CHAPTER 9:

901: VENTS REQUIRED 905.2 Where vents connected to a horizontal drainage pipe, such vent
pipe connection shall have its invert pipe taken off above the drainage
Each plumbing fixture trap, except as otherwise provided in this Code, center line of such pipe downstream of the trap being served.
shall be protected against siphonage and back-pressure. Air circulation
shall be assured throughout all parts of excreta drainage system by 905.3 Unless prohibited by structural conditions, each vent shall rise
means of vent pipes installed in accordance with the requirements of vertically to a point not less than 152mm above the highest flood level
this chapter and as required in this Code. rim of the fixtures serve before offsetting horizontally to join the vent
stack or stack vent and the bottom connection shall be installed with
902: VENTS NOT REQUIRED approve drainage of fittings and installed with proper grade to the
horizontal drain.
902.1 Where permitted by the administrative authority, vent piping may
be omitted on an interceptor when such interceptor acts as primary 905.4 All vent pipes shall extend undiminished in size above the roof of
settling tank and discharges through a horizontal indirect waste pipe shall be reconnected with the soil or waste stack vent of proper size at
into a secondary interceptor. The second interceptor shall be tapped a point below the roof, the vent through the roof (VSTR) shall be
and vented. increased one pipe above the reconnection of point of stack vent and
horizontal vent.
902.2 Traps serving sinks which are part of the equipment of bars, soda
fountains and counters need not to be vented when the location and 905.5 The vent opening from the soil or waste pipe. Excepts for water
construction of such bars, soda fountains and counters is to make it closets and similar fixture, shall not be below the weir or trap.
impossible to do so. When such conditions exist, said sink shall be
discharged by means of approved indirect waste pipe into a floor sink or 905.6 Two fixtures mat be served by common vertical vent pipe when
other approved type receptor. each such fixture waste separately into an approved double branch
fitting having inlet opening at the same level.
903: MATERIALS
906: VENT TERMINATION
903.1 Vent pipes shall be cast iron, ductile cast iron, galvanized steel,
galvanized wrought iron, lead, copper, brass, Schedule 40, ABS, DWV, 906.1 Each vent pipe or stack through roof shall extend its flashing all
Series 1000, PVC or other approved materials having a smooth and around and the stack vent shall terminate vertically not less than 15mm
uniform bore except: above the roof nor less than 0.3m from any vertical surface nearby.

903.1.1 No galvanized wrought or galvanized steel pipe shall be used 906.2 Each vent opening shall terminate not less than 3m from, or at
underground and shall be kept at least 15cm above ground. least 0.9m above any openable window, door opening, air intake or
vent shaft, nor less than 0.9m away from any lot line, alley and street
903.1.2 Horizontal and vertical vent lines and vent stacks shall be boundary lines.
copper, cast iron, galvanized wrought iron or polyvinyl chloride pipes.
906.3 Vent pipe shall be extended separately or combined, of full
903.2 Vent fittings shall be cast iron, ductile cast iron, galvanized steel, required size, not less than 15cm above the roof or fire wall. Flagpoling
galvanized wrought iron, lead, copper, brass, ABS, PVC or other of vents is prohibited except where the roof is used for purposes other
approved materials except no galvanized malleable iron of galvanized than weather protection.
steel shall be buried underground but shall be kept at least 152 mm
above finish ground level. 906.4 Vertical vent pipes for outdoor installations except to at least 3m
distant to any part of the roof that is used for other purposes and shall
903.3 Changes in direction of vent pipe shall be made by the not extent no less than 2.1m above such roof and shall securely stay.
appropriate use of approve fittings and no such pipe shall be strained or
bent. Burred end shall be reamed to the full bore of the pipe. 906.5 Joints at the roof around stack vent pipes shall made watertight
by the use of approved flashing material and installation.
904: SIZE OF VENTS
907: VENT STACKS AND RELIEF VENTS
904.1The sizes of vent piping shall be determined from its length and
the total number of fixture units connected thereto, as set forth in Table 907.1 Each soil or waste stack which extents two or more stories
7 5 of this Code. In addition, the drainage piping of each building and above the building drain shall be served by a parallel vent stack which
each connections to a public sewer or a private sewage disposal shall extend undiminished in size from its upper terminal at the roof and
system shall be vented by means of one or more vent pipes, the connect to the soil or waste stack at ground level and at the fifth floor
aggregate cross-sectional area of which not less the that of the largest levels with a yoke vent at a point below the horizontal soil or waste
required building sewer, as determined from Table 7 8, page 88. branch connection to the stack and nearby vent stack above the same
floor to provide a relief vent. The size of the yoke vent shall not be less
Exception: when connected to a common building sewer, the drainage than in diameter than either soil stack or vent stack, whichever is
piping of two or more buildings located on the same lot under one smaller.
ownership may be vented by means of piping size in accordance with
Table 7 5 provided the aggregate cross-sectional area of all the vents 907.2 The yoke vent connection with the vent stack shall be placed not
is not less than that of the largest required common building sewer. less than 1m above the floor level, and the yoke vent connection with
the drainage stack shall be by means of a wye branch fitting placed
904.2 The length of horizontal portion of a vent may exceed one-third of below the fixture branch serving that floor.
the total length of vertical and horizontal portions as limited by Table 7
5 provided the vent to one pipe size larger for its entire length. 908: VENTS NOT REQUIRED

905: VENT PIPE GRADES AND CONNECTIONS 908.1 Where permitted by the administrative authority, vent piping
may be omitted on an interceptor when such interceptor acts as primary
905.1 All horizontal vent and branch pipes shall be free from drops or settling tank and discharges through a horizontal indirect waste pipe
sag and each vent shall be graded and connected to drip back by into a secondary interceptor. The second interceptor shall be tapped
gravity to the drainage pipe it serves. and vented.

MV, 4B
908.2 Traps serving sinks which are part of the equipment of bars, 908.2 Traps serving sinks which are part of the equipment of bars,
soda fountains and counters need not to be vented when the location soda fountains and counters need not to be vented when the location
and construction of such bars, soda fountains and counters is to make it and construction of such bars, soda fountains and counters is to make it
impossible to do so. When such conditions exist, said sink shall be impossible to do so. When such conditions exist, said sink shall be
discharged by means of approved indirect waste pipe into a floor sink or discharged by means of approved indirect waste pipe into a floor sink or
other approved type receptor. other approved type receptor.

909: MATERIALS 909: MATERIALS

909.1 Vent pipes shall be cast iron, ductile cast iron, galvanized steel, 909.1 Vent pipes shall be cast iron, ductile cast iron, galvanized steel,
galvanized wrought iron, lead, copper, brass, Schedule 40, ABS, DWV, galvanized wrought iron, lead, copper, brass, Schedule 40, ABS, DWV,
Series 1000, PVC or other approved materials having a smooth and Series 1000, PVC or other approved materials having a smooth and
uniform bore except: uniform bore except:

909.1.1 No galvanized wrought or galvanized steel pipe shall be used 909.1.1 No galvanized wrought or galvanized steel pipe shall be used
underground and shall be kept at least 152mm above ground. underground and shall be kept at least 152mm above ground.

910: Size of Vents

910.1 The sizes of vent piping shall be determined from its length
and the total number of fixture units connected thereto, as set forth in
Table 7 5 of this Code. In addition, the drainage piping of each 910: Size of Vents
building and each connections to a public sewer or a private sewage
disposal system shall be vented by means of one or more vent pipes, 910.1 The sizes of vent piping shall be determined from its length
the aggregate cross-sectional area of which not less than that of the and the total number of fixture units connected thereto, as set forth in
largest required building sewer, as determined from Table 7 8, page Table 7 5 of this Code. In addition, the drainage piping of each
88. building and each connections to a public sewer or a private sewage
disposal system shall be vented by means of one or more vent pipes,
910.2 No more than one-third of the total length, per Table 7 5 of the aggregate cross-sectional area of which not less than that of the
any minimum sized vent shall be installed in a horizontal position. largest required building sewer, as determined from Table 7 8, page
88.

910.2 No more than one-third of the total length, per Table 7 5 of


any minimum sized vent shall be installed in a horizontal position.