JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-1 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 150 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 47 WB - OF 82 WB - OF 64
PARTITION AREA 197 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 150 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 150 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1200 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1200 x 0.0166 = 20
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-2 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 159 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 55 WB - OF 82 WB - OF 64
PARTITION AREA 85 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 159 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 159 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1272 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1272 x 0.0166 = 21
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-3 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 160 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 56 WB - OF 82 WB - OF 64
PARTITION AREA 86 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 160 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 160 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1280 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1280 x 0.0166 = 21
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-4 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 135 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 42 WB - OF 82 WB - OF 64
PARTITION AREA 72 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 135 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 135 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1080 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1080 x 0.0166 = 18
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-5 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 135 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 42 WB - OF 82 WB - OF 64
PARTITION AREA 72 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 135 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 135 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1080 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1080 x 0.0166 = 18
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-6 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 165 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 48 WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 165 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 165 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1320 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1320 x 0.0166 = 22
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA LABOR-1 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 165 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 48 WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 165 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 165 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1320 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1320 x 0.0166 = 22
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA LABOR-2 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 165 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 50 WB - OF 82 WB - OF 64
PARTITION AREA 80 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 165 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 165 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1320 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1320 x 0.0166 = 22
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA CONSULTING ROOM TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 155 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 80 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 155 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 155 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1240 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1240 x 0.0166 = 21
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA NURSH TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 143 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 143 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 143 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1144 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1144 x 0.0166 = 19
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA SCAN TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 146 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 80 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 146 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 146 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1168 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1168 x 0.0166 = 19
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA END ROOM TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 237 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 126 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 237 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 237 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1896 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1896 x 0.0166 = 31
TOTAL VENTILATION CFM 31
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA ROOM TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 124 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 124 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 124 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 992 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 992 x 0.0166 = 16
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA AUDIO TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 82 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 82 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 82 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 656 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 656 x 0.0166 = 11
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA GYNO TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 220 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 226 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 220 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 220 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1760 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1760 x 0.0166 = 29
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA XRAY TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 247 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 129 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 247 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 247 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1976 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1976 x 0.0166 = 33
TOTAL VENTILATION CFM 33
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA STORE TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 237 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 111 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 237 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 237 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1896 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1896 x 0.0166 = 31
TOTAL VENTILATION CFM 31
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA PO-7 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 230 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 240 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 230 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 230 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1840 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1840 x 0.0166 = 31
TOTAL VENTILATION CFM 31
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA LABOR-3 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 80 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 220 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 80 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 80 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 640 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 640 x 0.0166 = 11
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA EXCUT TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 134 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 134 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 134 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1072 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1072 x 0.0166 = 18
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA DENTAL TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 134 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 134 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 134 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1072 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1072 x 0.0166 = 18
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA OPTHO TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 162 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 162 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 162 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1296 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1296 x 0.0166 = 22
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA OPTHOMOLOGY - 2 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 162 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 0.5 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 162 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 162 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1296 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1296 x 0.0166 = 22
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA WORK STATION TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 2200 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 78
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 66
PARTITION AREA 1124 SQ.FT TH - BTU/LB 46 TH - BTU/LB 31.5
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 80
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 30 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 2.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 2200 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 2200 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 17600 CU.FT INSIDE 78 55 66 31.5 80
BYPASS FACTOR 0.12
PEOPLE - BASIS 30 x 7.5 = 225 DIFFERENCE 25 16 14.5 52
EXHAUST =
AIR CHANGE BASIS 1 x 17600 x 0.0166 = 292
TOTAL VENTILATION CFM 292
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA CASUALITY TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 546 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 224 WB - OF 82 WB - OF 64
PARTITION AREA 448 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 8 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 546 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 546 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 4368 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 8 x 7.5 = 60 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 4368 x 0.0166 = 73
TOTAL VENTILATION CFM 73
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA ACCOUNT TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 120 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 120 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 120 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 960 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 960 x 0.0166 = 16
TOTAL VENTILATION CFM 30
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA OPTICAL TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 336 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 320 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 336 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 336 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 2688 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 2688 x 0.0166 = 45
TOTAL VENTILATION CFM 45
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA WAITING AREA TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 2138 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 78
GLASS AREA -SQ.FT 30 180 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 190 620 WB - OF 82 WB - OF 66
PARTITION AREA 1424 SQ.FT TH - BTU/LB 46 TH - BTU/LB 31.5
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 80
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 42 FACTORS
CFM/PERSON 10 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 2.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 2138 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 2137.5 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 17100 CU.FT INSIDE 78 55 66 31.5 80
BYPASS FACTOR 0.12
PEOPLE - BASIS 42 x 10 = 420 DIFFERENCE 25 16 14.5 52
EXHAUST =
AIR CHANGE BASIS 1 x 17100 x 0.0166 = 284
TOTAL VENTILATION CFM 420
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA PHARMACY TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 435 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 270 WB - OF 82 WB - OF 64
PARTITION AREA 480 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 5 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 435 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 435 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 3480 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 5 x 7.5 = 37.5 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 3480 x 0.0166 = 58
TOTAL VENTILATION CFM 58
JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA MANAGER ACCOUNTANT TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 200 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 200 WB - OF 82 WB - OF 64
PARTITION AREA 150 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 5 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 200 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 200 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1600 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 5 x 7.5 = 37.5 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1600 x 0.0166 = 27
TOTAL VENTILATION CFM 38