Академический Документы
Профессиональный Документы
Культура Документы
7.2.6 No steam generator should be closed or walled-in without authorization and inspection by authorized
government representative and who will conduct a hydrostatic test of 150% of stipulated working pressure.
7.2.7 Clearance
7.2.7.1 When boilers are replaced or new boilers are installed in existing or new 2130mm shall be provided
between the top of the boiler proper and the celling expect in single installation of self-contained boiler where a
minimum height of wean the highest point of any valve steam, of fitting and the celling.
7.2.7.2 All boilers and unfired pressure vessels shall be so located that adequate space will be provided for the
proper operation of the boiler and its appurtenances for the inspection of all surfaces, tubes, water wall,
economizers, piping, valve and other equipment and for their necessary maintenances and repair.
7.2.7.3 Smokestacks should be sufficient capacity to handle flue gases, self-supporting or guyed to withstand a
wind load 160kph and rise at least 5000mm above the eaves of any buildings within a radius of 50 meters.
7.2.7.4 No smokes should be closer than 305mm from any exposed woodwork or framing.
7.2.7.5 All steam generators should be each be provide with two means of feed water two pumps, one steam
driven and one pump and one injector.
7.2.7.6 When feeding hot water, feed pump should at least be 1220mm below hot well at prevents vapor lock.
7.2.7.7 Two check valves should be provided between any feed pump and boiler.
7.2.7.8 Where two or more steam generators will be connected in parallel each steam outlets should be provided
with a non-returns
7.2.7.9 Only steam pressure sufficient for requirements should be allowed. No high pressure will be generated just
to be reduced on the line to suit requirement.
7.2.7.10 All construction features of boiler should be in conformity with P.S.M.E. Boiler Construction Code when
available or its equivalent.
7.2.7.11 All new boiler installations, including reinstalled boilers, shall be installed in accordance with the
requirements of the latest revision of the P.S.M.E. Boiler Construction code and/or the rules and regulations
provided herein.
7.2.7.12 Ladders and Catwalks. A steel catwalk or platform at least 455 mm wide and provided with standard
handrails and toe-board on either side shall be installed across the tops of adjacent boilers or at some other
convenient level for the purpose of affording safe access to the boilers. All catwalks shall have at least two means
of exit, each exit to be remotely located to a permanent stairway or inclined ladder leading to the floor level.
7.2.7.13 Inspections. Upon completion of the installation, all boilers shall be inspected by the authorized
government engineer or assistant engineer of the locality.
Article 7.3 Specific Requirements for Power Boilers
7.3.1 Maximum Allowable Working Pressure. The maximum allowable working pressure on the shell of a boiler or
drum shall be determined by the strength of the weakest SECTION OF THE STRUCTURE, computed from the
thickness of the plate, the tensile strength of the plate, the efficiency of the longitudinal joint, OR TUBE
LIGAMENTS, the inside diameter of the outside coarse and the factor of safety by these rules.
= maximum allowable working pressure in MPa
: = ultimate tensile strength of the shell plates, N/mm2
= Minimum thickness of the shell plate, in weakest course in mm, minimum thickness for boiler plate shall be
6.35mm
= Efficiency of longitudinal joint.
X 100%
:
P = pitch of rivets, mm
= Diameter or rivet hole after driving, mm
For riveted construction, E shall be determined by the formula:
E= X 100%
P = pitch of rivets
= Rivet diameter
or fusion welding, E shall be taken as equal to 90% or E shall be determined by the following P.S.M.E. Code. For
seamless construction, Eshall be 100%.
7.3.2.1 Tensile strength. When the tensile strength of steel or wrought iron shell plates is not known, it shall be
taken as 379.31 N/mm2 for steel and 310.04 N/mm2 wrought iron.
7.3.2.2 Crushing strength of mild steel. The resistance to crushing of mild steel shall be taken at 655.17 N/mm 2 of
cross sectional area.
7.3.2.3 Strength of rivet in shear. When computing the ultimate strength of rivet in shear, the following values in
N/mm2 of the cross sectional area of the rivet shank shall be used:
Iron rivets in single shear................. 262 N/mm2
Iron rivets in double shear................ 524 N/mm2
Steel rivets in single shear................. 303 N/mm2
Steel rivets in double shear................ 607 N/mm2
7.3.3.1 When the diameter of the rivet holes in the longitudinal joints of a boiler is not known, the diameter and
cross section area of rivets, after driving, may be selected from the following table or ascertained by cutting out
one rivet in the body of the joint.
Valve or valves, and shall be run full size without use of reducers or bushing. The piping shall be extra heavy
wrought iron or steel and shall not be galvanized.
7.3.11.6 Whenever repairs are made to fittings or appliances or it become necessary to replace them, the work
shall comply with the code for new installation.
7.3.11.7 Each existing boiler shall be identified by a serial number. The number shall be assigned by the Chief
Inspector/Engineering and stamped by the authorized representative. The stamping shall be kept free of paint and
lagging so that it will be plainly visible and easily read by Engineers.
7.3.11.8 All authorized representative of the government agency shall notify the owners and users who must
provide for those requirements, in a written notice to the owner or user that the necessary work must be
completed within six months from the date of notifications.
7.3.11.9 All cases not specifically covered by these rules and regulations shall be treated as New Installation or
may be referred to the government agency for instructions concerning the requirements.
7.3.4.1 The following factors of safety shall be increased by the engineer if the condition and safety of the boilers
demand it.
7.3.4.2 the lowest factor of safety permissible on existing installations shall be 4.5 excepting for horizontal return
tubular boilers having continuous lap seems more than 3650 mm in length where this latter type of boiler is
removed from its existing settings, it shall not be reinstalled for pressures in excess of 1.05 kg/cm^2 gage.
7.3.4.3 Reinstalled or secondhand boilers shall have a minimum factor of safety of 6 when the longitudinal seams
are of lap riveted construction, and a minimum factor of safety of 5 when the longitudinal seams are to butt and
double strap construction.
7.3.4.5 Age limit of fire tube boilers. The age of limit of a horizontal return tubular, flue or cylinder boiler having a
longitudinal lap joint and operating at a pressure in excess of 0.345 MPa or 3.45 Bar gage shall be thirty years (30
years). A reasonable time for replacement shall be given at the discretion of the inspector not o exceed one year
(1year).
7.3.4.6welded boilers. Boilers having either longitudinal or circumferential seams or fusion welded construction
shall be constructed and stamped in accordance with the rules and regulations of the P.SM.E boiler construction
Code.
7.3.4.7 Pressure on old boilers. In no case shall be the maximum working pressure of an old boiler be increased to
a greater pressure than would be allowed for a new boiler of same construction.
7.3.4.7.1 Cast iron headers and Mud drums. The maximum allowable working pressure on a water tube boiler, the
tubes of wich are secured to cast iron or malleable iron headers, or which have cast iron mud drums, shall be not
exceed 1.10MPa or 11.0 Bars.
7.3.4.7.2 Pressure on cast iron boilers. The maximum allowable working pressure for any cast iron boiler except
hot water boiler, shall be 1.0 Bar gage.
7.3.8.1 The use of weighted-lever safety valves shall be prohibited and these valves shall be replaced by direct
spring-loaded pop types valves.
7.3.8.2 Safety valves having either the seat or disc of cast iron shall not be used.
7.3.8.3 Each boiler shall have at least one safety valve and if it has more than 46.5 m2 of water heating surface or
the generating capacity exceeds 910 kg/hr, it shall have two (2) or more safety valves.
7.3.8.4 The valve or valves shall be connected direct to- the boiler, independent of any other steam connection,
and attached as closed as possible to the boiler, without unnecessary intervening pipe or fittings. Where alteration
is required to conform to this rule and regulation, owners or users shall be allowed one (1) year in which to
complete the work.
7.3.8.5 No valve of any description shall be placed between the safety valve and the boiler nor on the escape pipe
(if used) between the safety valve and the atmosphere. When an escape pipe is used, it shall be full size and fitted
with an open drain to prevent water lodging in the upper part of the safety valve or escape pipe. When an elbow is
placed on a safety valve outlet or the escape pipe shall be securely anchored and supported. All safety valve
discharges shall be so located or piped as to be carried clear from walkways or platform used to control the main
stop valves of boilers or steam headers.
7.3.8.6 The safety valve capacity of each boiler shall be such that the safety valve or valves will discharge all the
steam that can be generated by the boiler without allowing the pressure to rise more than 6% above the highest
pressure to which any valve is set, and in no case to more than 6% above the maximum allowable working
pressure.
7.4.1.1 No Miniature Boiler, except reinstalled boilers and those exempted by these Rules and Regulations, shall
hereafter be installed unless it has been constructed/inspected and stamped in conformity with P.S.M.E. Boiler
Construction Code and is approved, registered and inspected in accordance with these rules and regulations.
7.4.2.1 Rules and Regulations, as adopted for power boilers applying to strength of materials and calculations to
determine maximum allowable working pressure, shall be use for miniature boilers unless a special rule stated
herein.
7.4.3.1 Maximum Allowable Working Pressure. The maximum allowable working pressure on the shell of a boiler
or drum shall be determined by the Rules in section 7.3.1.
7.4.3.2 Construction. The construction of miniature boilers including factor of safety, except where otherwise
specified, shall conform to that required for power boilers.
(b) The lowest permissible water level shall be at a point one-third of the height of the shell, except where
the boiler is equipped with internal furnace, in which case it shall not be less than one-third of the tube
length above the top of the furnace.
(c) For small boilers where there is insufficient space for the usual type of gage glass, water level
indicators of the glass bulls eye type may be used.
1) Where the boiler is connected to a water main or system having sufficient pressure to feed the boiler at any
time while under pressure.
2) Where the fuel burned is such that all heat input can be discontinued instantaneously by the operation of the
valve, cock or switch, thereby permitting the boiler pressure to be quickly lowered to a point where water can be
introduced from the connection to the
7.5.6 Fired Radiators. A radiator in which steam pressure is generated at a pressure of 1.056 kg/cm2 or less is con-
sidered a low-pressure boiler.
7.5.7 General Requirements. If in the judgement of the engineer based on the following and other re -
quirements, a steam heating boiler is unsafe for operation at the pressure previously approved, the pressure shall be
reduced, proper repair made or the boiler retired from service.
7.5.7.1 Safety Valves. Each steam heating boiler shall be provided with one or more safety valves with a total area
of not less than 25.4 m2 for each 0.465 m2 of grate area, or equivalent, if grates are not used. It is further provided
that the steam relieving capacity of the safety valve or valves on any boiler shall be sufficient to prevent a boiler
pressure greater than 1.4 kg/cm 2. If there is any doubt as to the capacity of the safety valve an accumulation test
shall be run. No stop valve of any description shall be located between a boiler and its safety valve; nor in the
safety valve discharge pipe. The safety valve may be located on a main steam pipe connection at the boiler.
7.5.7.2 Water relief valves. Each Hot Water Heating or Hot Water Supply boiler shall have one or more relief
valves of the spring-loaded type without disc guides on the pressure side of the valve.
The valves shall be set to relieve at or below the maximum allowable working pressure of the boiler and so
arranged that they cannot be reset to relieve at a higher pressure of the boiler. Each relief valve shall have a
substantial device which will positively lift the disc from its seat at least 1.5 mm when there is no pressure on the
boiler.
7.5.7.3 Steam gage. Each steam boiler shall have a steam pressure gage connected to the steam space of the
boiler itself or on steam pipe near the boiler. The graduations of the steam gage shall not be less than 1.0 bar nor
more than 2.0 bars.
7.5.7.4 Water Gage Glass and Gage Cocks. Each steam boiler shall have at least one water gage glass with the
lowest visible part above the heating surfaces in primary combustion chamber. When, in the judgement of an
Engineer the heating surfaces above the low water line may be injured by contact with gases of high temperature
the water gage shall be raised until the lowest visible part of the gage glass is above such heating surface. Each
steam boiler shall have two or more gage cocks located within the visible length of the water gage glass; except
when such boiler is provided with two water gage glasses.
7.5.7.5 Stop Valves and Check Valves. If a boiler may be closed off from the heating system by closing a steam stop
valve, there shall be a check valve in the condensate return line between the boiler and the system. If any part of
heating system may be closed off from the remainder of the system by closing a steam stop valve, there shall
be a check valve in the condensate return pipe from that part of the system.
7.5.7.6 Feedwater Connections. Feedwater con-sections shall be independent of any water gage connections
and be made to the condensate return pipe or reservoir of the "condensate return pump. There should be a stop
valve and a check valve in the feedwater line at the boiler.
7.5.7.7 Return Pump. Each condensate returns pump where practicable shall be provided with an automatic
water level control set to maintain the water level within the limits of two game cocks.
7.5.7.8 Repairs and Renewal of Fittings and Appliances. Whenever repairs are made to fittings or appliances or it
becomes necessary to replace them, the work must comply with the Code for New Installations.
7.6.1.1 Requirements. No Unfired Pressure Vessel except reinstalled vessels and those exempt by these Rules
and Regulations, shall hereafter be installed unless it has been constructed, inspected and stamped inconformity
with P.S.M.E. Unfired Pressure Vessel Boiler Construction Code and is approved, registered and inspected in
accordance with the requirements of these Rules and Regulations.
7.6.1.2 All new installation unfired pressure vessels, including reinstalled unfired pressure vessels shall be
installed in accordance with the requirements of the latest. Revision of the P.S.M.E. Unfired Pressure Vessel Boiler
Construction Code, and these Rules and Regulations.
7.6.1.3 Inspections. Upon completion of the installation, all unfired pressure vessels shall be inspected by the
representative authorized by the government agency concerned.
7.6.1.4 Rupture Discs. Rupture discs or safety heads may be used for additional protection of pressure vessels.
7.6.3.1 Inspection of Boiler and Unfired Pressure Vessels. All boilers and unfired pressure vessels, unless otherwise
exempt by these Rules and Regulations, and which are subject to annual inspections as provided for in this code
shall be prepared for such inspections, or hydrostatic tests whenever necessary, by the owner or user when
notified by the authorized representative of the government agency. The owner or user shall prepare each boiler
and fired pressure vessel for internal inspection, and shall prepare for and apply the hydrostatic test whenever
necessary, on the data specified by the authorized government, representative which data shall be not less than
ten (10) days, after the data of notification.
7.6.3.2 Preparation for Internal Inspection. The owner or user shall prepare a boiler for internal inspection in the
following manner:
(a) Water shall be drawn off and the boiler thoroughly washed,
(b) All manhole and plates and wash-out plugs and water column connections shall be removed, the furnace and
combustion chambers thoroughly cooled and cleaned,
(c) All grates of internally fired boilers shall be removed,
(d) At each annual Inspection brickwork shall be removed as required by the Inspector in order to determine the
condition of the boiler, headers, furnace, supports or other parts,
(e) The steam gage shall be removed for testing,
(f) Any leakage of steam or hot water into the oiler shall be cut off by disconnecting the pipe or valve at the most
convenient point. Unfired pressure vessels shall be prepared for inspection to the extent deemed necessary by the
Inspector.
7.6.3.3 Improperly Prepared Requirement for Inspection. If a boiler or unfired pressure vessel has not been
properly prepared for an internal inspection or the owner or user fails to comply with the requirements for
hydrostatic test as set forth in these rules, the Engineer may decline to make the inspection shall be withheld until
the owner or user complies with the requirements.
7.6.3.4 Removal of Covering to Permit Inspection. If the boiler or unfired pressure is jacketed so that the
longitudinal seams of shells, drums, or domes cannot be seen, enough of the jacketing, setting wall, or other form
of casting or housing shall be removed so that the size of the rivets, pitch of the rivets and other data necessary to
determine the safe of the boiler or unfired pressure vessel may be obtained, provided such information cannot be
determined by other means.
7.6.3.5 Lap Seam Crack. The shell or drum of a boiler or unfired pressure vessel in which a lap seam crack is
discovered along a longitudinal riveted joint shall be immediately discontinued from use. If the boiler or unfired
pressure vessel is not more than 15 years of age, a complete new course of the original thickness may be installed
at the discretion of the authorized representative of the government agency. Patching is prohibited.
7.6.3.6 Hydrostatic Pressure Tests. A hydrostatic pressure test, when applied to boilers or unfired pressure vessels
of riveted or welded construction, except locomotive boilers, shall not exceed one and one half times the
maximum allowable working pressure. Hydrostatic pressure applied to locomotive boilers shall not exceed one and
one quarter times the maximum allowable working pressure. Hydrostatic pressure supplied to glass lined vessels
shall not exceed the maximum allowable working pressure. During the hydrostatic pressure test, the safety valve
or valves shall be removed or each valve disc shall be held down by means of a testing clamp and not be applying
addition load to the spring with the compression screw. It is suggested that the minimum temperature of the
water used to apply a hydrostatic test be not less than 21 C but the maximum temperature shall not exceed 71 C.
1. For all cases involving the question of tightness, the pressure shall be equal to the release pressure of the safety
valve or valves having the highest release setting.
2. For all cases involving the question of safety, the pressure shall be equal to one and one half times the maximum
allowable working pressure, except for locomotive boilers, in which case it shall be one and one quarter times the
maximum allowable working pressure.
7.6.3.7 Low Water Fuel Cut offs. All automatically fired steam or vapor boilers, excepting boilers having a constant
attention who has no other duties while the boiler Is in operation, shall be equipped with an automatic low water
fuel cut off and/or water feeding device so constructed that the water inlet valve cannot feed water into the boiler
through the float chamber, and so located as to automatically cut off the fuel supply and/or supply requisite feed
water when the surface of the wall falls to the lowest safe water line. This point should be not lower than the
bottom of the water glass. Such a fuel or feed water control device may attached direct to a boiler or to the tapped
openings provided for attaching a water glass direct to the boiler, provided that such connections from the boiler
are non-ferrous tees or Ys not less than 12.7 mm diameter piper size between the blur and the water glass so that
the water glass is attached direct and as close as possible to the boiler; the straightway tapping of the Y or tee to
take the water glass fittings, the side outlet of the Y or the tee to take the fuel cut off or water feeding device. The
ends of all nipples shall be reamed to full size diameter. Designs embodying a float and float bowl shall have a
vertical straight away valve drain piper at the lowest point in the water equalizing piper connections by which the
bowl and equalizing pipe can be flushed and the device tested.
7.6.3.8 Safety Appliances. No person shall remove or tamper with any safety gadgets or components
prescribed by these rules except for the purpose of making repairs. The resetting of safety gadgets or components shall
be done in the presence of an authorized representative of the government agency concerned.
7.6.3.10 Location of Blow-offs. The discharge of safety valves, blow-off pipes and other outlets shall be located
so as to prevent injury to personnel or avoid making a nuisance to the surrounding vicinity.
7.6.3.11 Underground Installations. Where necessary to install a vessel underground, it shall be enclosed in a
concrete or brick pit with a removable cover so that inspection of the entire shell and heads of the vessel can be
made.
7.6.3.12 Supports. Each unfired pressure vessel shall be supported by masonry or structural supports of
sufficient strength and rigidity to safely support the vessel and its contents. There shall be no vibration in
either the vessel or its connecting piping.
7.6.3.14 Electric Steam Generators. All appliances required for electric steam generators shall be attached in
accordance with the rules.
Reference:
Philippine Mechanical Code
CASE STUDY NO. 3
-------------
-------------
Presented to the
College of Engineering
University of the East - Caloocan
-------------