TOUCH VOLTAGE & GROUND CURRENT CALCULATION

:Three Phase System: :Single Phas


Line-to-Neutral Volts (Vn) 230 Volts
Line 1 Calculated Load (A1) 50 Amp
Line 2 Calculated Load (A2) 60 Amp
Line 3 Calculated Load (A3) 60 Amp
Service Neutral Impedance Z1 0.1
Ground Resistance (3-point method) R 100

RESULTS RESU
Neutral/Ground Parallel Resistance 0.10
Line 1 Resistance 4.600
Line 2 Resistance 3.83
Line 3 Resistance 3.83

Line 1 - Actual Load 49.58 Amp


Line 1 Watts 11307.72 Watts
Line 1 - Loads Operates at Volts 228.07 Volts

Line 2 - Actual Load 59.74 Amp


Line 2 Watts 13678.53 Watts
Line 2 - Loads Operates at Volts 228.99 Volts

Line 3 - Actual Load 59.74 Amp


Line 3 Watts 13678.53 Watts
Line 3 - Loads Operates at Volts 228.99 Volts

Parallel Neutral/Ground Path 69.89 Amp


Neutral Watts 487.98 Watt
Neutral Current 69.82 Amp
Ground Current 0.07 Amp
Touch Voltage from Metal Parts to Earth 6.98 Volts

DOW RESTRICTED - For internal use only


Jignesh.Parmar jiguparmar@yahoo.com www.electricalnotes.wordpress.com

:Single Phase System:


Circuit Voltage 230 Volts
Circuit Ampere 16 Amp
Load Resistance 14.38

Ground Resistance 1
Electrode Resistance 25
Body Resistance 1000

RESULTS
Total Resistance 38.77
Total Current 5.93 Amp
Load Voltage Drop 85.29 Volts

Ground/Body Voltage Drop 144.71 Volts


Body Resistance 1000.00
Body Current 144.71 mA
Circuit Current 14.96 Amp

DOW RESTRICTED - For internal use only