F A U L T R E C O R D E R S

Platinum 2.5K Multi-Function Recorder


FOR GENERATION, TRANSMISSION, AND DISTRIBUTION POWER SYSTEM MONITORING

MULTI-FUNCTION
RECORDER
For all types of power system
events, the Platinum 2.5K
Multi-Function Recorder pro-
vides all the information you
need to capture the complete
picture. With the true integrated
functionality of the Platinum
2.5K, you have one place for all
your answers. Simultaneously
perform: transient recording,
disturbance recording, phasor measurements, power
quality analysis, and sequence of events recording. FEATURES AND BENEFITS
The Platinum 2.5K provides answers when you need
them with as much information as you need to get Transient fault recorder - post fault analysis
results quick. The system can operate automatically to verify protection and circuit breaker
to retrieve events and perform an expert analysis so operations, fault clearance times
you have the answers fast, saving time and money.
The Platinum 2.5K takes the place of several devices, Disturbance recorder/logger - analyze
integrating their functions into one unit, saving you power system stability by recording recluse
money on equipment and installation while provid- sequences, power swing, and frequency
ing all the answers in one software platform. All of oscillations
these functions are performed at the highest level so
it will meet your needs of today and in the future. In Trend recording - verify voltage regulation
a deregulated environment, the Platinum 2.5K is the and balancing
best tool to provide the necessary data to increase
revenues and retain your customers. Power quality monitor - voltage and
The Platinum 2.5K recorder incorporates the latest frequency profiles, voltage dips and surges,
advancements in technology and low power com- loss of supply, harmonic content, flicker,
ponents for ultimate reliability. No longer needing a voltage and current imbalance
hard drive, the units 40GB Solid State Drive can
store over 1000 fault and disturbance records Automatically or manually export fault,
simultaneously, providing a large volume of both disturbance and power quality data using
high-speed sinusoid data for traditional fault the IEEE Std 1159.3 PQDiff or IEEE Std
analysis and slower speed data for disturbance or C37.111 COMTRADE format
swing recording. The unit also includes steady-state
logging of RMS and harmonic spectrum values on Phasor Measurement Unit - synchronized
every channel and frequency as a standard feature. phasor measurements, in accordance with
Optimize your power system to improve reliability, IEEE Std C37.118-2005
shorten your fault clearance times, and verify correct
operation of your switchgear and protection equip- Fault locator - calculates distance to fault
ment. The Platinum 2.5K is ideally suited for your based on configurable line model
generation, transmission, and distribution power sys-
tem monitoring. Real time monitor - view analog, digital
inputs, and computed values in near real time
The Platinum 2.5K can be matched to any application
with 16 models available in one robust, utility-hard- Multiple simultaneous connections over
ened chassis: serial, modem or Ethernet, secured with
8 Analog / 16, 48, 80, 112 or 144 Digital Inputs
strongly encrypted passwords.
16 Analog / 32, 64, 96, 128 or 160 Digital Inputs
24 Analog / 48, 80 or 112 Digital Inputs Sequence of events recorder - 1 msec or
32 Analog / 64, 96 or 128 Digital Inputs better resolution on digital contacts

POWER INSTRUMENTS

Experience the Power


F A U L T R E C O R D E R S

SPECIFICATIONS
INPUTS RECORDING COMMUNICATIONS
Number of Channels (DISTURBANCE LOGGING) Serial Ports
8, 16, 24, or 32 Analog 2 x RS232 type
16, 32, 48, 64, 80, 96, 112, 128, 144
OPTIONAL
Default Setting
Sample Rate
or 160 Digital 57.6 kbaud, 8 bits, 1 stop, no parity.
Voltage Inputs 1/2 x supply frequency (25/30 Hz) Rates can be set up to 115 kbaud.
63.5 or 110 V RMS nominal Recording Time Modem
Current Inputs 2 weeks Hayes compatible type internal or
1 A or 5 A RMS nominal (thru current external, fax compatible
shunts/CICTs) RECORDING (TREND) Phone Line Sharing
Frequency Response Sampling Interval External unit to share a single phone
DC 1/2 sampling rate (1/4 sampling 1 minute, or 10 minutes data can line with a station phone
rate for 384 samples per cycle only) be retrieved at up to a 60 minute Network
Accuracy interval 10Base2 (50 ohm coax and BNC),
Better than 0.1% of full scale Record Length 10baseT, Fiber
Digital Inputs 52 weeks Network protocol: TCP/IP
24/48/125/250 VDC normally open or Stored Parameters
closed wetted contact Maximum, minimum, and average DATA STORAGE
voltage, current, frequency (2), power, Permanent Storage
RECORDING (TRANSIENT) flicker, harmonics, and imbalance.
Digital data in SER format at user 40 GB Solid State Drive
Recording Resolution defined time resolution
16 bits, 65536 levels (15 plus sign) POWER SUPPLY
Sample Rate TRIGGERING (TRANSIENT) Input Voltage Options
384 samples per cycle 100 to 300 VDC, 85 to 264 VAC,
Analog Channels
Optional: 768 samples/cycle (optional 85 to 150 VDC, 85 to
Over/under RMS level, Rate-of-
Pre-fault Time 264 VAC)
Change and THD. Positive, zero and
2 to 600 cycles negative sequence triggers, over, Power Requirement
Post-fault time under and R-o-C frequency triggers, 60VA (16 channel), 70VA (32 channel)
Fault length will extend as long as a differential frequency
trigger condition exists. Minimum is Digital Channels VOLTAGE WITHSTAND
8 to 100 cycles Normal to alarm state and return to Isolation, Impulse Voltage, RFI and
normal state. Edge or level sensitive
Safety Window ESD per IEEE/IEC Standards
Number of 'clear' cycles that must
occur at the end of the recording: TRIGGERING ENCLOSURE
0 to 16 cycles (DISTURBANCE) Cabinet
Maximum Record Length Analog Channels 6U TR-2508 and TR-2516
Maximum size 1 to 60 sec. (this pre- Under/over level of fundamental and 8U TR-2508-D1, TR-2508-D2,
vents memory filling with a continuous R-o-C, frequency and ROCOF, power TR-2516-D1, TR-2516-D2, TR-2524
trigger) and frequency oscillation, imbalance and TR-2532
and impedance, cross trigger from 9U TR-2508-D3, TR-2508-D4,
RECORDING transient recorder TR-2516-D3, TR-2516-D4,
TR-2524-D1, TR-2524-D2,
(DISTURBANCE) SYSTEM TIMING TR-2532-D1, and TR-2532-D2
Sample Rate Time Source
2 x supply frequency (100/120 Hz) ENVIRONMENT
Internal GPS receiver with 1 PPS Operating Temperature
Pre-fault output for phasor measurement
10 sec. to 10 min. 14O to 131OF (-10O to 55OC)
Optional IRIG-B
Relative Humidity
Post-fault Time Accuracy
0 to 97% non-condensing
Fault length will extend as long as a Normally better than +/- 60 ns
trigger point condition exists. Synchronization
Minimum value is 30 sec. to 5 min. CERTIFICATION
1 pulse per second on optical port.
Maximum Record Any number of systems can be linked CE
Absolute maximum: 30 minutes together
Computed Values
Voltage and current, real power,
reactive power, apparent power,
power factor, total harmonic POWER INSTRUMENTS
distortion and frequency (x2), positive,
negative and zero sequence, voltage
imbalance

For Customer Support U.S.A. Headquarters European Headquarters Asia Pacific Headquarters AMETEK Instruments India PVT. LTD.

AMETEK Power AMETEK Power Instruments Unit 21 Suite 6, Ridgeway No. 43 Changi South Avenue 2 1st Floor, Prestige Featherlite Tech Park
Instruments 50 Fordham Road Donibristle Industrial Estate #04-01 Plot 148, EPIP Phase II
255 North Union Street Wilmington, MA 01887 Dunfermline Singapore 486164 Whitefield, Bengaluru 560 066
Rochester, NY 14605 Tel: +1 978.988.4903 Fife, Scotland KY11 9JN, UK Tel: +65 6484.2388 Tel: +91 80.67823252
Tel: +1 585.263.7700 Fax: +1 978.988.4990 Tel: +34 672.729.762 Fax: +65 6481.6588 Fax: +91 80.67823232
Fax: +1 585.454.7805 power.sales@ametek.com Fax: +44 1383.825715 sales@ametekasia.com power.sales@ametek.com
www.ametekpower.com power.sales@ametek.com
power.sales@ametek.com

2014, by AMETEK, Inc. All rights reserved. 25M606A (2100XX) ISO 9001 Certified