Вы находитесь на странице: 1из 40

Transformer EcoDesign

Regulation No 548/2014
Overview & Clarification of the
Regulation
g
The history of transformers

Transformers have been in use since 1886


Built by William Stanley (working for Westinghouse)
Used in Great Barrington, Massachusetts
The design concept remains the same
Copper and iron remain the core materials
Steel composition has changed over the years
Cooling methods have changed
How a transformer is designed has changed
Transformers all around us

Transformers are an every day essential component in the efficient


distribution of electricity
Without a transformer you dont get LV!
They exist in a wide various of sizes
There are 100,000s installed in the UK
Power stations
Grid
G id substations
b t ti
DNO overhead line
Wind farms
.....
HV/MV power substation to the MV/LV distribution
substation
b t ti
Power station

NETWORK
400 kV

NETWORK
NETWORK
O
132 kV
Power station Step-up Substation Substation 400 /132 kV 33 kV
33/400 kV

Substation 132/33 kV

NETWORK
33 kV

NETWORK
11 kV

NETWORK
11 kV
NETWORK Substation 33/11 kV
240V

NETWORK11 NETWORK
kV 433 V
Client

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 4
Transformer windings
indings

> HV Higher Voltage Winding


Does not relate to any specific voltage band
> LV Lower
L V
Voltage
lt Wi
Winding
di
Does not relate to any voltage band, on an 11kV to 3.3kV step down
transformer the L.V. winding would be in the HV range

Confidential Property of Schneider Electric

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 5
Principle operation of a transformer
A transformer works on the principle of electromagnetic induction.
If an alternating flux produced by an alternating current in one coil links
with a secondary coil, then an electro-motive force (e.m.f.) is induced in
the second coil, the magnitude of which is given by Faradays Law of
Electromagnetic Induction
Magnetic Flux
C
Core

Ip Is

Vp
Ep Tp Ts Es Vs

Primary Coil Secondary Coil

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 6
Transformer losses

> By the nature of the operation of a transformer, there is a heat loss


created, due to current flow in conductors and a magnetic flux
circulating around a magnetic core core.
> The heat loss given off is in effect the transformer waste.
> For a specific transformer rating rating, the higher the loss = the less efficient
the transformer
> Transformers are inherentlyy efficient transformers usually y around 99%
plus
> A Copper Development Association survey estimated Distribution
T
Transformer f Losses
L representt 25% off the
th network
t k losses
l in
i the
th UK
system
> Under peak load conditions these amount to 1300MW equivalent to the
output of one large power station.
> Transformer efficiencyy can be improved p by
y design,
g , byy reducing g the
losses
Confidential Property of Schneider Electric

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 7
Transformers affected are.....

Package
P k
Distribution substations Cast resin Power

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 8
TRANSFORMER ECODESIGN
REGULATION NO 548/2014

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 9
Summary
EcoDesign regulation imposes in EU the maximum level of losses for
transformers Placed On The Market or Put Into Service after 1.7.2015.
It has been published in the Official Journal of the European Union and came
into force on June 11th 2014.
After
Aft 1.7.2015
1 7 2015 it will
ill nott be
b possible
ibl to
t place
l on th
the market
k t transformers
t f nott
fulfilling the minimum requirements
p
Manufacturers are responsible to apply
pp y the law
Running frame contracts signed before June 11th 2014 can go on until the end
date even with deliveries after July 1, 2015.
UK G Govermentt has
h apointed i t d th
the NNational
ti lM
Measurementt Offi
Office (NMO) as the th
Verification Authority for the Eco Regulation for the UK
NMO Position Paper p dated 18th December 2014 p provides clarification of the
Regulation with regard to defining Placed on the Market and Putting Into
Service

Official EU documents at :
http://eur-lex.europa.eu/legal-content/EN/TXT/?uri=OJ:JOL_2014_152_R_0001
Rational : European Union commitments
EU is implementing
p g its 20-20-20 p
program
g by
y 2020 :
Reduction of 20 % of greenhouse gases emission
Reduction of 20% of energy consumption
Reach 20% from renewable energy in total production

Power Transformer losses represents approx. 2.5% of total EU energy consumption

By 2020, savings of approximately 16TWh/year are achievable with new regulation

EcoDesign aims two major objectives on the Transformer product:


Reduce electrical losses (1st step in 2015/ 2nd step in 2021)
Clarify and make more visible indication of performance
Harmonisation of maximum losses levels in European Union
Efficiency request on MPT for the 1st time
EcoDesign impact on Transformers

Oil Distribution & Cast Resin Transformers :


New Defined Maximum level of losses for Oil Distribution and Cast Resin Dry Type
Transformers up to and including 3150kVA
Reduced Losses compared to transformers currently supplied

Medium Power and Large Power Transformers:


Defined Level of Peak Efficiency (Mix of load losses and no load losses) for
transformers >3150kVA

Special transformers are not impacted by this regulation

Significant increase of Equipment cost and weights

Reduction of operation cost (Total cost of ownership optimized)


NMO Postion Paper 18/12/2014
Position Paper Issued to Clarify Definitions of the Eco Regulation,
specifically regarding Placed
Placed on the Market
Market and Putting into Service.

Excerpts from the Position Paper (grey text) :-

The Regulation establishes ecodesign requirements for placing on the market or putting into
service power Power Transformers with a minimum power rating of 1 kVA used in 50 Hz
electricity transmission and distribution networks or for industrial applications. The Regulation is
only applicable to Power Transformers purchased after the entry into force of the Regulation.

Placing on the Market is defined as making a product available for the first time on the
Community market with a view to its distribution or use within the Community, whether for
reward or free of charge and irrespective of the selling technique.

Putting into Service means the first use of a product for its intended purpose by an end-user in
the Community;

Entry into force of the Regulations is 10 June 2014


NMO Postion Paper 18/12/2014 (continued)
Excerpts from the Position Paper (grey text) :-

Ready for use Power Transformers placed on the market before 1 July 2015 or purchased (as
described in recital four of the regulation) prior to 10 June 2014, can remain in the distribution
chain (e
(e.g.
g in the stocks of DNOs) regardless of the scheduled changes in the legislative
requirements. Power Transformers placed on the market before 1 July 2015 can be sold to the
end-user and can be energised after 1 July 2015 without regard to this regulation, provided they
are readyy for use.

Products are ready for use if they can be used as intended without the insertion of additional
parts; if all parts from which they are to be assembled are placed on the market by one person
only; if they only need to be mounted or plugged in; or they are placed on the market without the
parts that are usually procured separately and inserted for the intended use (e.g. a cable for
electric supply).

In Summary :-
Transformers manufactured prior to the 1st July 2015 - i.e. Placed on The Market do not have
to meet the ECO Regulation loss levels
These non ECO Regulation loss level transformers can be sold/supplied to customers after the
1st July 2015 provided they are Placed On The Market prior to 1st July 2015
These transformers can be installed, energised, commissioned etc after the 1st July 2015 without
regard to the Eco regulation
Transformer Losses

Transformer Losses fall into two major categories:-

1) No Load Loss, also known as Iron Loss

2) Load Loss also known as Copper Loss

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 15
Transformer Losses
1) No Load Loss or Iron Loss
Iron Loss arises within the magnetic core of a transformer and is due
to the energy consumed in hysteresis and eddy currents within the
material as it is taken through its alternating cycles of magnetisation
((UK 50 times per
p second i.e. 50Hz))
The magnetic core of a transformer is made up of thin laminations of
core steel which have a coating of insulation to reduce the eddy current
build up within the complete core.

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 16
Transformer Losses
No Load Loss or Iron Loss (continued)
The characteristics of heat output (loss) from core material varies based on the
grade of material used and the working flux density

There are two ways of reducing Iron Loss in a Transformer :-


1) Reduce flux density by increasing the cross sectional area of the magnetic core.
2) By using higher grades of core steel to reduce the watts/kg for a particular
flux density.

The No Load Loss of a Transformer is a Constant Loss ( does not vary with load)

Either way or a combination of both means additional cost in the core

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 17
Transformer Losses
Load Loss or Copper Loss
Load loss arises mainly as a result of the resistance of the transformer
windings, that is the I2R loss produced by the flow of load current within the
windings.
Increasing the copper cross sectional area within a transformer winding has
the effect of reducing the current density of the winding - this has the effect of
reducing the I2R losses.
The load loss of a transformer varies to the square of the load. i.e. at 50% load
the actual load losses are 0.5 x 0.5 = 25% of the full load loss.

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 18
Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 19
Loss Options of a Transformer
Within the UK there has been no usable standards that stipulate the loss levels that
g of transformers.
should be achieved for various ratings
The level of losses are created by the manufacturers and can be very different for
the same transformer rating.
e.g. For Schneider Electric Leeds, we used to offer various levels of losses
1) Industrial Loss
High Losses = Low First Cost = Increased Running Costs
2) Low Loss
Low to Medium Losses = Medium First Cost = Reduced Running Costs
3) Extra Low Loss
Low Losses = Increased First Cost = Further Reduced Running Costs

The Introduction of the ECO Regulation now imposes


Maximum Loss Levels / Peak Efficiency Index levels

Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 20
European Loss References
The Eco Regulation uses letter references for various loss levels which is common
practice in Europe but not often used in UK taken from EN50464

No Load Losses examples are Ao, Bo, Co Load Loss examples are Ak, Bk, Ck
Schneider Electric - B.U. Energy LoB Transformer EcoDesign Regulation A new Standard for Transformer 06/2014 21
EcoDesign
g Impact
p on 3 Ph Oil Distribution Transformers
Loss levels to be applied (reference of MV 24 kV and LV 1.1 kV)
Rated Tier 1 : from 1st July
y Tier 2 : from 1st July
y
power (kVA) 2015 2021
No Load Loss (W) Load Loss (W) No Load Loss (W) Load Loss (W)
25 70 (Ao) 900 (Ck) 63 (Ao-10%) 600 (Ak)
50 90 (Ao) 1100 (Ck) 81 (Ao-10%) 750 (Ak)
100 145 (Ao) 1750 (Ck) 130 (Ao-10%) 1250 (Ak)
160 210 (Ao) 2350 (Ck) 189 (Ao-10%) 1750 (Ak)
250 300 ((Ao)) 3250 ((Ck)) 270 ((Ao-10%)) 2350 ((Ak))
315 360 (Ao) 3900 (Ck) 324 (Ao-10%) 2800 (Ak)
400 430 (Ao) 4600 (Ck) 387 (Ao-10%) 3250 (Ak)
500 510 (Ao) 5500 (Ck) 459 (Ao-10%) 3900 (Ak)
630 600 (Ao) 6500 (Ck) 540 (Ao
(Ao-10%)
10%) 4600 (Ak)
800 650 (Ao) 8400 (Ck) 585 (Ao-10%) 6000 (Ak)
1000 770 (Ao) 10500 (Ck) 693 (Ao-10%) 7600 (Ak)
1250 950 (Ao) 11000 (Bk) 855 (Ao-10%) 9500 (Ak)
1600 1200 (Ao) 14000 (Bk) 1080 (Ao-10%) 12000 (Ak)
2000 1450 (Ao) 18000 (Bk) 1305 (Ao-10%) 15000 (Ak)
2500 1750 (Ao) 22000 (Bk) 1575 (Ao-10%) 18500 (Ak)
3150 2200 (Ao) 27500 (Bk) 1980 (Ao-10%) 23000 (Ak)

Tolerances
Measured parameter Before With new regulation

Load losses +15% Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


EcoDesign
g Impact
p on 3 Ph Dry
y Type
yp Distribution Transformers
Loss levels to be applied (reference of MV 24 kV and LV 1.1 kV)

Rated
R d Tier 1 : from 1st July Tier 2 : from 1st July
power (kVA) 2015 2021
No Load Loss (W) Load Loss (W) No Load Loss (W) Load Loss (W)
50 200 (Ao) 1700 (Bk) 180 (Ao-10%)
(Ao 10%) 1500 (Ak)
100 280 (Ao) 2050 (Bk) 252 (Ao-10%) 1800 (Ak)
160 400 (Ao) 2900 (Bk) 360 (Ao-10%) 2600 (Ak)
250 520 ((Ao)) 3800(Bk)
( ) 468 ((Ao-10%)) 3400 ((Ak))
400 750 (Ao) 5500 (Bk) 675 (Ao-10%) 4500 (Ak)
630 1100 (Ao) 7600 (Bk) 990 (Ao-10%) 7100 (Ak)
800 1300 (Ao) 8000 (Ak) 1170 (Ao-10%) 8000 (Ak)
1000 1550 (A(Ao)) 9000 (Ak) 1395 (A(Ao-10%)
10%) 9000 (Ak)
1250 1800 (Ao) 11000 (Ak) 1620 (Ao-10%) 11000 (Ak)
1600 2200 (Ao) 13000 (Ak) 1980 (Ao-10%) 13000 (Ak)
2000 2600 (Ao) 16000 (Ak) 2340 (Ao
(Ao-10%)
10%) 16000 (Ak)
2500 3100 (Ao) 19000 (Ak) 2790 (Ao-10%) 19000 (Ak)
3150 3800 (Ao) 22000 (Ak) 3420 (Ao-10%) 22000 (Ak)

Tolerances
T l
Measured parameter Before With new regulation

Load losses +15% Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


EcoDesign impact on MPTs and LPTs (above 3150kVA)
No loss levels imposed but minimum PEI (Peak efficiency Index)
PEI corresponds to :
Tier 1: start on 1.7.2015
the maximum efficiency of the transformer Tier 2: start on 1.7.2021
Ratio between the no load losses and losses 99.800

99.750

99.700

99.650

PEI (%)
99.600
T1 T2
99.550

99.500

99.450
0 20 40 60 80 100 120
Rated Power (MVA)
Tolerances
Measured parameter Before With new regulation

Load losses +15%


1 % Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


Required electrical power required by the
cooling system for no load operatoin No requirement declared value +5% max
EcoDesign
g impact
p on Liquid
q Immersed MPT and LPT
(Peak Efficiency Index values)

99.800
Sr PEI T1 PEI T2
(MVA) (%) (%) 99.750

4 99 465
99,465 99 532
99,532
99.700
5 99,483 99,548
99.650

PEI (%)
6,3 99,510 99,571

8 99,535 99,593 99.600

T1 T2
10 99,560 99,615 99.550
,
12,5 99,588
, 99,640
,
99.500
16 99,615 99,663
99.450
20 99,639 99,684
0 20 40 60 80 100 120
25 99,657 99,700 Rated Power (MVA)

31,5 99,671 99,712

40 99,684 99,724

50 99,696 99,734

63 99,709 99,745 Tier 1: start on 1.7.2015


80 99 723
99,723 99 758
99,758
Tier 2: start on 1.7.2021
100 99,737 99,770
EcoDesign
g Impact
p on Dry
y Type
yp Medium Power Transformers

Rated Tier 1 : from 1st July


y Tier 2 : from 1st July
y
power (kVA) 2015 2021
Minimum Peak Efficiency Index (PEI) %
3150<Sr4000
3150 < Sr 4000 99 348
99.348 99 382
99.382
5000 99.354 99.387
6300 99.356 99.389
8000 99 357
99.357 99 390
99.390
10000 99.357 99.390

Tolerances

Measured parameter Before With new regulation

Load losses +15% Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


EcoDesign
g Impact
p on Dry
y Type
yp Large
g Power Transformers
Rated Tier 1 : from 1st July Tier 2 : from 1st July
power
p 2015 2021
(MVA) Minimum Peak Efficiency Index (PEI) %
4 99.158 99.225
5 99 200
99.200 99 265
99.265
6.3 99.242 99.303
8 99.298 99.356
10 99 330
99.330 99 385
99.385
12.5 99.370 99.422
16 99.416 99.464
20 99.468
99 68 99.513
99 5 3
31.5 99.521 99.564
40 99.567 99.592
50 99.585 99.623
63 99.590 99.626

Tolerances
Measured parameter Before With new regulation

Load losses +15% Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


EcoDesign Impact on 3 Phase Pole Mount Transformers
Loss levels to be applied (reference of MV 24 kV and LV 1.1 kV)

Rated Tier 1 : from 1st July Tier 2 : from 1st July


power (kVA) 2015 2021
No Load Loss (W) Load Loss (W) No Load Loss (W) Load Loss (W)
25 70 (Ao) 900 (Ck) 70 (Ao) 725 (Bk)
50 90 (Ao) 1100 (Ck) 90 (Ao) 875 (Bk)
100 145 (Ao) 1750 (Ck) 145 (Ao) 1475 (Bk)
160 300 (Co) 3102 (Ck+32%) 270 (Co-10%) 3102 (Ck+32%)
200
00 356 (C
(Co)) 2750
50 (C
(Ck)) 310
3 0 ((Bo)) 2333
333 ((Bk))
250 425 (Co) 3250 (Ck) 360 (Bo) 2750 (Bk)
315 520 (Co) 3900 (Ck) 440 (Bo) 3250 (Bk)

Tolerances
Measured parameter Before With new regulation

Load losses +15%


15% Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


EcoDesign impact on Oil Distribution and Cast
R i T
Resin Transformers
f ( 3 150kVA)
Loss levels to be applied (reference of MV 24 kV and LV 1.1 kV)
Tier 2 : from 01.07.2021
Maximum Loss Levels Rated power Tier 1 : from 01.07.2015
(Values subject to further validation)

25, 50 and 100 kVA AoCk AoBk


Pole mounted 160 kVA CoCk+32% Co-10% Ck+32%
200, 250 and 315 kVA CoCk BoBk

1000kVA
1000kVA AoCk
ODT
>1000kVA : AoBk
Ao-10% Ak
630kVA AoBk
CRT
> 630kVA AoAk

Tolerances
Measured parameter Before With new regulation

Load losses +15% Zero Positive Tolerance

No load losses +15% Zero Positive Tolerance


Required electrical power required by the
cooling system for no load operatoin No requirement declared value
EcoDesign impact on ODTs and CRTs ( 3 150kVA)
ODT and CRT not covered by reference transformers :
(additional losses allowed compared to standard losses ranges)
Impact on no load losses Impact on load losses
Other requirement
compared to standard losses table compared to standard losses table

MV insulation level 24 kV
LV insulation level > 1.1 kV
+10% +10%

MV insulation level = 36 kV
LV insulation level 1.1 kV
+15% +10%

MV insulation level = 36 kV
LV insulation level > 1.1 kV
+20% +15%

Dual voltage on MV winding


and No impact No impact
85% power limitation on higher MV voltage
Dual voltage on MV winding
and No impact No impact
85% p
power limitation on higher
g LV voltage
g
Dual voltage on one winding
(MV or LV) +15% +10%
and full power on all voltages considered
Dual voltage on both windings
(MV and LV)
+20% +20%

Transformers with tappings for operation while being


+20%
energized +5%
(reduced to +10% in 01-07-2021)
(such as Voltage Regulation Distribution Transformers)
Limitation of scope of appliance 1/2
Out of scope
Instrument transformers, for instruments, meters, relays and other similar apparatus
Transformers with low-voltage windings specifically designed for use with
rectifiers to provide a DC supply;
Transformers specifically designed to be directly connected to a furnace;
Transformers specifically designed for offshore applications and floating offshore
applications
Transformers specially designed for emergency installations
Transformers and auto-transformers specifically designed for railway feeding
systems
t
Earthing or grounding transformers : Three-phase transformers intended to provide a
neutral point for system grounding purposes
Traction transformers mounted on rolling stock: Transformers connected to an AC
or DC contact line, directly or through a converter, used in fixed installations of railway
applications;
Starting
St ti transformers,
t f specifically designed for
f starting
t ti three-phase
th h induction
i d ti
motors so as to eliminate supply voltage dips
Limitation of scope of appliance 2/2
Out of scope
Testing transformers: specifically designed to be used in a circuit to produce a specific
voltage or current for the purpose of testing electrical equipment
Welding
g transformers: specifically
p y designed
g for use in arc welding
g equipment
q p or
resistance welding equipment
Transformers specifically designed for explosion-proof and underground
miningg applications
Transformers specifically designed for deep water (submerged) applications
Medium Voltage (MV) to Medium Voltage (MV) interface transformers up to 5
MVA
Large power transformers1 where it is demonstrated that for a particular
application, technically feasible alternatives are not available to meet the
minimum efficiency requirements set out by this Regulation;
Large power transformers1 which are like for like replacements in the same
physical location/installation for existing large power transformers, where this
replacement cannot be achieved without entailing disproportionate costs
associated to their transportation and/or installation
Comparisons
p to Currently
y Supplied
pp Liquid
q Immersed
Distribuition Transformers 1000kVA
Comparisons
p to Currently
y Supplied
pp Liquid
q Immersed
Distribuition Transformers 2000kVA
Comparisons
p to Currently
y Supplied
pp Liquid
q Immersed
Distribuition Transformers 3150kVA
Typical
yp Dimensions
Oil Filled Free Breathing Ground Mounted Cable Connected
ECOLOSSTRANSFORMERS
Basicdimensionsandweightsoftransformers
Basic dimensions and weights of transformers
TransformerRating Length(mm) Width(mm) Height(mm) TotalWeight

L W H WithOil(kg)

315kVA 1720 960 1710 1710


500kVA 1720 1120 1710 2500
800kVA 1720 1080 1710 3300
1000kVA 1720 1320 1710 3650
1250kVA 1720 1210 1710 4050
1500kVA
k 1720 1370 1710 4450
1600kVA 1720 1370 1710 4500
2000kVA 1720 1450 1850 5000

INDUSTRIAL LOSS TRANSFORMERS


INDUSTRIALLOSSTRANSFORMERS
Basicdimensionsandweightsoftransformers
TransformerRating Length(mm) Width(mm) Height(mm) TotalWeight

L W H WithOil(kg)

315kVA 1680 1085 1700 1840


500kVA 1680 1170 1700 2130
800kVA 1740 1245 1700 2730
1000kVA 1740 1310 1700 2970
1250kVA
k 1740 1550 1830 3630
1500kVA 1740 1830 1830 3970
1600kVA 1740 1910 1830 4150
2000kVA 1740 1880 1960 4860
Comparisons
p to Currently
y Supplied
pp Liquid
q Immersed
Distribuition Transformers 3150kVA
Typical Price Indications
Oil Filled Free Breathing Ground Mounted Cable Connected

Industrial
Low Loss Extra Low Loss ECO Loss
Losses

500kVA
8,500 10,500 12,000 11,250
1000kVA
10,750 14,750 16,250 15,000
1500kVA
13,750 17,250 18,250 20,000
2000kVA
16,250 22,500 23,750 24,500
Comparisons
p to Currently
y Supplied
pp Cast Resin
Distribuition Transformers 1600kVA
Typical
yp Dimensions
Cast Resin Ground Mounted Cable Connected IP00
ECOLOSSTRANSFORMERS
Basicdimensionsandweightsoftransformers
Basic dimensions and weights of transformers
TransformerRating Length(mm) Width(mm) Height(mm) TotalWeight
L W H (kg)

250kVA 1270 680 1340 1140


315kVA 1290 800 1410 1260
400kVA 1320 800 1510 1460
500kVA 1370 800 1530 1640
630kVA 1410 800 1660 1880
800kVA 1530 800 1720 2400
1000kVA 1620 950 1880 3020
1250kVA 1700 950 1940 3600
1600kVA 1830 950 2140 4180

STANDARD LOSS TRANSFORMERS


STANDARDLOSSTRANSFORMERS
Basicdimensionsandweightsoftransformers
TransformerRating Length(mm) Width(mm) Height(mm) TotalWeight
L W H (kg)

250kVA 1180 650 1200 960


315kVA 1220 795 1350 1100
400kVA 1375 795 1330 1210
500kVA 1370 795 1430 1540
630kVA 1450 820 1530 1640
800kVA 1510 835 1670 2040
1000kVA 1525 945 1675 2125
1250kVA 1605 945 1860 2580
1600kVA 1665 945 2035 3210
Comparisons
p to Currently
y Supplied
pp Cast Resin
Distribuition Transformers 1600kVA
Typical Price Indications
Cast Resin Ground Mounted Cable Connected IP00

Standard
ECO Loss
Losses

250kVA
4,395 5,994
500kVA
5,787 7,349
1000kVA
8,071 11,611
1250kVA
9,031 13,424
1600kVA
10 710
10,710 16 281
16,281
S
Summary
ECO Regulation came into force as of 11th June 2014

Two Stages of implemtation 2015 and 2021

Maximum Loss Levels / Minimum Efficiencyy levels defined

Implications on Price and Dimensions / Weights

Transformers (except for those that are exempt) will be required to be ECO
compliant after 1st July 2015

Transfomers Placed
Placed On The Market
Market prior to 1st July 2015 can be sold
sold,
supplied, energised after the 1st July 2015 without regard to the Regulation
Make the most of your energy
energy

Вам также может понравиться