DATOS DE ENTRADA
Caudal de diseo 72 m3/hr
Cota terreno 137.2 msnm
Cota Entrada afluente a la Estacin de Bombeo 136.2 msnm
Cota del Nivel de Entrega 160.6 msnm
Longitud entre salida de Estacin de Bombeo y descarga 520 m
Temperatura del liquido 20 C
Tiempo del ciclo requerido 15 min
Valor por kW $/kW.hr
Periodo de diseo aos
Tasa Aumento del costo energtico
Tasa de descuento EA
21.9
0
0
7.2
0.1
0
0
0
1.35
0
0
0.2
0
0
1
0
0
1
INFORMACIN DEL PUNTO BOMBEO
Caudal 20.00 l/s Dimetro de tubera 6.00
Caudal 72 m3/hr Prdidas por friccin Impulsin 1 4.08
Caudal 317.46 gpm Prdidas menores Impulsin 1 0.66
Altura Geomtrica 26.95 m Peso especfico 9.789
Altura Total 31.69 m Potencia til 9.31
16
Froude 0.9
Pendientes de trabajo de tuberas PVC SDR 21
FRMULA DE DARCY
Rugosidad [k] 0.0015 mm
Q1 (m3/s) 0.020 m3/s
1 2 3 4
CODE PN D A V hv
DN D Real bar Espesor mm m2 m/seg m
3 88.5 10.0 4.2 80 0.01 3.97 0.80
4 114 10.0 5.4 103 0.01 2.39 0.29
6 168 10.0 8.0 152 0.02 1.10 0.06
8 219 10.0 10.4 198 0.03 0.65 0.02
10 273 10.0 13.0 247 0.05 0.42 0.01
12 323 10.0 15.4 292 0.07 0.30 0.00
PN D A V hv
bar mm m2 m/seg m
3 88.5 10.0 4.2 80 0.005 3.97 0.80
4 114 10.0 5.4 103 0.008 2.39 0.29
6 168 10.0 8.0 152 0.018 1.10 0.06
8 219 10.0 10.4 198 0.031 0.65 0.02
10 273 4.0 13.0 247 0.048 0.42 0.01
12 323 10.0 15.4 292 0.067 0.30 0.00
FRMULA DE MANNING
n (Manning) 0.01
Q (m3/s) 0.020 m3/s
PN D A V hv
bar mm m2 m/seg m
3 88.5 10.0 4.2 80 0.01 3.97 0.80
4 114 10.0 5.4 103 0.01 2.39 0.29
6 168 10.0 8.0 152 0.02 1.10 0.06
8 219 10.0 10.4 198 0.03 0.65 0.02
10 273 10.0 13.0 247 0.05 0.42 0.01
12 323 10.0 15.4 292 0.07 0.30 0.00
de tuberas PVC SDR 21
5 6 7 8 9
Re f n S
%
2.09E+05 0.0156 0.0073 15.603%
1.62E+05 0.0163 0.0078 4.600%
1.10E+05 0.0176 0.0087 0.715%
8.46E+04 0.0185 0.0093 0.200%
6.79E+04 0.0194 0.0099 0.070%
5.74E+04 0.0201 0.0104 0.031%
Re f n S
%
2.09E+05 0.0145 0.0071 15.680%
1.62E+05 0.0150 0.0075 4.565%
1.10E+05 0.0158 0.0082 0.693%
8.46E+04 0.0163 0.0087 0.190%
6.79E+04 0.0168 0.0092 0.065%
5.74E+04 0.0172 0.0096 0.029%
Re f n S
%
2.09E+05 0.0286 0.0100 28.715%
1.62E+05 0.0263 0.0100 7.440%
1.10E+05 0.0232 0.0100 0.945%
8.46E+04 0.0212 0.0100 0.230%
6.79E+04 0.0198 0.0100 0.071%
5.74E+04 0.0187 0.0100 0.029%
DIMENSIONAMIENTO POZO HMEDO DEL BOMBEO DE AGUA RESID
Dimetro 2.50 m
h3 (altura til) 2.30 m
(NMax) Nivel de Alarma Aguas Mximas 136.00 msnm
(NA) Nivel de Arranque 135.95 msnm
(NP) Nivel de Parada 133.65 msnm
(NMin) Nivel de Alarma Aguas Mnimas 133.60 msnm
(CF) Cota fondo pozo 133.20 msnm
Altura total del pozo hmedo 4.00 m
MBEO DE AGUA RESIDUAL
CT: 137.20
NMax 136.00
NA 135.95
NP 133.65
NMin 133.60
CF 133.20