DOWNFLOW MODELS 4

A B
OVERCURRENT PROTECTION DEVICES
17 C D
6 60 Hz 16
Alternate
17 Location

P64
CONTACTORS P67
PRIMARY SECONDARY

15

CONTACTORS, RELAYS, &


OVERLOAD PROTECTORS

1 6 DS DOWNFLOW 3

Note: Typical orientation of components shown. Component location varies by option and unit size.
DA080/085 UPFLOW AND DOWNFLOW
LOW VOLT SECTION
19 20 9 24 18 21

82 83 88 89 75 76 94 95 96 97 91 92 93 80 81 11 12 CAUTION:
Risk of broken or shorted low volt
wiring. Field installed low volt wiring
UPFLOW 3
A B must be routed with loop as shown
to allow electric box to swing.
26 25 23 7 8 10 22

58 59 84 85 37C38C37B38B 37 38 24 50 51 55 56 70 71 230 72 73 A B

C D
C D
11
SH
49-1
49-3

12

Item 12 Installation Conditions


E E
1. Follow all local installation codes.
2. Do not run CAN cables in same conduit, raceway, or POINT OF HINGED LOW
chase as high voltage wires (120-600V).
Form No.: DPN001040_REV4

VOLT ELECTRIC BOX


3. Separate high volt wires from CAN wires by 12 inches.
UPFLOW LOW VOLT SECTION
DPN000807 REV : 15
Page :4 /4 REV DATE : 4/17
LIEBERT iCOM
PRODUCT INFORMATION
UNIT MOUNTED DISPLAY

The Liebert iCOM display is a microprocessor 9 inch color touch screen in an ergonomic, aesthetically
pleasing housing. The display and housing will be viewable while the unit accent panels are open or closed.
The display can be easily detached to view while the panel is open.

Menu Layout- The menus will be broken out into two main menu screens: User screen and Service screen.
The User screen contains the menus to access parameters required for basic unit control and setup.
The Service screen is designed for service personal and provides access to advanced control setup features
and diagnostic information.

Password Protection- The display will contain two unique passwords to protect against unauthorized changes.
An auto hide/show feature allows the user to see applicable information based on the login used.

Unit Backup and Restore- The user shall have the ability to create safety copies of important control parameters.
The display has the ability for the user to automatically backup unit configuration settings to internal memory or USB
storage drive. Configuration settings may be transferred to another unit for a more streamlined unit startup.

Parameter Download- The display has the ability for the user to download a report that lists parameter names,
factory default settings and user programmed settings in .csv format for remote reference.

Parameter Search- The display has search fields for efficient navigation and parameter lookup.

Setup Wizards- The display will contain step by step tutorials or wizards to provide easy setup of the control.
Form No.: DPN001040_REV4

DPN003245 REV : 4
Page :1 /2 REV DATE : 1/17
LIEBERT iCOM
PRODUCT INFORMATION
UNIT MOUNTED DISPLAY

Context Sensitive Help- The display will have an onboard help database. The database will provide context
sensitive help to assist with setup and navigation of the menus.

Display Setup- The user has the ability to configure the display information based on the specific users preference.
Language, units of measure, screen contrast, home screen layout, back light timer and the hide/show of certain
readouts will be configurable through the display.

Additional Readouts- The display has the ability for the user to configure custom widgets on the main screen.
Widget options will include items such as fan speed, call for cooling, call for free cooling, maintenance status,
call for hot water reheat, call for electric reheat, call for dehumidification, call for humidification, airflow, static pressure,
fluid flow rate and cooling capacity.

Status LEDs- The display will provide the user with the units operating status using an integrated LED.
The LED will indicate if the unit has an active alarm; if the unit has an active alarm that has been acknowledged;
or if the unit is on, off, or in a standby status.

Unit Alarms All unit alarms are annunciated through both audio and visual cues, clearly displayed on the screen,
automatically recorded in the event log, and communicated to optional IntelliSlot monitoring cards.

Event Log The display will automatically store the last 400 unit-only events (messages, warnings, and alarms).

Service Contact Information The display has the ability to store the local service or sales contact information.

Upgradeable Display upgrades are performed through a USB connection.

Unit-to-Unit (U2U) Communication Communication via private Ethernet network allows for advanced control
functionality (Teamwork modes, sharing sensor data, Standby Rotation, Lead-Lag, and Cascade operation).
Form No.: DPN001040_REV4

DPN003245 REV : 4
Page :2 /2 REV DATE : 1/17
LIEBERT DSE
FLOORSTAND DIMENSIONAL DATA
DOWNFLOW AIR COOLED DA080-DA085
W/ DIGITAL SCROLL COMPRESSORS

Piping access area

31 1/2"
800mm 32"
Center of Feet 813mm
at each end Center of Feet
between each end
1"
25mm
Typ.

13 3/4" 32 3/4"
349mm 832mm
Center of Feet Center of Feet 4
95 1/2"
2426mm
Center of Feet 99 3/4"
2534mm
99"
2515mm 33"
2" 838mm
51mm

2"
51mm 6
19 1/4"
5 489mm
F

7/8"
23mm
Typ.

3" 34 1/2"
76mm Typ. 876mm
98 1/2" At each end
2502mm
35"
889mm
Overall Depth
Notes:
1. This floorstand should be used when EC fans are intended to be lowered under
a raised floor. 24-48" floorstands allow fan to be lowered under raised floor.
2. Right side of paneled unit is flush with right side of floorstand. All other paneled sides
overhang floorstand 1" (25mm).
3. The floorstand used with EC units is not symmetrical and its orientation to the
Liebert DSE is critical for lowering the EC fans. Unless the floor stand is installed in
the correct position, the blowers will not lower into the floorstand. Height in ( mm )
4. Jack and jack support are shipped loose and are intended to be placed into position F 5
under each fan and utilized to lower or raise that fan as needed.
5. Leveling feet are provided with u 1-1/2 (38mm) adjustment from nominal height F. 18 (457) 7
24 (610)
6. Applies to 36", 42" & 48" Floorstand. 30 (762)
7. Fans may be lowered into 18" floor, however this application does not allow for the use of a factory provided floor jack. 36 (914)
Form No.: DPN001040_REV4

Other methods of raising/lowering fans must be employed for raised floors less than 24". 42 (1067)
48 (1219)

DPN004073 REV : 0
Page :1 /1 REV DATE : 2/17
LIEBERT DS & DSE
FAN LOWERING PROCEDURE
DOWNFLOW MODELS W/ EC FANS
WARNING -RISK OF ELECTRIC SHOCK AND HIGH SPEED ROTATING FAN BLADES! CAN CAUSE INJURY OR DEATH!
DISCONNECT ALL LOCAL AND REMOTE ELECTRIC POWER SUPPLIES AND VERIFY THAT FAN BLADES HAVE STOPPED
ROTATING BEFORE WORKING WITHIN.
WARNING - RISK OF FAN MODULES DROPPING DOWNWARD SUDDENLY! CAN CAUSE INJURY OR DEATH! SUPPORT FAN
MODULES BEFORE REMOVING MOUNTING HARDWARE. USE CAUTION TO KEEP BODY PARTS OUT OF THE FAN MODULES
PATHWAY OF MOVEMENT DURING REPOSITIONING. ONLY QUALIFIED PERSONNEL SHOULD WORK ON THIS EQUIPMENT.
LIEBERT DS042 UNIT SHOWN WITH LIEBERT 24" FLOORSTAND. CUSTOMER UNIT MAY
APPEAR DIFFERENT. READ USER MANUAL AND INSTRUCTION SHEET
195788 BEFORE RE-POSITIONING THE FAN MODULES.

TABS

DETAIL A A
B B JACK LOCATION
SECTION
NOT SHOWN

3
TOOLS NEEDED: LOWERING PROCEDURE (24" FLOOR HEIGHT MINIMUM):
1/2" HEX SOCKET & WRENCH
FACTORY SUPPLIED JACK, CRANK 1. REMOVE THE MIDDLE AND BOTTOM PANELS
AND JACK SUPPORT FROM THE FRONT OF THE UNIT.
CABLE TIE CUTTER
2. FOR EASE OF FAN LOWERING, REMOVAL OF
Section removed THE HUMIDIFIER PAN IS RECOMMENDED.
for clarity
3. POSITION THE FACTORY SUPPLIED JACK AND
FAN DECK JACK SUPPORT UNDER THE FAN MODULE TO
BE LOWERED. USING THE CRANK, RAISE THE
JACK TO SAFELY SUPPORT THE FAN BEFORE
REMOVING ANY HARDWARE.
NOTE: A PROPERLY POSITIONED JACK WILL BE
CENTERED BETWEEN THE FIRST AND SECOND
5 5
SET OF TABS ON THE JACK SUPPORT.

4. CUT & REMOVE THE CABLE TIE THAT RETAINS


THE WIRING LOOP TO THE BLOWER MOUNTING
PLATE. ALL OTHER CABLE TIES THAT ROUTE
THE FAN WIRING SHOULD REMAIN INTACT.

SECTION B-B
TOP VIEW OF FAN DECK
5. REMOVE THE SIX HEX-HEAD SCREWS USING
A 1/2" HEX SOCKET OR WRENCH. RETAIN
HARDWARE FOR LATER STEPS.
Form No.: DPN001040_REV4

4 WIRING LOOP

DPN003172 REV : 3
Page :1 /2 REV DATE : 1/17
LIEBERT DS & DSE
FAN LOWERING PROCEDURE
DOWNFLOW MODELS W/ EC FANS

FAN MODULE
6 RESTING
ON FRAME

C C

6
6

6. USING THE FACTORY SUPPLIED JACK


AND CRANK, LOWER THE FAN MODULE
UNTIL IT RESTS ON THE FRAME OF THE UNIT.
USE CAUTION TO PREVENT DAMAGE
TO THE FAN WIRE HARNESS.

7. USE THE HEX HEAD SCREWS


REMOVED IN STEP 5 TO SECURE THE FAN MODULE
DIRECTLY TO THE FRAME. SCREW CLEARANCE
HOLES ARE PROVIDED IN THE FAN MODULE.

NOTE: NOT ALL HARDWARE REMOVED IN STEP 5 WILL


BE USED TO RETAIN FANS IN LOWERED POSITION.

8. REPEAT STEPS 3-7 TO LOWER REMAINING FAN


MODULE(S) IF PRESENT.

SECTION C-C NOTE: THE FANS MUST BE OPERATED IN EITHER


THE FULLY RAISED POSITION OR FULLY LOWERED
POSITION. NO OTHER COMBINATION OF FAN
POSITIONING IS SUPPORTED.
Form No.: DPN001040_REV4

DPN003172 REV : 3
Page :2 /2 REV DATE : 1/17
LIEBERT ECONOPHASE
Electric Box
End of Unit
CABINET DIMENSIONAL DATA
PR050-PR125
42"
1067mm
Minimum
Clearance

Pump Access
Typical Both Sides

36" 36"
914mm
Minimum
914mm
Minimum
B
Clearance Clearance
ISOMETRIC VIEW
21 3/8"
543mm 1-3/8" Liquid from Condenser
4 13/16" 42 1/8"
122mm 1071mm 36 3/16"
919mm

System System
Circuit 2 Circuit 1
Liquid In Liquid In

36 15/16" 40 1/8"
939mm System 1019mm
System
Circuit 2 Circuit 1
Liquid Out Liquid Out
9 3/8"
238mm

4 13/16" 7/8" Liquid to 40 11/16" 35 7/8"


123mm 1033mm 911mm
Indoor Unit
21 5/16"
541mm A A
REAR VIEW LEFT SIDE VIEW FRONT VIEW
(PIPING END) O 7/16" Typical 8 Places
(11mm) for unit mounting

40"
1016mm
39 3/8"
1000mm
O 7/16" Typical 8 Places
(11mm) for unit mounting

DETAIL B
5/8" 2 15/16"
16mm 74mm
Model Circuits Unit Voltage, Hz Approximate Dry Weight lbs (kg) 12 15/16"
208/230V, 460V 60Hz 217 (98) 328mm
PR050 1 22 15/16"
575V 60Hz 242 (110) 582mm
415V 50Hz 217 (98) 32 15/16"
836mm
208/230V, 460V 60Hz 340 (154)
35 7/8"
PR085-125 2 575V 60Hz 390 (177) 911mm
Form No.: DPN001040_REV4

415V 50Hz 347 (157)


SECTION A-A
DPN002326 REV : 6
Page :1 /1 REV DATE : 2/17
LIEBERT ECONOPHASE
UNIT ARRANGEMENT DIAGRAM
CONDENSER AND DUAL CIRCUIT ECONOPHASE UNIT
TOP VIEW

CIRCUIT 1

CIRCUIT 2
LIQUID LINE
TO ECONOPHASE
Air Cooled Condenser UNIT FROM BOTTOM
Air Cooled Condenser OF RECEIVER
42" Entering Hot Gas Line
Entering Hot Gas Line 1067mm
Minimum CIRCUIT 2
CIRCUIT 1 Clearance
TOP VIEW
3
Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2 in. per 10 ft.) down towards
EconoPhase unit.

3 Liquid from Condenser 1-3/8".


DO NOT TRAP LINE!
Slope (2 in. per 10 ft.) down
towards EconoPhase unit.

CIRCUIT 1 CIRCUIT 2
EconoPhase Unit
1
60"
1524mm
Typ.

FACTORY SUPPLIED, FIELD INSTALLED


Notes: FIELD PIPING

1. For proper pump function, a minimum elevation difference of 60 (1524 mm) must be maintained between the bottom of condenser box to the bottom of EconoPhase unit.
2. All indoor and outdoor field refrigerant piping must be insulated, 1/2" minimum. All outdoor insulation must be UV and ozone resistant.
Form No.: DPN001040_REV4

3. Components are not supplied by Liebert but are required for proper circuit operation and maintenance.
4. For Piping Elevation refer to DCN003994.
DPN002324 REV : 8
Page :1 /1 REV DATE : 1/17
LIEBERT ECONOPHASE
ELECTRICAL FIELD CONNECTIONS
PR050 - PR125 MODELS
PR085 - 125 PR050
Dual Circuit Single Circuit

Field Connection from Field High Voltage Connection Field Ground Connection
Condenser CANbus Wire per local codes Wire per local codes Field Connection from
Wire per local codes Condenser CANbus Field Ground Connection
Wire per local codes Wire per local codes
Field High Voltage Connection
Wire per local codes

Optional High Voltage


field wiring connection
2" (51mm) knockout
Optional Low Voltage Optional High Voltage
field wiring connection field wiring connection
7/8" (22mm) knockout 1-1/8" (29mm) knockout Optional Low Voltage Optional High Voltage
field wiring connection field wiring connection
7/8" (22mm) knockout 1-1/8" (29mm) knockout
Form No.: DPN001040_REV4

DPN002327 REV : 8
Page :1 /1 REV DATE : 4/17
LIEBERT VFD APPLICATIONS
DISCONNECTION EMC FILTER FOR OPERATION WITH
DELTA-CONNECTED POWER

COMMANDER SK SIZE C & D INVERTERS

UNIDRIVE M SIZE 3 INVERTERS UNIDRIVE M SIZE 4 INVERTERS

TO ELECTRICALLY DISCONNECT THE INTERNAL EMC FILTER, REMOVE THE SCREW AS SHOWN.
Form No.: DPN001040_REV4

DPN001946 REV : 2
Page :1 /2 REV DATE : 4/17
LIEBERT VFD APPLICATIONS
DISCONNECTION EMC FILTER FOR OPERATION WITH
DELTA-CONNECTED POWER

UNIDRIVE M SIZE 5 INVERTERS

REMOVE THE THREE M4 TERMINAL NUTS . LIFT AWAY THE COVER TO EXPOSE
THE M4 TORX INTERNAL EMC FILTER REMOVAL SCREW. FINALLY REMOVE THE M4 TORX
INTERNAL EMC FILTER REMOVAL SCREW TO ELECTRICALLY DISCONNECT THE INTERNAL
EMC FILTER.

UNIDRIVE M SIZE 6 INVERTERS


Form No.: DPN001040_REV4

TO ELECTRICALLY DISCONNECT THE INTERNAL EMC FILTER, REMOVE THE SCREW AS SHOWN.

DPN001946 REV : 2
Page :2 /2 REV DATE : 4/17
LIEBERT INTELLISLOT
UNITY PLATFORM CARDS
Product Specification/Installation Guide

The Liebert IntelliSlot Unity Platform ADDITIONAL FEATURES Liebert SN Environmental Sensor
brings SNMP, BACnet IP, BACnet Support (Web, SNMP, SMS and
SNMPv1, SNMPv2c and SNMPv3
MSTP, Modbus TCP, Modbus RTU, SMTP): Temperature, Humidity, Door
with MIB-II support
YDN23 and Web management Closure, Contact Closure and Leak
capability to many models of Vertivs HTTP/HTTPS 1.1 Detection: Liebert SN-2D, Liebert
power and cooling equipment. The BootP SN-3C, Liebert SN-L, Liebert SN-T,
cards employ Ethernet and RS-485 Liebert SN-TH, Liebert SN-Z01,
networks to monitor and manage a DHCP per RFC2131/2132 Liebert SN-Z02 and Liebert SN-Z03
wide range of operating parameters, Remote firmware updates via a Web IntelliSlot Unity cards are a form, fit,
alarms and notifications. The card also browser and function replacement for several
supports communication for LIFE
IPv6 support for HTTP/HTTPS, Liebert IntelliSlot Web and 485 cards.
Services by VERTIV.
DHCPv6, e-mail, SMS, SNMP v1/v2c/
v3 and Modbus TCP

COMPATABILITY with Liebert Equipment


IntellSlot Card Compatible with

IS-UNITY-DP Alber BDSU-50 Liebert Deluxe System/3 Liebert GXT3 Liebert PeX *
IS-UNITY-SNMP Liebert APM Liebert DS Liebert GXT4 Liebert PPC
IS-UNITY-LIFE Liebert APS Liebert DSE Liebert HPC Liebert RDC
Liebert Challenger Liebert EPM Liebert HPC-S/M/R/W/Generic Liebert RX
3000 Liebert EXC Liebert HPM Liebert XDC
Liebert CRV Liebert eXL Liebert NX 225-600 kVA Liebert XDP
Liebert CW Liebert EXL S1 Liebert NXC Liebert XDP-Cray
Liebert DCL Liebert eXM Liebert NXL *
Liebert DCP Liebert FDC Liebert NXR
Liebert FPC Liebert PCW/PDX
* YDN23 supported only for Liebert PeX and Liebert NXL.

590-1307-501C/SL-52646_REV11_6-17
1
LIEBERT INTELLISLOT UNITY PLATFORM CARDS
Product Specification/Installation Guide

COMPATABILITY with Communication Protocols


Life Communication Protocol
Liebert
Services
IntelliSlot Card HTTP Velocity Email SMS SNMP BACnet IP Modbus TCP YDN23*
Support
HTTPS Protocol v1,v2c,v3 BACnet MSTP Modbus RTU

IS-UNITY-DP

IS-UNITY-SNMP

IS-UNITY-LIFE

* YDN23 supported only for Liebert PeX and Liebert NXL.


4-3/4 (121 mm) 1/2 (11 mm)
DIMENSIONS
3 (76 mm)

1-1/2 2-3/8
(38 mm) (60.3 mm)

Front face

SPECIFICATIONS Board

Power Requirements DC Inputs 7 to 12VDC

Power Consumptions: 3.6W maximum

Dimensions, W x D x H 2.97 x 5.2 x 1.45 in. (75.5 x 15 x 37 mm)

Weight (assembled) Net: 7 oz (0.2 kg)

Shipping: 1.3 lb (0.6 kg)

Ambient Operating Environment 32 to 104F (0 to 40C); 10% to 90% RH (non-condensing)

Ambient Storage Temperature 4 to 140F (20 to 60C)

Communication Ports Ethernet Communication RJ-45 (LIFE Services requires a network


connection to the Internet)

RJ-45 (RJ-45 to 2-position terminal-block adapter)

WIRING
10/100 Mb/s Ethernet connector Standard Category 5E Cable 328 ft. (100m)
RJ-45 - One-Wire Connector Liebert Integrated One-Wire Sensor 65.6 ft. (20m)
Cable or 2m Cat 5E to Modular 1-Wire

VertivCo.com | Vertiv Headquarters, 1050 Dearborn Drive, Columbus, OH, 43085, USA
2017 Vertiv Co. All rights reserved. Vertiv and the Vertiv logo are trademarks or registered trademarks of Vertiv Co. All other names and logos referred to are trade names, trademarks or
registered trademarks of their respective owners. While every precaution has been taken to ensure accuracy and completeness herein, Vertiv Co. assumes no responsibility, and disclaims all
liability, for damages resulting from use of this information or for any errors or omissions. Specifications are subject to change without notice.

590-1307-501C/SL-52646_REV11_6-17
2
LIEBERT MC CONDENSER
PREMIUM EFFICIENCY CONTROL
STANDARD & OPTIONAL FEATURES

STANDARD FEATURES
COIL Liebert microchannel coils are allaluminum construction. Tubes are created by extruding small parallel refrigerant flow paths
into aluminum. Fulldepth louvered aluminum fins fill spaces between the tubes. Tubes, fins and aluminum headers are ovenbrazed to
form a complete refrigeranttoair heat exchange coil. Baffles are used in the headers to separate one coil slab into multiple passes
as needed. Coils are factory leak tested at a minimum of 300 PSIG and dehydrated. Copper stub pipes are electric resistance welded
to aluminum coils and joints are protected with polyolefin to seal joint from environmental corrosive elements. Hot gas and liquid lines
are brazed to the stub pipes with spun closed ends for customer piping connections. Coil pipe assembles are filled and sealed with a
nitrogen holding charge for shipment. One coil is used per fan assembly.
FAN/MOTOR ASSEMBLY The fan/motor assembly is complete with external rotor motor, fan blades and fan/finger guard. Fan blades are
constructed of stamped aluminum or steel extrusion coated with PP plastic. Fan guards are heavy gauge, close meshed, steel wire,
coated with a black corrosion resistant finish. Fan terminal blocks located on the top of the fan guard with IP54 protection class. Fans
are factory balanced and tested before shipment.
FAN MOTORS Fan motors are specifically designed for variable speed and have ball bearings. The EC fans provide internal overload
protection through the builtin electronics. Each EC fan motor has builtin controller and communication module, linked via
RS485 communication wire to each fan and the Premium Control Board. This allows each fan to receive and respond to precise fan
speed inputs from the Premium control board.
PREMIUM EFFICIENCY FAN CONTROL The Liebert premium efficiency condenser control system is complete with control board, EC
fan motor(s),refrigerantpressure transducer(s), refrigeranttemperature thermistor(s), ambienttemperature thermistor, and motor
overload protection in the factory wired control panel. The control board maintains EC fans on the same circuit to the same speed in order
to maintain refrigerant head pressure. The control board receives a run signal from the compressor of the indoor unit via fieldsupplied
low voltage interlock wires and fieldsupplied CANbus communication wires from the indoor unit iCOM. The control system
provides refrigerant head pressure and system starting for outdoor ambient temperature as low as -30F (35 C), provided the
total temperature design range (from minimum to maximum) is 125F (70C) or less.
HOUSING The condenser housing is constructed of bright aluminum sheet and divided into individual fan sections by full width baffles.
Internal structural support members, including coil support frame, are galvanized steel for strength and corrosion resistance. Panel doors
are provided on two sides of each coil/fan section to provide for coil cleaning. Aluminum legs are provided with rigging holes for hoisting
the unit into position.
COMMUNICATION The Premium Efficiency Control communicates with the iCOM control of the indoor Liebert unit using field supplied CANbus
wires. The communication link allows for condenser alarm condition communication to iCOM, communication of other measurable items
on the condenser, and fan control features to improve efficiency, sound and wintertime operation based on iCOM programming.
UNIT DISCONNECT SWITCH Locking unit disconnect switch is factory installed and wired in attached condenser control section.

OPTIONAL FEATURES
LIEBERT LEETEMP LOW AMBIENT CONTROL LeeTemp receiver kits can be added to achieve head pressure control down to minimum
ambient temperatures of 30 F (34 C). The premium efficiency fan control when used with the Liebert LeeTemp receiver kits runs
the fan(s) at lower speeds during cold temperatures saving fan energy.
575V POWER SUPPLY The factory installed condenser option will include a secondary enclosure, a 575V-to-480V, 3 phase, step down
transformer, secondary fuses for the transformer, and all wiring between the main and secondary electrical enclosures. Site
power connections will be made in the main electrical enclosure and the secondary enclosure will be located on the condenser end
Form No.: DPN001040_REV4

opposite of the main electrical enclosure.

DPN002155 REV : 2
Page :1 /1 REV DATE : 12/16
LIEBERT MC CONDENSER
CABINET & ANCHOR DIMENSIONAL DATA
575V
Option 4 FAN (MCM160, MCL220)
B
575V
Option
Lifting Eyebolts
Typ. (4) Places
F

H
A* TOP OF
A FAN GUARD
G

Lee-Temp or DSE Receiver


Entering
Hot Gas and
C Leaving
Liquid Piping
E D

A
Main
Full height Leg Electric
Anchor Plan supplied for each Box M L K
Lee-Temp or DSE End
Receiver required 3
6 1/2"
165mm Ref.
J
Left Side of Unit Lee-Temp or DSE Only
15 1/4"
387mm
6 1/2"
165mm Ref.
3
Note: Dual Circuit Only 15 1/4"
3 387mm
3 5/8" 1. Liebert recommends a clearance of 36 (915mm)
3 Dual
93mm on each side for proper operation and component access.
13/16" Circuit
21mm Typ. K Only
1 7/8" 2 Cross bracing required for legs longer than 18" (457.2mm).
Typ. 48mm
Typ. Quantity varies per model & options selected. Front View (Lee-Temp shown)
3 For DSE models only, 6-1/2" (165mm) dimension is 9-1/4" (235mm)
and 15-1/4 (387mm) dimension is not applicable.
7" LIEBERT
F 2
178mm MODEL
Typ. LEG HEIGHT DIMENSIONS in. (mm)
NUMBER
18 (457) 36 (914) 48 (1219) 60 (1524)
1/2" (13mm) X 1" (25mm) MCM160
Obround Typ. DIM "G" 31-5/8 (803) 49-5/8 (1260) 61-5/8 (1565) 73-5/8 (1870)
DETAIL A DIM "H" 39-5/8 (1006 57-5/8 (1464) 69-5/8 1768) 81-5/8 (2073)
Typical all legs MCL220
DIM "G" 35-7/8 (911) 53-7/8 (1368) 65-7/8 (1673) 77-7/8 (1978)
DIM "H" 43-5/8 (1108) 61-5/8 (1565) 73-5/8 (1870) 85-5/8 (2175)

Dimensions in. (mm)


J
LIEBERT
A* Lee-Temp or
MODEL A B C D E K L M
(575V ONLY) DSE Receiver
NUMBER
Only
Form No.: DPN001040_REV4

MCM160 202-7/16 (5142) 210-5/8 (5350) 113-1/2 (2883) 192-1/4 (4883) 94-7/16 (2398) 96-3/16 (2444) 46-5/16 (1177) 46 (1168) 44-3/8 (1127) 39-5/16 (999)
MCL220 236-5/16 (6003) 245-5/16 (6231) 129-9/16 (3291) 224-3/8 (5699) 110-1/2 (2806) 112-1/4 (2851) 54-3/8 (1381) 55-1/2 (1410) 53-7/8 (1368) 48-3/4 (1238)

DPN003439 REV : 4
Page :1 /1 REV DATE : 3/17
LIEBERT MC CONDENSER
CONDENSER AND OPTION WEIGHT DATA, lb(kg)
Size Small (MCS) Medium (MCM)
Condenser Model MCS028 MCS056 MCM040 MCM080 MCM160
Refrigerant Circuits 1 2 1 1 2 2
18" Leg 154 ( 70) 270 ( 122) 231 ( 105) 441 ( 200) 441 ( 200) 860 ( 390)
Condenser Dry 36" Leg 286 ( 130) 419 ( 190) 363 ( 165) 590 ( 268) 590 ( 268) 1066 ( 484)
Weight 48" Leg 318 ( 144) 451 ( 205) 395 ( 179) 622 ( 282) 622 ( 282) 1114 ( 505)
60" Leg 349 ( 158) 482 ( 219) 426 ( 193) 653 ( 296) 653 ( 296) 1160 ( 526)
Additional Weight for Options
PDX-EEV Receiver 45 ( 20) 45 ( 20) 45 ( 20)
Lee-Temp 55 ( 25) 110 ( 50) 55 ( 25) 100 ( 45) 110 ( 50) 220 ( 100)
DSE Receiver DA050/080/085 88 ( 40)
DSE Receiver DA125/150/165 184 ( 83)
575V Transformer 55 ( 25) 65 ( 29) 60 ( 27) 70 ( 32) 70 ( 32) 80 ( 36)
Coated Coil 4 ( 2) 8 ( 4) 5 ( 2) 10 ( 5) 10 ( 5) 20 ( 9)
Seismic/Wind Bracing 18" legs 40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 40 ( 18) 57 ( 26)

Size Large (MCL)


Condenser Model MCL055 MCL110 MCL165 MCL220
Refrigerant Circuits 1 1 2 1 1 2
18" Leg 344 ( 156) 602 ( 273) 602 ( 273) 891 ( 404) 1186 ( 538) 1186 ( 538)
Condenser Net 36" Leg 486 ( 220) 766 ( 347) 766 ( 347) 1136 ( 515) 1453 ( 659) 1453 ( 659)
weight 48" Leg 518 ( 235) 798 ( 362) 798 ( 362) 1184 ( 537) 1501 ( 681) 1501 ( 681)
60" Leg 549 ( 249) 829 ( 376) 829 ( 376) 1230 ( 558) 1547 ( 702) 1547 ( 702)
Additional Weight for Options
PDX-EEV Receiver 45 ( 20)
Lee-Temp 60 ( 27) 115 ( 52) 120 ( 54) 175 ( 79) 215 ( 98) 240 ( 109)
DSE Receiver DA050/080/085 45 ( 20) 90 ( 41) 45 ( 20) 90 ( 41)
DSE Receiver DA125/150/165 94 ( 43) 188 ( 85) 94 ( 43) 94 ( 43) 188 ( 85)
575V Transformer 67 ( 30) 77 ( 35) 77 ( 35) 118 ( 54) 118 ( 54) 118 ( 54)
Coated Coil 8 ( 4) 16 ( 7) 16 ( 7) 24 ( 11) 32 ( 15) 32 ( 15)
Seismic/Wind Bracing 18" legs 40 ( 18) 40 ( 18) 41 ( 19) 57 ( 26) 57 ( 26) 57 ( 26)

Total weight is the sum of 'Condenser' + ('PDX-EEV Receiver' or 'Lee-Temp' or 'DSE Receiver 050/080/085' or 'DSE Receiver
125/150/165')'+'Coated Coil' + '575V Transformer'.+ 'Seismic/Wind Bracing'
Form No.: DPN001040_REV4

DPN003034 REV : 3
Page :1 /1 REV DATE : 12/16
LIEBERT MC CONDENSER
PIPING DIMENSIONAL DATA
DUAL CIRCUIT 2 FAN & 4 FAN UNITS

COVER *
VERTICAL

INVERTED TRAPS
ARE FACTORY PROVIDED
INSIDE CONDENSER

FIELD PIPING
LEAVING LIQUID
LINE

HORIZONTAL

ENTERING HOT
GAS LINE
DETAIL A
CIRCUIT #1 CIRCUIT #2

OPTIONAL FUSIBLE PLUG SERVICE KIT TO


BE BRAZED INTO THE LIQUID LINE(S) IN
EITHER THE VERTICAL OR HORIZONTAL
POSITION (WHERE REQUIRED).
(VERTICAL POSITION IS PREFERRED,
HORIZONTAL POSITION IS OPTIONAL.)

FOR TWO CIRCUIT SYSTEMS, ONE


FUSIBLE PLUG KIT WILL NEED TO
BE INSTALLED IN EACH CIRCUIT. A

NUMBER CONDENSER CONNECTION SIZES ,OD,IN


MODEL NO.
OF FANS CIRCUITS HOT GAS LINE LIQUID LINE
MCS 056 2 2 7/8 5/8
MCM 080 2 2 7/8 5/8
MCL 110 2 2 1-1/8 7/8
MCM 160 4 2 1-1/8 7/8
MCL 220 4 2 1-3/8 1-1/8
Form No.: DPN001040_REV4

* SHIPPING COVER IS NOT NECESSARY FOR PROPER CONDENSER OPERATION AND


MAY BE RECYCLED IF FIELD PIPING INTERFERES WITH PROPER REATTACHMENT.
DPN002425 REV : 6
Page :1 /1 REV DATE : 12/16
LIEBERT AIR COOLED SYSTEMS
RECOMMENDED REFRIGERANT LINE SIZES CU, OD
LIEBERT AIR-COOLED SYSTEMS USING R-410A
System Fluid : R-410A Any Compressor Type
Indoor Model Equivalent Length 50 ft (15m) 100 ft (30m) 150 ft (45m) 300 ft (91m) 450ft (137m)
2
CR019RA/ Hot Gas Line, in. 3/4 3/4 3/4 7/8
CR020RA Liquid Line, in. 5/8 5/8 5/8 3/4
2
Hot Gas Line, in. 7/8 7/8 7/8 1-1/8
CR035RA
Liquid Line, in. 3/4 3/4 3/4 7/8
2 2 2
Hot Gas Line, in. 1/2 5/8 5/8 5/8
PX011
Liquid Line, in. 3/8 1/2 1/2 1/2
2
Hot Gas Line, in. 5/8 5/8 5/8 3/4
PX018
Liquid Line, in. 1/2 1/2 1/2 5/8
2
Hot Gas Line, in. 3/4 3/4 3/4 7/8
PX023
Liquid Line, in. 5/8 5/8 5/8 5/8
2
Hot Gas Line, in. 7/8 7/8 7/8 1-1/8
PX029
Liquid Line, in. 5/8 5/8 5/8 3/4
3
DA050 / DA080/ Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
DA085 3
Liquid Line, in. 7/8 7/8 7/8 7/8 7/8
3
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
DA125 3
Liquid Line, in. 7/8 7/8 7/8 7/8 7/8
3
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
DA150 3
Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8
3
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
DA165
Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8 1-1/8 3

Notes:
1. Consult factory for proper line sizing for runs longer than maximum equivalent length shown in table.
2. Must downsize vertical riser one trade size (1-1/8 to 7/8 or 7/8 to 3/4 or 3/4" to 5/8" or 5/8" to 1/2").
3. Consult factory when actual pipe length between condenser/EconoPhase and Liebert DSE unit will exceed 300 ft (91 m).
Form No.: DPN001040_REV4

DPN000788 REV : 5
Page :1 /2 REV DATE : 3/17
LIEBERT AIR COOLED SYSTEMS
RECOMMENDED REFRIGERANT LINE SIZES CU, OD
LIEBERT AIR-COOLED SYSTEMS USING R-407C
4-Step Semi-Hermetic
System Fluid : R-407C Standard Scroll Models (Non-Digital Scroll)
or Digital Scroll Models
Indoor Model Equivalent Length 50 ft (15m) 100 ft (30m) 150 ft (45m) 200 ft (60m) 50 ft (15m) 100 ft (30m) 150 ft (45 m)
Hot Gas Line, in. 7/8 7/8 7/8 3/4 3/4 7/8
DS028
Liquid Line, in. 1/2 5/8 5/8 1/2 5/8 5/8
Hot Gas Line, in. 7/8 7/8 7/8 3/4 7/8 7/8
DS035
Liquid Line, in. 1/2 5/8 5/8 1/2 5/8 5/8
1
Hot Gas Line, in. 7/8 7/8 7/8 7/8 7/8 1-1/8
DS042
Liquid Line, in. 1/2 5/8 5/8 5/8 5/8 5/8
1 1
Hot Gas Line, in. 7/8 1-1/8 1-1/8 7/8 1-1/8 1-1/8
DS053
Liquid Line, in. 5/8 7/8 7/8 7/8 7/8 7/8
1 1 1
Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
DS070
Liquid Line, in. 7/8 7/8 7/8 7/8 7/8 7/8
Hot Gas Line, in. 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8 1-1/8
DS0772
Liquid Line, in. 7/8 7/8 7/8 7/8 7/8 7/8
Hot Gas Line, in. 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8 1-3/8
DS1052
Liquid Line, in. 7/8 7/8 1-1/8 7/8 7/8 1-1/8
3 3 3 3
Hot Gas Line, in. 1-1/8 1-1/8 1-3/8 1-3/8
XDC160
Liquid Line, in. 7/8 1-1/8 1-1/8 1-1/8

System Fluid : R-407C Standard Scroll Models (Non-Digital Scroll)

Indoor Model Equivalent Length 50 ft (15m) 75 (23m) 100 ft (30m) 125 (38m) 150 ft (45m)
Suction Line, in. 5/8 5/8 7/8 7/8 7/8
MMD12
Liquid, Line, in. 3/8 3/8 3/8 3/8 3/8
Suction Line, in. 5/8 7/8 7/8 7/8 7/8
MMD18 / DME020
Liquid, Line, in. 3/8 3/8 3/8 1/2 1/2
Suction Line, in. 7/8 7/8 7/8 7/8 7/8
MMD24 / DME027
Liquid, Line, in. 3/8 3/8 1/2 1/2 1/2
1 1
MMD36/ MMD35 / DME037 / Suction Line, in. 7/8 7/8 1-1/8 1-1/8 1-1/8 1
MMD96-3T / MMD95-3T Liquid, Line, in. 1/2 1/2 1/2 1/2 1/2
MMD60/ MMD59 / MMD96-5T Suction Line, in. 1-1/8 1-1/8 1-1/8 1-3/8 1-3/8
/MMD95-5T Liquid, Line, in. 1/2 5/8 5/8 5/8 5/8

Note:
Consult factory for proper line sizing for runs longer than maximum equivalent length shown in tables above.
1. Downsize vertical riser one trade size (1-1/8" to 7/8")
2. Digital scroll not available on 077 and 105 models.
3. Double risers are required when hot gas vertical rise is 15 ft (4.6m) or more. Refer to XDC user manual
Form No.: DPN001040_REV4

DPN000788 REV : 5
Page :2 /2 REV DATE : 3/17
LIEBERT DSE
AIR COOLED PIPING SCHEMATIC
LIEBERT MC & ECONOPHASE MOUNTED ABOVE LIEBERT DSE
*Liquid from Condenser 1-3/8".
DO NOT TRAP LINE!
Slope (2" per 10') down towards Liebert MC Condenser Field Piping
EconoPhase unit. Unit
Notes:

Gas 1. Trapping must be practiced at bottom of riser with any


60" leg height rise over 5 feet (1.5m) high. If rise exceeds 25 feet (7.5m),
Typical, then a trap is required in 20 foot (6.1m) increments or evenly
6 divided.
2. Pitch horizontal hot gas piping at a minimum of 1/2" per
10 feet (42mm per 10m) so that gravity will aid in moving
5 60" oil in the direction of the refrigeration flow.
1524mm
3. Single Circuit system shown for clarity, Most Liebert
DSE systems are dual circuit.
4. Unit piping entrance varies by unit and may be through
EconoPhase Unit the top of the unit.
48.52" 5. The outlet of the unheated receiver must be higher than the
(1232mm) elevation of the EEV inside the indoor unit.
6. For proper pump function, a minimum elevation difference of
Liquid 60 (1524 mm) must be maintained between the bottom of
condenser box to the bottom of EconoPhase unit.
7. All indoor and outdoor field refrigerant piping must be
insulated, 1/2" minimum. All outdoor insulation must
be UV and ozone resistant.
8. For Liebert MC Condenser and Single Circuit Econophase unit
arranagement. See DPN003552
9. For Liebert MC Condenser and Dual Circuit Econophase unit
arranagement. See DPN002324.

DSE unit
60'
(18.3m)
Maxium
Vertical
Rises
EEV Height
for Downflow &
1 Upflow Units
5
Gas
Liquid
43"
(1092 mm)
1

Gas

Gas
FRONT VIEW
4

1 2 Liquid
Form No.: DPN001040_REV4

Liquid

DPN003994 REV : 0
Page :1/2 REV DATE : 1/17
LIEBERT DSE
AIR COOLED PIPING SCHEMATIC
LIEBERT MC & ECONOPHASE AND LIEBERT DSE
AT SIMILAR LEVELS
DSE

*Liquid from Condenser 1-3/8".


DO NOT TRAP LINE!
Slope (2" per 10') down towards Liebert MC Condenser
EconoPhase unit. Unit EEV Height
5 for Downflow &
Gas Upflow Units
60" leg height
Typical,
5 6

EconoPhase Unit 60"


1524mm
43"
48.52" (1092 mm)
(1232mm)

Gas

Liquid
Gas
4
FRONT VIEW
Gas
1
Liquid

Notes:

1. Trapping must be practiced at bottom of riser with any


rise over 5 feet (1.5m) high. If rise exceeds 25 feet (7.5m), Field Piping
then a trap is required in 20 foot (6.1m) increments or evenly
divided.
2. Pitch horizontal hot gas piping at a minimum of 1/2" per
10 feet (42mm per 10m) so that gravity will aid in moving
oil in the direction of the refrigeration flow.
3. Single Circuit system shown for clarity, Most Liebert
DSE systems are dual circuit.
4. Unit piping entrance varies by unit and may be through
the top of the unit.
5. The outlet of the unheated receiver must be higher than the
elevation of the EEV inside the indoor unit.
6. For proper pump function, a minimum elevation difference of
60 (1524 mm) must be maintained between the bottom of
condenser box to the bottom of EconoPhase unit.
7. All indoor and outdoor field refrigerant piping must be
insulated, 1/2" minimum. All outdoor insulation must
be UV and ozone resistant.
8. For Liebert MC Condenser and Single Circuit Econophase unit
arranagement. See DPN003552
Form No.: DPN001040_REV4

9. For Liebert MC Condenser and Dual Circuit Econophase unit


arranagement. See DPN002324.

DPN003994 REV : 0
Page :2/2 REV DATE : 1/17
LIEBERT MC CONDENSER
DSE RECEIVER MOUNTING
MCM160 DUAL CIRCUIT DUAL CONDENSER OUTLET RECEIVERS

7
CIRCUIT 2
4 3 2 CIRCUIT 1 12
TRIM PIPING
TYP (4) PLACES
A AS NEEDED DETAIL A 8
2 16 15

1 1 12 7
7 8 8

TRIM PIPING
AS NEEDED

2 3 4
TYP (4) PLACES
8

15 16
8
11 1/8"
283mm 7

1 1
64 5/8" 36" 5 6 9
1642mm 914mm TYP
CLEARANCE REQUIRED FOR 2
VIEWING SIGHT GLASS.

ITEM NO. DESCRIPTION QTY


CROSS BRACING 1 RECEIVER AND BRACKET ASSEMBLY 2
NOT SHOWN 2 CAP SCREW HXDIN933M8-1.25X25A2 12
3 FENDER WASHER DIN9021 M8X24 A2 20
4 LOCK NUT HEX NYL INSR M8 12
5 CLAMP OMEGA 7/8" 1
6 SCREW SD HWH YZ 10-16 X 5/8 2
7 90 ELBOW FTGXC 7/8" CU 3
NOTES 8 COPPER FORMED TUBE 7/8" 2
9 COPPER FORMED TUBE 7/8" 1
1. SMALL RECEIVER SHOWN. ACTUAL RECEIVER 12 COPPER TUBE 7/8" SWAGED 1
SIZE MAY VARY. 15 SUPPORT LEG 1
16 FASTENER ASSEMBLY: CAP SCREW, LOCK WASHER, FENDER WASHER 4
Form No.: DPN001040_REV4

2. RECEIVER LEG IS SAME HEIGHT AS OTHER LEGS


AND NEEDS TO BE ANCHORED WITH THEM.

DPN002383 REV : 8
Page :1 /1 REV DATE : 3/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
FAN 2

FAN 1

8
10
SH
12
13
70
71
9 230

NOTICE !
THIS HOLE FOR FIELD
SUPPLIED EXTRA LOW
VOLTAGE CONTROL WIRING

KEY ELECTRICAL DETAILS:


1) Three phase electrical service Terminals are on top of disconnect switch for one and two fan units. Terminals are on bottom of
disconnect switch for three and four fan units. Three phase service not by Liebert. See note 5.
2) Earth ground Field lug terminal for earth ground connection. Ground terminal strip for fan motor ground connection.
3) Primary high voltage entrance Two 7/8 (22.2mm) diameter knockouts located at the bottom of the enclosure.
Form No.: DPN001040_REV4

4) SPD field connection terminals High voltage surge protective device (SPD) terminals. SPD is an optional device.
DPN002169 REV : 10
Page :1 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
5) CANbus terminal connections Field terminals for CANbus cable connection.
5A is the CANbus connectors.
o TB49-1 is the input terminal for CANbus high.
o TB49-3 is the input terminal for CANbus low.
o TB50-1 is output terminal for CANbus high.
o TB50-3 is the output terminal for CANbus low.
o Each CANbus cable shield is connected to terminal SH, item 9.
5B is the END OF LINE jumper.
5C is the CANbus DEVICE ADDRESS DIP SWITCH. CANbus cable not by Liebert. See Note 2. (below)
6) Remote unit shutdown Replace existing jumper between terminals TB38-1 and TB38-2 with field supplied normally closed
switch having a minimum 75VA 24VAC rating. Use field supplied Class 1 wiring. (This is an optional feature that may be owner specified.)
7) Alarm terminal connections
a. Common Alarm Relay indicates when any type of alarm occurs. TB74-1 is common, TB74-2 is normally open, and TB74-3 is
normally closed. 1 Amp 24VAC is the maximum load. Use Class 1 field supplied wiring.
b. Shutdown Alarm Relay indicates when condenser loses power, or when a critical alarm has occurred that shuts down the
condenser unit. TB74-4 is common, TB74-5 is normally open, and TB74-6 is normally closed. 1 Amp 24VAC is the maximum load.
Use Class 1 field supplied wiring.
8) Indoor unit interlock and SPD alarm terminals
a. On any call for compressor operation, normally open contact is closed across terminals 70 and 71 for Circuit 1, and normally open
contact is closed across terminals 70 and 230 for Circuit 2 from indoor room unit.
b. During SPD alarm, normally open contact is closed across terminals 12 & 13. SPD is an optional device.
9) CANbus shield terminal Terminal for field shield connection of the CANbus field supplied cables. The shield of CANbus field supplied
cables must not be connected to ground at the condenser.
10) Primary low voltage entrance One 7/8 (22.2mm) diameter knockout that is free for customer low voltage wiring.
11) SPD entrance One 7/8 (22.2mm) diameter knockout hole located at the bottom of the enclosure. High voltage surge protective device
(SPD) is optional.
NOTES:
1. Refer to specification sheet for unit voltage rating, full load amp, and wire size amp ratings.
2. The CANbus wiring is field supplied and must be:
- Braided shield or foil shield with drain wire
- Shield must be wired to ground at indoor unit
- 22-18AWG stranded tinned copper
- Twisted pair (minimum 4 twists per foot)
- Low Capacitance (15pF/FT or less)
- Must be rated to meet local codes and conditions
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER
3. Do not run in same conduit, raceway, or chase as high voltage wiring.
4. For CANbus network lengths greater than 450FT (137M) call Factory.
Form No.: DPN001040_REV4

DPN002169 REV : 10
Page :2 /3 REV DATE : 2/17
LIEBERT MC CONDENSER
ELECTRICAL FIELD CONNECTIONS
PREMIUM EFFICIENCY CONTROL
5. All wiring must be sized and selected for insulation case per NEC and other local codes.
6. Do not bend cables to less than four times the diameter of the cable.
7. Do not deform cables when securing in bundles or when hanging them.
8. Avoid running the cables by devices that may introduce noise, such as machines, fluorescent lights, and electronics.
9. Avoid stretching cables.
10. The electrically commutated (EC) motors included in the Liebert MC Condenser are suitable for connection to power supplies with a
solidly grounded neutral or high resistance to ground or corner ground.
a. Acceptable power supplies for 208 to 575V nominal units:
208V wye with solidly grounded neutral and 120V line to ground;
380V wye with solidly grounded neutral and 220V line to ground;
480V wye with solidly grounded neutral and 277V line to ground;
575V wye with solidly grounded neutral and 332V line to ground (uses step-down transformer);
Wye with high resistance (or impedance) ground;
Delta with corner ground
b. Unacceptable power supplies for 208V to 575V nominal units:
Delta without ground or with floating ground;
Delta with grounded center tap.
Form No.: DPN001040_REV4

DPN002169 REV : 10
Page :3 /3 REV DATE : 2/17
LIEBERT DSE
CANbus & INTERLOCK COMMUNICATIONS
USING 1 LIEBERT MC CONDENSER & OPTIONAL ECONOPHASE UNIT ECONOPHASE ECONOPHASE
FACTORY WIRING BETWEEN CONTROL BOARD CONTROL BOARD
CONTROL BOARDS AND SINGLE CIRCUIT DUAL CIRCUIT
(FACTORY SET) (FACTORY SET)
TERMINAL STRIP. CIRCUIT ONE CIRCUIT ONE

1
J6 J6

3
ON ON

CAN SW6 CAN SW6

CIRCUIT TWO
NO SHIELD

1
CONNECTION
CANbus J6

3
DETAIL 4 ADDRESSING
SWITCH ON ECONOPHASE UNIT
CAN CABLE CONNECTION (B) LAST DEVICE ON CANBUS
CAN SW6
(IF PRESENT)

B
P80 P15
B A
ONE ONE CONDENSER
CONDENSER WITH ECONOPHASE
TB50
B CANBUS COMMUNICATION CABLE
H

CAN H
TB50

1
1

OUTPUT 2
D58
3 CAN L
L

J6 J6
1
H

J4
TB49
3

3
3
TB49

1
INPUT 2 ON ON
L

CONDENSER
3
1

J6
3

CAN SW6
CAN SW6

A
BOOTPSWD SYS APP

TB50

3
1 CAN H
OUTPUT 2
3 CAN L

TB49
1
INPUT 2
3

CANbus
ON

ADDRESSING
CAN SW6
SWITCH

DETAIL 3
CAN CABLE CONNECTION (A) (B) SHIELD CONNECTION

B FACTORY WIRING BETWEEN


MC CONTROL BOARD AND
A SH
TERMINAL STRIP.
70 REMOVE JUMPER
71
FOR DUAL CIRCUIT
F 230

LOW VOLTAGE FIELD ENTRANCE HEAT REJECTION


LOCATED ON BOTTOM LEFT OF
CONDENSER ENCLOSURE. HEAT REJECTION INTERLOCK (F)
F INTERLOCK WIRE
DETAIL 2
HEAT REJECTION INTERLOCK (F)
A CANBUS
CABLE
COMMUNICATION

70 71 230
2
1
SHIELD CONNECTION F
SH
49-1
A
49-3
Form No.: DPN001040_REV4

DETAIL 1 CAN CABLE CONNECTION (A) INDOOR DSE UNIT


FACTORY WIRING BETWEEN ICOM AND TERMINAL STRIP.

DPN003284 REV : 2
Page :1 /2 REV DATE : 1/17
LIEBERT DSE
CANbus & INTERLOCK COMMUNICATIONS
USING 1 LIEBERT MC CONDENSER & OPTIONAL ECONOPHASE UNIT
COMPONENT NOTES:
1. COMPONENT APPEARANCE, ORIENTATION , AND POSITION MAY VARY BETWEEN PRODUCT LINES. TERMINAL NAMES AND CALLOUTS REMAIN
CONSTANT.
2. ALL CIRCUITS TO THESE CONNECTION POINTS ARE CLASS 2.

CAN & CABLE NOTES (A, B):


1. CABLE MUSTHAVE THE FOLLOWING SPECIFICATIONS:
- BRAIDED SHIELD OR FOIL SHIELD WITH DRAIN WIRE
- SHIELD MUST BE WIRED TO GROUND AT INDOOR UNIT
- 22-18AWG STRANDED TINNED COPPER
- TWISTED PAIR (MINIMUM 4 TWISTS PER FOOT)
- LOW CAPACITANCE (15pF/FT OR LESS)
- MUST BE RATED TO MEET LOCAL CODES AND CONDITIONS.
- EXAMPLES BELDEN 89207 (PLENUM RATED), OR ALPHA WIRE 6454 CATEGORY 5, 5E, OR HIGHER.
- DO NOT RUN IN SAME CONDUIT, RACEWAY, OR CHASE AS HIGH VOLTAGE WIRING.
FOR CANBUS NETWORK LENGTHS GREATER THAN 450FT(137M), CONTACT LIEBERT FACTORY.

INTERLOCK WIRE NOTES (F):


1. FIELD SUPPLIED WIRE
- 18AWG OR GREATER
- RATED 600V
2. FOR SINGLE CIRCUIT SYSTEMS, RUN TWO WIRES FROM INDOOR UNIT TO CONDENSER\S.
3. FOR DUAL CIRCUIT SYSTEMS, RUN THREE WIRES FROM THE INDOOR UNIT TO FIRST CONDENSER, AND ONE WIRE FROM FIRST CONDENSER TO
SECOND CONDENSER (IF PRESENT).
Form No.: DPN001040_REV4

DPN003284 REV : 2
Page :2 /2 REV DATE : 1/17