Вы находитесь на странице: 1из 9

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO.

2, APRIL 2013 779

Fault Detection and Isolation in Low-Voltage


DC-Bus Microgrid System
Jae-Do Park, Member, IEEE, and Jared Candelaria, Student Member, IEEE

AbstractA fault detection and isolation scheme for low-voltage


dc-bus microgrid systems is presented in this paper. Unlike tradi-
tional ac distribution systems, protection has been challenging for
dc systems. The goals of the proposed scheme are to detect the fault
in the bus between devices and to isolate the faulted section so that
the system keeps operating without disabling the entire system. To
achieve these goals, a loop-type dc-bus-based microgrid system,
which has a segment controller between connected components, is
proposed. The segment controller consists of master and slave con-
trollers that monitor currents and control the segment separation,
which include solid-state bidirectional switches and snubber cir-
cuits. The proposed system can detect faults on the bus regardless
of fault current amplitude or the power supplys feeding capacity.
The proposed concepts have been verified by OrCAD/PSpice sim-
ulations and experiments on hardware test bed.
Index TermsDC distribution, fault protection, microgrids,
solid-state switch.
Fig. 1. Conceptual diagram of a dc-bus microgrid system.

I. INTRODUCTION
Microgrid systems can be divided into ac-bus and dc-bus sys-
tems, based on the bus to which the component systems are con-

R ECENTLY, many distributed power systems have been


researched and developed, especially to meet the demand
for high penetration of renewable energy resources, such as
nected. The advantage of the ac-bus-based microgrids is that
the existing ac power grid technologies are readily applicable.
However, problems with the ac grid issues, including synchro-
wind turbines and photovoltaic systems. The distributed power nization, reactive power control, and bus stability, still persist.
systems have advantages, such as the capacity relief of trans- DC-bus-based systems can become a feasible solution because
mission and distribution, better operational and economical microgrids are small, localized systems where the transmission
generation efficiency, improved reliability, eco-friendliness, loss is negligible. Moreover, they do not have the problems that
and higher power quality [1], [2]. The energy policy of many ac systems do, and system cost and size can be reduced com-
governments in the world competitively increases the require- pared to the typical ac-dc-ac conversion configuration because
ment of the penetration of renewable energy resources and dc power is generally used in the power-electronics devices as
distributed generation (DG). For instance, in the U.S., Cali- a medium. A conceptual diagram of the dc-bus microgrid is
fornia is trying to increase the usage of renewable generation up shown in Fig. 1.
to 33% by 2020 [3] and Colorado has set specific requirements While the advantages of dc microgrids are considerable,
for DG from eligible renewable energy resources [4]. the protection of dc distribution systems has posed many
The microgrid system is a small-scale distributed power challenges, such as autonomously locating a fault within a
system consisting of distributed energy sources and loads, microgrid, breaking a dc arc, dc protective equipment, and
and it can be readily integrated with the renewable energy certainly the lack of standards, guidelines, and experience [8].
sources [5][7]. Due to the distributed nature of the micro- This paper presents a fault detection and isolation scheme
grid approach, the connection to the central dispatch can be for a low-voltage dc-bus microgrid system. The goals of the
removed or minimized so that the power quality to sensitive proposed scheme are to detect the fault in a bus segment be-
loads can be enhanced. Generally, they have two operation tween devices and then to isolate the faulted section so that the
modes: stand-alone (islanded) mode and grid-connected mode. system continues to operate without disabling the entire system.
To accomplish these goals, this paper proposes a loop-type
Manuscript received March 06, 2012; revised October 26, 2012 and De- dc-bus-based microgrid system which has a segment controller
cember 22, 2012; accepted January 22, 2013. Date of publication February 12, between connected components.
2013; date of current version March 21, 2013. Paper no. TPWRD-00238-2012.
The authors are with the Department of Electrical Engineering, University of
Colorado Denver, Denver, CO 80204 USA. II. LOW-VOLTAGE DC-BUS MICROGRID
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. Compared to high-voltage dc (HVDC) systems, the
Digital Object Identifier 10.1109/TPWRD.2013.2243478 low-voltage dc (LVDC) system is a relatively new concept in

0885-8977/$31.00 2013 IEEE


780 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

to ground. The line-to-ground faults are the most common types


of faults in industrial distribution systems [13].
VSCs may experience internal switch faults that can cause
a line-to-line short-circuit fault. This is a terminal fault for the
device that cannot be cleared; in most cases, the device needs
to be replaced. Hence, dc fuses would be a proper protection
measure for this kind of fault. In ac systems, the ac-side CB
will trip.
Fig. 2. Fault types in dc systems: (a) line-to-ground fault and (b) line-to-line B. DC Fault Currents
fault.
When a fault occurs in a segment, the line current will split
between load current and fault current
electric power distribution. For small-scale systems, LVDC (1)
microgrids have many advantages over traditional ac distribu-
tion systems. For both ac and dc microgrids, power-electronic The magnitude of the fault current depends on the fault loca-
converters are required to connect a variety of sources and tion and resistance of the fault current path. If the impedance of
loads to a common bus. Using a dc bus requires fewer stages fault path is low (e.g., a line-to-ground fault with solid ground),
of conversion [8][10]. Furthermore, the cables for the ac and the current polarity at the receiving end could be reversed, pre-
dc power systems are chosen based upon the peak voltage of venting the load from being supported at all. The fault current
the system, and the power delivered by an ac system is based from the power source and bus capacitors can be given as fol-
on the rms values, while the dc power is based on the constant lows:
peak voltage. Hence, the dc system can deliver times that
of an ac system with the same cable. And dc systems do not (2)
suffer from the skin effect. Therefore, the dc system can utilize
the entire cable, thus decreasing losses [9], [11]. where is the line voltage, and are the equivalent re-
Problems arise with dc microgrids when a system needs re- sistance and inductance including source, line and ground com-
liable and versatile protection. AC systems have plenty of ex- ponent, and and are the equivalent series resistance
perience and standards when it comes to system protection. DC (ESR) and capacitance of bus capacitors, respectively. The time
systems do not have either of these advantages. The switchgear constant of the dc fault current is quite small because the line
in dc systems must be very robust in order to handle the dc arc resistance of the dc system is negligible compared to ac power
that is created during the interruption of fault currents. The pro- systems that have high reactance in the line. The bus voltage will
tection devices commercially available for low-voltage dc-bus drop or even collapse, depending on the capacity of the power
systems are fuses and circuit breakers (CBs) [8]. Traditional ac supply and energy-storage device in the bus, and the grounding
CB mechanisms, which rely on the natural zero crossing of the impedance.
ac current to open the circuit, are inadequate to interrupt dc cur-
C. Current Techniques
rents. More important, the fault persists because the operating
time of the CB increases. Allowing a fault current to persist on The common practice in dc power systems is not to install
a microgrid bus could be catastrophic. any protection on the dc side, and upon fault detection the ac
Because the microgrid systems need to be multiterminal, CBs that link the ac and dc systems are opened [14], [15]. A
voltage-source converters (VSCs) must be used to interface handshake method was suggested in [15] to isolate and locate
different subsystems to bus. When a fault occurs on the dc side the faulted segment: however, this method completely de-ener-
of a VSC system interfacing the ac source, the insulated-gate gizes the dc system until the fault is removed and the systems
bipolar transistors (IGBTs) lose control and the freewheeling can be re-energized. It works for HVDC and medium-voltage
diodes become a bridge rectifier feeding the fault. The chal- dc (MVDC) transmission systems where the dc system is a con-
lenge of protecting VSC systems is that the fault current must duit between the ac systems and loads. However, this method
be detected and extinguished very quickly as the converters can create unnecessary outages in LVDC microgrids where mul-
fault withstand rating is generally only twice the full-load rating tiple sources and loads are connected to a common bus. Protec-
[12]. tion techniques such as overcurrent [8], [9], [11], current time
derivatives [8], undervoltage and directional protection [9] have
been reported for LVDC distribution systems and dc shipboard
III. FAULTS IN DC DISTRIBUTION SYSTEMS power systems, but the dynamics of voltage and current on a
faulted segment, especially when it is separated has not been
A. Possible Faults
extensively investigated.
Two types of faults exist in dc systems: 1) line to line and 2) Due to the limitations of fuses and traditional ac CBs in
line to ground, which can be seen in Fig. 2. A line-to-line fault dc systems, a solid-state CB has become a valid option for
occurs when a path between the positive and negative line is cre- dc power system protection. There are several alternatives for
ated, short-circuiting them together. A line-to-ground fault oc- solid-state devices for the CBs, such as gate turn-off thyristors
curs when either the positive or negative pole is short-circuited (GTOs), IGBTs, and insulated-gate commutated thyristors
PARK AND CANDELARIA: FAULT DETECTION AND ISOLATION IN LV DC-BUS MICROGRID SYSTEM 781

(IGCTs). GTOs offer a high-voltage blocking capability and


a low on-state voltage, but suffer from slow switching speeds
[16]. IGBTs are widely used in the low-voltage ( 1200 V)
systems and their advantages include fast interruption time
and high short-circuit current withstanding capability [17].
However, high conduction loss is their disadvantage [18].
IGCTs have the lower conduction losses of a thyristor with the
turnoff capability of a transistor. The IGCT has high voltage
and current ratings as much as IGBTs, and the conduction loss
is relatively low [19]. In order for the microgrid bus to allow
power flow in either direction, the solid-state CB needs to be
bidirectional.
Fuses or molded case CBs (MCCBs) can be utilized on dc
systems [8]. Fuses can be problematic as they will only trip the
faulted line, leaving the unfaulted pole energized. Although this
problem can be solved with MCCBs, the drawback of fuses and
MCCBs is that neither can be controlled autonomously. In the
event of a fault, human intervention is required to re-energize Fig. 3. Conceptual diagram of the proposed protection scheme. Protection con-
trollers in segment B and C are omitted.
the system once the fault has been removed from the system.
Another way to protect the system from excessive fault cur-
rent is to limit the bus current under fault conditions. The fault
current limiters can be used in conjunction with CBs. The ad-
vantages of fault current limiting include ridethrough for tempo-
rary faults, safe operation of switchgear, and system cost down
by switchgear capacity reduction. Several devices have been uti-
lized to limit the fault current, such as superconductors [20], sat-
urated inductors [21], and power-electronics devices [22].

IV. PROPOSED PROTECTION SCHEME

A. Proposed Controller
This paper proposes a novel protection scheme for the dc-bus
microgrid system. Instead of shutting down the whole system or Fig. 4. Implementation of the proposed protection scheme. Arrows denote the
limiting the bus current, the proposed scheme detects the fault switching action when a fault is detected.
and separates the faulted section so that the rest of the system
keeps operating. The loop-type dc bus is suggested for the pro-
posed scheme to make the system robust under faulted con- B. Fault Detection and Isolation
ditions. It has also been reported that the loop-type bus has a The master controller monitors the difference of two current
good system efficiency especially when the distribution line is readings of slave controllers in a segment
not long [23]. The entire loop will be divided into a series of
segments between subsystems. Each segment will consist of a (3)
section of bus (positive and negative lines or positive line and
ground) and a segment controller. The conceptual diagram of where and is the line current at each end of the bus
the proposed protection scheme is shown in Fig. 3. The protec- segment. When the difference exceeds the threshold, the con-
tion system is shown only in segment A, and controllers on other troller sends the appropriate commands to slave controllers so
segments are omitted. that the faulted segment can be separated from the system. Be-
The proposed protection system consists of one master con- cause the proposed system uses the differential relaying prin-
troller, two slave controllers, and freewheeling branches be- ciple monitoring only the relative difference of input and output
tween each line and ground. The slave controllers read the cur- current of a segment, it can detect the fault on the bus regardless
rent at each end of the bus segment connecting two components of fault current amplitude or power supplys feeding capacity.
and send it to the master controller. They also operate the bidi- Once the faulted segment has been isolated, the bus voltage will
rectional solid-state switches on the bus segment and the free- be restored and remainder of the system can continue to operate
wheeling branch according to the commands from the master on the loop-type bus. Even with multiple faulted segments, the
controller. In the course of normal operations, the currents mea- system can operate partially if the segments from some power
sured at each end of the bus segment should be nearly iden- sources to loads are intact. The possibility of the fault around the
tical and the master controller sends commands to put the bus device connection point can be minimized if the segment con-
switches on normal positions. trollers are installed as close to the connection point as possible.
782 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

Fig. 5. Fault current and operation of the proposed protection scheme. (a) Line-to-ground fault between point A to G. (b) Isolated line-to-ground fault. (c) Line-to-
line fault between point A and B. (d) Isolated line-to-line fault.

The implementation of the proposed protection scheme is of insufficient capacity. This is especially true for the VSC-in-
shown in Fig. 4, which shows the configuration of segment A terfaced microgrid systems. Furthermore, the fault current needs
in Fig. 3. Semiconductor-based bidirectional switches and to be extinguished as quickly as possible even if the system has
diodes are used for segment separation and fault current sufficient current feeding capacity. Therefore, one of the best
freewheeling, respectively. In normal operations, switches solutions would be to isolate the faulted line as soon as possible
are closed and diodes are open. When a fault occurs, the and continue operation with intact bus segments and subsys-
master controller detects it using the current information from tems. To achieve this, the segment controller needs to be capable
the slave controllers and opens switches. Diodes are of fast differential current detection and bus switch control. An
conducting at the same time to form a freewheeling path for automatic reclosing algorithm would be necessary for fault re-
fault currents so that the switches can open and the fault covery and more robust operation [24].
current can be extinguished through resistors. The segment con-
trollers can detect the fault current of the line-to-ground fault C. Snubber Circuit
(from point A or B to G) and line-to-line fault (from point A
to B). A turnoff snubber circuit is included for switches to Snubber circuits are indispensable to protect the solid-state
limit the voltage overshoot due to the line inductance. CBs from the voltage transient due to the inductance of the
The line-to-ground fault and the line-to-line fault are shown bus cable. It is more so especially in a loop-type bus where
in Fig. 5. It can be seen that the fault current is isolated and the line inductance exists on both sides of the CB unlike
extinguished in the freewheeling loop. The freewheeling path the point-to-point-type system. Although the fault current
impedance determines the extinction rate of the fault current, needs to be interrupted as quickly as possible, the high
which can be given as follows: could make the transient voltage catastrophically high for the
solid-state switches. There are a couple of snubber circuit
topologies to suppress the overvoltage at turn-off due to line
(4) inductance, such as decoupling capacitor, discharge restricted
decoupling capacitor, discharge-charge-type RCD snubber,
where and represent the resistance and inductance in and discharge-suppressing-type RCD snubber [25]. It has
the freewheeling path, respectively. been reported that the decoupling capacitor has low losses
When a line-to-ground or a line-to-line fault occurs in the dis- but also oscillation issues, and RCD snubbers have higher
tribution line, the bus voltage collapse would not allow the load losses but no oscillation problem and good for higher current
to ride through if the current is limited from the source because applications [26]. Since the solid-state CBs do not switch in
PARK AND CANDELARIA: FAULT DETECTION AND ISOLATION IN LV DC-BUS MICROGRID SYSTEM 783

the fault current to an appropriate level for detection and ex-


tinction. However, some protective devices are still needed even
with the resistance grounding schemes, because the fault current
cannot be sustained.
The dc system grounding options are: 1) solid grounding; 2)
low-resistance grounding; 3) high-resistance grounding; and 4)
no grounding [13]. Although ungrounded systems are used in
some applications to avoid the effect of low-resistance pole-to-
ground fault and stray current, ungrounded systems are sensitive
to changes in the grounding plane and can be dangerous espe-
Fig. 6. Snubber circuits on the source side. (a) Discharge-suppressing-type cially under abnormal fault conditions [28]. International stan-
RCD snubber. (b) Charge-discharge-type RCD snubber.
dard IEC 60364 defines three grounding systems. Low-voltage
power systems ( 1 kVac or 1.5 kVdc) using the two-letter codes
high frequency, charge-discharge-type RCD snubber has been TN, TT, and IT depending on how the source and conductive
chosen for better voltage suppression performance. Although body of electric devices are connected to earth [29]. The TN
the discharge-suppressing-type RCD snubber could eliminate system ensures that distributed grounding and fault detection is
the separate freewheeling path as can be seen in Fig. 6(a), straightforward but faults at a higher voltage level can increase
it would be difficult to handle bidirectional currents. The the touch voltage. The TT system is easy to install and faults
charge-discharge-type RCD snubber is shown in Fig. 6(b). do not migrate to others but high-voltage stress is possible. The
A case of source-to-load power flow has been considered. IT system has very low or even zero fault current and can op-
The capacitor in the charge-discharge-type snubber is fully dis- erate with a single fault, but insulation monitoring is required
charged in normal operation when the switch is closed. When and high fault current is possible with another ground fault [30].
a fault is detected and the switch is trying to open, the diode It is a common practice to ground power subsystems at a
is forward biased and the snubber capacitor is charged to single point and as close to the source as possible [27], like in a
absorb the energy stored in the line inductance . The energy TN system. Multiple ground points in a TT system could form
stored in the line inductance can be given as unnecessary circulating current paths. Possible grounding point
for a dc system can be either one of the poles or the midpoint of
(5) the bus, and it has been reported that the balanced dc-side mid-
point grounding significantly reduces circulating current com-
where is the line current. The capacitance of snubber capac- pared to the ac-side neutral-grounded system [27]. Furthermore,
itor to absorb the energy can be determined as follows: it is safer because of lower ground potential compared to the di-
rect pole grounding, and the ground impedance at the midpoint
(6) can limit the fault current under a safe level. The ground resistor
can be used to detect the ground fault as well, although it is not
(7) able to identify the location of the fault because of the single
ground point practices.
where is the allowable voltage overshoot over . The
snubber resistor forms a discharging path when the switch V. SIMULATION RESULT
is closed. Once the fault has been detected and separated, the A computer simulation has been performed for a microgrid
system can check if the fault is cleared by reclosing test. When system that consists of three typical energy devices: a source, a
the switch is closed, most of the energy stored in the capacitor load, and energy storage. They are connected as shown in Fig. 7.
(6) should be discharged before the switch is re-opened in case Stiff dc power sources are assumed so that a constant fault cur-
the fault persists. Hence, the resistance can be determined by rent is fed by the sources without a voltage drop. A 240 V bipolar
dc bus with 200 m bus cable segments [31] and a fault at the
(8) middle (100 m) of the bus is simulated. Simulation parameters
can be found in Table I.
where is the percentage of stored energy to be discharged in A positive line-to-ground fault in the middle of the bus seg-
time before the next switch opening. ment A is simulated at 1 ms. Fig. 8 shows the source- and
load-side current of a line-to-ground fault with and without pro-
D. Grounding tection. It can be seen that the current from source increased to
Grounding is one of the most important factors in the power 180 A after 0.5 msec. The fault current magnitude depends on
system safety and protection. For a dc distribution system, the the impedance of the fault path. The currents at each end of the
advantages of the grounding include predictable operating con- segment which had been identical before fault show clear dif-
ditions, minimum voltage stress for the system components, and ference after fault. Line-to-line fault current will be higher be-
easier fault detection [27]. The ground fault current can also cause there is no resistance to limit it. Therefore, fast detection
be limited by using the resistance grounding. Since the typical and isolation are critical.
power-electronics converters connected in the LVDC systems It has been assumed in the simulation that the segment con-
cannot feed large fault currents, it would be beneficial to reduce trollers can detect it and open/close solid-state CBs in 250 s.
784 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

Fig. 7. Simulation circuit for the line-to-ground fault in the three-node microgrid system that contains two sources and a load. A fault is simulated in the segment
between source 1 and load.

TABLE I
SIMULATION PARAMETERS

Fig. 8. Simulation: Source-side current (top) and load-side current (bottom)


for a line-to-ground fault with and without protection.
Considering the speed of current microcontrollers and switching
devices, fast interruption in this speed range is feasible. Fig. 8
also shows that the fault currents are extinguished when the shows the fault extinction in the freewheeling path. The voltage
faulted segment is separated. transient at turnoff due to the line inductance and high can
Fig. 9 shows the voltage across the load and the current in be very high and it can easily damage the solid-state switch. It
the freewheeling path. The ground fault pulls the positive pole can also be seen that the voltage transient is suppressed by a
voltage to zero, and the bipolar dc bus will experience a voltage snubber circuit at a tolerable level.
offset on the faulted pole. However, the load voltage is quickly The protective devices in bus segments B and C have been
restored after the faulted segment has been separated. omitted in this simulation because the proposed protective
Fig. 10 shows the voltage transient across the solid-state CB scheme that detects the difference in net current flow will not
without and with the snubber circuits, respectively. It also be triggered if there is no fault in the bus. This can be verified
PARK AND CANDELARIA: FAULT DETECTION AND ISOLATION IN LV DC-BUS MICROGRID SYSTEM 785

Fig. 9. Simulation: Load voltage with and without protection (top) and current Fig. 11. Simulation: Voltage of bus segments B and C (top) and currents of
in a freewheeling path in the proposed scheme (bottom). segment C and (bottom). Intact segment C currents (incoming) and
(outgoing) are identical.

Fig. 12. Schematic of the experimental setup.

the same IGBT has been utilized to form the ground fault path.
Fig. 10. Simulation: Voltage across switch at turnoff without (top) and
with (bottom) the snubber. IGCTs can be considered for lower conduction losses. The free-
wheeling path has an IR diode T40HF60 and a 2- freewheeling
resistor. Using a diode in the freewheeling branch simplifies the
by the currents flowing into and out of the intact bus segment control circuits and it can be used for the line-to-ground fault
C shown in Fig. 11. Even with the transient caused by the fault protection. The RCD snubber circuit is attached to the IGBT
on the bus segment A, the incoming and outgoing currents with a 10- F capacitor, a 12- resistor, and a diode T40HF60.
of segment C are identical. The proposed scheme that detects The circuit parameters have not been scaled down because of
the current difference is robust to common-mode noise and the inductance in the power supplies. The schematic of the ex-
transient due to a fault. perimental test bed is shown in Fig. 12.
The differential protection algorithm described in
VI. EXPERIMENTAL VALIDATION Section IV-B is implemented in TIs TMS320F28335 dig-
A lab-scale experiment setup in about 6:1 scale from the sim- ital signal processing (DSP) microcontroller. As shown in
ulation circuit has been built to validate the feasibility of the pro- Fig. 12, the controller monitors the source and load-side current
posed protection scheme with actual hardware. The setup has a using Tektronics A622 current probes through analog-to-digital
source-load-storage structure of Fig. 3, but only with positive channels of DSP, and controls the IGBT CBs. A threshold of
pole and ground to simulate a line-to-ground fault. Two chan- 20% has been used for (3) in the experiments, but the threshold
nels of 30-V 3-A power supply Instek GPC-3030D have been level may vary depending on bus conditions to increase sensi-
utilized for 20-V source and energy storage, and 12.5- resis- tivity or to avoid malfunction. The controller sends out a digital
tive load is used. Each source supplies about 1 A of load current output to the gate driver board, which generates isolated gating
in normal operation. Three 15- H inductors and six 220-pF ca- signal using optocoupler HCPL-3120. In this experiment, the
pacitors are installed in the positive line to simulate the line in- analog-digital conversion of the current measurement is done
ductance and stray capacitance, respectively. But no resistance in the 100- s interrupt service routine. Although the controller
has been added in the bus due to the low current capacity of the takes the analog signal directly from the current sensors because
power supply. Two IXYS 600 V IGBT IXGN60N60C2D1 mod- of the small size of the test bed, digital communication between
ules have been used to make a bidirectional solid-state CB and the master and slave controller should be considered for larger
786 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 28, NO. 2, APRIL 2013

Fig. 13. Experimental test bed and DSP controller.


Fig. 15. Experiment: Load voltage with and without protection (top) and cur-
rent in the freewheeling path in the proposed scheme (bottom).

Fig. 14. Experiment: Source-side current (top) and load-side current


Fig. 16. Experiment: IGBT collector-emitter voltage without (top) and
(bottom) with and without protection.
with (bottom) the snubber circuit.

scale systems. Distributed control without the master controller experiment. Without protection, 6-A fault current flows from
can be possible if the two slave controllers are communicating two power-supply channels after transient. Fig. 15 shows that
with each other. The experimental test bed is shown in Fig. 13. the load voltage is restored to a normal level quickly after the
A line-to-ground fault has been experimentally tested. In faulted segment is separated; otherwise, it collapses to a low
normal steady-state condition, the source power supply supplies voltage without the protection system. Fig. 16 shows that the
20 W of power (20 V, 1 A) to the load and the power-supply snubber circuit effectively suppresses the voltage overshoot and
simulating energy storage monitors the bus voltage. When the oscillation across the IGBT.
ground fault IGBT is turned on, two power-supply channels
feed the fault current, and the segment controller measures VII. CONCLUSION
the current shown in Fig. 14. The difference is quite large This paper has presented a fault detection and isolation
because the direction of the load-side current is reversed unlike scheme for the low-voltage dc-bus microgrid system. The
the simulation due to the low fault impedance. The controller proposed protection scheme consists of segment controllers
readily detects the difference of the bus currents and isolates capable of detecting abnormal fault current in the bus and
the faulted segment immediately. It turned out that the power separating the faulted segment to avoid the entire system
supply can feed about 40-A peak transient fault current for a shutdown. A loop-type dc-bus-based microgrid system with
couple hundred microseconds before each channel settles down segment controllers between connected components and the
to 3 A of the power supplys rated current. It should be noted freewheeling branch has been proposed. The proposed pro-
that this power-supply characteristic makes the waveform of tection concepts have been validated by computer simulations
experimental fault current different from that of the simulation and experiments. A prototype system with a segment controller
in Fig. 8. that consists of master and slave controllers has been tested
Fig. 14 shows that the fault current is extinguished to zero on an actual hardware test bed and it has shown successful
as simulated. The fault current extinction time, which depends fault detection and isolation capability. The proposed scheme
on the freewheeling path impedance, was about 100 s in this can be applied to dc power systems, such as Green Buildings,
PARK AND CANDELARIA: FAULT DETECTION AND ISOLATION IN LV DC-BUS MICROGRID SYSTEM 787

with sustainable energy resources and data centers with a [20] F. Luo, J. Chen, X. Lin, Y. Kang, and S. Duan, A novel solid state fault
server array. Challenges, such as a reduction of conduction current limiter for DC power distribution network, in Proc. IEEE 23rd
Annu. Appl. Power Electron. Conf. Expo., Feb. 2008, pp. 12841289.
loss in the solid-state CBs and fault ridethrough capability, and [21] W. Fei, Y. Zhang, and Z. Lu, Novel bridge-type FCL based on self-
fault-location techniques need to be investigated. turnoff devices for three-phase power systems, IEEE Trans. Power
Del., vol. 23, no. 4, pp. 20682078, Oct. 2008.
REFERENCES [22] U. Ghisla, I. Kondratiev, and R. Dougal, Branch circuit protection for
DC systems, in Proc. IEEE Elect. Ship Technol. Symp., Apr. 2011, pp.
[1] R. Dugan and T. McDermott, Distributed generation, IEEE Ind.
234239.
Appl. Mag., vol. 8, no. 2, pp. 1925, Mar./Apr. 2002.
[23] M. Saisho, T. Ise, and K. Tsuji, Configuration of DC loop type
[2] F. Blaabjerg, R. Teodorescu, M. Liserre, and A. Timbus, Overview
quality control center, in Proc. Power Convers. Conf., 2002, vol. 2,
of control and grid synchronization for distributed power generation
pp. 434439.
systems, IEEE Trans. Ind. Electron., vol. 53, no. 5, pp. 13981407,
[24] J. Machowski, J. Bialek, and J. Bumby, Power System Dynamics: Sta-
Oct. 2006.
bility and Control. Hoboken, NJ: Wiley, 2011.
[3] U.S. Department of Energy, (2009). States With Renewable Portfolio
[25] N. Mohan, T. Undeland, and W. Robbins, Power Electronics Con-
Standards. [Online]. Available: http://www..energy.ca.gov/renewables
verters, Applications, Design, 3rd ed. Hoboken, NJ: Wiley, 2003.
[4] U.S. Department of Energy Energy Efficiency and Renewable Energy
[26] Y. Zhang, S. Sobhani, and R. Chokhawala, Snubber considerations for
News, (2010). Colorado Boosts its Renewable Energy Requirement to
IGBT applications, 2002. [Online]. Available: www.irf.com/technical-
30% by 2020. [Online]. Available: http://apps1.eere.energy.gov/news/
info/designtp/tpap-5.pdf
news\_detail.cfm/news\_id=15878
[27] B. Jacobson and J. Walker, Grounding considerations for dc and
[5] R. Lasseter and P. Paigi, Microgrid: A conceptual solution, in
mixed dc and ac power systems, Naval Eng. J., vol. 119, no. 2, pp.
Proc. 35th Annu. IEEE Power Electron. Specialists Conf., 2004, pp.
4962, October 2007.
42854290.
[28] D. Paul, DC traction power system grounding, IEEE Trans. Ind.
[6] H. Nikkhajoei and R. Lasseter, Distributed generation interface to
Appl., vol. 38, no. 3, pp. 818824, May/Jun. 2002.
the CERTS microgrid, IEEE Trans. Power Del., vol. 24, no. 3, pp.
[29] IEC 60364-1 Low-Voltage Electrical InstallationsPart 1: Funda-
15981608, Jul. 2009.
mental Principles, Assessment of General Characteristics, Definitions,
[7] F. Katiraei, R. Iravani, N. Hatziargyriou, and A. Dimeas, Microgrids
IEC 60364-1, 2005.
management, IEEE Power Energy Mag., vol. 6, no. 3, pp. 5465, May/
[30] R. Kamel, A. Chaouaski, and K. Nagasaka, Design and testing of three
Jun. 2008.
earthing systems for micro-grid protection during the islanding mode,
[8] D. Salomonsson, L. Soder, and A. Sannino, Protection of low-voltage
Smart Grid Renew. Energy, vol. 1, pp. 132142, Sep. 2010.
DC microgrids, IEEE Trans. Power Del., vol. 24, no. 3, pp.
[31] Transmission Line Reference Book 345 kV and Above, Elect. Power
10451053, Jul. 2009.
Res. Inst., 1987.
[9] M. Saeedifard, M. Graovac, R. Dias, and R. Iravani, DC power sys-
tems: Challenges and opportunities, in Proc. IEEE Power Energy Soc.
Gen. Meeting, July 2010, pp. 17.
[10] R. Cuzner and G. Venkataramanan, The status of DC micro-grid pro-
tection, in Proc. IEEE Ind. Appl. Soc. Annu. Meeting, Oct. 2008, pp. Jae-Do Park (M07) received the Ph.D. degree in
18. electrical engineering from the Pennsylvania State
[11] P. Salonen, P. Nuutinen, P. Peltoniemi, and J. Partanen, LVDC dis- University, University Park, in 2007.
tribution system protection: Solutions, implementation and measure- Currently, he is an Assistant Professor of Elec-
ments, in Proc. 13th Eur. Conf. Power Electron. Appl., 2009, pp. 110. trical Engineering at the University of Colorado
[12] J. Candelaria and J.-D. Park, VSC-HVDC system protection: A re- Denver, Denver, CO, USA. Prior to his arrival at
view of current methods, in Proc. IEEE/Power Energy Soc. Power the University of Colorado Denver, he was Manager
Syst. Conf. Expo., Mar. 2011, pp. 17. of Software and Controls for Pentadyne Power
[13] J. Das and R. Osman, Grounding of AC and DC low-voltage and Corporation, CA, where he took charge of control
medium-voltage drive systems, IEEE Trans. Ind. Appl., vol. 34, no. algorithm design and software development for the
1, pp. 205216, Jan./Feb. 1998. high-speed flywheel energy-storage system. He is
[14] P. Cairoli, R. Dougal, U. Ghisla, and I. Kondratiev, Power sequencing interested in various energy and power system research and education topics,
approach to fault isolation in dc systems: Influence of system parame- including electric machines and drives, energy-storage and harvesting systems,
ters, in Proc. IEEE Energy Convers. Congr. Expo., 2010, pp. 7278. renewable energy sources, grid-interactive distributed generation, microturbine
[15] L. Tang and B. Ooi, Locating and isolating DC faults in multi-terminal control, and microgrid systems.
DC systems, IEEE Trans. Power Del., vol. 22, no. 3, pp. 18771884,
Jul. 2007.
[16] H. Iwamoto, K. Satoh, M. Yamamoto, and A. Kawakami, High-power
semiconductor device: A symmetric gate commutated turn-off Jared Candelaria (S10) is currently pursuing the
thyristor, Proc. Inst. Elect. Eng., Elect. Power Appl., vol. 148, no. 4, M.S.E.E. degree in power options at the University
pp. 363368, Jul. 2001. of Colorado Denver, Denver, CO, USA.
[17] Y. Ito, Y. Zhongqing, and H. Akagi, DC micro-grid based distribu- He is an Electrical Engineer at NEI Electric Power
tion power generation system, presented at the 4th Int. Conf. Power Engineering, Arvada, CO. His duties at NEI include
Electron. Motion Control, Xian, China, Aug. 2004. arc flash, interconnection of distributed generation,
[18] R. Schmerda, S. Krstic, E. Wellner, and A. Bendre, IGCTs vs. IGBTs supervisory control and data acquisition, substation
for circuit breakers in advanced ship electrical systems, in Proc. IEEE design, industrial design, and protective relaying.
Electric Ship Technol. Symp., Apr. 2009, pp. 400405. His research interests include power systems appli-
[19] P. Steimer, O. Apeldoorn, E. Carroll, and A. Nagel, IGCT technology cations, power system protection, and HVDC.
baseline and future opportunities, in Proc. IEEE/Power Energy Soc. Mr. Candelaria is a registered E.I.T. in the state of
Transm. Distrib. Conf. Expo., 2001, vol. 2, pp. 11821187. Colorado.

Вам также может понравиться