Академический Документы
Профессиональный Документы
Культура Документы
Abstract: In order to study the effect on Induced voltage initiate by ground wire transposition in the same tower dou-
ble circuit transmission line, we attempted to analyze the formation mechanism of ground wire induction voltage.
Simulation models of typical 500kV double-circuit transmission line are established by ATP-EMTP software and cal-
culations of induce voltage on ground wires are performed with different phase sequence array. The results show that,
the restriction by ground wire transposition is mainly caused by the phase difference of inductive electromotive forces
in the two ground wires. The restriction effect is better when phase difference is greater, and the best effect to reduce
inductive voltage is adopting reverse phase sequence which the inductive electromotive forces in two sides of ground
wire are almost inverse. Due to the inductive electromotive forces in ground wire transposition points are not totally
inverse, the effect is not multiple while continuous and multiple transposition were made.
Key wordsInsulated ground wire; inductive voltage; phase sequence array; ground wire transposition
10
D0 = 210 2 Table2 Parameters of conductor and ground wire
f
conductor Ground wire
In the above two formulas, D0 is equivalent depth type 4*LGJ-400/35 JLB20A-150
of vagabond current, which depends on the earth internal diame-
0.334 0.594
resistivity mand current frequency fHz ter/cm
re is effective radius of the wire. external diame-
1.177 0.687
Mutual impedance between the conductor and ter/cm
ground wire is DC resistance/
0.01847 0.5807
D /km
Z mn = 0.05 + j 0.145lg 0 3
d mn Split interval/mm 450 -
Wherein, dmn is the distance between the Split angle/(e) 90 -
conductor and the ground wire.
During the transmission line normal opera-
tion, the three-phase current is balance,
Ia = Ib = 2 Ic 4
n
d d
E2 = j 0.145 I iA 2 lg 2ia + lg 2ia 6 Fig.1 Conductors layout of the crossing transmission
i =1 d 2ib d 2ic
lines
3
3. The simulation of ground wire transpo- different arrangement of the phase sequence, over-
sition head ground wire insulated is single-point grounded
3.1 Ground wire transposition effects of different across the board, and the end of the line is the
phase sequence arrangement grounding point. The ground wire interchanged at
Phase sequence arrangement of tower dou- the middle of the line tower (#50 tower). Observe
ble-circuit line can be divided into three categories: the left ground wire, and the ground wire induced
same phase sequence arrangement as ABC/ABC; voltage variations by simulation are shown in Fig-
Reverse phase sequence arrangement as ABC/CBA ure 2.
and different phase sequence arrangement. With
Figure.2 Induced voltage distribution of ground wire before and after transposition with different phase sequence
It began to change after the transposition points(#
It can be concluded from the figure 2 that the 50 tower). Phase sequence arrangements of tower
distribution of the ground wire induced voltage be- double-circuit line are different, while the effects of
fore transposition point is as the same as the ground wire transposition limitation to induced
distribution that the ground wire is not transposed. voltage are different. The comparison of the maxi-
mum induced voltage along the Ground wire around
transposition is shown as in table 3.
Transpose once In the middle of ground wire,
and the induced voltage of ground wire is not
changed completely in the case of same phase se-
quence arrangement; while the induced voltage
dropped to 48.55% in the case of reverse phase se-
quence arrangement, approximately halved
compared with no-transposition. All induced volt-
ages have declined when it applies four kinds of
different phase sequence arrangement, and the de- Figure.3 Multiple transposition induction voltage dis-
crease amplitudes are between 0.63% and 13.78%. tribution with Inverse phase sequence
Figure 3 shows that ground wire transposes twice
Table3Induced voltage of ground wire before and after continuously, the maximum induced voltage is situ-
transposition with different phase sequence ated in the end of the line, which is 1420.59V, a
Decline little less than the induced voltage that transposed
phase se-
type before/V after/V range once, dropping to 50.53% of the induced voltage
quence
/% with no transposition. Ground wire transposes three
same sequence ABC/ABC 6908.93 6908.93 0 times continuously, the maximum induced voltage
Inverse phase of ground wire is 1135.97V, which is 40.4% of the
ABC/CBA 2811.56 1446.51 48.55
sequence induced voltage with no transposition. It can be
ABC/ACB 6432.97 6392.2 0.63 seen that, the more times ground wire transposes,
Other
ABC/BAC 5597.78 5241.3 6.37 the greater limiting effect to the induced voltage is.
phase
ABC/BCA 3960.82 3415.06 13.78 In the actual line, the requirements for the tower
sequence
ABC/CAB 4266.09 3493.93 18.1 model, construction sites and construction technol-
ogy are relatively high. Thus, it is recommended
3.2 The simulation of ground wire repeatedly that carrying out ground wire transposition
transposition measures once at most to control induced voltage of
Ground wire transposed one time in the middle of ground wire in an insulated inner section of over-
line, it can be found that inverse phase sequence head ground wire.
arrangement limits the ground wire induced voltage 4. Reason analysis of simulation results
most. Induced voltage is reduced to 1/2of the max-
4.1 Ground wire transposition results under dif-
imum value approximately after transposed. In
ferent phase sequence
order to understand the limiting of ground wire
From the simulation results, transposition
transposition to induced voltage better, in the case
measures on the ground wire would not limit the
of reverse phase sequence arrangement, set the
induced voltage effectively in the case of same
overall length of overhead ground wire as L, and
phase sequence arrangement. But it can play a role
then carry out transposition for consecutive n times
to varying degrees in different arrangement of phase
to overhead ground wire. Make sure that the trans-
sequence. Generally, it can play the greatest role in
position is on average, and the distribution of
the case of reverse phase sequence arrangement.
overhead Ground wire induced voltage along the
And the maximum induced voltage of ground wire
line is shown in Figure 3.
is reduced to approximately 1/2 of the original.
5
,QGXFHGYROWDJH9
6LPXODWLRQWLPHPV
D$%&$%&
6LPXODWLRQWLPHPV
,QGXFHGYROWDJH9
I$%&&$%
12.9
B -98.6 -85.7
Other ABC/BA 5597.78 5542.68
37.6
phase C -132.5 -170.1
se- ABC/BC 3960.82 4266.09
65.8
quence A 221.8 156
ABC/CA 4266.09 3960.82
65.7
6LPXODWLRQWLPHPV B -83.9 -18.2
H$%&%&$
The phase value of ground wire induced voltage ble 3, we can find that , after transposition, the in-
under each phase sequence arrangement in Figure 4 duced voltage drop of class is greater than class
are shown in Table 4. From the aspect of the value .
of the induced voltage, induced voltage has a max- Through the above analysis, it can be concluded
imum value in the case of same phase sequence that : when double circuit transmission lines is un-
arrangement; while it has a minimum value in dif- der different phase sequence arrangement, EMF
ferent arrangement of phase sequence; and the value phase- difference of the left and right sides of
of reverse phase sequence arrangement falls in be- ground wire is between 0 to . The larger the phase
tween. It can be seen that reverse phase sequence difference is, the more obvious limiting effect to
arrangement can limit induced voltage value of induced voltage of ground wire transposition is.
ground wire for the most advantageous. 4.2 Analysis of ground wire transposition for
The limitation of ground wire transposition is many times
mainly caused by the induced electromotive force Simulation shows that, ground wire transposition
retardation from both sides of ground wire. When for many times cannot help limiting on the induced
the tower double-circuit line is under reverse phase voltage. Take reverse phase sequence arrangement
sequence arrangement, the phase difference be- for example, Supposing the overall length of ground
tween left and right sides of ground wire induced wire is L, across the board insulated endpoints are
electromotive force is 132.7 degrees, close to the grounded, overhead ground wire transposed con-
inverting. After transposition, EMF of insulating tinuously and uniformly for n times, as shown in
segment besides the transposition point on the same Figure 5. Respectively set the EMF of the first
ground wire is approximately reversal superimposi- transposition point`s both sides as Ef1 and Ef2, then
tion. So the induced voltage of ground wire is to be the induced voltage at the end of the line after first
offset substantially. Induced voltage decreased transposition U= Ef1+ Ef2, as the phase diagram
gradually from the transposition point. But when it shown in Figure 6.
arranged at the same phase sequence, amplitude and
phase of EMF on both sides of ground wire are ex-
actly same . EMF of both sides of the transposition
point cannot cancel each other out after transposi-
tion, so it would not achieve the effect of limiting.
The arrangement in addition to same & reverse
phase sequence arrangement is called different Figure.5 Multiple transposition
phase sequence arrangement, that there are four
different kinds of phase sequence arrangement. The
analysis shows that it can be broadly classified into
two categories: Class arranged as ABC / ACB
and ABC / BAC , referring to the phase sequence
arrangement that the phase are same at both ends of
the cross arm ; the EMF phase difference under this
arrangement on both sides of ground wire is less
than / 4 ; Class arranged as ABC/BCA and
ABC/CAB, referring to the phase sequence ar-
rangement that the phase are different at both ends
of the cross arm; the EMF phase difference under Figure.6 The phasor diagram of the induced voltage
this arrangement is between / 4 to / 2. From ta- after the grounding line transposition
7
The induced voltage at the end of the line after 4) When double-circuit transmission line arranged
first transposition U is the phasor sum of the EMF by Inverse phase sequence and the OPGW is trans-
on both sides of transposition point. If the ground posed at the middle, the highest induced
wire is not transposed, the induced voltage of pitch electromotive voltage can be deduced to half of it
end is 2Ef1. Obviously, U2Ef1, so the ground wire without transposition. The induced electromotive
transposition makes the induced voltage on the line voltage cant be totally offset because the induced
reduced. And because of the Ef1 and Ef2 not com- electromotive forces at both side of ground wire
pletely inverted, both sides of the EMF is not fully transposition point is not exactly inverse phase. So
offset after transposition. So ground wire transposi- successive transposition of ground wire cannot
tion for many times cannot limit the inducted double the limit effect of induced electromotive
voltage double. voltage. From the result, it is suggested that one
transposition of earth wire is enough for an insulat-
5. Conclusion
ing section of OPGW.
1)The simulation results of ground wire induced
voltage by ATP-EMTP is very close to measured 5HIHUHQFHV
data, which means the simulation results is reliable.
[1] Zhang Dian-sheng, Design handbook for high voltage power sup-
2) Limiting effect of ground wire transposition is
ply circuit of electric power engineering [M]. Beijing: China
mainly caused by the phase difference of induced Electric Power Press, 1999:156-161.
electromotive force of two side ground wire. Dou- [2] Xue Zhen-dong, Yang Xiao-hong, Cui Ding-xin, Jiang Jun. Test
and analysis of inductive voltage on overhead ground wire of 1000
ble-circuit transmission line arranged by different
kV UHV AC Line. High Voltage Engineering,
phase sequence, and the phase difference of the in- 2009,35(8):1802-1806.
duced electromotive force between left and right [3] Chen Ci-xuan. Electrical Engineering Foundation[M].Beijing:
China Electric Power Press, 2003.
side of ground wire ranges from o to . The bigger
[4] Song Li-jun, Jiang Tao-ning, Zou Jun, Wang Ya-ting. Research on
the difference is, the more obviously the limiting Voltages Across Both Terminals of Ground Wire Insulation Gap for
effect on induced electromotive force by earth wire UHV AC Transmission Line. Power System Technology, 2013,
37(3):686-691.
transposition is.
[5] Hu Jun-hua. The analysis of the different grounding modes of
3) When double-circuit transmission line arranged overhead ground wire for 500kV transmission line[D]. Beijing:
by Inverse phase sequence, the induced electromo- North China Electric Power University, 2013.
[6] Zhao Hua, Ruan Jiang-jun, Huang Dao-chun.Calculation of the
tive force between left and right side of ground wire
induction voltage on double circuit transmission lines[J]. Relay,
is almost opposite-phase. After ground wire trans- 2005, 33(22): 37-40, 52.
position, induced electromotive force at insulating [7] Amirnaser Yazdani, Reza Iravani. A unified dynamic model and
control for the voltage-sourced converter under unbalanced grid
section on both sides of the transposition point is
conditions[J]. IEEE Trans on Power Delivery, 2006,
stacked opposite-phase, so the induced electromo- 21(3):1620-1629.
tive voltage is substantially offset, the induced [8] DLT5092-1999 110-500kV Technical specification for design of
overhead transmission line [S]. 1999.
electromotive voltage starts declining from transpo-
[9] ZENG Lin-ping, ZHANG Peng, FENG Yuchang, et al. Simulation
sition point. When double-circuit transmission line calculation of induced voltage and induced current on 750kV
arranged by same phase sequence induced electro- overhead ground wires[J]. Power System and Clean Energy, 2008,
24(6):21-23.
motive force of both side is exactly the same on [10] Li Bao-ju, Zhou Hao. Simulation and analysis of induced voltage
value and phase, the transposition of ground wire and current on overhead ground wire of Huai-
cant limit the induced electromotive voltage. The nan~Wannan~Zhebei~Huxi 1000 kV UHV AC double-circuit
transmission line
effect of limit the induced electromotive voltage [11] KOMODAM, SASAKIK. Method of reducing power loss of
shows different degree under the four kind of phase ground wore of overhead transmission lines[J]. English translation