AUTOSYNCHRONIZING RELAY,
USING DOBLE's TEST EQUIPMENT
& PROTEST ASYNCH MACRO
PT-BUS
SYNCROCLOSER
M-193B
CLOSE CB
TB 1
* BUS
1
2
UNIT POWER 3
TRANSFORMER 4
GENER.
PT-GENERATOR
*
11
CLOSING TIME
GENERATOR 180 ms
60.1Hz 20
26
27
TB 2
28
A
CLOSE CB B
COMMAND
PT-POTENTIAL TRANSFORMER
1.2. CB closing is allowed only, when
the two sources are:
* Close to synchronism within the ALLOWED
CB Closing Angle
* In phase.
The allowed CB Closing Angle is the calculated
angle to insure the Generator & Power System
safety & stability.
Allowed CB
Closing Area
0 1 V GEN
3 2 1 0 1 2 3
2.29 1.29 0.29
x x
7 6 5 4 3 2 1 0
TB2
A
Breaker Close Contact
B
3. OPTIONS OF TESTING (see Fig.4)
0.5
CB Closing Time = 80 ms
-0.5
0 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.45 0.475
Slip Frequency (Hz), Fast
Breaker Closing Angle Error Comparison (using all three methods and F6150 and Asynch Macro)
CONCLUSION
1.During testing the reported Closing Angle
Error test results were less than Expected &
shown in Relay Instruction Book Information
(see Fig, 5, 6).
Ref. Syncrocloser Unit M-0193B Application Guide.