TheNegativeBranchImpedanceinthe

TransformerSequenceCircuitModel

ElmoPrice Krzysztof Kulasek GaryKobet


ABBInc. ABBInc. TennesseeValleyAuthority
Introduction
H3 Y3

X3
IY0 ZH0 (+/-) ZX0
Y1
Y2 * H0 X0
IN
N H1
C S X
* IY0 ZY0
IC0 X1 X
* PolarizingCurrent
X2 N

H2
(a)Autotransformerwithdeltatertiary (b)Zerosequencecircuit

Commonassumption:IN andIY0 donotchangedirectionsfor


faultsoneithersideofthetransformer,thereforeagood
polarizingquantity
Currentreversalsoccurduetoaverysmallornegativelow
voltage(X)sidebranchimpedance
Introduction
Aspectsoftransformerdesignthataffectthe
positiveandzerosequenceTbranch
impedancemodel
ThedevelopmentandeffectoftheTbranch
modelonpolarizingcurrentreversal.
Asurveyautotransformerapplicationsfrom
twoutilities
Discussmitigation
Makerecommendations
LeakageImpedance
ParametersAffecting
LeakageImpedance
N * I DH DX t H t X
Z HX 2.48 *10 6 * f * * *( d HX ) * K R [%]
e * hW 2 3
t H t X d HX
KR 1
* hW
WindingPlacementaffects
onLeakageImpedance
ImpedanceTesting

SinglePhaseTesting
TBranchModel

2
ThreephaseAutotransformer
PositiveSequenceImpedanceTesting

ZHX1 ZHY1
ThreephaseAutotransformer
ZeroSequenceImpedanceTesting

ZHX0 ZHY0
EffectofCoreTypeon
ZeroSequenceImpedance
EffectofCoreTypeon
ZeroSequenceImpedance
PhantomTertiary
EffectofCoreTypeon
ZeroSequenceImpedance
TBranchModel

ZY0 mayvary0.5to1.0times
positivesequencemeasurement
RefertoIEEEStandard
C57.12.90 2010forzero
sequenceimpedancetesting
ImpedancesforDifferent
WindingArrangements
WindingConfiguration PositiveSequence PositiveSequence
Impedance Impedance
H X H Y X Y H X Y
1 CoreTVLVHV 10.6 29.0 14.4 12.6 2.00 16.4
2 CoreLVTVHV 10.2 8.4 11.4 3.6 6.6 4.8
3 CoreLVHVTV 10.4 39.7 70.3 10.1 20.5 49.8
Allimpedancesarein%on0.6*280MVAbaseatratedwindingvoltage.ZBase =kV2/MVA,
ZW =ZBase xZ%/100,HVR regulatingwinding

280MVAAutotransformer
ZeroSequenceCurrentsforSingleG
GroundFaultonHVandLV
SCCase Winding HV(kA) LV(kA) TV(kA)
Configuration Line Series Line Common Line Winding
winding winding

1 fault 1 1.558 1.558 3.734 2.176 0.00 0.24


on HV
2 2.804 2.804 2.42 0.384 0.00 11.93
3 3.51 3.51 5.69 2.183 0.00 7.271

1 fault 1 1.82 1.82 7.69 5.87 0.00 9.844


on LV
2 1.132 1.132 4.957 3.826 0.00 6.625
3 2.64 2.64 5.01 2.365 0.00 3.53

280MVAAutotransformer
Determiningk0

Perunit
Current

ZeroSequenceTBranchModel
RelativeAmpsinThreeWinding
YYDTransformers

Autotransformer Conventional
ApplicationCriteriaforPolarization

HighSideFault LowSideFault

Delta 1 1

Neutral / /
FieldApplicationStudy
UtilityA UtilityB Both

Totalunitsinsurvey 57 28 85

#(%)withnegativehighsidebranch
0 0 0
impedance

# (%) with negative low side branch 42 17 60


impedance (72%) (61%) (71%)
# (%)notsuitablefortertiarycurrent
1(2%) 0 1(1%)
polarization,k0>1
#(%)notsuitableforneutralcurrent 38 10 48
polarization,k0 >VX/VH (67%) (36%) (56%)
Summaryofautotransformerapplicationdata
FieldApplicationStudy
Autotransformersaredesigned,unlessotherwisespecified,
withtheirwindingconfigurationbuildfromcoresuchthat
negativelowvoltagebranchimpedanceisrathercommon
occurringin71%ofthecasesstudied.
Thenegativeimpedancesaregenerallysmallenoughsuch
thatthelowvoltagesourceimpedanceovercomesthe
effectofthetransformersnegativelowvoltagebranch
impedancemakingtheuseofthedeltatertiarysuitablefor
99%ofthecasesstudied.
Thetransformersneutralcurrentisnotsuitableasa
polarizingsource in56%ofthecases.
Thesenumberswillvarywithtransformerdesignand
likewisefromutilitytoutilitythatusethem
FieldApplicationStudy
UtilityA UtilityB
Mostapplicationsinvolving Mostapplicationsinvolving
newertechnologyusedvoltage newertechnologyusedvoltage
polarizing polarizing
Tertiarycurrentpolarizingwas Tertiarycurrentpolarizingwas
usedmostlyforlegacyproducts usedwheredualpolarization
whereavailable (usingbothvoltageandcurrent)
Neutralcurrentpolarizingwas wasdesired.
notused Polarizingcurrentderivedfrom
highandlowvoltagelinect
connectionswasusedinone
application.
Neutralcurrentpolarizingwas
usedinsomecaseswheretertiary
currentwasnotavailableand
therewerenoapplicationissues.
Mitigation
AlternativetoNeutralCurrentPolarization
Usedeltatertiarypolarizationcurrentifctsareavailable.

BuriedorNonloadedTertiary LoadedTertiary
Mitigation
AlternativetoNeutralCurrentPolarization
Useequivalentdeltatertiarypolarizationcurrentifdeltacts
arenotavailable.

NeutralandLowSideCts HighandLowSideCts
Mitigation TransformerDesign
Deltatertiarycurrentreversalis
eliminatedbyavariednumberof
designschangingtherelative
impedancebetweenwindings.
Example:placingthetertiary
betweentheseriesandcommon
windings.
Effectsontransformersfirstand
operatingcostsareconsidered.
Specifiedbysomeutilities
Neutralcurrentmaystillreverse
asitisdependentonVX/VH ratio
forhighsidefault
Mitigation
[Compensated]PolarizingVoltage
ZeroandNegativesequencevoltagesarefarmore
reliablepolarizationmethodsifsensitivityisnotan
issue.
Thisisparticularlytrueinapplicationswheremutual
couplingaffectsthereliabilityofbothzerosequence
voltageandcurrentpolarizationmethodsandnegative
sequencevoltagepolarizationneedstobeused.
Microprocessortechnologymethodshavebeen
developedthatreliablycompensatezeroandnegative
sequencepolarizingvoltageswiththerespectiveline
zeroornegativesequencecurrenttoaddress
sensitivityissues
Mitigation
[Compensated]PolarizingVoltage
Zerosequencevoltagecompensatedwithzerosequencecurrent
Conclusions
Voltagepolarizationandimpedancecompensatedvoltage
polarizationarerecommendedasfirstchoices.
Reliablepolarizationcurrentcangenerallybeobtainedfromthe
deltatertiarywinding.
Thereareafewexceptionswherezerosequencesource
impedanceisverysmallanddoesnotallowitsuse.
Schemesinvolvingtheneutralandlinectsareavailabletoprovide
aproportionalquantitywhentertiarywindingsarenotprovided
withcts.
Eachapplicationshouldbereviewedwithsystemchanges.
Polarizationcurrentfromtheneutralctisnotgenerallyreliable
and,therefore,notrecommendedwherealternativesare
available.
Usingtheneutralctconnectedtolinectswithanauxiliary
transformermayverywellbesuitable(above).
Conclusions
Accuratezerosequencetestingisdesiredfor
developmentoftheTbranchmodel.
Differentwindingconfigurationscaneliminate
thenegativeimpedance.
Thepossibleextracosts,firstandevaluated,
shouldbeconsidered
Differentwindingconfigurationscanmovethe
negativeimpedancetothehighvoltageside.
PossiblefortransformerswithhighVH/VX turns
ratios(e.g.345/34.5kV).