TransformerSequenceCircuitModel
X3
IY0 ZH0 (+/-) ZX0
Y1
Y2 * H0 X0
IN
N H1
C S X
* IY0 ZY0
IC0 X1 X
* PolarizingCurrent
X2 N
H2
(a)Autotransformerwithdeltatertiary (b)Zerosequencecircuit
SinglePhaseTesting
TBranchModel
2
ThreephaseAutotransformer
PositiveSequenceImpedanceTesting
ZHX1 ZHY1
ThreephaseAutotransformer
ZeroSequenceImpedanceTesting
ZHX0 ZHY0
EffectofCoreTypeon
ZeroSequenceImpedance
EffectofCoreTypeon
ZeroSequenceImpedance
PhantomTertiary
EffectofCoreTypeon
ZeroSequenceImpedance
TBranchModel
ZY0 mayvary0.5to1.0times
positivesequencemeasurement
RefertoIEEEStandard
C57.12.90 2010forzero
sequenceimpedancetesting
ImpedancesforDifferent
WindingArrangements
WindingConfiguration PositiveSequence PositiveSequence
Impedance Impedance
H X H Y X Y H X Y
1 CoreTVLVHV 10.6 29.0 14.4 12.6 2.00 16.4
2 CoreLVTVHV 10.2 8.4 11.4 3.6 6.6 4.8
3 CoreLVHVTV 10.4 39.7 70.3 10.1 20.5 49.8
Allimpedancesarein%on0.6*280MVAbaseatratedwindingvoltage.ZBase =kV2/MVA,
ZW =ZBase xZ%/100,HVR regulatingwinding
280MVAAutotransformer
ZeroSequenceCurrentsforSingleG
GroundFaultonHVandLV
SCCase Winding HV(kA) LV(kA) TV(kA)
Configuration Line Series Line Common Line Winding
winding winding
280MVAAutotransformer
Determiningk0
Perunit
Current
ZeroSequenceTBranchModel
RelativeAmpsinThreeWinding
YYDTransformers
Autotransformer Conventional
ApplicationCriteriaforPolarization
HighSideFault LowSideFault
Delta 1 1
Neutral / /
FieldApplicationStudy
UtilityA UtilityB Both
Totalunitsinsurvey 57 28 85
#(%)withnegativehighsidebranch
0 0 0
impedance
BuriedorNonloadedTertiary LoadedTertiary
Mitigation
AlternativetoNeutralCurrentPolarization
Useequivalentdeltatertiarypolarizationcurrentifdeltacts
arenotavailable.
NeutralandLowSideCts HighandLowSideCts
Mitigation TransformerDesign
Deltatertiarycurrentreversalis
eliminatedbyavariednumberof
designschangingtherelative
impedancebetweenwindings.
Example:placingthetertiary
betweentheseriesandcommon
windings.
Effectsontransformersfirstand
operatingcostsareconsidered.
Specifiedbysomeutilities
Neutralcurrentmaystillreverse
asitisdependentonVX/VH ratio
forhighsidefault
Mitigation
[Compensated]PolarizingVoltage
ZeroandNegativesequencevoltagesarefarmore
reliablepolarizationmethodsifsensitivityisnotan
issue.
Thisisparticularlytrueinapplicationswheremutual
couplingaffectsthereliabilityofbothzerosequence
voltageandcurrentpolarizationmethodsandnegative
sequencevoltagepolarizationneedstobeused.
Microprocessortechnologymethodshavebeen
developedthatreliablycompensatezeroandnegative
sequencepolarizingvoltageswiththerespectiveline
zeroornegativesequencecurrenttoaddress
sensitivityissues
Mitigation
[Compensated]PolarizingVoltage
Zerosequencevoltagecompensatedwithzerosequencecurrent
Conclusions
Voltagepolarizationandimpedancecompensatedvoltage
polarizationarerecommendedasfirstchoices.
Reliablepolarizationcurrentcangenerallybeobtainedfromthe
deltatertiarywinding.
Thereareafewexceptionswherezerosequencesource
impedanceisverysmallanddoesnotallowitsuse.
Schemesinvolvingtheneutralandlinectsareavailabletoprovide
aproportionalquantitywhentertiarywindingsarenotprovided
withcts.
Eachapplicationshouldbereviewedwithsystemchanges.
Polarizationcurrentfromtheneutralctisnotgenerallyreliable
and,therefore,notrecommendedwherealternativesare
available.
Usingtheneutralctconnectedtolinectswithanauxiliary
transformermayverywellbesuitable(above).
Conclusions
Accuratezerosequencetestingisdesiredfor
developmentoftheTbranchmodel.
Differentwindingconfigurationscaneliminate
thenegativeimpedance.
Thepossibleextracosts,firstandevaluated,
shouldbeconsidered
Differentwindingconfigurationscanmovethe
negativeimpedancetothehighvoltageside.
PossiblefortransformerswithhighVH/VX turns
ratios(e.g.345/34.5kV).