New features of IA-NT sw V2.2.

1 Page 1 of 1

1. Available firmware, archives and documentation


Firmware
Mhx file
IA-NT-STD-2.2mhx
IA-NT-PWR-2.2mhx

Archives
Archives
IA-NT-STD-2.2.ail
IA-NT-PWR-2.2.ail
IA-NT-PWR-StarterKit-2.2.ail

Documentation
PDF files Description
NT
InteliATS NT STD-2.0-Reference Manual for InteliATS STD controller
Guide.pdf
NT
InteliATS NT PWR-2.0-Reference Manual for InteliATS PWR controller
Guide.pdf
InteliATS NT 2.2.1 New features.pdf List of new features for software update version 2.0

2. Main changes in IA-NT 2.2.1

Repairs
Ready To AMF output fixed
Logical binary output Ready To AMF behavior was modified.
This output is activated when the controller is in AUT mode and no Trip alarm is active or
unconfirmed. It remains active when the engine is running.

3. Main changes in IA-NT 2.2

New features
New binary output DualMainsFail has been added (PWR version only).
This output is activated when controller is used in dual mains application and both mains fail.
New binary output Ctrl HeartBeat has been added.
Output signalizes Watchdog Reset. In a healthy state it blinks at 500ms : 500ms rate. When
Watchdog Reset occurs, it stops blinking.
Change in Cascading wiring
It is not necessary to connect through binary input GenReadyToLoad with binary output Gen
Start/Stop when you want to use this controller as a Slave in cascading system. When binary
input MainsHealthy is configured all AMF and generator protections will be switched off and
binary input GenReadyTo Load will be internally connected through with binary output Gen
Start/Stop.

Repairs

InteliATS NT 2.2.1 New features / ComAp April 2014 / InteliATS NT 2.2.1New features.pdf

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 246 316 647
180 00 Prague 8 E-mail: info@comap.cz
t

alit
Qu

en

Czech Republic y Managem Internet: http://www.comap.cz


New features of IA-NT sw V2.2.1 Page 2 of 1

Problem with Emergency Stop


Problem with Emergency Stop has been fixed. Output Gen Start/Stop is deactivated immediately
when binary input Emergency Stop is activated.
New MCB and GCB feedback delay (STD version only).
Default delay has been changed to 2s.

4. Main changes in IA-NT STD 2.1.1

Repairs

Problem with battery undervoltage / overvoltage protection Problem with


battery voltage protection has been fixed.

5. Main changes in IA-NT STD 2.1

New features
New setpoint MCB Logic has been added.
The default value is CLOSE-OFF.
CLOSE-ON: The output is closed when the MCB is requested to be closed (normal, positive
logic).

CLOSE-OFF: The output is closed when the MCB is requested to be open (inverted, negative
logic).

6. Main changes in AI-NT STD/PWR 2.1

Repairs

Problem with MCB fail when mains failure


Problem with MCB fail when mains failure has been fixed.

Problem with Normally Close feedbacks


Problems with MCB and GCB feedbacks with negative logic (NC Normally Close) has been
fixed.

InteliATS NT 2.2.1 New features / ComAp April 2014 / InteliATS NT 2.2.1New features.pdf

Ap
om s.r.
C

o.

ComAp, spol. s r.o. Tel.: +420 246 012 111


Kundratka 2359/17 ISO 9001 Certified Fax: +420 246 316 647
180 00 Prague 8 E-mail: info@comap.cz
t

alit
Qu

en

Czech Republic y Managem Internet: http://www.comap.cz

Вам также может понравиться