Calculate Size of Inverter for following Electrical Load .Calculate Size of Ba ery Bank and decide Connection of Ba ery.
Temp. C Factor
80 1.00
70 1.04
60 1.11
50 1.19
40 1.30
30 1.40
20 1.59
Calculation:
Total Load of Ba ery Bank= (Total Load x Backup Capacity) / Ba ery Bank Volt
Total Load of Ba ery Bank=(380 x 2) / 24 Amp Hr
Total Load of Ba ery Bank= 32.66 Amp Hr
Temperature Correction Factor for 46C (Tp)=1
Size of Ba ery Bank=[ (Load) x (1+LF) x (1+Ag) x Tp] / [n x DOD] Amp/Hr
Size of Ba ery Bank= (32.66 x (1+20%) x (1+20%) x 1) / (90% x 50%)
Size of Ba ery Bank= 101.3 Amp/Hr
Series Connection:
Series congurations will add the voltage of the two ba eries but keep the amperage rating (Amp Hours) same.
Condition-I :
Selection of Ba ery for Voltage = Volt of Each Ba ery <= Volt of Ba ery Bank
Selection of Ba ery for Voltage =12< 24
Condition-I is O.K
No of Ba ery for Voltage = Volt of Ba ery Bank / Volt of Each Ba ery
No of Ba ery for Voltage =24/12 = 2 Nos
Condition-II :
Selection of Ba ery for Amp Hr = Amp Hr of Ba ery Bank <= Amp Hr of Each Ba ery
Selection of Ba ery for Amp Hr =3<=120
Condition-II is O.K
We can use Series Connection for Ba ery & No of Ba ery required 2 Nos
In Parallel connection, the current rating will increase but the voltage will be the same.
More the number of ba eries more will be the amp/hour. Two ba eries will produce twice the amp/hour of a single ba ery.
Condition-I :
Selection of Ba ery for Amp Hr = Amp Hr of Ba ery Bank / Amp Hr of Each Ba ery <=1
Selection of Ba ery for Amp Hr =101/120 = 0.84=1 Nos
Condition-I is O.K
Condition-II :
Selection of Ba ery for Voltage = Volt of Ba ery Bank = Volt of Each Ba ery
Condition-II :Selection of Ba ery for Voltage for Amp Hr = 24<=12
Condition-II is Not Full Fill
We cannot use Parallel Connection for Ba ery as per our requirement But If We do Practically It is Possible and it will give more
Hours of back
(h ps://electricalnotes.les.wordpress.com/2015/10/parallel_ba ery_cong.jpg)Series-Parallel Connection:
Connecting the ba eries up in series will increase both the voltage and the run time.
Condition-I :
Selection of Ba ery for Amp Hr = Amp Hr of Each Ba ery <= Amp Hr of Ba ery Bank
Selection of Ba ery for Amp Hr =120<=101
Condition-I is Not Full Fill
Condition-II :
Selection of Ba ery for Voltage = Volt of Each Ba ery <= Volt of Ba ery Bank
Selection of Ba ery for Voltage = 12<=24
Condition-II is OK
We cannot use Parallel Connection for Ba ery
Series Connection:
Selection of Ba ery for Voltage = Volt of Each Ba ery <= Volt of Ba ery Bank
Selection of Ba ery for Voltage =12< 24
Condition-I is O.K
No of Ba ery for Voltage = Volt of Ba ery Bank / Volt of Each Ba ery
No of Ba ery for Voltage =24/12 = 2 Nos
Condition-II :
Selection of Ba ery for Amp Hr = Amp Hr of Ba ery Bank <= Amp Hr of Each Ba ery
Selection of Ba ery for Amp Hr =3<=60
Condition-II is Not Full Fill
We can use Series Connection for Ba ery
Parallel Conguration
Condition-I :
Selection of Ba ery for Amp Hr = Amp Hr of Ba ery Bank / Amp Hr of Each Ba ery <=1
Selection of Ba ery for Amp Hr =101/60 = 1.63=1 Nos
Condition-I is O.K
Condition-II :
Selection of Ba ery for Voltage = Volt of Ba ery Bank = Volt of Each Ba ery
Condition-II :Selection of Ba ery for Voltage for Amp Hr = 24=12
Condition-II is Not Full Fill
We cannot use Parallel Connection for Ba ery as per our requirement.
Series-Parallel Connection:
Condition-I :
Selection of Ba ery for Amp Hr = Amp Hr of Each Ba ery <= Amp Hr of Ba ery Bank
Selection of Ba ery for Amp Hr =120<=60
Condition-I is OK
No of Ba ery for Amp Hr = Amp Hr of Ba ery Bank / Amp Hr of Each Ba ery
No of Ba ery for Amp Hr = 120/60 =1.68 =2 Nos
Condition-II :
Selection of Ba ery for Voltage = Volt of Each Ba ery <= Volt of Ba ery Bank
Selection of Ba ery for Voltage = 12<=24
Condition-II is OK
No of Ba ery for Voltage = Volt of Ba ery Bank / Volt of Each Ba ery
No of Ba ery for Voltage = 24 / 12 =2 Nos
No of Ba ery Required = No of Ba ery Amp Hr x No of Ba ery for Voltage
No of Ba ery Required = 2 x 2= 4 Nos
We can use Series-Parallel Connection for Ba ery
(h ps://electricalnotes.les.wordpress.com/2015/10/series-parallel_ba ery_cong.jpg)
Summary:
Advertisements
About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical) from Gujarat University. He has more than 14 years
experience in Power Transmission-Power Distribution-Electrical energy theft detection-Electrical Maintenance-Electrical
Projects(Planning-Designing-coordination-Execution). He is Presently associate with one of the leading business group as a Deputy
Manager at Ahmedabad,India. He is Freelancer Programmer of Advance Excel and design useful Excel Sheets of Electrical
Engineering as per IS,NEC,IEC,IEEE codes. He is technical Author for "Electrical Mirror" and "Electrical India" Magazines. He is
Technical Blogger and Familiar with English, Hindi, Gujarati, French languages. He wants to Share his experience & knowledge and
help technical enthusiasts to nd suitable solutions and updating themselves on various Engineering Topics.