Archives
Archives
IA-NT-STD-2.2.ail
IA-NT-PWR-2.2.ail
IA-NT-PWR-StarterKit-2.2.ail
Documentation
PDF files Description
NT
InteliATS NT STD-2.0-Reference Manual for InteliATS STD controller
Guide.pdf
NT
InteliATS NT PWR-2.0-Reference Manual for InteliATS PWR controller
Guide.pdf
InteliATS NT 2.2.1 New features.pdf List of new features for software update version 2.0
Repairs
Ready To AMF output fixed
Logical binary output Ready To AMF behavior was modified.
This output is activated when the controller is in AUT mode and no Trip alarm is active or
unconfirmed. It remains active when the engine is running.
New features
New binary output DualMainsFail has been added (PWR version only).
This output is activated when controller is used in dual mains application and both mains fail.
New binary output Ctrl HeartBeat has been added.
Output signalizes Watchdog Reset. In a healthy state it blinks at 500ms : 500ms rate. When
Watchdog Reset occurs, it stops blinking.
Change in Cascading wiring
It is not necessary to connect through binary input GenReadyToLoad with binary output Gen
Start/Stop when you want to use this controller as a Slave in cascading system. When binary
input MainsHealthy is configured all AMF and generator protections will be switched off and
binary input GenReadyTo Load will be internally connected through with binary output Gen
Start/Stop.
Repairs
InteliATS NT 2.2.1 New features / ComAp April 2014 / InteliATS NT 2.2.1New features.pdf
Ap
om s.r.
C
o.
alit
Qu
en
Repairs
New features
New setpoint MCB Logic has been added.
The default value is CLOSE-OFF.
CLOSE-ON: The output is closed when the MCB is requested to be closed (normal, positive
logic).
CLOSE-OFF: The output is closed when the MCB is requested to be open (inverted, negative
logic).
Repairs
InteliATS NT 2.2.1 New features / ComAp April 2014 / InteliATS NT 2.2.1New features.pdf