Technical Guide P220/EN TD/B43

MiCOM P220

Technical Data
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 1/30

CONTENTS

1. PROTECTION FUNCTIONS 3

1.1 Thermal replica 3


1.2 Short-circuit protection 3
1.3 Earth fault protection 3
1.4 Unbalance protection 3
1.5 Too long start-up protection 4
1.6 Locked rotor protection 4
1.7 Under current protection 4
1.8 RTD temperature detection or thermistors 4

2. AUTOMATION FUNCTIONS 5

2.1 Limitation of the number of start-ups 5


2.2 Time between 2 start-ups 5
2.3 Re-acceleration authorization 5
2.4 Logic Inputs / Auxiliary timers 5
2.5 Logic Equations 5
2.6 Logic equation time delay 5
2.7 Auxiliary Output Relays 5
2.8 Latching of the output relays 5
2.9 Trip Output Relay 5
2.10 Latching of the Trip Order 5
2.11 Control and monitoring of the breaker device 6

3. OPTIONAL FUNCTIONS 7

3.1 Optional analogue output 7


3.2 Optional 6 RTD inputs 7
3.3 Optional 2 thermistors inputs 7

4. RECORDING FUNCTIONS 8

4.1 Event recorder 8


4.2 Fault recorder 8
4.3 Oscillography 8

5. COMMUNICATION 9

5.1 MODBUSTM communication 9


5.2 Front communication 9
P220/EN TD/B43 Technical Guide
Technical Data
Page 2/30 MiCOM P220

6. INPUTS AND OUTPUTS 10

6.1 Inputs 10
6.2 Logic inputs 10
6.3 Output relays 10
6.4 Auxiliary voltage 11

7. ACCURACY 11

8. CT DATA 11

9. HIGH VOLTAGE WITHSTAND 11

10. ELECTRICAL ENVIRONMENT 12

11. ENVIRONMENT 12
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 3/30

1. PROTECTION FUNCTIONS
1.1 Thermal replica
Thermal current threshold 1> 0.2 to 1.5 In by steps of 0.01 In
Overload time-constant Te1 1 to 180 min by steps of 1 min
Start-up time-constant Te2 1 to 360 min by steps of 1 min
Cooling time-constant Tr 1 to 999 min by steps of 1 min
Negative sequence current recognition factor Ke 0 to 10 by steps of 1
Trip thermal threshold Set to 100%
Trip thermal threshold hysteresis 97%
Thermal alarm threshold 20 to 100% by steps of 1%
Thermal alarm threshold hysteresis 97%
Start-up inhibition 20 to 100% by steps of 1%
1.2 Short-circuit protection
Current threshold I>> 1 to 12 In by steps of 0.1 In
Time-delays tl >> 0 to 100 s by steps of 0.01 s
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 95%
1.3 Earth fault protection
Current thresholds lo>, lo>> 0.002 to 1 Ion by steps of 0.001
Ion
Time-delays tlo>, tlo>> 0 to 100 s by steps of 0.01 s
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 95%
1.4 Unbalance protection
Negative sequence current threshold li> 0.05 to 0.8 In by steps of 0.025 In
Time-delays tli> 0.04 to 200 s by steps of 0.01 s
Negative sequence current threshold Ii >> 0.2 to 0.8 In by steps of 0.05 In
IDMT time-delay operating time t = 1.2 / (I2/In)
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 95%
P220/EN TD/B43 Technical Guide
Technical Data
Page 4/30 MiCOM P220

1.5 Too long start-up protection


Start-up detection criteria (Closing 52) or (closing 52 +
current threshold) optional
Current threshold Istart 1 to 5 I by steps of 0.5 I
Time-delays T Istart 1 to 200 s by steps of 1 s
1.6 Locked rotor protection
Current threshold Istall 1 5 I by steps of 0,5 I
Hysteresis 95%
Time delays tlstall 0.1 60 s by steps of 0.1 s
Locked rotor at start-up detection Yes/No
1.7 Under current protection
Current threshold I< 0.1 to 1 In by steps of 0.01 In
Time-delays tl< 0.2 to 100 s by steps of 0.1 s
Inhibition time at start-up Tinhib 0.05 to 300 s by steps of 0.1 s
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 105%
1.8 RTD temperature detection or thermistors
RTD (or THERMISTOR + RTD) function -Optional YES/NO
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 5/30

2. AUTOMATION FUNCTIONS
2.1 Limitation of the number of start-ups
Reference period Treference 10 to 120 min by steps of 5 min
Number of cold starts 0 to 5 by steps of 1
Number of hot starts 0 to 5 by steps of I
Restart inhibition time Tinterdiction 1 to 120 min by steps of 5 min
2.2 Time between 2 start-ups
Inhibition time Tbetw 2 start 1 to 120 min by steps of 5 min
2.3 Re-acceleration authorization
Voltage collapse duration Treacc 0.2 to 10 s by steps of 0.05 s
2.4 Logic Inputs / Auxiliary timers
1Logic input CB position
1Logic input Speed Switch
3 Programmable Logic inputs
Logic inputs with alarm message on occurence 2 external signals, EXT1 and EXT2
Logic inputs without alarm message on occurence 2 external signals, EXT3 and EXT4
(from V3.A software version)
Timers tEXT1, tEXT2, tEXT3 and tEXT4 0 to 200 s by step of 0.01s
2.5 Logic Equations
4 AND logic equations
2.6 Logic equation time delay
Pick-up time delay 0 to 60 min by steps of 0.1 s
Reset time 0 to 60 min by steps of 0.1 s
2.7 Auxiliary Output Relays
1 Trip Output Relay (RL1) Programmable
4 Auxiliary Output relays (RL2,RL3,RL4,RL5) Programmable
1 watchdog relay.( for equipment default)
2.8 Latching of the output relays
Latching of the output relays (RL2,RL3,RL4,RL5)on Short-circuit, earth fault,
unbalance, AND logical gates
2.9 Trip Output Relay
1 Trip Output Relay (RL1) Programmable
(Association of one or more information to the Trip Output Relay).
2.10 Latching of the Trip Order
Latching of the information(s) associated to the RL1.
P220/EN TD/B43 Technical Guide
Technical Data
Page 6/30 MiCOM P220

2.11 Control and monitoring of the breaker device


SW Operating time alarm 0.05 to 1 by steps of 0.05 s
Number of operations alarm 0 to 50 000 operations by steps of 1
Summated contact breaking duty 106 to 4000.106 by steps of 106
Adjustment of the exponent n 1 or 2
Close command hold 0.2 to 5 s by steps of 0.1 s
Open command hold 0.2 to 5 s by steps of 0.1 s
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 7/30

3. OPTIONAL FUNCTIONS
3.1 Optional analogue output
Rating 0-20 mA, 4-20 Ma
Insulation 2 kV
Maximum load with active source mode 500 for ratings 0-20 mA, 4-20 mA
Maximum voltage with passive source mode 24 Volt
Accuracy 1% full scale
3.2 Optional 6 RTD inputs
RTD type PT100, Ni120, Ni100, Cu10
Connection type 3 wires + 1 shielding
Insulation 2 kV, active supply
Setting of thresholds 0 to 200 C by steps of 1 C
Settings of timings 0 to 100 s by steps of 0.1 s
Influence of thermal image Yes/No
3.3 Optional 2 thermistors + 4 RTD inputs
Thermistor type PTC or NTC
Setting of thresholds 100 to 30000 by steps of 100
Time-delay Set to 2 seconds
P220/EN TD/B43 Technical Guide
Technical Data
Page 8/30 MiCOM P220

4. RECORDING FUNCTIONS
4.1 Event recorder
Capacity 75 events
Time-tag To 1 millisecond
Triggers Any protection alarm and threshold
Any logic input change of state
Self test events
Any setting changes
4.2 Fault recorder
Capacity 5 records
Time-tag To 1 millisecond
Triggers Any trip order (relay RL1 operation)
Data Fault date
Active setting group
Faulty phase(s)
Fault type, protection threshold
Magnitude of the fault current
Phases and earth currents
magnitudes
4.3 Oscillography
Capacity 5 records of 3 s each
Sampling rate 32 samples per frequency cycle
Pre-time setting 0.1 to 3 s by steps of 0.1 s
Post-time setting 0.1 to 3 s by steps of 0.1 s
Triggers Any protection threshold overreach
or any trip order
(relay RL1 operation)
Logic input
Remote command
Data 4 analogue channels (3 phase
currents + earth current)
Logic input and output states
Frequency value
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 9/30

5. COMMUNICATION
5.1 MODBUSTM communication
Mode RTU (standard)
Transmission mode Synchronous
Interface RS 485, 2 wires and 1 Earth
Data rate 300 to 38400 baud (programmable)
Relay address 1 to 255
Connection Multi-point (32 connections)
Cable type Half duplex (screened twisted wire pair)
Maximum cable lengt 1000 meters
Connector Connector screws or snap-on
Insulation 2 kV RMS
5.2 Front communication
Interface RS232
Protocol MODBUSTM RTU
Connectors Sub-D 9 pin female connector
Cable type Screened twisted wire cable, no-crossed
P220/EN TD/B43 Technical Guide
Technical Data
Page 10/30 MiCOM P220

6. INPUTS AND OUTPUTS


6.1 Inputs
Phase current In 1 and 5 Ampere
Earth current Ion 1 and 5 Ampere
Frequency Range 45 to 65 Hz
Nominal 50/60 Hz
Burdens Phase current inputs < 0.3 VA (5A)
< 0.025 VA (1A)
Earth current input < 0.01 VA at 0.1 Ion (5A)
<0.004 VA at 0.1 Ion (1A)
Thermal withstand of the phase 100 In - 1 s
and earth current inputs 40 In - 2 s
4 In continuous
6.2 Logic inputs
Type Independent optical isolated
Number 5 (3 programmable, 2 fixe)
Burden < 10 mA for each input
Recognition time = 2.5 ms
The logic inputs shall be powered with a dc voltage.

Logic input operation


Cortec Relay auxiliary Minimum voltage Minimum current
Code voltage range* level (Volt) level (milli-Amp)
A 24 60 Vdc 15 V 3,35 mA
F 48 150 Vdc 25 V 3,35 mA
M 130 250 Vdc 38 V 2,20 mA
110 250 Vac

* The tolerance on the auxiliary voltage variations for the logic inputs is 20%
6.3 Output relays
Type Dry contact AgCdO
Number 6 (5 programmable + 1 watchdog)
Commutation capacity Make 30 Amps for 3 s
Carry continuously 5 Amps
Break 135 Vdc, 0.3 Amps (L/R = 30 ms)
250 Vdc, 50 W resistive
250 Vdc, 25 W inductive (L/R = 40 ms)
220 Vac, 5 Amps (50/60Hz-cos =0.6)
Operation time < 7 ms
Durability > 100 000 operations
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 11/30

6.4 Auxiliary voltage


Auxiliary voltage 3 ranges 24-60 Vdc
48-150 Vdc
130-250 Vdc /110-250 Vac
Variations 20%
Residual peak to peak ripple 12 %
Power off withstand 50 ms
Burden <3 W standby + 0.25 for each output
relay energized in Vdc < 6 VA in Vac

7. ACCURACY
Protection thresholds 2%
Time delays 2 % with a minimum of 10 ms
NOTE: The user shall take into consiredation the Operating Time
(30ms) of the protection functions when setting the timers to low
values.
Measurements Typical 0.2 % at In for currents
2 C for temperatures
Pass band for measurements 500Hz
of true RMS values

8. CT DATA
Phases CT primary 1 to 3000 by steps of 1
Earth CT primary 1 to 3000 by steps of 1
Phases CT secondary 1 or 5
Earth CT secondary 1 or 5
Recommended phases CT 5P10 - 5VA (typical)
Recommended earth CT Residual connection or core balanced CT
(preferred in isolated neutral systems)

9. HIGH VOLTAGE WITHSTAND


Dielectric withstand (50/60Hz) IEC 60255-5 2 kV in common mode
BS 142 1 kV in differential mode
ANSI C37.90
Impulse voltage (1.2/50 s) IEC 60255-5 5 kV in common mode
BS 142 1 kV in differential
mode
Insulation resistance EC 60255-5 > 100 M
P220/EN TD/B43 Technical Guide
Technical Data
Page 12/30 MiCOM P220

10. ELECTRICAL ENVIRONMENT


High frequency disturbance IEC 61000-4-12 2.5 kV in common mode, class 3
1 kV in differential mode, class 3
Fast transient disturbance IEC 61000-4-4 4 kV auxiliary supply, class 4
ANSI C37.90.1 2 kV other, class 4
Electrostatic discharge IEC 61000-4-2 8 kV, class 4
Radio frequency impulse ANSI C37.90.2 35 V/m
IEC 61000-4-3 10 V/m

11. ENVIRONMENT
Temperature IEC 60255-6
Storing and transportation 40C to + 70C
Operation 25C to + 55C
Humidity IEC 60068-2-3 56 days at 93% RH and 40C
Enclosure protection IEC 60529 IP 52, IK 07
Vibration IEC 60255-21-1 Response and endurance, class 2
Shock and bump IEC 60255-21-2 Response and withstand, class 1
Seismic withstand IEC 60255-21-3 Class 2
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 13/30

12. THERMAL OVERLOAD CURVES

Thermal overload characteristic curves


Thermal constant times :
- overload condition : T e1 = 12 minutes
- start-up condition : T e2 = 6 minutes
10 000

1 000

Cold curve
Thermal status = 0 %
Operating time (seconds)

100

10

Hot curve
Thermal status = 90%

0
0.1 1 10
Thermal equivalent current I eq in terms of the current thermal threshold
I > P0159ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 14/30 MiCOM P220

Thermal overload characteristic curves


Cold curves
Initial thermal state of 0%
100 000

10 000

Te1 = Te2 = 60 mn

Te1 = Te2 = 54 mn

1 000 Te1 = Te2 = 48 mn

Te1 = Te2 = 42 mn
Operating time (seconds)

Te1 = Te2 = 36 mn

100

10
Te1 = Te2 = 30 mn

Te1 = Te2 =24 mn

Te1 = Te2 = 18 mn

1 Te1 = Te2 = 12 mn

Te1 = Te2 = 6 mn

Te1 = Te2 = 1 mn

0
1 10
Thermal equivalent current I eq in terms of the current
thermal threshold I > P0160ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 15/30

Thermal overload characteristic curve


Cold curves
Initial thermal state of 0%
100 000

10 000

Te1 = Te2 = 62 mn

Te1 = Te2 = 56 mn

Te1 = Te2 = 50 mn
1 000

Te1 = Te2 = 44 mn
Operating time (seconds)

Te1 = Te2 = 38 mn

100

Te1 = Te2 = 32 mn

10 Te1 = Te2 =26 mn

Te1 = Te2 = 20 mn

Te1 = Te2 = 14 mn

1 Te1 = Te2 = 8 mn

Te1 = Te2 = 2 mn

0
1 10

Thermal equivalent current Ieq in terms of the current


thermal threshold I q >
P0161ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 16/30 MiCOM P220

Thermal overload characteristic curves


Cold curves
Initial thermal state of 0%
100 000

10 000

Te1 = Te2 = 64 mn

Te1 = Te2 = 58 mn

1 000 Te1 = Te2 = 52 mn


Operating time (seconds)

Te1 = Te2 = 46 mn

Te1 = Te2 = 40 mn

100

Te1 = Te2 =34 mn

10 Te1 = Te2 =28 mn

Te1 = Te2 = 22 mn

Te1 = Te2 = 16 mn

1 Te1 = Te2 = 10 mn

Te1 = Te2 = 4 mn

0
1 10
Thermal equivalent current Ieq in terms of the current
thermal threshold I > P0162ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 17/30

Thermal overload characteristic curves


Hot curves
Initial thermal state of 90%
100 000

10 000

1 000

Te1 = Te2 = 60 mn
Operating time (seconds)

Te1 = Te2 = 54 mn

100 Te1 = Te2 = 48 mn

Te1 = Te2 = 42 mn

Te1 = Te2 = 36 mn

10

Te1 = Te2 = 30 mn

Te1 = Te2 =24 mn


1

Te1 = Te2 = 18 mn

Te1 = Te2 = 12 mn

Te1 = Te2 = 6 mn

Te1 = Te2 = 1 mn
0
1 Thermal equivalent current I eq in terms of the current 10

thermal threshold I > P0163ENa


P220/EN TD/B43 Technical Guide
Technical Data
Page 18/30 MiCOM P220

Thermal overload characteristic curves


Hot curves
Initial thermal state of 90%
100 000

10 000

1 000

Te1 = Te2 = 62 mn
Operating time (seconds)

Te1 = Te2 = 56 mn

100
Te1 = Te2 = 50 mn

Te1 = Te2 = 44 mn

Te1 = Te2 = 38 mn

10

Te1 = Te2 = 32 mn

Te1 = Te2 =26 mn

1
Te1 = Te2 = 20 mn

Te1 = Te2 = 14 mn

Te1 = Te2 = 8 mn

Te1 = Te2 = 2 mn
0
1 10

Thermal equivalent current I eq in terms of the current


thermal threshold > P0164ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 19/30

Thermal overload characteristic curves


Hot curves
Initial thermal state of 90%
100 000

10 000

1 000

Te1 = Te2 = 64 mn
Operating time (seconds)

Te1 = Te2 = 58 mn

Te1 = Te2 = 52 mn

100
Te1 = Te2 = 46 mn

Te1 = Te2 = 40 mn

10

Te1 = Te2 =34 mn

Te1 = Te2 =28 mn

Te1 = Te2 = 22 mn
1
Te1 = Te2 = 16 mn

Te1 = Te2 = 10 mn

Te1 = Te2 = 4 mn

0
1 10
Thermal equivalent current I eq in terms of the current
thermal threshold I > P0165ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 20/30 MiCOM P220

BLANK PAGE
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 21/30
Cooling down thermal curves
Initial thermal state of 90%

100

90

80
Tr = 96 mn

70 Tr = 84 mn
Thermal state (en %)

60 Tr = 72 mn

50
Tr = 60 mn

Tr = 48 mn
40
Tr = 36 mn

30

20

Tr = 24 mn
10
Tr = 12 mn
Tr = 5 mn
0
0 100
Operating time (minutes)
P0221ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 22/30 MiCOM P220
Cooling down thermal curves
Initial thermal state of 90%

100

90

80

Tr = 204 mn
70
Tr = 192 mn
Thermal state (en %)

60 Tr = 180 mn

50 Tr = 168 mn

40 Tr = 156 mn

30 Tr = 144 mn

Tr = 132 mn
20
Tr = 120 mn
10
Tr = 108 mn

0
0 100 200
Operating time (minutes)
P0222ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 23/30
Cooling down thermal curves
Initial thermal state of 90%
100

90

80

Tr = 450 mn
70 Tr = 425 mn

Tr = 400 mn
Thermal state (en %)

60

Tr = 375 mn
50
Tr = 350 mn
40 Tr = 325 mn

30
Tr = 300 mn

20 Tr = 275 mn

10 Tr = 250 mn

Tr = 225 mn
0
0 100 200 300 400 500 600
Operating time (minutes)
P0223ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 24/30 MiCOM P220
Cooling down thermal curves
Initial thermal state of 100%
100

90

80 Tr = 96 mn

70 Tr = 84 mn

60 Tr = 72 mn
Thermal state (%)

50 Tr = 60 mn

Tr = 48 mn
40
Tr = 36 mn

30

20

Tr = 24 mn
10
Tr = 12 mn
Tr = 5 mn
0
0 100
Operating time (minutes) P0224ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 25/30

Cooling down thermal curves


Initial thermal state of 100%
100

90

80 Tr = 204 mn

Tr = 192 mn
70
Tr = 180 mn
60
Thermal state (%)

Tr = 168 mn

50
Tr = 156 mn

40

Tr = 144 mn
30
Tr = 132 mn
20
Tr = 120 mn

10
Tr = 108 mn

0
0 100 200 300
Operating time (minutes)
P0225ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 26/30 MiCOM P220

Cooling down thermal curves


Initial thermal state of 100%
100

90

Tr = 450 mn
80

Tr = 425 mn
70
Tr = 400 mn

60
Thermal state (%)

Tr = 375 mn

50 Tr = 350 mn

Tr = 325 mn
40

30
Tr = 300 mn

20 Tr = 275 mn

10 Tr = 250 mn

Tr = 225 mn
0
0 100 200 300 400 500 600
Operating time (minutes)
P0226ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 27/30

Negative phase sequence protection


Inverse time characteristic curve
Ii>> element
10

Ii>> setting range


from 0,2 to 0,8 I2/In
Operating time (seconds)

0
0.1 1 10

Ratio "Negative phase sequence current/rated current" : I2 / In


P0227ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 28/30 MiCOM P220

13. EQUIVALENCE TABLE BETWEEN THE RTD IMPEDANCE MEASURED


VALUE AND TEMPERATURE

100 OHM 100 OHM 120 OHM 10 OHM


Temperature (C)
Platinum () Nickel () Nickel () Copper ()
-40 84.27 79.13 92.76 7.490
-30 88.22 84.15 99.41 7.876
-20 92.16 89.23 106.41 8.263
-10 96.09 94.58 113.0 8.649
0 100.0 100.0 120.0 9.035
10 103.9 105.6 127.2 9.421
20 107.8 111.2 134.5 9.807
30 111.7 117.1 142.1 10.19
40 115.5 123.0 149.8 10.58
50 119.4 129.1 157.7 10.97
60 123.2 135.3 165.9 11.35
70 127.1 141.7 174.3 11.74
80 130.9 148.3 182.8 12.12
90 134.7 154.9 191.6 12.51
100 138.5 161.8 200.6 12.90
110 142.3 168.8 209.9 13.28
120 146.1 176.0 219.3 13.67
130 149.8 183.3 228.9 14.06
140 153.6 190.9 238.8 14.44
150 157.3 198.7 249.0 14.83
160 161.0 206.6 259.3 15.22
170 164.8 214.8 269.9 15.61
180 168.5 223.2 280.8 16.00
190 172.2 231.6 291.9 16.38
200 175.8 240.0 303.5 16.78
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 29/30

14. EQUIVALENCE TABLE BETWEEN ANALOGUE OUTPUT SIGNAL VALUE


AND REMOTE MEASUREMENT
The hereafter table provides equivalence data between the current signal issued from
the analogue output of the MiCOM P220 and the measurement value.
Rating 0 - 20 mA :

Rating
Measurement type HMI sign Unit Variation range
0 - 20 mA
Phase A current IA RMS Ampre 0 to 2 In Ias * 2 In / 20 mA
(True RMS value)
Phase A current IB RMS Ampre 0 to 2 In Is s* 2 In / 20 mA
(True RMS value)
Phase A current IC RMS Ampre 0 to 2 In Ias * 2 In / 20 mA
(True RMS value)
Earth current IE RMS Ampre 0 to 2 In Ias * 2 In / 20 mA
(True RMS value)
Motor thermal state TH STATE % 0 to 150 % Ias * 150 / 20 mA
Load in % of the full % I LOAD % 0 to 150 % Ias * 150 / 20 mA
load current
Time before a Tbef Start Minutes 0 to 120 Minutes Ias * 120 / 20 mA
permitted start
Time before a thermal Tbef Trip Minutes 0 to 120 Minutes Ias * 120 / 20 mA
trip
RTDs temperature TC RTD C - 40 to 215 C Ias * 255 / 20 mA 40C
P220/EN TD/B43 Technical Guide
Technical Data
Page 30/30 MiCOM P220

Rating 4 - 20 mA :

Rating
Measurement type HMI sign Unit Variation range
4 - 20 mA
Phase A current IA RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Phase A current IB RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Phase A current IC RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Earth current IE RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Motor thermal state TH STATE % 0 to 150 % (Ias 4 mA) * 150 / 16 mA
Load in % of the full % I LOAD % 0 to 150 % (Ias 4 mA) * 150 / 16 mA
load current
Time before a Tbef Start Minutes 0 to 120 Minutes (Ias 4 mA) * 120 / 16 mA
permitted start
Time before a thermal Tbef Trip Minutes 0 to 120 Minutes (Ias 4 mA) * 120 / 16 mA
trip
RTDs temperature TC RTD C - 40 to 215 C (Ias 4 mA) * 255 / 16 mA
40C

NOTE : Ias is the value of the current signal generated by the


analogue output.
In the case where the measurement value to remote through
the analogue output is outside the permissible variation
range, the current signal is restricted to the limit value of the
variation range.
In the case where the thermal alarm ALARM is not
energised, the current signal value meaning the time before a
thermal trip Tbef Trip is equal to 20 mA.