Академический Документы
Профессиональный Документы
Культура Документы
5. Where open style foundations per FEMA 550 Design B2.2. Girders shall be selected as follows.
Cases B, C, D or G are used, sheathing type adjustments
per WFCM Section 3.4.4.2.1 and Table 3.17D are per- Primary girder - Girders supporting any floor or roof
mitted only where the tabulated adjustment factor is framing perpendicular to the axis of the girder and resist-
greater than 1, resulting in greater shearwall lengths. ing reactions from shearwall segments shall be designed
as a primary girder. The maximum allowable primary
Exception: Use of tabulated adjustment factors less
girder spans for one-story homes are specified in Table
than 1 is permitted where girders and girder connec-
B1(1); maximum primary girders spans for two-story
tions to open foundations are designed to applicable
homes are specified in Table B1(2).
requirements of the International Building Code.
6. Open style foundations using concrete columns and Secondary girder - Girders supporting no floor or roof
grade beams per FEMA 550 Design Cases B, C, D and G framing oriented perpendicular to the axis of the girder
are constructed with primary, secondary and center floor and resisting reactions from shearwall segments may be
girders and connections in accordance with Section B2 designed as a secondary girder. Maximum spans for sec-
of this standard or designed to applicable requirements ondary girders for one-story homes shall be as specified
of the International Building Code. in Table B2(1); secondary girders for two-story homes
shall be as specified in Table B2(1).
7. Girder and girder connections for open style braced tim-
ber pile foundations (FEMA 550 Case A) shall be Center girder - Girders supporting only floor framing
designed as required by Section 305.4. oriented perpendicular to the axis of the girder and not
8. Design roof snow load is 20 psf (98 kg/m 2) or less supporting any roof loads or resisting any reactions from
shearwall segments may be designed as a center girder.
B1.2 Flood hazards areas. Flood hazard areas shall be estab- Center girders for one-story homes shall be as specified
lished by International Residential Code Table R301.2(1). in Table B3(1); center girders for two-story homes shall
B.2 Building/foundation interface. Where required by Sec- be as specified in Table B3(2).
tion C1.1, Item 6, floor girders and connections attaching the
elevated residential building to the flood-resistant foundation B.2.3 Girder spans. Primary girder spans may not exceed
shall be in accordance with Section B.2 of this standard. spans specified in Table B1(1) for single-story homes and
B1(2) for two-story homes. Secondary girders spans shall
B.2.1. Girders shall be considered primary, secondary or not exceed spans specified in Table B2(1) for single-story
center based on the supported loads. Girders for a rectangu- homes and B2(2) for two-story homes. Center girder spans
lar building element with conventional floor and roof fram- may not exceed spans specified in Table B3(1) for sin-
ing are shown in Figure B2. gle-story homes and B3(2) for two-story homes.
ROOF FRAMING
PERPENDICULAR TO ORIENTATION
RIDGE SHEAR PANELS
SEE WFCM TABLE 3.17A
PARALLEL TO
bles RIDGE SHEAR
See Ta 3(2) PANELS
B
B3(1) & SEE WFCM
TABLE 3.17B
CONCRETE
COLUMN
SEE
FEMA 550
S
SHEAR PANEL SEE PAN
TIE DOWN B2(1 TABLES B3 SPAN ES
)&B
2(2) TABL
B4 SEE & B1(2)
)
B1(1
CENTER GIRDER
(TYP)
SECONDARY GIRDER
(TYP) FLOOR JOIST PRIMARY GIRDER
ORIENTATION (TYP)
FIGURE B2
GIRDER IDENTIFICATION
TABLE B1(1)
PRIMARY GIRDER SPANS FOR ONE-STORY HOMES
(beam supporting gravity loads and shear reactions from wind loads parallel to ridge)b,c,d,e,f,g,h
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3 4
TABLE B1(2)
PRIMARY GIRDER SPANS FOR TWO-STORY HOMES
(beam supporting gravity loads and shear reactions from wind loads parallel to ridge)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3 4
TABLE B2(1)
SECONDARY GIRDER SPANS FOR ONE-STORY HOMESb,c,d,e,f,g,h
(beam supporting end wall and shear reactions from wind loads parallel to ridge)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
LENGTH OF SHEAR WALLS 2 3
TABLE B2(2)
SECONDARY GIRDER SPANS FOR TWO-STORY HOMESb,c,d,e,f,g,h
(beam supporting end wall and shear reactions from wind loads parallel to ridge)
TABLE B3(1)
CENTER GIRDER SPANS FOR TWO-STORY HOMESb,c,d,e,f,g,h
(beam supporting gravity loads from floor and interior walls only and no shear reactions)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
1 2 3
93 127 14a
For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm, 1 pound per square foot = 47.88 Pa, 1 pound per square inch = 6.895 kPa, 1 pound per lineal foot = 14.59 N/m.
a. Exceeds the 14 foot column spacing limit of the FEMA 550 foundation designs.
b. Girder spans are based on simply supported girders exposed to uniform gravity loads and point loads from shear panel reactions.
c. Girder spans are based on girder clear spans using 16 inch square columns. Spacings for larger columns can be increased provided the girder clear span does not
exceed the tabulated span minus 16 inches.
d. Girder spans are based on girders constructed with Structural Glued Laminated Softwood Timbers with an unfactored reference design values of: fiber bending
stress Fbx 2,800 psi, shear parallel to grain Fvx 300 psi, and Modulus of Elasticity Ex 2.1*106 psi (designated 28F-2.1E). Design values for members making up the
girders are listed in Table 5A of the 2005 NDS National Design Specification for Wood Construction (ANSI/AF&PA NDS-2005).
e. Girder spans are based on laminated timbers manufactured in a balanced layup (F bx- = Fbx+).
f. Members making up the girders shall be field assembled and fastened as directed by manufacturers literature. Where no literature is available, members may be
fastened by two rows of 1/2 inch through bolts located 24 inches on centers.
g. Load duration factors (CD) are as specified in ANSI/AF&PA NDS-2005. The load duration factor for live load equals 1.0; for wind loads, the load duration factor
equals1.6. And the load duration factor for dead loads equals 0.9. A wet service adjustment factor CM of 0.8 was applied to Fb to address moisture content above
19 percent.
h. Girder spans are based on shear panel reactions resulting from 10 foot tall shear panels loaded at 436 pounds/linear foot. The prescriptive girder designs shall not
be used for homes constructed with shear panels exposed to higher shear loads.
TABLE B3(2)
CENTER GIRDER SPANS FOR TWO-STORY HOMESa,b,c,d,e,f,g
(beam supporting gravity loads from floor and interior walls only and no shear reactions)
MAXIMUM GIRDER SPAN
(ctr to ctr column spacing in ft-in.)
Number of Members
13/4 by 117/8 structural glued laminated timber 28F-2.1E
1 2 3 4
B.2.4 Horizontal shearwall connections. Horizontal shear (10.39 kN) for 10 foot (3048 mm) tall shear panels
connections between horizontal diaphragms and vertical [3,488 pounds (15.5 kN) for 8 foot (2438 mm) tall shear
shearwalls shall comply with Chapter 3 of ICC 600 Stan- panels). Tie-downs securing shear panels for two-story
dard for Residential Construction in High Wind Regions. homes shall have a working design load of 8,720 pounds
B.2.5 Vertical shearwall connections. Connections (38.79 kN) for 10-foot (3048 mm) tall shear panels
between shearwall hold-downs and primary floor girders [6,976 pounds (31 kN) for 8-foot (2438 mm) tall shear
shall be constructed as detailed in Figure B3. Connections panels).
between shearwall hold-downs and secondary floor girders B.2.5.3 Connections between primary, secondary and
shall be constructed as detailed in Figure B4. center girders and the reinforced columns of FEMA 550
B.2.5.1 Hold-downs securing shear panels for one-story open foundations shall be as detailed in FEMA 550. Col-
homes shall have a listed working allowable load of umn sizes may be increased up to 4 inches (102 mm) to
4,360 pounds (20,47 kN) for 10 foot (3048 mm) tall accommodate wider beams than those detailed in FEMA
shear panels [3,488 pounds (15.5 kN)for 8 foot (2438 550 if the 21/2 inch (64 mm) concrete cover for reinforc-
mm) tall shear panels]. Hold-downs securing shear pan- ing steel prescribed in FEMA 550 is maintained.
els for two-story homes shall have a working design B.2.5.4 Connections between FEMA 550 enclosed foun-
allowable load of 8,720 pounds (38.79 kN) for 10-foot dations (Design Cases E and F) shall be in accordance
(3048 mm) tall shear panels [6,976 pounds (31 kN) for with Section 305.2.3 of ICC-600 Standard for Residen-
8-foot (2438 mm) tall shear panels]. tial Construction in High Wind Regions.
B.2.5.2. Tie-downs securing shear panels for one-story
homes shall have a listed working load of 4,360 pounds
SHEAR PANEL
TIE DOWN
SHEAR
PANEL
TIE DOWN
FLOOR
JOIST
LAMINATED
TIMBER LAMINATED
(WITH SPACER TIMBER
FOR TIE DOWN (WITH SPACER
BOLT) FOR TIE
DOWN BOLT)
4 4 /8 PLATE
3
4 4 /8 PLATE
3
SHEAR PANEL TIE DOWN ROD SHEAR PANEL TIE DOWN ROD
For SI: 1 inch = 25.4 mm. For SI: 1 inch = 25.4 mm.
FIGURE B3 FIGURE B4
PRIMARY BEAM AND SHEAR PANEL SECONDARY BEAM AND SHEAR PANEL
TIE-DOWN CONNECTION DETAIL TIE-DOWN CONNECTION DETAIL