Вы находитесь на странице: 1из 7

BUSBAR SIZING CALCULATION

Published on Published onDecember 21, 2015

V.R V

FollowFollow V.R V
Li ke 199
22
Comment

35
Write an article

Generally there are 'THREE' Factors are involved for the Fire Causes. They are"

I) Accidental.

II) Natural.

III) Incendiary.

Comparing 'THREE', the most dangerous one is 'ACCIDENTAL'. Here Electricity


plays major role for the Fire Accident most of the Times.

There are 'THREE' Elements must be present, for a 'FIRE' to initiate. These are
Oxygen, Fuel and Heat. Electricity Plays major role to provide 'HEAT' most of the
Times.

SOURCES for the 'HEAT' in the 'ELECTRICAL SYSTEMS' :

Most of the Time, Fire happens in the Electrical Panels, Which we observed from
the Existing Cases. So it is better to mention that, Sources for the 'HEAT' in the
Electrical Panels.

a) SHORT CIRCUIT.
b) OVER LOAD.

c) POOR QUALITY IN EARTHING DESIGN.

d) ABSENCE OF VENTILATION IN THE PANELS.

e) POOR QUALITY IN DESIGNING. [Ex. Under Sized Cables].

Anything else apart from the Above,...........................................Yes. That Source


should be Top in the above list.

What is that 'Important Factor'??... It is none other than 'UNDER SIZED BUSBAR
IN THE PANELS'...

This Article Gives Clear Picture of 'BUSBAR SIZING CALCULATION' and


What Care We should have to take 'Sizing of Busbar'. Here I will like to describe
Busbar Sizing of LT & HT Panel System. While This Methodology doesn't
have any relation with 'CALCULATION OF CONDUCTOR BUS SIZING
[ACSR]' for the Switch yard Projects. Both Calculations having different Steps &
Procedure to find Final Results.

The 'Electrical Design Engineer' Should have in-depth knowledge of 'Sizing of


BUSBAR for the Electrical Panels [Both HT & LT]. I have seen many times in my
past experience, Most of the Engineers doing Busbar Sizing Calculation by 'Thumb
Rule' Method, Even though Some of the Senior Engineers in the Consultant offices
& Leading Panel Fabricator will Practice the Same 'THUMB RULE' method.

There are methods are exist in the world, To determine Proper sizing of Busbar for
the Electrical Systems. People not have that much Patience for the Practicing
Calculation. Now Software available to determine Proper Size of Busbar for the
panels. I would like to add more inputs in this article, which I had experienced in
my past years.
THUMB Rule for Busbar :

For Aluminium : 0.7 Amps / 1 Sq.mm of Bar.

For Copper : 1.2 Amps / 1 Sq.mm of Copper.

Here the above mentioned rules are not standard. Because some case people will
add Tolerance in the Positive End. i.e They used 0.75 Amps / 1 Sq.mm of Bar &
1.4 Amps / 1 Sq.mm for Aluminium & Copper Respectively.

The Cost of the Aluminium bar in the Market based on the Quality. While
Practicing 'THUMB' Rule people should aware the Quality Standards of
Aluminium & Copper Bar. Sometimes we didn't aware the bar Quality which is
used by the fabricator in the Panel. Panel Fabricators should not take responsible in
case Panel gets fire due to the Busbar Under Sized. It will directly hit EPC
Contractor Market Value in the Industry.Also it leads to Black Mark in their
Industry. He should have to answer Client, Electrical Inspectorate & Consultant.
So People should take More Care for Busbar Sizing for both LT & HT Panels.

I would like to share one of the Example I experienced in my past. Consultant


given Busbar Size for the Main MV Panel. [That Panel should cater 10 MW of
Power of the IT Building, Panel gets power from 3 Transformers & 6 Generators].
Panel should capable to Carry 6300A. Busbar Size Should be Equal or More than
of 6300A. Consultant Recommended Busbar Size based on the 'THUMB Rule' We
noticed, Busbar Size is Low to Carry 6300A. Consultant Challenged Contractor
that, His recommended Size of Busbar will carry full load Current, then Contractor
approached 'CPRI Testing for their internal verification. Finally Busbar gets melted
when it carried full load Current [6300A] for the interval 1 Minute. Here it is not
the case for the carrying Short Circuit Current. If Busbar doesn't able to carry the
Full Load Current, then how it will carry Short Circuit Current for the Second.???
After that we will fabricate the Panel with Proper Sizing of busbar which we
derived from the Proper Calculation. In some cases people only practicing
Calculation with only consider the 'K' Factors. There is formula exist apart from
the 'K' Factors.

The Design Engineer should consider the following points while doing
'BUSBAR SIZING CALCULATION':

Adequate minimum required clearance between Phases and Phase to Earth.


Selection of Adequate Busbar Insulator Standoffs.
Bolting Arrangements for Continuous Busbar Connections.
Thermal Effects on Busbar and Insulator Standoffs under normal and Fault
conditions.
Electrodynamic Forces applied to Busbars and Insulator Standoffs under
Fault Conditions.
Avoidance of mechanical resonance under normal operating and Fault
Conditions.

TEMPERATURE RISE:

Maximum Permissible Temperature Rise for bolt - connected devices, including


busbars

Source Reference : IEC 62271 - 1


Co-Efficient Factors 'K' :

The Total 'K' Factor derived from Six 'K' factors, which is listed below :

K = K1 x K2 x K3 x K4 x K5 x K6

K1 is a Function of the Number of Bars per Phase and their space.

K2 is Corresponds to the Surface Finish of the Busbars.

K3 is a Function of the Mounting Arrangement.

K4 is a Function of the Installed Location.

K5 is a Function of any Artificial Ventilation.

K6 is a Function of the Type of Current.

Busbar Clearances as per IS : 4237 - 1967

Example :

Transformer Rating : 11 / 0.433 kv, 800 kVA Transformer. What is the


recommendable size of Copper Busbar in the LT Panel ??
If we consider 80 x 10 mm of Copper Bar, How many bars required to carry full
load current of Transformer Secondary End ?

Transformer Secondary Full load Current = 1066.72A,

Breaker Size Needed = 1250A. [Either ACB or MCCB]

According to Thumb Rule,

For Copper : 1.2 Amps / 1 Sq.mm of Copper.

for the Area 800 Sq.mm [80 x 10 mm], Current Carrying Capacity will be 960A..,
Then additional one Run of Busbar needed to carry the Current of 1067A.

According to the Formula as per IEC 62271 - I

K = K1 x K2 x K3 x K4 x K5 x K6

K = 1 x 1 x 1 x 0.8 x 1 x 1 = 0.8

According to the Main Formula, Derived Value will be = 1547A

Rated Current = 0.8 x 1547 A = 1238 A

Conclusion:

To Carry the Current of 1067 A, One Run of 80 x 10 mm of Copper Bar is


enough.

Cheers !!!

Вам также может понравиться