SLD HV Protection (Rev. E).

vsd

LEGEND
Busbar - I 132 kV, 50 Hz 1600A 40kA -1s
MARSHALLING PROTECTION CONTROL + SYNCHR. SYMBOL DESCRIPTION
KIOSK PANEL PANEL SURGE ARRESTER
from VT from VT
Busbar - II T15-17 T25-27
CIRCUIT BREAKER
X X
V/V INDUCTIVE VOLTAGE
X TRANSFORMER
X
-Q1 -Q2 Hz/Hz
DISCONNECTING SWITCH
X X

X X EARTHING SWITCH
25 25
DISCONNECTING SWITCH
Areva WITH EARTHING SWITCH
KAVS 100
-T1 T5 P1
CURRENT TRANSFORMER
X X
2400-1200-600/1A, 60/30/15 VA, 0.2Fs5
X LINE TRAP
2400-1200-600/1A, 60/30/15 VA, 5P20
79C C 21 DISTANCE RELAIS
2400-1200-600/1A, 60/30/15 VA, 5P20
Areva 50 INST. OVERCURRENT RELAY
X X MICOM
2400/1A, 30 VA, 5P20
21 P442 51 OVERCURRENT RELAY IDMT

2400/1A, 30 VA, 5P20 50N INST. E/F O/C RELAY


A
X
P2 50BF BREAKER FAILURE RELAY

Areva TEST BLOCK


-Q0 GL 312 MW
1600 A C C
A AMMETER

V VOLTMETER
X X 50/51 MVAr
50N/51N 50BF
MW MEGA WATT METER
-Q9
Areva Areva Hz FREQUENCY METER
-Q8 MICOM MICOM
P122 P821 PF
MVAr MEGA VAr METER
to to
87B 87B X X X PF POWER FACTOR METER
CL 0.5 30VA
-T6 T7 ACTIVE / REACTIVE ENERGY
132.000 110 110 Areva MWhr
V 74TC1 MVAhr METER (IMPORT / EXPORT)
3 3 3 MVAX 31
CL 0.2M 30VA
74TC
TRIP CIRCUIT SUPERVISION
Areva RELAIS
74TC2
MVAX 31
VSS V
C COMMUNICATION INTERFACE
Areva
94 94 TRIPPING RELAIS
MVAJ 10
79 AUTO RECLOSE RELAY
Areva
94
-LT MVAJ 10 VSS VOLTAGE SWITCH SELECTOR

to PLC (Power Line Carrier)

-F1

132 kV OHL -1

Revision Date Init Date Project Name -


B Initial Release 11.12.08 HB Single Line Diagram HV Protection
08.10.08
Hans
Berchtenbreiter 132 kV; 50Hz HUBCO Pakistan +
C Revised Version 02.04.09 HB

D Revised Version 28.04.09 HB Detail: Feder Concept Diagram Project No. Drawing No. Page
PE4-AUG
E Revised Version 16.09.09 HB 5300162 11.99233-0473 1/3
SLD HV Protection (Rev. E).vsd

LEGEND
Busbar - I 132 kV, 50 Hz 1600A 40kA -1s
DESCRIPTION
SYMBOL
MARSHALLING PROTECTION CONTROL METERING
KIOSK PANEL PANEL BOARD SURGE ARRESTER

Busbar - II CIRCUIT BREAKER

INDUCTIVE VOLTAGE
X X X TRANSFORMER
-Q1 -Q2 DISCONNECTING SWITCH
X X X

EARTHING SWITCH
X X X
DISCONNECTING SWITCH
CL 0.2M 30VA WITH EARTHING SWITCH
-T52 C C
132.000 110
V
-T1 T6 P1 3 3 CURRENT TRANSFORMER

400/1A, 30 VA, 0.2Fs5


X X 50/51 LINE TRAP
50BF
50N/51N
400/1A, 30 VA, 0.2Fs5
21 DISTANCE RELAIS
Areva Areva
MICOM MICOM
400/1A, 30 VA, 5P20
P821 50 INST. OVERCURRENT RELAY
P122
X X
400/1A, 30 VA, 5P20 A 51 OVERCURRENT RELAY IDMT

2400/1A, 30 VA, 5P20 50N INST. E/F O/C RELAY


X X 50BF
2400/1A, 30 VA, 5P20 BREAKER FAILURE RELAY
X X PF

P2 MWhr TEST BLOCK


P1 MVAhr
A AMMETER
-T11 400/1A, 30 VA, 0.2Fs5
Areva
For WAPDA P2 Areva
74TC1 87T MICOM V VOLTMETER
Metering MVAX 31
CL 0.2M 30VA P631
-T51 MW MEGA WATT METER
132.000 110
V
3 3
Areva
Areva 74TC2 Hz FREQUENCY METER
MVAX 31
-Q0 GL 312
1600 A
MVAr MEGA VAr METER

X X PF POWER FACTOR METER

MWhr ACTIVE / REACTIVE ENERGY


MVAhr METER (IMPORT / EXPORT)
-Q9 Areva
94 TRIP CIRCUIT SUPERVISION
MVAJ 10 74TC
-Q8 RELAIS
Areva
94 C COMMUNICATION INTERFACE
MVAJ 10

Areva
94 TRIPPING RELAIS
94
MVAJ 10
79 AUTO RECLOSE RELAY
-F1
VSS VOLTAGE SWITCH SELECTOR

70 MVA from VTs


YNd5 BB1 T15-17
132/15 kV
Uk=14%
BB2 T25-27
to
to
15kV CT
87B BB1
87B BB2

TO 15kV SWITCHGEAR

Revision Date Init Date Project Name -


B Initial Release 11.12.08 HB Single Line Diagram - HV Protection
08.10.08
Hans
Berchtenbreiter 132 kV; 50Hz HUBCO Pakistan +
C Revised Version 02.04.09 HB

D Revised Version 28.04.09 HB Detail: Step Up Transformer Concept Diagram Project No. Drawing No. Page
PE4-AUG
E Revised Version 16.09.09 HB 5300162 11.99233-0473 2/3
SLD HV Protection (Rev. E).vsd

Busbar - I 132 kV, 50 Hz 1600A 40kA -1s LEGEND


MARSHALLING PROTECTION CONTROL
SYMBOL DESCRIPTION
KIOSK PANEL PANEL
SURGE ARRESTER
Busbar - II
CIRCUIT BREAKER

V
V
INDUCTIVE VOLTAGE

110
110

3
3
-Q9 TRANSFORMER
-Q9

-T16 T17

-T26 T27

110
110

3
3
DISCONNECTING SWITCH
Areva
94

132.000
132.000
MVAJ 10

3
3
EARTHING SWITCH
-Q8 -Q8 Areva DISCONNECTING SWITCH
94
-T1 T5 P1 MVAJ 10

CL 0.5

CL 0.5

CL 0.5

CL 0.5
WITH EARTHING SWITCH

30VA

30VA

30VA

30VA
X X X
2400-1200-600/1A, 60/30/15 VA, 0.2Fs5 CURRENT TRANSFORMER
Areva
2400-1200-600/1A, 60/30/15 VA, 5P20 74TC1
MVTP 31 LINE TRAP

2400-1200-600/1A, 60/30/15 VA, 5P20


A
Areva 21 DISTANCE RELAIS
74TC2
MVTP 31
X X X
2400/1A, 60 VA, 5P20 50 INST. OVERCURRENT RELAY

2400/1A, 60 VA, 5P20 X X Areva VSS 51 OVERCURRENT RELAY IDMT


50/51
C MICOM
50N/51N
P2 P122 V
50N INST. E/F O/C RELAY
X X Areva
50BF C 50BF BREAKER FAILURE RELAY
MICOM
P821
X X X TEST BLOCK

X X VSS A AMMETER
C
Areva V V VOLTMETER
-Q0 GL 312
1600 A MFAC34
87B BB1 MW MEGA WATT METER
MVTP
Hz FREQUENCY METER

X X MVAr MEGA VAr METER

PF POWER FACTOR METER

MWhr ACTIVE / REACTIVE ENERGY


MVAhr METER (IMPORT / EXPORT)
X X TRIP CIRCUIT SUPERVISION
74TC
MFAC34 RELAIS
87B BB2
MVTP
C COMMUNICATION INTERFACE
X X C 94 TRIPPING RELAIS

79 AUTO RECLOSE RELAY

VSS VOLTAGE SWITCH SELECTOR

to CT CT
PF Step up OHL
1-n 1-n

Revision Date Init Date Project Name -


B Initial Release 11.12.08 HB Single Line Diagram - HV Protection
08.10.08
Hans
Berchtenbreiter 132kV; 50Hz HUBCO Pakistan +
C Revised Version 02.04.09 HB

D Revised Version 28.04.09 HB Detail: Bus Coupler Concept Diagram Project No. Drawing No. Page
PE4-AUG
E Revised Version 16.09.09 HB 5300162 11.99233-0473 3/3