COMMISSIONING INSTRUCTIONS
INDUSTRIAL- AND COOLING WATER
3.6 Industrial- and cooling water
3.6.1 Water quality requirements
In order for the individual components to function reliably and to avoid
damage to the cooling circuit, it is essential that good water quality be
guaranteed.
+ Water type: fresh water
+ Flow temperature max. 25°C / 77°F
ANALYSIS
total - hardness <11°dH
carbonate - hardness <8°dH
non-carbonate - hardness <3°dH
pH-value =68
electrical conductivity < 2500 pSicm
pKs 8.2 <3 mmol
pKs 4.3 < 25 mmol
iron content Fe < 0,2 mg/i
manganese content Min < 0,05 mg/l
calcium content Ca < 400 mg/i
magnesia content Mg < 50 mg/l
sodium content Na < 200 mg/i
chloride content CI < 250 mg/l
sulphate content SO4 < 240 mg/
nitrate content NOS. < 50 mg/l
free carbon dioxide CO2 < 10 mg/l
soluble organic carbon C < 1,7 mg/l
sediments after 0.5 h < 0,1 mil
Edition 08/06 §-338 DEZ GHOMROUD. 3-26