-178.11
-516.7279
-855.3458
-1193.9638
-1532.5817
-1976.8657
-1976.7729
NIVEL Carga Muerta Carga Viva Vx Vy
Tapa Tanque 9.0072 0 2.847 3.3972
Elevado
Base Tanque 30.0504 0 11.0574 12.5868
Elevado
Azotea 173.6349 18.9886 44.1087 54.888
Quinto Piso 317.2195 53.7478 75.6188 89.8824
Cuarto Piso 460.804 88.507 97.6835 114.9158
Tercer Piso 604.3886 123.2662 113.5684 132.4228
Segundo Piso 747.9731 158.0254 124.0791 143.2896
Primer piso 909.8248 199.2882 129.0204 148.4615
Semi Sotano 945.6776 199.2882 129.7893 149.0894
s 0.311
Vest 298.45
Vx% 2.07
%Vy 1.80
V 278.7854
Excentricidad Excentricidad
XCM (m) YCM (m) XCR (m) YCR (m) X-X (m) Y-Y (m)
NIVEL
Semi-Sotano 10.7841 5.2553 11.8806 5.3271 1.0965 0.0718
Primer piso 10.1438 4.415 10.0266 7.8753 -0.1172 3.4603
Segundo Piso 10.1438 4.415 9.4594 8.6024 -0.6844 4.1874
Tercer Piso 10.1438 4.415 9.0935 8.8071 -1.0503 4.3921
Cuarto Piso 10.1438 4.415 8.8223 8.8663 -1.3215 4.4513
Quinto Piso 10.0281 4.5291 8.634 8.8865 -1.3941 4.3574
Derivas
Deriva CM x- Deriva CM y-y Deriva Max Deriva Max Ratio X-X
NIVEL x x-x y-y
Azotea 0.0030 0.0039 0.0044 0.0059 1.50
Quinto Piso 0.0032 0.0039 0.0046 0.0060 1.43
Cuarto Piso 0.0031 0.0037 0.0044 0.0056 1.42
Tercer Piso 0.0027 0.0031 0.0038 0.0047 1.42
Segundo Piso 0.0018 0.0021 0.0025 0.0027 1.40
Primer piso 0.0002 0.0005 0.0003 0.0007 1.46
Base 0.0000 0.0000 0.0000 0.0000 0.00
Verificacin
ETIQUETA SECCION P (ton) M3 (ton.m) M2 (ton.m) % Capacidad Momento
C1 80x30 33.71 3.96 2.61 24.60% Ok
C3 50 173.4 2.777 5.524 73.30% Ok
C4 50 197.87 6.41 3.74 83.90% Ok
C5 110x65 25.85 6.52 4.12 13.80% Ok
Psismico Area Tnf/m2
1062.23
Ratio Y-Y
1.53
1.53
1.52
1.51
1.32
1.40
0.00
2.847 3.3972
2.85 3.40
11.0574 12.5868
8.21 9.19
44.1087 54.888 33.05 42.30
75.6188 89.8824 31.51 34.99
97.6835 114.9158 22.06 25.03
113.5684 132.4228 15.88 17.51
124.0791 143.2896 10.51 10.87
129.0204 148.4615 4.94 5.17
129.7893 149.0894 0.77 0.63
Load P VX VY T MX
Story Case/Comb Location
o tonf tonf tonf tonf-m tonf-m
S X ampli
Azotea Bottom 0 94.8366 79.2872 944.5198 259.1529
Max
S Y ampli
Azotea Bottom 0 71.5037 102.6363 1197.6075 318.3326
Max
tonf-m
9.1819
7.8568
59.0594
50.5758
295.8191
229.1209
709.0029
517.3357
1242.3132
880.5091
1852.2048
1298.523
2511.4302
1747.3786
2937.707
2036.7786
3204.1396
2213.9269
VERIFICACION DE LA COLUMNA ESTRUCTURAL
Load
Unique
Story Column Case/Comb Station P V2 V3
Name o
Semi Sotano C4 198 Envolve Max 0 -92.6921 3.881 -1.5288
T M2 M3
P Mx My
CM -104.5074 -1.6696 1.6234
CV -28.4683 -0.5914 0.5606
Sx 1.3645 0.5343 0.382
Sy 1.0145 0.66 0.1707
Cumulative Cumulative
Mass X Mass Y XCM YCM
Story Diaphragm X Y
tonf-s/m tonf-s/m m m tonf-s/m tonf-s/m
Primer piso D1 13.40902 13.40902 10.7841 5.2553 13.40902 13.40902
Segundo D2 11.48021 11.48021 10.1438 4.415 11.48021 11.48021
Piso
Tercer Piso D3 11.48021 11.48021 10.1438 4.415 11.48021 11.48021
Cuarto Piso D4 11.48021 11.48021 10.1438 4.415 11.48021 11.48021
Quinto Piso D5 11.48021 11.48021 10.1438 4.415 11.48021 11.48021
Azotea D6 10.48875 10.48875 10.0281 4.5291 10.48875 10.48875
m m m m
10.7841 5.2553 11.8806 5.3271
Dx Dy
Azotea 0.010694 0.013174
Quinto Piso 0.00842 0.0102
Cuarto Piso 0.00595 0.007184
Tercer Piso 0.003565 0.00434
Segundo 0.001505 0.001942
Piso
Primer piso 0.000152 0.00036
Semi Sotano 0 0
0.002111 0.002597
0.000222 0.000504
0 0
1.4CM+1.7CV
197.8704 -3.4916 3.1785 4.8075 -4.2684
1.25*(CM+CV)+/-CSx Max
166.9868 -2.3662 3.0514 4.678 -3.0003
1.25*(CM+CV)+/-CSY Max
167.6894 -2.3403 2.8581 5.0181 -3.061
0.9CM+/-CSX Max
93.6121 -0.9849 1.8004 2.7803 -1.3217
0.9CM+/-CSY Max
94.3147 -0.959 1.6071 3.1204 -1.3824
M3 M2 M3
3.1785 4.8075 -4.2684
3.0514 4.678 -3.0003
2.8581 5.0181 -3.061
1.8004 2.7803 -1.3217
1.6071 3.1204 -1.3824
Momento Momento
Ultimo Resistente
ETIQUETA SECCION % Capacidad Verificacin ETIQUETA SECCION
Actuante Ultimo
(Ton.m) (Ton.m)
B9 20x65 15.48 29.67 52.17% Ok B9 20x65
B9 30x60 -11.76 -44.27 26.56% Ok B9 30x60
B25 25x40 12.85 34.19 37.58% Ok B25 25x40
B25 20x65 -17.14 -42.16 40.65% Ok B25 20x65
B5 30x60 2.46 22.45 10.96% Ok B5 30x60
B5 25x40 -9.44 -22.75 41.49% Ok B5 25x40
Cortante Cortante
Ultimo Resistente % Capacidad Verificacin
Actuante Cortante
Ultimo (Ton)
(Ton)
13.81 14.68 94.07% Ok
-14.74 -14.68 100.41% Ok
17.12 29.67 57.70% Ok
-14.62 29.67 -49.28% Ok
2.35 19.34 12.15% Ok
-9.87 29.67 -33.27% Ok