Preaction System with DV-5 Deluge Valve


Double Interlock Electric/Pneumatic Actuation
1-1/2 thru 8 Inch (DN40 and DN200)
General
Description
The DV-5 Double Interlock Preaction
System with Electric/Pneumatic Actu-
ation (Fig. 1) is designed for use in ap-
plications, such as refrigerated areas,
requiring the maximum degree of pro-
tection against inadvertent flooding of
the sprinkler system piping.
The DV-5 Double Interlock Preaction
System with Electric/Pneumatic Actu-
ation utilizes a DV-5 Deluge Valve and
a Riser Check Valve. The Riser Check
Valve (that does not require the use of
priming water) isolates the Deluge Valve
from the system air pressure. The re-
leasing trim for the Deluge Valve uti-
lizes a Solenoid Valve and a Dry Pilot
Actuator in a series configuration. The
system air pressure holds the Dry Plot
Actuator closed, whereas the Solenoid
Valve remains closed until it is electri-
cally energized by a Deluge Valve Re-
leasing Panel (automatic control unit).
The Releasing Panel is operated by ei-
ther a fire detection device or manual
electric pull station.
The DV-5 Deluge Valve (described in diaphragm supply connections. This re-
In order for the Double Interlock Preac-
Technical Data Sheet TFP1305) is a sults in a rapid pressure drop in the Dia-
tion System to automatically actuate,
diaphragm style valve that depends phragm Chamber below the valve trip
two independent events must occur.
upon water pressure in the Diaphragm point. The water supply pressure then
The Deluge Valve Releasing Panel must
Chamber to hold the Diaphragm closed forces the Diaphragm open permitting
operate and open the Solenoid Valve
against the water supply pressure. water to flow into the system piping, as
upon automatic operation of the electric
When the DV-5 Valve is set for service, well as through the Alarm Port to actu-
fire detection initiating circuit or manu-
the Diaphragm Chamber is pressurized ate the system alarms.
al operation of the electric-manual pull
through the trim connections from the
initiating circuit, and the sprinkler sys- As water flows into the system, the
inlet side of the systems main control
tem piping must lose air pressure due Model FSV-1 Fail-Safe Valve (Item 5
valve, for example an O.S.&Y. gate valve
to operation of one or more sprinklers. Fig. 3A), also described in Technical
or butterfly valve (Fig. 1). Data Sheet TFP1386) becomes pres-
The Double Interlock Preaction System
Operation of the Solenoid Valve and Dry surized and upon operation constantly
will automatically actuate only when
Pilot Actuator at the same time releas- vents the DV-5 Diaphragm Chamber
both the Dry Pilot Actuator and the So-
es water from the Diaphragm Cham- so as to maintain the DV-5 Valve in the
lenoid Valve are open at the same time.
ber faster than it can be replenished open (operated) position until the sys-
Accidental opening of just the Dry Pilot
through the 1/8 inch (3,2 mm) Priming tem is reset.
Actuator (e.g., a lift truck accidentally
Supply Restriction (Item 7 Fig. 3A) in the
dislodges a sprinkler), or just energizing
Continued on Page 4
the Solenoid Valve (e.g., an accidental
operation of an electric pull station), will
only cause an alarm, and will not ac-
tuate the system or flood the sprinkler
system piping.

Page 1 of 16 JULY 2014 TFP1460


TFP1460
Page 2 of 16

13

17

6
20

18 15

9 16
11

14
7

8
3
4

1
2

19

1 - DV-5 Deluge Valve 9 - System Drain Valve (N.C.) 17 - System Shut-Off Valve (N.O.)
2 - Main Control Valve (N.O.) 10 - Main Drain Valve (N.C.) 18 - Air Pressure Gauge
3 - Diaphragm Chamber Supply (Shown at Rear of Valve) 19 - Automatic Air/Nitrogen Supply
Control Valve (N.O.) 11 - Fail-Safe Valve 20 - Low Pressure Alarm Switch
4 - Local Manual Control Station 12 - Waterflow Pressure Alarm Switch 21 - Dry Pilot Actuator
5 - Automatic Sprinklers (Shown at Rear of Valve)
6 - Heat Detectors, Smoke Detectors, 13 - Water Motor Alarm (Optional)
etc. (Fire Detection) 14 - Solenoid Valve
7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
8 - Diaphragm Chamber Pressure 16 - Riser Check Valve
Gauge

FIGURE 1 (1 OF 2)
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
SYSTEM SCHEMATIC (FRONT VIEW)
TFP1460
Page 3 of 16

5
6

17

20
9
13
21

16

14

12

15

19
1 10

1 - DV-5 Deluge Valve 7 - Water Supply Pressure Gauge 15 - Deluge Valve Releasing Panel
2 - Main Control Valve (N.O.) (Shown at Front of Valve) 16 - Riser Check Valve
3 - Diaphragm Chamber Supply 8 - Diaphragm Chamber Pressure 17 - System Shut-Off Valve (N.O.)
Control Valve (N.O.) Gauge (Shown at Front of Valve)
18 - Air Pressure Gauge
(Shown at Front of Valve) 9 - System Drain Valve (N.C.) (Shown at Front of Valve)
4 - Local Manual Control Station 10 - Main Drain Valve (N.C.) 19 - Automatic Air/Nitrogen Supply
(Shown at Front of Valve) 11 - Fail-Safe Valve 20 - Low Pressure Alarm Switch
5 - Automatic Sprinklers (Shown at Front of Valve)
21 - Dry Pilot Actuator
6 - Heat Detectors, Smoke Detectors, 12 - Waterflow Pressure Alarm Switch
etc. (Fire Detection) 13 - Water Motor Alarm (Optional)
14 - Solenoid Valve

FIGURE 1 (2 OF 2)
DOUBLE INTERLOCK PREACTION SYSTEM WITH ELECTRIC/PNEUMATIC ACTUATION
SYSTEM SCHEMATIC (REAR VIEW)
TFP1460
Page 4 of 16

PREACTION
To ease field assembly of the trim ar-
WATERFLOW DOUBLE rangement, the trim components are
PRESSURE INTERLOCK provided partially assembled as shown
ALARM ELECTRIC/ in Figure 3B.
SWITCH LOW AIR PNEUMATIC
PRESSURE ACTUATION The trim arrangement is provided with
ALARM TRIM galvanized or black nipples and fittings.
SWITCH
The galvanized trim is intended for
CHECK non-corrosive or corrosive conditions,
VALVE whereas the black trim is principally in-
tended for use with AFFF systems.
NOTES:
1. SEE FIGURE 3, PER VALVE SIZE
NOTE: When the system pressure is
AS APPLICABLE, FOR TRIM greater than 175 psi (12,1 bar), provision
ARRANGEMENT WITH BILL OF is to be made to replace the standard
MATERIALS AND COMPONENT order 300 psi (20,7 bar) Water Pres-
PART NUMBERS. sure Gauges, shown in Figure 3A/3B
2. TRIM SHOWN FULLY ASSEMBLED; with separately ordered 600 psi (41,4
COMPONENTS SUCH AS GAUGES bar) Water Pressure Gauges.
DV-5 AND SWITCHES MAY REQUIRE
DELUGE ASSEMBLY IN TRIM AT VALVE System Design Considerations
VALVE INSTALLATION.
Because a double interlock preaction
system requires time for a drop in sys-
SYSTEM tem air pressure to occur (concurrently
GROOVED SHUT-OFF with the response time for the separate
VALVE
COUPLING fire detection system) before it will allow
water to enter the system piping, this
FIGURE 2 system has characteristics similar to a
DV-5 PRE-TRIMMED DELUGE VALVE, dry pipe sprinkler system. Therefore,
ELECTRIC/PNEUMATIC ACTUATION the system design considerations for
a dry pipe system are normally applied
NOTICE Valve Trim to a double interlock preaction system
The Double Interlock Preaction System including a 30% increase in design
The DV-5 Double Interlock Preaction with Electric/Pneumatic Actuation Trim
System with Electric/Pneumatic Ac- area; a maximum 1 minute water deliv-
(Fig. 3A/3B) forms a part of the labora- ery time for system capacities of 750
tuation described herein must be in- tory listings and approvals. The trim is
stalled and maintained in compliance gallons (2800 liters) or more; and, pro-
necessary for proper operation of the hibition of gridded system piping.
with this document, as well as with the DV-5 Valve.
applicable standards of the National In order to readily perform the System
Fire Protection Association, in addition Each package of trim includes the fol- Inspection Procedure described in
to the standards of any other authori- lowing items: the Care and Maintenance section, it
ties having jurisdiction. Failure to do so Water Supply Pressure Gauge is recommended that a System Shut-
may impair the performance of the re- Off Valve be installed above the Riser
lated devices. Diaphragm Chamber Pressure Gauge Check Valve, as shown in Figure 1. The
The owner is responsible for maintain- Diaphragm Chamber Connections System Shut-Off Valve should be a list-
ing their fire protection system and de- ed or approved (as appropriate) indi-
Manual Control Station cating valve with a supervisory switch
vices in proper operating condition.
Contact the installing contractor or Main Drain Valve to monitor the normally open position.
manufacturer with any questions. System Drain Valve Detection System
Alarm Test Valve The Double Interlock Preaction Sys-
Technical Automatic Drain Valve
tem With Electric/Pneumatic Actuation
Trim provides for electric operation of
Data System Air Pressure Gauge the DV-5 Valve by a detection system
consisting of electrical devices such as
Air Supply Connections heat sensitive thermostats, smoke de-
Approvals
UL and C-UL Listed Low Air Pressure Alarm Switch tectors, and/or electric manual pull sta-
FM Approved tions. Information on the various types
Waterflow Pressure Alarm Switch of separately ordered Solenoid Valves
Deluge Valve Dry Pilot Actuator that may be used with this trim pack-
DV-5 age is given in Technical Data Sheet
Pressure Operated Relief Valve TFP2180. Nominal installation dimen-
Riser Check Valve The following items are included in the sions for the Double Interlock Preaction
Model CV-1FR Pre-Trimmed Valve Assembly and can System With Electric/Pneumatic Actua-
NOTE: 1-1/2 inch (DN40) risers utilize be ordered separately for the valve trim: tion Trim are shown in Figure 4.
a 2 inch (DN50) Model CV-1FR Riser Model BFV-N Butterfly Valve The Deluge Valve Releasing Panel (au-
Check Valve connected to the 1-1/2 tomatic control unit) with battery back-
inch (DN40) DV-5 Deluge Valve by a Waterflow Pressure Alarm Switch up, fire detection devices, manual pull
2 x 1-1/2 inch Figure 716 Reducing (PS10-2) stations, and signaling devices that are
Coupling Figure 577 Grooved Coupling utilized with the Double Interlock Pre-
Continued on Page 10
TFP1460
Page 5 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 35 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 36 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 11 CH P19 1" x 3/4" x 1/2" Tee. . . . . . . . . . . . . . . . . . . . 1 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 37 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P20 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 38 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P21 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
5 Model FSV-1 Fail-Safe Valve . . . . . . . . . . . . 1 52-343-1-001 39 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P22 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
6 Waterflow Pressure Alarm Switch, 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P23 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 41 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P24 1/2" x 9" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
7 Priming Supply Restriction . . . . . . . . . . . . . . 1 92-020-1-009 42 1/2" x 8" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P25 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
8 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P26 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
9 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 44 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH P27 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
10 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 45 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P28 1" x 2" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
11 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 46 3/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
12 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 COMPONENTS INCLUDED ONLY IN
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 PRE-TRIMMED VALVE ASSEMBLIES:
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 A1 Model CV-1FR Check Valve, 2" (DN50) . . . 1 59-590-1-020
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 P3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 A2 Butterfly Valve, Power Ball 300:
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 P4 Low Air Pressure Alarm Switch, 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 51024A
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 51021A
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 2 CH P5 Solenoid Valve Ordered Separately Refer to A3 Figure 577 Coupling:
19 1/2" x 12" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet 1-1/2" (DN40) . . . . . . . . . . . . . . . . . . . . . . . . 1 57715ACP
20 1/2" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH P6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 2" (DN50) . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 57720ACP
21 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004 A4 Coupling for 1-1/2" (DN40) DV-5:
22 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P8 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 Figure 716 Reducing Coupling, 2" x 1-1/2". . 1 7162015ES
23 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P9 3/4" Angle Valve . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-005 Coupling for 2" (DN50) DV-5:
24 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P10 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH Figure 577 Coupling, 2" . . . . . . . . . . . . . . . . 1 57720ACP
25 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P11 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
26 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P12 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
27 3/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH Select Appropriate Nipple Sizes
28 3/4" x 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . 1 CH P14 1/2" 45 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH Nipple per DV-5 Deluge Valve Size
29 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P15 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 4 CH Number
1-1/2" (DN40) 2" (DN50)
30 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH P16 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
31 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P17 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH 43 1/2" x 1-1/2" 1/2" x 2"
32 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P25 1/2" x 2-1/2" 1/2" x 2"
33 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P26 1/2" x 6" 1/2" x 5-1/2"
34 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH

P8 P6
P22 P20
P23 P1
P22 P4
P15 P7 P18 28 P17
P13 P2
44 P14
P22 36 P10 P22
P22 P25 P12
P11
6 P22 P15 P15
16
(GREEN P16 P23 P3
P13 4
TINT) 17 30 P24
P28 P22 P21
P26 P5
31 26
13 (ORDERED
33 P19 SEPARATELY)
22 P27 15 35
PLUG 14 P22
38 P9 23
UNUSED 39
PORTS P21
45 44 26 36
LOCATION P12 P15
FOR OPTIONAL 44
44 32
ELECTRICALLY A1 36 18 23
44 P12 42
SUPERVISED 36 24
N.O. ALARM 11 44 26 20 30
CONTROL 33 39 1
5 36
VALVE A4
43 27 (HEX ENDS,
26 12 46 "FSV-1") 29 36 31
8
41
9
38 1 36 3
A3
NOTES: 23 7
21 2 23
1. Supervised Double Interlock
Preaction Trim with Electric/ 40 26 35
10 37
Pneumatic Release is comprised 36 36 19
of Items 1-46 plus Items P1-P28. 37 18
34 31 36
Items A1-A4 included only in 2" (DN50) 26 26
34 23
pre-trimmed valve assemblies 25 GROOVE x GROOVE A2
as applicable; otherwise DV-5 DELUGE VALVE NOTES:
ordered separately. SHOWN 36 4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are Deluge Valve Port identification.
galvanized (Standard Order). 8 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 15.
FIGURE 3A (1 OF 3)
1-1/2 AND 2 INCH (DN40 AND DN50) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM EXPLODED VIEW
TFP1460
Page 6 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 28 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 29 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH P8 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 30 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P9 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 31 3/4" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P10 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH
5 Model FSV-1 Fail-Safe Valve . . . . . . . . . . . . 1 52-343-1-001 32 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P11 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH
6 Waterflow Pressure Alarm Switch, 33 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P12 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 34 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
7 Priming Supply Restriction . . . . . . . . . . . . . . 1 92-020-1-009 35 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 14 CH P14 1/2" 45 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
8 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 36 1/2" x 2-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P15 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 4 CH
9 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 37 1/2" x 3-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH P16 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH
10 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 38 1/2" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P17 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
11 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 39 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
12 1-1/4" Angle Valve . . . . . . . . . . . . . . . . . . . . 1 46-048-1-007 40 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P19 1-1/4" x 1-1/4" x 1/2" Tee. . . . . . . . . . . . . . . 1 CH
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 41 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P20 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 42 1/2" x 8" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P21 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 43 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 5 CH P22 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 8 CH
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 44 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P23 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 3 CH
17 1/4" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH 45 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH P24 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 2 CH 46 1-1/4" x 4" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH P25 1/2" x 10-1/2" Nipple. . . . . . . . . . . . . . . . . . . 1 CH
19 1/2" x 18" Tubing . . . . . . . . . . . . . . . . . . . . . 2 CH P26 1-1/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
20 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 P27 1-1/4" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . 1 CH
21 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002
22 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 COMPONENTS INCLUDED ONLY IN
23 3/4" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P4 Low Air Pressure Alarm Switch, PRE-TRIMMED VALVE ASSEMBLIES:
24 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730
25 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P5 Solenoid Valve Ordered Separately Refer to A1 Model CV-1FR Check Valve, 3" (DN80) . . . 1 59-590-1-030
26 3/4" x 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet A2 Model BFV-N Butterfly Valve, 3" (DN80) . . . 1 59300F030N
27 1-1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . 1 CH P6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020 A3 Figure 577 Coupling, 3" (DN80) . . . . . . . . . . 2 57730ACP

P7 P22 P6 P20
P22 P22 P1
P4
P22 P18 26 P17
P15 P2
P13
43 P14
P8 35 P10 P22
P22 P23 P13 P12
P22 P15 P15
6
16 P16 P23 P3
(GREEN 4 P11
17 P23 29 P21
TINT)
P24 P25
30 P26 13 P5
32 P9 25 (ORDERED
P27 15 35
21 PLUG 14 P22 SEPARATELY)
P19 UNUSED
22 39
36 31 PORTS P21
43 P12 25 35
44 23 A1 P15
LOCATION
FOR OPTIONAL 43
43 P12 38 35 18 22
ELECTRICALLY 42
SUPERVISED 35 11
25 19 29
N.O. ALARM 43
CONTROL A3 35 1
32 5
VALVE
35 (HEX ENDS,
27 "FSV-1") 28 35 30
25 8 45 46 41
9
12 35 3
40 35
1
NOTES: 7 22
25
1. Supervised Double Interlock 22 10
Preaction Trim with Electric/ 20 2
37 34
Pneumatic Release is comprised A3 35 19
39
of Items 1-46 plus Items P1-P27. 18
Items A1-A3 included only in 35 25 25
33 22 35
pre-trimmed valve assemblies 30
as applicable; otherwise 33 NOTES:
ordered separately. 24 3" (DN80) 35 4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are GROOVE x GROOVE Deluge Valve Port identification.
galvanized (Standard Order). DV-5 DELUGE VALVE 8 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. SHOWN A2 Item 15.
FIGURE 3A (2 OF 3)
3 INCH (DN80) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM EXPLODED VIEW
TFP1460
Page 7 of 16

NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N NO. DESCRIPTION QTY. P/N
1 300 psi/ 2000 kPa Water Pressure Gauge . . 2 92-343-1-005 41 1/2" x 9" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P29 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 42 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P30 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
3 Model MC-1 Manual Control Station . . . . . . 1 52-289-2-001 43 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH
4 Model AD-1 Automatic Drain Valve . . . . . . . 1 52-793-2-004 44 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH COMPONENTS INCLUDED ONLY IN
5 Model FSV-1 Fail-Safe Valve . . . . . . . . . . . . 1 52-343-1-001 45 3/4" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH PRE-TRIMMED VALVE ASSEMBLIES:
6 Waterflow Pressure Alarm Switch, 46 3/4" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
Model PS10-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25710 47 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH A1 Model CV-1FR Check Valve:
7 Priming Supply Restriction . . . . . . . . . . . . . . 1 92-020-1-009 48 1" x Close Nipple . . . . . . . . . . . . . . . . . . . . . 2 CH 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-040
8 1/2" Ball Valve . . . . . . . . . . . . . . . . . . . . . . . 2 46-050-1-004 49 1" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 1 CH 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-060
9 1/2" Spring Loaded Check Valve . . . . . . . . . 1 92-322-1-002 50 2" x 3" Nipple . . . . . . . . . . . . . . . . . . . . . . . . 2 CH 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59-590-1-080
10 1/2" Y-Strainer . . . . . . . . . . . . . . . . . . . . . . . 1 52-353-1-005 A2 Model BFV-N Butterfly Valve:
11 3/4" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-005 P1 250 psi/ 1750 kPa Air Pressure Gauge . . . . 1 92-343-1-012 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F040N
12 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 P2 1/4" Gauge Test Valve . . . . . . . . . . . . . . . . . 1 46-005-1-002 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F060N
13 Drip Funnel Connector . . . . . . . . . . . . . . . . . 1 92-211-1-005 P3 Model DP-1 Dry Pilot Actuator . . . . . . . . . . . 1 52-280-1-001 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 1 59300F080N
14 Drip Funnel Bracket . . . . . . . . . . . . . . . . . . . 1 92-211-1-003 P4 Low Air Pressure Alarm Switch, A3 Figure 577 Coupling:
15 Drip Funnel . . . . . . . . . . . . . . . . . . . . . . . . . . 1 92-343-1-007 Model PS40-2. . . . . . . . . . . . . . . . . . . . . . . . 1 25730 4" (DN100) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57740ACP
16 3/32" Vent Fitting . . . . . . . . . . . . . . . . . . . . . 1 92-032-1-002 P5 Solenoid Valve Ordered Separately Refer to 6" (DN150) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57760ACP
17 1/4" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH Per Data Sheet TFP2180 . . . . . . . . . . . . . . . 1 Data Sheet 8" (DN200) . . . . . . . . . . . . . . . . . . . . . . . . . . 2 57780ACP
18 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 2 CH P6 1/4" Pressure Relief Valve . . . . . . . . . . . . . . 1 92-343-1-020
19 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH P7 1/2" Swing Check Valve . . . . . . . . . . . . . . . . 1 46-049-1-004
20 Select Tube per Table ..................... 1 CH P8 1/2" Globe Valve . . . . . . . . . . . . . . . . . . . . . 1 46-047-1-004 Select Appropriate Tube Size
21 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P9 2" Angle Valve . . . . . . . . . . . . . . . . . . . . . . . 1 46-048-1-009 Tube per DV-5 Deluge Valve Size
22 3/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P10 1/2" Tubing Connector . . . . . . . . . . . . . . . . . 1 CH No. 4" 6" 8"
23 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 5 CH P11 1/2" x 24" Tubing . . . . . . . . . . . . . . . . . . . . . 1 CH (DN100) (DN150) (DN200)
24 1" Union . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P12 1/4" Plug. . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 CH 20 1/4" x 24" 1/4" x 24" 1/4" x 30"
25 1/4" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH P13 1/2" Union. . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH
26 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 7 CH P14 1/2" 45 Elbow . . . . . . . . . . . . . . . . . . . . . . . 1 CH
27 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P15 1/2" 90 Elbow . . . . . . . . . . . . . . . . . . . . . . . 4 CH Select Appropriate Nipple Sizes
28 1/2" Tee . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 CH P16 1/2" Cross. . . . . . . . . . . . . . . . . . . . . . . . . . . 1 CH Nipple per DV-5 Deluge Valve Size
29 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 3 CH P17 1/2" x 1/4" x 1/2" Tee . . . . . . . . . . . . . . . . . . 1 CH
No. 4" 6" 8"
30 3/4" x 1/2" x 3/4" Tee . . . . . . . . . . . . . . . . . . 2 CH P18 1/2" x 1/2" x 1/4" Tee . . . . . . . . . . . . . . . . . . 1 CH
31 1" x 1/2" 90 Elbow. . . . . . . . . . . . . . . . . . . . 1 CH P19 2" x 2" x 1/2" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH (DN100) (DN150) (DN200)
32 1" x 3/4" x 1" Tee . . . . . . . . . . . . . . . . . . . . . 1 CH P20 1/4" x Close Nipple. . . . . . . . . . . . . . . . . . . . 1 CH 42 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8 -1/2"
33 2" 90 Elbow. . . . . . . . . . . . . . . . . . . . . . . . . 1 CH P21 1/2" x Close Nipple. . . . . . . . . . . . . . . . . . . . 2 CH 43 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2"
34 1/4" x Close Nipple ..................... 2 CH P22 1/2" x 1-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 6 CH 44 1/2" x 4" 1/2" x 5" 1/2" x 6"
35 1/2" x Close Nipple ..................... 1 CH P23 1/2" x 2" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH
47 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
36 1/2" x 1-1/2" Nipple . . . . . . . . . . . . . . . . . . . . . 11 CH P24 1/2" x 4-1/2" Nipple. . . . . . . . . . . . . . . . . . . . 1 CH
37 1/2" x 2-1/2" Nipple ..................... 2 CH P25 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P25 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 11-1/2"
38 1/2" x 3" Nipple. . . . . . . . . . . . . . . . . . . . . . . 1 CH P26 1/2" x 11" Nipple. . . . . . . . . . . . . . . . . . . . . . 1 CH P27 1/2" x 7" 1/2" x 5-1/2" 1/2" x 10"
39 1/2" x 5" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P27 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P28 1/2" x 3-1/2" 1/2" x 6" 1/2" x 8"
40 1/2" x 7" Nipple. . . . . . . . . . . . . . . . . . . . . . . 2 CH P28 Select Nipple per Table . . . . . . . . . . . . . . . . 1 CH P29 1/2" x 2" 1/2" x 2-1/2" 1/2" x 4"

P6 P20
P8 P22 P1
P22
P22
P4 P18 P17
P22 P2
P15 P14
P13 31
P10 P22
P12
P22 38 4 P15
P29
P28 P7 48 P23 P3
P24
6 P16 P11
16 P21
P13 P26
(GREEN 28
TINT) 17 P27 P15
P30 P5
13 (ORDERED
29 26 SEPARATELY)
PLUG P25
30 15
UNUSED 43
22 14 P15
P9 P30 PORTS
P19 23 44
37 P12 P21
A1 41 26
32 36
LOCATION 46
24 P12 26
FOR OPTIONAL 36 18
ELECTRICALLY 45 23
SUPERVISED 11 48 28
36 20
N.O. ALARM 47 49
36 1
CONTROL 37 5
30 (HEX ENDS,
VALVE A3
42 "FSV-1") 27 36 29
26 33 40
8 10
50 50 36 3
36
12
7 23
1
NOTES: 40 9
26
1. Supervised Double Interlock 23 35
21 2 39
Preaction Trim with Electric/ 36 19
Pneumatic Release is comprised A3 18
39 26 26
of Items 1-50 plus Items P1-P30. 23
36 36
Items A1-A3 included only in A2
pre-trimmed valve assemblies 34 29
as applicable; otherwise 36 NOTES:
25 34
ordered separately. 4" (DN100)
4. See Figure 2 of TFP1305 for
2. All Fittings and Nipples are GROOVE x GROOVE 8 Deluge Valve Port identification.
galvanized (Standard Order). DV-5 DELUGE VALVE
SHOWN 5. Route all Tubing to Drip Funnel,
3. CH: Common Hardware. Item 15.

FIGURE 3A (3 OF 3)
4, 6, AND 8 INCH (DN100, DN150, AND DN200) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM EXPLODED VIEW
TFP1460
Page 8 of 16

NOTES: Nipple Select Appropriate Nipple and Tube Sizes per DV-5 Deluge Valve Size
1. Use only 2" (DN50) Model CV-1FR Riser Number 1-1/2" (DN40) 2" (DN50) 3" (DN80) 4" (DN100) 6" (DN150) 8" (DN200)
Check Valve in 1-1/2" (DN40) and 2" (DN50)
1 1/2" x 1-1/2" 1/2" x 2" 1/2" x 1-1/2" 1/2" x 2-1/2" 1/2" x 5-1/2" 1/2" x 8-1/2"
assemblies. Use CV-1FR Valve size equal
to mating DV-5 Valve in larger assemblies. 2 1/2" x Close 1/2" x Close 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2"
2. Nipples 1-8 and Tube 1 vary in length relative 3 1/2" x 3-1/2" 1/2" x 3-1/2" 1/2" x 4-1/2" 1/2" x 4" 1/2" x 5" 1/2" x 5-1/2"
to DV-5 size. Select per table. All other 4 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 1-1/2" 3/4" x 2-1/2" 3/4" x 3-1/2" 3/4" x 4-1/2"
nipples and tubing packed unassembled 5 1/2" x 6" 1/2" x 5-1/2" 1/2" x 5" 1/2" x 7" 1/2" x 5-1/2" 1/2" x 3"
shall be installed per appropriate trim 6 1/2" x 2-1/2" 1/2" x 2" 1/2" x 2" 1/2" x 3-1/2" 1/2" x 6" 1/2" x 8"
exploded view, Figure 3A Part 1, 2, or 3.
7 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 2" 1/2" x 2" 1/2" x 2-1/2" 1/2" x 4"
3. Install subassemblies in alphabetical order.
8 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 1-1/2" 1/2" x 4-1/2" 1/2" x 4-1/2" 1/2" x 11-1/2"
4. See Figure 2 of TFP1305 for Deluge Valve
Port identification. System
Main Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
5. Route all Tubing to Drip Funnel. Size
6. When DV-5 trips, Fail-Safe Valve opens,
partially diverting diaphragm supply to drain, Main
allowing diaphragm chamber to remain Drain 3/4" NPT 3/4" NPT 1-1/4" NPT 2" NPT 2" NPT 2" NPT
de-pressurized after decrease in system Size
flow. Tube 1 1/2" x 18" 1/2" x 18" 1/2" x 18" 1/2" x 24" 1/2" x 24" 1/2" x 30"

LOW AIR
WATERFLOW VENT FITTING SYSTEM PRESSURE SYSTEM
PRESSURE (GREEN TINT) AIR SUPPLY ALARM SWITCH AIR SUPPLY
ALARM SWITCH CONTROL VALVE PRESSURE
(NORMALLY GAUGE
OPEN) 1/2 INCH NPT
3/4 INCH NPT CONNECTION
CONNECTION FOR F FOR SYSTEM G
DRIP 1/2 INCH
WATER MOTOR FUNNEL AIR SUPPLY
AUTOMATIC CONDUIT
ALARM WITH 1-1/4
DRAIN CONNECTION
B VALVE INCH NPT FOR "ELECTRIC
NIPPLE
CONNECTION DETECTION"
4 DRY PILOT
TO DRAIN
LOCATION ACTUATOR
NIPPLE (NORMALLY
FOR OPTIONAL PLUG 5 NIPPLE NIPPLE SOLENOID
UNUSED 6 7 CLOSED) VALVE,
ELECTRICALLY
SUPERVISED PORTS NIPPLE ORDERED
SYSTEM
N.O. ALARM RISER 8 SEPARATELY
MAIN DRAIN (NORMALLY
CONTROL CONNECTION CHECK VALVE
VALVE (NOTE 1) NIPPLE CLOSED)
(SIZED PER
TABLE) 2
NIPPLE SYSTEM MAIN TUBE
1 DRAIN VALVE 1 DIAPHRAGM
NIPPLE
(NORMALLY CHAMBER
MAIN 3
CLOSED) PRESSURE
DRAIN VALVE
(NORMALLY GAUGE
E
CLOSED)
ALARM MANUAL
TEST VALVE A CONTROL
D STATION
(NORMALLY
CLOSED)
FAIL-SAFE
SYSTEM VALVE
WATER C 4" (DN100) (NORMALLY
DIAPHRAGM CLOSED)
SUPPLY
FLANGE x GROOVE CHAMBER SUPPLY
PRESSURE
DV-5 DELUGE CONTROL VALVE
GAUGE MAIN DRAIN 1/2 INCH NPT
VALVE SHOWN (NORMALLY
CONNECTION CONNECTION FROM OPEN)
(SIZED PER TABLE) WATER SUPPLY
FIGURE 3B
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM OPERATIONAL COMPONENTS
SEMI-PREASSEMBLED TRIM EXPLODED ARRANGEMENT
TFP1460
Page 9 of 16

Valve Nominal Installation Dimensions in Inches and (mm)


Size A B C D E F G H J K L M N
1-1/2" 7.00 8.88 13.00 10.50 27.13 4.00 5.81 5.81 3.00 7.00 4.00 14.81 4.02
(DN40) (177,8) (225,4) (330,2) (266,7) (689,0) (101,6) (147,6) (147,6) (76,2) (177,8) (101,6) (376,2) (102,1)
2" 7.13 9.13 13.00 10.50 27.50 3.13 6.00 6.00 3.00 7.00 3.13 15.38 4.09
(DN50) (181,0) (231,8) (330,2) (266,7) (698,5) (79,4) (152,4) (152,4) (76,2) (177,8) (79,4) (390,5) (103,9)
3" 7.81 10.44 14.50 10.50 31.00 1.69 6.69 6.69 4.25 7.00 0.25 21.13 3.85
(DN80) (198,4) (265,1) (368,3) (266,7) (787,4) (42,9) (170,0) (170,0) (108,0) (177,8) (6,4) (536,6) (98,0)
4" 10.00 11.75 17.88 10.50 35.63 1.75 6.50 8.56 6.25 7.13 0.38 25.38 4.56
(DN100) (254,0) (298,5) (454,0) (266,7) (904,9) (44,5) (165,1) (217,5) (158,8) (181,0) (9,5) (644,5) (116,0)
6" 11.38 14.31 18.75 10.50 36.19 3.50 7.88 9.94 6.25 7.13 1.56 29.63 5.86
(DN150) (289,0) (363,5) (476,3) (266,7) (919,2) (88,9) (200,0) (252,4) (158,8) (181,0) (39,7) (752,5) (149,0)
8" 12.00 16.00 21.25 10.50 40.50 1.75 10.75 10.63 6.25 7.13 7.13 36.50 5.26
(DN200) (304,8) (406,4) (539,8) (266,7) (1028,7) (44,5) (273,1) (269,9) (158,8) (181,0) (181,0) (927,1) (134,0)

* MINIMUM CLEARANCE.

A* B C* D*

E*

N
F
G

H J K

LEFT VIEW FRONT VIEW


FIGURE 4
1-1/2 THRU 8 INCH (DN40 THRU DN200) DV-5 DOUBLE INTERLOCK PREACTION SYSTEM
WITH ELECTRIC/PNEUMATIC ACTUATION TRIM NOMINAL INSTALLATION DIMENSIONS
TFP1460
Page 10 of 16

action System with Electric/Pneumat-


45
ic Actuation must be UL Listed, ULC
Listed, C-UL Listed, or FM Approved, URE
as applicable. IR PRESS
EM A

AIR PRESSURE IN PSI


YST
NOTICE UM S
30 MINIM
Approval by Factory Mutual is contin- SURE
gent on the use of an FM Approved 24 ING PRES
VDC Solenoid Valve (P/N 52-287-1024 R OPEN
UATO
or P/N 52-287-1-124). FM only approves 15 EOF ACT
solenoid valves for use in non-hazard- RANG
ous locations.
Consult with the authority having ju-
risdiction regarding installation criteria
0
pertaining to electric actuation circuitry.
20 60 100 140 180 200 250
The Double Interlock Preaction Sys-
tem with Electric/Pneumatic Actuation WATER SUPPLY PRESSURE IN PSI
Trim is provided with a Model FSV-1
Fail-Safe Valve (Item 5 -Fig. 3A, also GRAPH A
described in Technical Data Sheet DOUBLE INTERLOCK PREACTION SYSTEM
TFP1386); consequently, the release AIR PRESSURE REQUIREMENTS
circuit of the Releasing Panel need
only provide the standard ten minutes system piping can create ice build up The DV-5 Valve must be installed in a
of alarm condition intended to ener- which could prevent proper operation readily visible and accessible location.
gize the Solenoid Valve to open. After of the system. The DV-5 Valve and associated trim
the ten minute duration, at which point Friction Loss must be maintained at a minimum tem-
should the Solenoid Valve become de- The nominal pressure loss versus flow perature of 40F (4C).
energized and closed (especially while data for the DV-5 Deluge Valve plus Ris-
operating under battery back-up), the Heat tracing of the DV-5 Valve or its
er Check Valve is provided in Graph B. associated trim is not permitted. Heat
Fail-Safe Valve will have already auto-
matically operated to constantly vent tracing can result in the formation of
the DV-5 Diaphragm Chamber, thereby
preventing the DV-5 Diaphragm Cham-
Installation hardened mineral deposits that can
prevent proper operation.
ber from becoming repressurized and NOTICE The DV-5 Deluge Valve is to be in-
preventing an inadvertent closing of the stalled in accordance with the follow-
DV-5 during a fire event. 1-1/2 inch (DN40) risers utilize a 2 inch ing criteria:
(DN50) Riser Check Valve in combina-
System Air Pressure Requirements tion with the 1-1/2 inch (DN40) DV-5 Step 1. All nipples, fittings, and de-
The required system air pressure for the Deluge Valve. vices must be clean and free of scale
Double Interlock Preaction System with and burrs before installation. Use pipe
Proper operation of the DV-5 Deluge thread sealant sparingly on male pipe
Electric/Pneumatic Actuation is shown Valve depends upon its trim being in-
in Graph A as a function of the antici- threads only.
stalled in accordance with the instruc-
pated water supply pressure. It is rec- tions given in this Technical Data Sheet. Step 2. The DV-5 Valve must be
ommended that the system air pressure Failure to follow the appropriate trim di- trimmed in accordance with Figure
be maintained by one of the following agram may prevent the DV-5 Valve from 3A/3B.
methods: functioning properly, as well as void list- Step 3. Care must be taken to ensure
A maximum 200 psi (13,8 bar) plant ings, approvals, and the manufacturers that check valves, strainers, globe
air supply in combination with the warranties. valves, etc. are installed with the flow
Model AMD-1 Air Maintenance De- Field adjustments of the Air Mainte- arrows in the proper direction.
vice described in Technical Data nance Device, Low Pressure Alarm
Sheet TFP1221 Step 4. Drain tubing to the drip funnel
Switch, and Pressure Relief Valve are must be installed with smooth bends
A dedicated air compressor in com- required. that will not restrict flow.
bination with the Model AMD-2 Air When using compressed air as op-
Maintenance Device described in Step 5. The main drain and drip funnel
posed to compressed nitrogen for re- drain may be interconnected provided a
Technical Data Sheet TFP1231 frigerated area service, alternate air check valve is located at least 12 inches
A maximum 3000 psi (206,9 bar) ni- supply connections with an air dryer (300 mm) below the drip funnel.
trogen cylinder in combination with may be required by the authority hav-
the Model AMD-3 Nitrogen Mainte- ing jurisdiction. The 1/2 Inch NPT Con- Step 6. Suitable provision must be
nance Device described in Technical nection For System Air Supply shown made for disposal of drain water. Drain-
Data Sheet TFP1241 in Figure 3B is to be plugged when us- age water must be directed so that it
ing an alternate air supply connection; will not cause accidental damage to
NOTICE the location of the Air Pressure Main- property or danger to persons.
The dew point of the air or nitrogen tenance is to be as specified by the au- Step 7. Connect the Diaphragm Cham-
supply, for a system exposed to freez- thority having jurisdiction; and, Step 10 ber Supply Control Valve to the inlet
ing conditions, must be maintained regarding the adjustment of the Pres- side of the systems Main Control Valve
below the lowest ambient temperature sure Relief Valve can be omitted, since in order to facilitate setting of the DV-5
to which the system piping will be ex- the Pressure Relief Valve in this case Valve (Fig. 4).
posed. Introduction of moisture into the will be ineffective.
TFP1460
Page 11 of 16

FLOW RATE IN LITRES PER MINUTE (LPM)


(1 GPM = 3,785 LPM)
200 400 600 1000 2000 3000 5000 7000 10000
15.0 1,00
0,90
0,80
10.0 0,70
9.0
NOMINAL PRESSURE DROP IN POUNDS PER SQUARE INCH (PSI)

0,60

0)
8.0

N4
0,50
(D
7.0

0)
CH

N5
6.0
(D
IN

H 0,40
1/2

NC

5.0

NOMINAL PRESSURE DROP IN BAR


1-

2I

0)
0,30

N8
4.0

(D

)
00

(1 PSI = 0,06895 BAR)


H

N1
NC

(D
3.0
3I
0,20

H
NC

)
50
4I

N1
(D
2.0

)
00
H
NC

N2
(D
6I
0,10

H
NC
0,09

8I
0,08
1.0 0,07
0.9 0,06
0.8
0.7 0,05

0.6 0,04
0.5
0,03
0.4
50 100 200 400 600 1000 2000 3000
FLOW RATE IN GALLONS PER MINUTE (GPM)
The approximate friction loss, based on the Hazen and Williams formula and expressed in equivalent length of pipe with
C=120, is as follows:
15 feet of 1-1/2 Sch. 40 pipe for the 1-1/2 inch Valve Combination**calculated on a typical flow rate of 100 gpm.
28 feet of 2 inch Sch. 40 pipe for the 2 inch Valve Combination* calculated on a typical flow rate of 175 gpm.
37 feet of 3 inch Sch. 40 pipe for the 3 inch Valve Combination* calculated on a typical flow rate of 350 gpm.
48 feet of 4 inch Sch. 40 pipe for the inch Valve Combination* calculated on a typical flow rate of 600 gpm.
73 feet of 6 inch Sch. 40 pipe for the 6 inch Valve Combination* calculated on a typical flow rate of 1500 gpm.
103 feet of 8 inch Sch. 30 pipe for the 8 inch Valve Combination* calculated on a typical flow rate of 2500 gpm.

GRAPH B
DELUGE AND CHECK VALVE COMBINATION*
NOMINAL PRESSURE LOSS VERSUS FLOW
*DV-5 Deluge Valve combined with Model CV-1FR Riser Check Valve
**1-1/2 inch DV-5 Deluge Valve combined with 2 inch Model CV-1FR Riser Check Valve
TFP1460
Page 12 of 16

Step 8. Unused pressure alarm switch


connections must be plugged. Valve Setting Step 10. Reset the actuation system.
Manual Actuation Push the oper-
Step 9. A suitable automatic supervi-
sory air (nitrogen) supply, as described
Procedure ating lever up; however, do not close
the hinged cover at this time.
in the Technical Data Section, is to be Steps 1 through 15 are to be performed
when initially setting the DV-5 Deluge Electric Actuation Reset the elec-
installed in accordance with the appli-
Valve; after an operational test of the tric detection system in accordance
cable Technical Data Sheet. Refer to
fire protection system; or, after system with the manufacturers instructions
Graph A for the system air pressure
operation due to a fire. to de-energize the Solenoid Valve.
requirements.
Step 1. Close the Main Control Valve. Step 11. Open the Diaphragm Cham-
An air dryer, when specified, is to be ber Supply Control Valve and allow full
installed as required by the authority Step 2. Close the Diaphragm Chamber pressure to build up in the Diaphragm
having jurisdiction. Supply Control Valve and the System Chamber.
Step 10. The Pressure Relief Valve (P6 Air Supply Control Valve.
Step 12. Operate (open) the Manu-
-Fig. 3A) is factory set to relieve at a Step 3. Open the Main Drain Valve, al Control Station to vent trapped air
pressure of approximately 45 psi (3,1 System Drain Valve, and all auxiliary from the Diaphragm Chamber. If nec-
bar), which can typically be used for a drains in the system. After water ceas- essary, first open the hinged cover, and
maximum system pressure of 40 psi es to discharge, close the System Drain then fully pull down on the operating
(2,8 bar). The Pressure Relief Valve may Valve and auxiliary drain valves. Leave lever. Slowly close the operating lever,
be reset; however, it must be reset to the Main Drain Valve open. by pushing it up, after aerated water
relieve at a pressure that is in accor- ceases to discharge from the Manual
dance with the requirements of the au- NOTICE Control Station drain tubing. Close the
thority having jurisdiction.
Do not open the Inspectors Test Con- hinged cover and insert a new break
To reset the Pressure Relief Valve, first nection and auxiliary drains if reset- rod in the small hole through the top of
loosen the jam nut and then adjust ting after a system test; otherwise, the enclosing box.
the cap accordingly clockwise for system air pressure will be relieved Step 13. Inspect the drain connections
a higher pressure setting or counter- unnecessarily. from the Manual Control Station and
clockwise for a lower pressure setting.
Step 4. Depress the plunger of the Au- the Dry Pilot Actuator. Any leaks must
After verifying the desired pressure set-
tomatic Drain Valve to verify that it is be corrected before proceeding to the
ting, tighten the jam nut.
open and that the DV-5 Valve is com- next step.
Step 11. The Low Pressure Alarm pletely drained. Step 14. Verify the ability for the DV-5
Switch (Item P4 -Fig. 3A) is to be ad-
Step 5. Clean the Strainer in the Dia- Diaphragm to hold pressure as follows:
justed to operate on falling pressure
at approximately 6 psi (0,4 bar) below phragm Chamber Supply connection by With the diaphragm chamber pres-
the minimum Double Interlock Dry Sys- removing the clean-out plug and strain- surized per Step 12, temporari-
tem air pressure requirement shown on er basket. The Strainer may be flushed ly close the Diaphragm Chamber
Graph B. out by momentarily opening the Dia- Supply Control Valve and observe
phragm Chamber Supply Control Valve. the Diaphragm Chamber Pressure
Use the instructions provided with the
Step 6. Inspect for and clear all ice Gauge for a drop in pressure.
switch to adjust the pressure setting.
plugs where system piping has been If a drop in pressure is noted, the
Step 12. Conduit and electrical con- exposed to freezing conditions and DV-5 Diaphragm is to be replaced
nections are to be made in accordance when there has been a flow of water and/or any leaks must be corrected
with the requirements of the authority into the system. before proceeding to the next step.
having jurisdiction and/or the National
Electric Code. Step 7. Replace all damaged or oper- If the Diaphragm Chamber Pressure
ated sprinklers. Replacement sprinklers Gauge does not indicate a drop in
Step 13. Before a system hydrostatic must be of the same type and tempera- pressure, re-open the Diaphragm
test is performed in accordance with ture rating as those that operated. Chamber Supply Control Valve and
NFPA 13 system acceptance test re- proceed to the next step.
quirements, the DV-5 Diaphragm NOTICE
Chamber is to be depressurized, the In order to prevent the possibility of a Step 15. Slowly open the Main Con-
Automatic Drain Valve (4, Fig. 3A) is to subsequent operation of an overheated trol Valve. Close the Main Drain Valve
be temporarily replaced with a 1/2 inch solder type sprinkler, any solder type as soon as water discharges from the
NPT plug, the 3/32 inch Vent Fitting (17 sprinklers possibly exposed to a tem- drain connection. Observe the Auto-
-Fig. 3A) is to be temporarily replaced perature greater than their maximum matic Drain Valve for leaks. If there are
with a 1/4 inch NPT plug, and the Dia- rated ambient must also be replaced. leaks, determine/correct the cause of
phragm Cover Bolts must be uniformly the leakage problem. If there are no
and securely tightened using a cross- Step 8. Service the air dryer, if appli- leaks, the DV-5 Valve is ready to be
draw sequence. After tightening, dou- cable, in accordance with the manufac- placed in service and the Main Control
ble-check to make certain that all of the turers instructions. Valve must then be fully opened.
Diaphragm Cover Bolts are securely Step 9. Open the System Air Supply
tightened. Control Valve and allow the system to NOTICE
automatically re-establish its nominal When the Main Control Valve is opened,
system air pressure per Graph A. Ob- the pressure on the Diaphragm Cham-
serve the Automatic Drain Valve for ber may increase. This increase in pres-
leaks. If there are leaks, determine/cor- sure is normal, and if the pressure is
rect the cause of the leakage problem greater than 250 psi (17,2 bar), the pres-
within the Riser Check Valve. sure is to be relieved by partially and
temporarily opening the Manual Con-
trol Station; however, do not allow the
TFP1460
Page 13 of 16

pressure as indicated on the Diaphragm control station, switches, and pres- Step 8. Open the Main Control Valve
Chamber Pressure Gauge to drop be- sure maintenance device should be (Fig. 1) one turn beyond the position at
low the supply pressure shown on the reviewed. which water just begins to flow from the
Water Supply Pressure Gauge, since Main Drain Valve.
The following procedures pertain to the
this action may result in tripping of the automatic control valve portion of the Step 9. Close the Main Drain Valve (Fig.
DV-5 Valve. Double Interlock Preaction System. Re- 2B).
After setting a fire protection system, fer to the manufacturers instructions Step 10. Close the Air Supply Control
notify the proper authorities and advise and NFPA 25 for care and maintenance Valve (Fig. 3B).
those responsible for monitoring pro- procedures for all other devices (e.g.,
prietary and/or central station alarms. electric detection, main control and Step 11. Open the Dry Pilot Actuator
system shut-off valves, supervisory by partially opening the System Main
Care and devices, sprinklers, etc.).
Before performing the System Inspec-
Drain Valve (Fig. 3B) to relieve air pres-
sure at the inlet to the Actuator. Verify
Maintenance tion Procedure, which will result in op-
eration of alarms, notify the proper au-
that there is no leakage from the Dry
Pilot Actuator.
The following procedures, inspections, thorities and all personnel who may be NOTICE
and maintenance must be performed affected.
as indicated, in addition to any spe- During this procedure, the Dry Pilot Ac-
cific requirements of the NFPA, and System Inspection Procedure tuator is opened; however, the Solenoid
any impairment must be immediately Step 1. Close the Main Control Valve Valve should remain closed and the
corrected. (Fig. 1) and then open the DV-5 Main DV-5 Deluge Valve Diaphragm Cham-
Drain Valve (Fig. 3B). ber should remain pressurized.
Before closing a fire protection system
main control valve for maintenance Step 2. Manually operate the Deluge This procedure is used to verify that the
work on the fire protection system that Valve Releasing Panel and verify the DV-5 Deluge Valve will remain set if the
it controls, permission to shut down the following: Dry Pilot Actuator operates due to loss
affected fire protection system must be of system air pressure and the electric
The operation of the Releasing Panel
obtained from the proper authorities detection system remains in a normal
and its associated alarms
and all personnel who may be affected condition.
by this action must be notified. That there is no leakage from the Dry
Step 12. Open (energize) the Solenoid
Pilot Actuator (Fig. 3B)
The owner is responsible for the in- Valve by operating the Deluge Valve Re-
spection, testing, and maintenance of NOTICE leasing Panel and verify the following:
their fire protection system and devices That the DV-5 Valve operates as is in-
During this procedure, the Solenoid
in compliance with this document, as dicated by a discharge of water from
Valve is opened; however, the Dry Pilot
well as with the applicable standards the System Main Drain Valve and the
Actuator should remain closed and the
of the National Fire Protection Associa- Automatic Drain Valve. The Automatic
DV-5 Deluge Valve Diaphragm Cham-
tion (e.g., NFPA 25), in addition to the Drain Valve may or may not close de-
ber should remain pressurized.
standards of any authority having juris- pending on the flow past the partially
diction. Contact the installing contrac- This procedure is used to verify that the open Main Control Valve
tor or product manufacturer with any DV-5 Deluge Valve will remain set if the
questions. electric detection system operates but That the Model FSV-1 Fail-Safe Valve
the sprinkler system remains in its nor- has operated as is indicated by water
It is recommended that automatic discharging into the Drip Funnel from
mally pressurized condition.
sprinkler systems be inspected, tested, the 1/2 inch drain tube connected to
and maintained by a qualified Inspec- Step 3. Open the Inspectors Test Con- the Model FSV-1 Fail-Safe Valve
tion Service in accordance with local nection but be prepared to close it im-
requirements and/or national codes. mediately after verifying that the Low That the Waterflow Pressure Alarm
Pressure Alarm Switch (Fig. 3B) and Switch (Fig. 3B) and its associated
It is recommended that the System In- alarms properly operate
its associated alarms operate properly.
spection Procedure be performed at
The Low Pressure Alarm Switch should That the Water Motor Alarm, if appli-
least semi-annually by a qualified In-
operate at the previously established cable, properly operates
spection Service. The Double Interlock
pressure (refer to Installation section,
Preaction System Inspection Procedure
Step 11). NOTICE
may be followed in lieu of performing
any of the operational tests recom- Close the Inspectors Test Connection. This procedure simulates opening of
mended in the Technical Data Sheets Step 4. Close the Diaphragm Chamber both the Dry Pilot Actuator (loss of sys-
for the DV-5 Deluge Valve, Riser Check Supply Control Valve (Fig. 3B). tem air pressure) and Solenoid Valve
Valve, 24 VDC Solenoid Valve, Dry Pi- (operation of the Deluge Valve Releas-
lot Actuator, and Model MC-1 Manual Step 5. Close the System Shut-Off ing Panel) to verify automatic system
Control Station. Valve (Fig. 1) after the system air pres- operation.
sure has been restored to normal.
It is recommended that the individuals Step 13. Reset the Double Interlock
responsible for the care and mainte- Step 6. Manually restore the electric fire Preaction System in accordance with
nance of the Double Interlock Preac- detection system to a normal condition the Resetting Procedure section.
tion System develop a working under- in accordance with the manufacturers
standing of the system, in general, prior instructions. The Solenoid Valve will Fail-Safe Valve
to performing inspection and/or mainte- then be de-energized and returned to If water does not discharge from the
nance procedures. These instructions, its normally closed position. 1/2 inch tube connected to the Model
as well as individual instructions for the Step 7. Open the Diaphragm Chamber FSV-1 Fail-Safe Valve during Step 12 of
deluge valve, riser check valve, sole- Supply Control Valve (Fig. 3B).
noid valve, dry pilot actuator, manual
TFP1460
Page 14 of 16

the System Inspection Procedure, the


Model FSV-1 Fail-Safe Valve is to be Limited Coupling (Select One)
P/Ns are for American Standard
disassembled, cleaned, and inspected
as follows: Warranty Grooved Connections. For other con-
figurations and finishes refer to Techni-
For warranty terms and conditions, visit cal Data Sheet TFP1830 and TFP1880.
Step 1. Take the sprinkler system out
www.tyco-fire.com. A coupling to attach the Riser Check
of service by using Steps 1 through 4
Valve to the outlet of the Deluge Valve
of the Resetting Procedure.
must be separately ordered. Specify:
Step 2. Remove the FSV-1 from the
Double Interlock Preaction Trim.
Ordering (Size), (Figure #), painted, (description),
P/N (specify). For 1-1/2 inch risers, or-
Step 3. Refer to Technical Data Sheet Procedure der an additional Reducing Coupling
for the outlet of the 2 inch Riser Check
TFP1386 and completely disassemble The DV-5 Deluge Valve with Double
the FSV-1. Valve.
Interlock Preaction Electric/Pneumat-
2 x 1-1/2 Inch Figure 716
Step 4. Clean all parts, and replace ic trim can be ordered pre-trimmed
Painted Reducing Coupling . . . . P/N 7162015ES
worn or damaged parts as necessary. or non-assembled as separate items. 2 Inch Figure 772
For non-assembled the following items
Step 5. Reassemble the FSV-1 in ac- must be ordered separately:
Painted Rigid Coupling . . . . . . . . P/N 77220ASC
cordance with Technical Data Sheet 3 Inch Figure 772
DV-5 Deluge Valve Painted Rigid Coupling . . . . . . . . P/N 77230ASC
TFP1386 and then reinstall the FSV-
4 Inch Figure 772
1 into the Double Interlock Preaction CV-1FR Riser Check Valve Painted Rigid Coupling . . . . . . . . P/N 77240ASC
Trim. 6 Inch Figure 772
Couplings
Step 6. Place the system into service Painted Rigid Coupling . . . . . . . . P/N 77260ASC
in accordance with the Resetting Pro- Double Interlock Preaction Electric/ 8 Inch Figure 772
cedure section and then perform the Pneumatic Trim, Semi-Preassembled Painted Rigid Coupling . . . . . . . . P/N 77280ASC
System Inspection Procedure to verify Supervisory Air Supply Double Interlock Preaction Trim
proper operation of the system, as well (Select One)
as the FSV-1 Fail-Safe Valve. Accessories Specify: (specify size and finish gal-
NOTE: 1-1/2 inch (DN40) risers utilize vanized is standard) Semi-Preassem-
Quarterly Waterflow Alarm Test bled Double Interlock Preaction System
a 2 inch (DN50) Model CV-1FR Riser
Procedure Check Valve connected to the 1-1/2 with Electric/Pneumatic Actuation Trim
Testing of the system waterflow alarms inch (DN40) DV-5 Deluge Valve by a for DV-5 Deluge Valves, P/N (specify):
must be performed quarterly. To test 2 x 1-1/2 inch Figure 716 Reducing 1-1/2 & 2 Inch Galvanized . . . . P/N 52-478-2-327
the waterflow alarm, open the Alarm Coupling. 1-1/2 & 2 Inch Black . . . . . . . . P/N 52- 478-1-327
Test Valve, which will allow a flow of 3 Inch Galvanized . . . . . . . . . . P/N 52-478-2-124
water to the Waterflow Pressure Alarm Replacement Trim Parts 3 Inch Black . . . . . . . . . . . . . . P/N 52-478-1-124
Switch and/or Water Motor Alarm. Specify: (description) for use with DV-5 4, 6 & 8 Inch Galvanized . . . . . P/N 52-478-2-321
Upon satisfactory completion of the Deluge Valve, P/N (see Figure 3A) 4, 6 & 8 Inch Black . . . . . . . . . P/N 52-478-1-321
test, close the Alarm Test Valve.
Automatic System Air Supply
DV-5 Deluge Valve (Select One)
P/Ns are for American Standard Groove (Select One)
A device capable of maintaining a nominal
x Groove Connections, and Threaded system air or nitrogen pressure per Graph
Ports. For other configurations refer to A must be separately ordered. Specify:
Technical Data Sheet TFP1305. Speci- (model and description), P/N (specify):
fy: (size) DV-5 Groove x Groove Deluge Model AMD-1 Air Maintenance
Valve, P/N (specify): Device (TFP1221) . . . . . . . . . . P/N 52-324-2-002
1-1/2 Inch . . . . . . . . . . . . . . . . P/N 52-477-1-919 Model AMD-2 Air Maintenance
2 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-910 Device (TFP1231) . . . . . . . . . . P/N 52-326-2-001
3 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-912 Model AMD-3 Nitrogen Maintenance
4 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-913 Device (TFP1241) . . . . . . . . . . P/N 52-328-2-001
6 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-915 Solenoid Valve (Select One)
8 Inch . . . . . . . . . . . . . . . . . . . . P/N 52-477-1-916 A Solenoid Valve compatible with the
Riser Check Valve (Select One) anticipated maximum water supply
P/Ns are for American Standard pressure must be ordered separately.
Grooved Connections. For other config- Refer to Technical Data Sheet TFP2180
urations refer to Technical Data Sheet for other voltage ratings and NEMA
TFP950 for the Groove x Groove Mod- classifications. Specify: 24 VDC, NEMA
el CV-1FR Riser Check Valve. Specify: 2, 4 and 4X, (specify 175 or 250 psi) So-
(size), Model CV-1FR Groove x Groove lenoid Valve, P/N (specify):
Riser Check Valve, P/N (specify): 175 psi . . . . . . . . . . . . . . . . . . . P/N 52-287-1-024
2 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-020 250 psi . . . . . . . . . . . . . . . . . . . P/N 52-287-1-124
3 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-030
4 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-040
6 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-060
8 Inch . . . . . . . . . . . . . . . . . . . . P/N 59-590-1-080
NOTE: For 1-1/2 inch (DN40) risers, use
the 2 inch (DN50) Riser Check Valve.
TFP1460
Page 15 of 16

Pre-Trimmed DV-5 Assembly with


Butterfly Valve
Specify: (size), G x G End Connection,
Pre-Trimmed DV-5 Assembly with But-
terfly Valve, P/N (specify):
1-1/2 Inch G x G . . . . . . . . . . . P/N 52-917-0-1AP
2 Inch G x G . . . . . . . . . . . . . . P/N 52-927-0-1AP
3 Inch G X G . . . . . . . . . . . . . . P/N 52-937-0-1AP
4 Inch G x G . . . . . . . . . . . . . . P/N 52-947-0-1AP
6 Inch G x G . . . . . . . . . . . . . . P/N 52-967-0-1AP
8 Inch G x G . . . . . . . . . . . . . . P/N 52-987-0-1AP
Pre-Trimmed DV-5 Assembly
without Butterfly Valve
Specify: (specify size), (specify) End
Connection, Pre-Trimmed DV-5 As-
sembly without Butterfly Valve, P/N
(specify):
3 Inch F x G . . . . . . . . . . . . . . . P/N 52-937-2-1AP
4 Inch F x G . . . . . . . . . . . . . . . P/N 52-947-2-1AP
6 Inch F x G . . . . . . . . . . . . . . . P/N 52-967-2-1AP
8 Inch F x G . . . . . . . . . . . . . . . P/N 52-987-2-1AP
Accessories (As Needed)
Specify: (description), P/N (specify)
600 PSI Water Pressure
Gauge . . . . . . . . . . . . . . . . . . . P/N 92-343-1-004
Model WMA-1 Water Motor
Alarm (TFP921) . . . . . . . . . . P/N 52-630-1-001P
TFP1460
Page 16 of 16