MiCOM P220
Technical Data
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 1/30
CONTENTS
1. PROTECTION FUNCTIONS 3
2. AUTOMATION FUNCTIONS 5
3. OPTIONAL FUNCTIONS 7
4. RECORDING FUNCTIONS 8
5. COMMUNICATION 9
6.1 Inputs 10
6.2 Logic inputs 10
6.3 Output relays 10
6.4 Auxiliary voltage 11
7. ACCURACY 11
8. CT DATA 11
11. ENVIRONMENT 12
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 3/30
1. PROTECTION FUNCTIONS
1.1 Thermal replica
Thermal current threshold 1> 0.2 to 1.5 In by steps of 0.01 In
Overload time-constant Te1 1 to 180 min by steps of 1 min
Start-up time-constant Te2 1 to 360 min by steps of 1 min
Cooling time-constant Tr 1 to 999 min by steps of 1 min
Negative sequence current recognition factor Ke 0 to 10 by steps of 1
Trip thermal threshold Set to 100%
Trip thermal threshold hysteresis 97%
Thermal alarm threshold 20 to 100% by steps of 1%
Thermal alarm threshold hysteresis 97%
Start-up inhibition 20 to 100% by steps of 1%
1.2 Short-circuit protection
Current threshold I>> 1 to 12 In by steps of 0.1 In
Time-delays tl >> 0 to 100 s by steps of 0.01 s
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 95%
1.3 Earth fault protection
Current thresholds lo>, lo>> 0.002 to 1 Ion by steps of 0.001
Ion
Time-delays tlo>, tlo>> 0 to 100 s by steps of 0.01 s
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 95%
1.4 Unbalance protection
Negative sequence current threshold li> 0.05 to 0.8 In by steps of 0.025 In
Time-delays tli> 0.04 to 200 s by steps of 0.01 s
Negative sequence current threshold Ii >> 0.2 to 0.8 In by steps of 0.05 In
IDMT time-delay operating time t = 1.2 / (I2/In)
Operating time < 30 ms
Drop-off time < 30 ms
Hysteresis 95%
P220/EN TD/B43 Technical Guide
Technical Data
Page 4/30 MiCOM P220
2. AUTOMATION FUNCTIONS
2.1 Limitation of the number of start-ups
Reference period Treference 10 to 120 min by steps of 5 min
Number of cold starts 0 to 5 by steps of 1
Number of hot starts 0 to 5 by steps of I
Restart inhibition time Tinterdiction 1 to 120 min by steps of 5 min
2.2 Time between 2 start-ups
Inhibition time Tbetw 2 start 1 to 120 min by steps of 5 min
2.3 Re-acceleration authorization
Voltage collapse duration Treacc 0.2 to 10 s by steps of 0.05 s
2.4 Logic Inputs / Auxiliary timers
1Logic input CB position
1Logic input Speed Switch
3 Programmable Logic inputs
Logic inputs with alarm message on occurence 2 external signals, EXT1 and EXT2
Logic inputs without alarm message on occurence 2 external signals, EXT3 and EXT4
(from V3.A software version)
Timers tEXT1, tEXT2, tEXT3 and tEXT4 0 to 200 s by step of 0.01s
2.5 Logic Equations
4 AND logic equations
2.6 Logic equation time delay
Pick-up time delay 0 to 60 min by steps of 0.1 s
Reset time 0 to 60 min by steps of 0.1 s
2.7 Auxiliary Output Relays
1 Trip Output Relay (RL1) Programmable
4 Auxiliary Output relays (RL2,RL3,RL4,RL5) Programmable
1 watchdog relay.( for equipment default)
2.8 Latching of the output relays
Latching of the output relays (RL2,RL3,RL4,RL5)on Short-circuit, earth fault,
unbalance, AND logical gates
2.9 Trip Output Relay
1 Trip Output Relay (RL1) Programmable
(Association of one or more information to the Trip Output Relay).
2.10 Latching of the Trip Order
Latching of the information(s) associated to the RL1.
P220/EN TD/B43 Technical Guide
Technical Data
Page 6/30 MiCOM P220
3. OPTIONAL FUNCTIONS
3.1 Optional analogue output
Rating 0-20 mA, 4-20 Ma
Insulation 2 kV
Maximum load with active source mode 500 for ratings 0-20 mA, 4-20 mA
Maximum voltage with passive source mode 24 Volt
Accuracy 1% full scale
3.2 Optional 6 RTD inputs
RTD type PT100, Ni120, Ni100, Cu10
Connection type 3 wires + 1 shielding
Insulation 2 kV, active supply
Setting of thresholds 0 to 200 C by steps of 1 C
Settings of timings 0 to 100 s by steps of 0.1 s
Influence of thermal image Yes/No
3.3 Optional 2 thermistors + 4 RTD inputs
Thermistor type PTC or NTC
Setting of thresholds 100 to 30000 by steps of 100
Time-delay Set to 2 seconds
P220/EN TD/B43 Technical Guide
Technical Data
Page 8/30 MiCOM P220
4. RECORDING FUNCTIONS
4.1 Event recorder
Capacity 75 events
Time-tag To 1 millisecond
Triggers Any protection alarm and threshold
Any logic input change of state
Self test events
Any setting changes
4.2 Fault recorder
Capacity 5 records
Time-tag To 1 millisecond
Triggers Any trip order (relay RL1 operation)
Data Fault date
Active setting group
Faulty phase(s)
Fault type, protection threshold
Magnitude of the fault current
Phases and earth currents
magnitudes
4.3 Oscillography
Capacity 5 records of 3 s each
Sampling rate 32 samples per frequency cycle
Pre-time setting 0.1 to 3 s by steps of 0.1 s
Post-time setting 0.1 to 3 s by steps of 0.1 s
Triggers Any protection threshold overreach
or any trip order
(relay RL1 operation)
Logic input
Remote command
Data 4 analogue channels (3 phase
currents + earth current)
Logic input and output states
Frequency value
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 9/30
5. COMMUNICATION
5.1 MODBUSTM communication
Mode RTU (standard)
Transmission mode Synchronous
Interface RS 485, 2 wires and 1 Earth
Data rate 300 to 38400 baud (programmable)
Relay address 1 to 255
Connection Multi-point (32 connections)
Cable type Half duplex (screened twisted wire pair)
Maximum cable lengt 1000 meters
Connector Connector screws or snap-on
Insulation 2 kV RMS
5.2 Front communication
Interface RS232
Protocol MODBUSTM RTU
Connectors Sub-D 9 pin female connector
Cable type Screened twisted wire cable, no-crossed
P220/EN TD/B43 Technical Guide
Technical Data
Page 10/30 MiCOM P220
* The tolerance on the auxiliary voltage variations for the logic inputs is 20%
6.3 Output relays
Type Dry contact AgCdO
Number 6 (5 programmable + 1 watchdog)
Commutation capacity Make 30 Amps for 3 s
Carry continuously 5 Amps
Break 135 Vdc, 0.3 Amps (L/R = 30 ms)
250 Vdc, 50 W resistive
250 Vdc, 25 W inductive (L/R = 40 ms)
220 Vac, 5 Amps (50/60Hz-cos =0.6)
Operation time < 7 ms
Durability > 100 000 operations
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 11/30
7. ACCURACY
Protection thresholds 2%
Time delays 2 % with a minimum of 10 ms
NOTE: The user shall take into consiredation the Operating Time
(30ms) of the protection functions when setting the timers to low
values.
Measurements Typical 0.2 % at In for currents
2 C for temperatures
Pass band for measurements 500Hz
of true RMS values
8. CT DATA
Phases CT primary 1 to 3000 by steps of 1
Earth CT primary 1 to 3000 by steps of 1
Phases CT secondary 1 or 5
Earth CT secondary 1 or 5
Recommended phases CT 5P10 - 5VA (typical)
Recommended earth CT Residual connection or core balanced CT
(preferred in isolated neutral systems)
11. ENVIRONMENT
Temperature IEC 60255-6
Storing and transportation 40C to + 70C
Operation 25C to + 55C
Humidity IEC 60068-2-3 56 days at 93% RH and 40C
Enclosure protection IEC 60529 IP 52, IK 07
Vibration IEC 60255-21-1 Response and endurance, class 2
Shock and bump IEC 60255-21-2 Response and withstand, class 1
Seismic withstand IEC 60255-21-3 Class 2
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 13/30
1 000
Cold curve
Thermal status = 0 %
Operating time (seconds)
100
10
Hot curve
Thermal status = 90%
0
0.1 1 10
Thermal equivalent current I eq in terms of the current thermal threshold
I > P0159ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 14/30 MiCOM P220
10 000
Te1 = Te2 = 60 mn
Te1 = Te2 = 54 mn
Te1 = Te2 = 42 mn
Operating time (seconds)
Te1 = Te2 = 36 mn
100
10
Te1 = Te2 = 30 mn
Te1 = Te2 = 18 mn
1 Te1 = Te2 = 12 mn
Te1 = Te2 = 6 mn
Te1 = Te2 = 1 mn
0
1 10
Thermal equivalent current I eq in terms of the current
thermal threshold I > P0160ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 15/30
10 000
Te1 = Te2 = 62 mn
Te1 = Te2 = 56 mn
Te1 = Te2 = 50 mn
1 000
Te1 = Te2 = 44 mn
Operating time (seconds)
Te1 = Te2 = 38 mn
100
Te1 = Te2 = 32 mn
Te1 = Te2 = 20 mn
Te1 = Te2 = 14 mn
1 Te1 = Te2 = 8 mn
Te1 = Te2 = 2 mn
0
1 10
10 000
Te1 = Te2 = 64 mn
Te1 = Te2 = 58 mn
Te1 = Te2 = 46 mn
Te1 = Te2 = 40 mn
100
Te1 = Te2 = 22 mn
Te1 = Te2 = 16 mn
1 Te1 = Te2 = 10 mn
Te1 = Te2 = 4 mn
0
1 10
Thermal equivalent current Ieq in terms of the current
thermal threshold I > P0162ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 17/30
10 000
1 000
Te1 = Te2 = 60 mn
Operating time (seconds)
Te1 = Te2 = 54 mn
Te1 = Te2 = 42 mn
Te1 = Te2 = 36 mn
10
Te1 = Te2 = 30 mn
Te1 = Te2 = 18 mn
Te1 = Te2 = 12 mn
Te1 = Te2 = 6 mn
Te1 = Te2 = 1 mn
0
1 Thermal equivalent current I eq in terms of the current 10
10 000
1 000
Te1 = Te2 = 62 mn
Operating time (seconds)
Te1 = Te2 = 56 mn
100
Te1 = Te2 = 50 mn
Te1 = Te2 = 44 mn
Te1 = Te2 = 38 mn
10
Te1 = Te2 = 32 mn
1
Te1 = Te2 = 20 mn
Te1 = Te2 = 14 mn
Te1 = Te2 = 8 mn
Te1 = Te2 = 2 mn
0
1 10
10 000
1 000
Te1 = Te2 = 64 mn
Operating time (seconds)
Te1 = Te2 = 58 mn
Te1 = Te2 = 52 mn
100
Te1 = Te2 = 46 mn
Te1 = Te2 = 40 mn
10
Te1 = Te2 = 22 mn
1
Te1 = Te2 = 16 mn
Te1 = Te2 = 10 mn
Te1 = Te2 = 4 mn
0
1 10
Thermal equivalent current I eq in terms of the current
thermal threshold I > P0165ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 20/30 MiCOM P220
BLANK PAGE
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 21/30
Cooling down thermal curves
Initial thermal state of 90%
100
90
80
Tr = 96 mn
70 Tr = 84 mn
Thermal state (en %)
60 Tr = 72 mn
50
Tr = 60 mn
Tr = 48 mn
40
Tr = 36 mn
30
20
Tr = 24 mn
10
Tr = 12 mn
Tr = 5 mn
0
0 100
Operating time (minutes)
P0221ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 22/30 MiCOM P220
Cooling down thermal curves
Initial thermal state of 90%
100
90
80
Tr = 204 mn
70
Tr = 192 mn
Thermal state (en %)
60 Tr = 180 mn
50 Tr = 168 mn
40 Tr = 156 mn
30 Tr = 144 mn
Tr = 132 mn
20
Tr = 120 mn
10
Tr = 108 mn
0
0 100 200
Operating time (minutes)
P0222ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 23/30
Cooling down thermal curves
Initial thermal state of 90%
100
90
80
Tr = 450 mn
70 Tr = 425 mn
Tr = 400 mn
Thermal state (en %)
60
Tr = 375 mn
50
Tr = 350 mn
40 Tr = 325 mn
30
Tr = 300 mn
20 Tr = 275 mn
10 Tr = 250 mn
Tr = 225 mn
0
0 100 200 300 400 500 600
Operating time (minutes)
P0223ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 24/30 MiCOM P220
Cooling down thermal curves
Initial thermal state of 100%
100
90
80 Tr = 96 mn
70 Tr = 84 mn
60 Tr = 72 mn
Thermal state (%)
50 Tr = 60 mn
Tr = 48 mn
40
Tr = 36 mn
30
20
Tr = 24 mn
10
Tr = 12 mn
Tr = 5 mn
0
0 100
Operating time (minutes) P0224ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 25/30
90
80 Tr = 204 mn
Tr = 192 mn
70
Tr = 180 mn
60
Thermal state (%)
Tr = 168 mn
50
Tr = 156 mn
40
Tr = 144 mn
30
Tr = 132 mn
20
Tr = 120 mn
10
Tr = 108 mn
0
0 100 200 300
Operating time (minutes)
P0225ENa
P220/EN TD/B43 Technical Guide
Technical Data
Page 26/30 MiCOM P220
90
Tr = 450 mn
80
Tr = 425 mn
70
Tr = 400 mn
60
Thermal state (%)
Tr = 375 mn
50 Tr = 350 mn
Tr = 325 mn
40
30
Tr = 300 mn
20 Tr = 275 mn
10 Tr = 250 mn
Tr = 225 mn
0
0 100 200 300 400 500 600
Operating time (minutes)
P0226ENa
Technical Guide P220/EN TD/B43
Technical Data
MiCOM P220 Page 27/30
0
0.1 1 10
Rating
Measurement type HMI sign Unit Variation range
0 - 20 mA
Phase A current IA RMS Ampre 0 to 2 In Ias * 2 In / 20 mA
(True RMS value)
Phase A current IB RMS Ampre 0 to 2 In Is s* 2 In / 20 mA
(True RMS value)
Phase A current IC RMS Ampre 0 to 2 In Ias * 2 In / 20 mA
(True RMS value)
Earth current IE RMS Ampre 0 to 2 In Ias * 2 In / 20 mA
(True RMS value)
Motor thermal state TH STATE % 0 to 150 % Ias * 150 / 20 mA
Load in % of the full % I LOAD % 0 to 150 % Ias * 150 / 20 mA
load current
Time before a Tbef Start Minutes 0 to 120 Minutes Ias * 120 / 20 mA
permitted start
Time before a thermal Tbef Trip Minutes 0 to 120 Minutes Ias * 120 / 20 mA
trip
RTDs temperature TC RTD C - 40 to 215 C Ias * 255 / 20 mA 40C
P220/EN TD/B43 Technical Guide
Technical Data
Page 30/30 MiCOM P220
Rating 4 - 20 mA :
Rating
Measurement type HMI sign Unit Variation range
4 - 20 mA
Phase A current IA RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Phase A current IB RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Phase A current IC RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Earth current IE RMS Ampre 0 to 2 In (Ias 4 mA) * 2 In / 16 mA
(True RMS value)
Motor thermal state TH STATE % 0 to 150 % (Ias 4 mA) * 150 / 16 mA
Load in % of the full % I LOAD % 0 to 150 % (Ias 4 mA) * 150 / 16 mA
load current
Time before a Tbef Start Minutes 0 to 120 Minutes (Ias 4 mA) * 120 / 16 mA
permitted start
Time before a thermal Tbef Trip Minutes 0 to 120 Minutes (Ias 4 mA) * 120 / 16 mA
trip
RTDs temperature TC RTD C - 40 to 215 C (Ias 4 mA) * 255 / 16 mA
40C