Вы находитесь на странице: 1из 6

APPENDIX B

FLOOD-RESISTANT FOUNDATIONS FOR RESIDENTIAL


BUILDINGS WITH WOOD OR LIGHT-STEEL FRAMED WALLS
[The information contained in this appendix is not part of this American National Standard (ANSI) and has not been processed in
accordance with ANSIs requirements for an ANS. As such, this appendix may contain material that has not been subjected to pub-
lic review or a consensus process. In addition, it does not contain requirements necessary for conformance to this standard.]

B1 General. buildings must be assembled from rectangular elements


B1.1 Scope. Placing a residential building in a Coastal High per Section 105 of ICC 600 Standard for Residential
Hazard Area (V Zone), Coastal A Zone or a Noncoastal A Zone Construction in High-Wind Regions.
landward of a Coastal A Zone is permitted on and anchored to a 4. The building has shearwalls per Tables 3.17A and 3.17B
flood-resistant foundation that is designed and constructed in or Tables A3.17A and A3.17B and Tables 3.17D and
accordance with FEMA 550 Recommended Residential Con- 3.17E of ANSI/AF&PA WFCM-2001 Wood Framed
struction for the Gulf Coast if the following conditions are met: Construction Manual for One- and Two-Family Dwell-
1. The building complies with ICC 600 Standard for Res- ings. Buildings constructed with cold-formed steel
idential Construction in High-Wind Regions. framed walls shall be permitted to have shearwall
lengths specified by Section E13.2 of AISI S230-07,
2. The building is one or two stories, constructed with Standard for Cold-Formed Steel Framing Prescriptive
wood or light-steel framed walls and floors. Building Method for One- and Two-Family Dwellings, if the
weights and loads are within the ranges specified in shearwall lengths are not less than those specified by
Appendix C of FEMA 550. Tables 3.17A and 3.17B or Tables A3.17A and A3.17B
3. The building is constructed with rectangular elements and Tables 3.17D and 3.17E of ANSI/AF&PA
and each element satisfies the dimensional limits WFCM-2001.
depicted in Figure B1 of this standard. Nonrectangular

Rectangular Element Dimensions

Roof pitch 3:12 (min) to 12:12 (max)


Eave overhang 2 feet (max)
1 story wall height 10 feet (max)
2 story wall height 20 feet (max)
Eave to ridge height 23 feet Max)
Endwall length 24 feet (min.) to 42 feet (max)
Sidewall length 28 feet (min)
For SI: 1 foot = 304.8 mm.
FIGURE B1
RANGE OF RECTANGULAR ELEMENT DIMENSIONS AND ROOF PITCHES

STANDARD FOR RESIDENTIAL CONSTRUCTION IN HIGH-WIND REGIONS2008 149


APPENDIX B

5. Where open style foundations per FEMA 550 Design B2.2. Girders shall be selected as follows.
Cases B, C, D or G are used, sheathing type adjustments
per WFCM Section 3.4.4.2.1 and Table 3.17D are per- Primary girder - Girders supporting any floor or roof
mitted only where the tabulated adjustment factor is framing perpendicular to the axis of the girder and resist-
greater than 1, resulting in greater shearwall lengths. ing reactions from shearwall segments shall be designed
as a primary girder. The maximum allowable primary
Exception: Use of tabulated adjustment factors less
girder spans for one-story homes are specified in Table
than 1 is permitted where girders and girder connec-
B1(1); maximum primary girders spans for two-story
tions to open foundations are designed to applicable
homes are specified in Table B1(2).
requirements of the International Building Code.
6. Open style foundations using concrete columns and Secondary girder - Girders supporting no floor or roof
grade beams per FEMA 550 Design Cases B, C, D and G framing oriented perpendicular to the axis of the girder
are constructed with primary, secondary and center floor and resisting reactions from shearwall segments may be
girders and connections in accordance with Section B2 designed as a secondary girder. Maximum spans for sec-
of this standard or designed to applicable requirements ondary girders for one-story homes shall be as specified
of the International Building Code. in Table B2(1); secondary girders for two-story homes
shall be as specified in Table B2(1).
7. Girder and girder connections for open style braced tim-
ber pile foundations (FEMA 550 Case A) shall be Center girder - Girders supporting only floor framing
designed as required by Section 305.4. oriented perpendicular to the axis of the girder and not
8. Design roof snow load is 20 psf (98 kg/m 2) or less supporting any roof loads or resisting any reactions from
shearwall segments may be designed as a center girder.
B1.2 Flood hazards areas. Flood hazard areas shall be estab- Center girders for one-story homes shall be as specified
lished by International Residential Code Table R301.2(1). in Table B3(1); center girders for two-story homes shall
B.2 Building/foundation interface. Where required by Sec- be as specified in Table B3(2).
tion C1.1, Item 6, floor girders and connections attaching the
elevated residential building to the flood-resistant foundation B.2.3 Girder spans. Primary girder spans may not exceed
shall be in accordance with Section B.2 of this standard. spans specified in Table B1(1) for single-story homes and
B1(2) for two-story homes. Secondary girders spans shall
B.2.1. Girders shall be considered primary, secondary or not exceed spans specified in Table B2(1) for single-story
center based on the supported loads. Girders for a rectangu- homes and B2(2) for two-story homes. Center girder spans
lar building element with conventional floor and roof fram- may not exceed spans specified in Table B3(1) for sin-
ing are shown in Figure B2. gle-story homes and B3(2) for two-story homes.

ROOF FRAMING
PERPENDICULAR TO ORIENTATION
RIDGE SHEAR PANELS
SEE WFCM TABLE 3.17A

PARALLEL TO
bles RIDGE SHEAR
See Ta 3(2) PANELS
B
B3(1) & SEE WFCM
TABLE 3.17B

CONCRETE
COLUMN
SEE
FEMA 550
S
SHEAR PANEL SEE PAN
TIE DOWN B2(1 TABLES B3 SPAN ES
)&B
2(2) TABL
B4 SEE & B1(2)
)
B1(1
CENTER GIRDER
(TYP)

SECONDARY GIRDER
(TYP) FLOOR JOIST PRIMARY GIRDER
ORIENTATION (TYP)

FIGURE B2
GIRDER IDENTIFICATION

150 STANDARD FOR RESIDENTIAL CONSTRUCTION IN HIGH-WIND REGIONS2008


APPENDIX B

TABLE B1(1)
PRIMARY GIRDER SPANS FOR ONE-STORY HOMES
(beam supporting gravity loads and shear reactions from wind loads parallel to ridge)b,c,d,e,f,g,h
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3 4

1.0 times WFCM 91 11 3 131


1.5 times WFCM 98 1110 139
2.0 times WFCM 100 122 14a
3.0 times WFCM 104 126 14a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Exceeds the 14 foot column spacing limit of the FEMA 550 foundation designs.
b. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
c. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased if the girder clear span does not exceed
the tabulated span minus 16 inches.
d. Girder spans are based on girders constructed with structural glued laminated softwood timbers with unfactored reference design values of: fiber bending stress
Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the gird-
ers are listed in Table 5A of the 2005 NDS, National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
e. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
f. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
g. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor, CM, of 0.8 was applied to Fb to address moisture content above
19 percent.
h. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.

TABLE B1(2)
PRIMARY GIRDER SPANS FOR TWO-STORY HOMES
(beam supporting gravity loads and shear reactions from wind loads parallel to ridge)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3 4

1.0 times WFCM 78 96 111


1.5 times WFCM 83 102 119
2.0 times WFCM 87 106 121
3.0 times WFCM 811 1010 125
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
b. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased provided the girder clear span does not
exceed the tabulated span minus 16 inches.
c. Girder spans are based on girders constructed with Structural Glued Laminated Softwood Timbers with an unfactored reference design values of: fiber bending
stress Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the
girders are listed in Table 5A of the 2005 NDS National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
d. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
e. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
f. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor CM of 0.8 was applied to Fb to address moisture content above
19 percent.
g. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.

STANDARD FOR RESIDENTIAL CONSTRUCTION IN HIGH-WIND REGIONS2008 151


APPENDIX B

TABLE B2(1)
SECONDARY GIRDER SPANS FOR ONE-STORY HOMESb,c,d,e,f,g,h
(beam supporting end wall and shear reactions from wind loads parallel to ridge)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3

1.0 times WFCM 121 14a


1.5 times WFCM 133 14a
2.0 times WFCM 140 14a
3.0 times WFCM 14a 14a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Exceeds the 14 foot column spacing limit of the FEMA 550 foundation designs.
b. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
c. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased provided the girder clear span does not
exceed the tabulated span minus 16 inches.
d. Girder spans are based on girders constructed with Structural Glued Laminated Softwood Timbers with an unfactored reference design values of: fiber bending
stress Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the
girders are listed in Table 5A of the 2005 NDS National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
e. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
f. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
g. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor CM of 0.8 was applied to Fb to address moisture content above 19
percent.
h. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.

TABLE B2(2)
SECONDARY GIRDER SPANS FOR TWO-STORY HOMESb,c,d,e,f,g,h
(beam supporting end wall and shear reactions from wind loads parallel to ridge)

MAXIMUM GIRDER SPAN


(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3 4

1.0 times WFCM 89 114 137


1.5 times WFCM 101 1211 14a
2.0 times WFCM 110 139 14a
3.0 times WFCM 1111 14a 14a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Exceeds the 14 foot column spacing limit of the FEMA 550 foundation designs.
b. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
c. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased provided the girder clear span does not
exceed the tabulated span minus 16 inches.
d. Girder spans are based on girders constructed with Structural Glued Laminated Softwood Timbers with an unfactored reference design values of: fiber bending
stress Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the
girders are listed in Table 5A of the 2005 NDS National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
e. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
f. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
g. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor CM of 0.8 was applied to Fb to address moisture content above
19 percent.
h. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.

152 STANDARD FOR RESIDENTIAL CONSTRUCTION IN HIGH-WIND REGIONS2008


APPENDIX B

TABLE B3(1)
CENTER GIRDER SPANS FOR TWO-STORY HOMESb,c,d,e,f,g,h
(beam supporting gravity loads from floor and interior walls only and no shear reactions)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
1 2 3

93 127 14a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Exceeds the 14 foot column spacing limit of the FEMA 550 foundation designs.
b. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
c. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased provided the girder clear span does not
exceed the tabulated span minus 16 inches.
d. Girder spans are based on girders constructed with Structural Glued Laminated Softwood Timbers with an unfactored reference design values of: fiber bending
stress Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the
girders are listed in Table 5A of the 2005 NDS National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
e. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
f. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
g. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor CM of 0.8 was applied to Fb to address moisture content above
19 percent.
h. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.

TABLE B3(2)
CENTER GIRDER SPANS FOR TWO-STORY HOMESa,b,c,d,e,f,g
(beam supporting gravity loads from floor and interior walls only and no shear reactions)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
1 2 3 4

714 97 116 131


For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
b. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased provided the girder clear span does not
exceed the tabulated span minus 16 inches.
c. Girder spans are based on girders constructed with Structural Glued Laminated Softwood Timbers with an unfactored reference design values of: fiber bending
stress Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the
girders are listed in Table 5A of the 2005 NDS National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
d. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
e. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
f. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor CM of 0.8 was applied to Fb to address moisture content above
19 percent.
g. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.

STANDARD FOR RESIDENTIAL CONSTRUCTION IN HIGH-WIND REGIONS2008 153


APPENDIX B

B.2.4 Horizontal shearwall connections. Horizontal shear (10.39 kN) for 10 foot (3048 mm) tall shear panels
connections between horizontal diaphragms and vertical [3,488 pounds (15.5 kN) for 8 foot (2438 mm) tall shear
shearwalls shall comply with Chapter 3 of ICC 600 Stan- panels). Tie-downs securing shear panels for two-story
dard for Residential Construction in High Wind Regions. homes shall have a working design load of 8,720 pounds
B.2.5 Vertical shearwall connections. Connections (38.79 kN) for 10-foot (3048 mm) tall shear panels
between shearwall hold-downs and primary floor girders [6,976 pounds (31 kN) for 8-foot (2438 mm) tall shear
shall be constructed as detailed in Figure B3. Connections panels).
between shearwall hold-downs and secondary floor girders B.2.5.3 Connections between primary, secondary and
shall be constructed as detailed in Figure B4. center girders and the reinforced columns of FEMA 550
B.2.5.1 Hold-downs securing shear panels for one-story open foundations shall be as detailed in FEMA 550. Col-
homes shall have a listed working allowable load of umn sizes may be increased up to 4 inches (102 mm) to
4,360 pounds (20,47 kN) for 10 foot (3048 mm) tall accommodate wider beams than those detailed in FEMA
shear panels [3,488 pounds (15.5 kN)for 8 foot (2438 550 if the 21/2 inch (64 mm) concrete cover for reinforc-
mm) tall shear panels]. Hold-downs securing shear pan- ing steel prescribed in FEMA 550 is maintained.
els for two-story homes shall have a working design B.2.5.4 Connections between FEMA 550 enclosed foun-
allowable load of 8,720 pounds (38.79 kN) for 10-foot dations (Design Cases E and F) shall be in accordance
(3048 mm) tall shear panels [6,976 pounds (31 kN) for with Section 305.2.3 of ICC-600 Standard for Residen-
8-foot (2438 mm) tall shear panels]. tial Construction in High Wind Regions.
B.2.5.2. Tie-downs securing shear panels for one-story
homes shall have a listed working load of 4,360 pounds

SHEAR PANEL
TIE DOWN

SHEAR
PANEL
TIE DOWN

FLOOR
JOIST
LAMINATED
TIMBER LAMINATED
(WITH SPACER TIMBER
FOR TIE DOWN (WITH SPACER
BOLT) FOR TIE
DOWN BOLT)

4 4 /8 PLATE
3
4 4 /8 PLATE
3

SHEAR PANEL TIE DOWN ROD SHEAR PANEL TIE DOWN ROD

For SI: 1 inch = 25.4 mm. For SI: 1 inch = 25.4 mm.
FIGURE B3 FIGURE B4
PRIMARY BEAM AND SHEAR PANEL SECONDARY BEAM AND SHEAR PANEL
TIE-DOWN CONNECTION DETAIL TIE-DOWN CONNECTION DETAIL

154 STANDARD FOR RESIDENTIAL CONSTRUCTION IN HIGH-WIND REGIONS2008

Вам также может понравиться