INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-1 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 150 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 47 WB - OF 82 WB - OF 64
PARTITION AREA 197 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 150 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 150 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1200 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1200 x 0.0166 = 20
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 47 x 0.33 x 31 = 481
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.83
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 595
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.36
PARTITION WALL 197 x 0.42 x 24 = 1986 DEHUMIDIFIED CFM TR = 1.49
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 150
x 0.51 x 23 = 1760
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 150 x 1 x 3.41 = 512
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 11041
SAFETY PERCENTAGE 7.5 = 828
ROOM SENSIBLE HEAT (RSH) = 11869
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11979
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 14355
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 16261
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-2 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 159 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 55 WB - OF 82 WB - OF 64
PARTITION AREA 85 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 159 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 159 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1272 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1272 x 0.0166 = 21
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 55 x 0.33 x 31 = 563
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.82
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 546
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.27
PARTITION WALL 85 x 0.42 x 24 = 857 DEHUMIDIFIED CFM TR = 1.37
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 159
x 0.51 x 23 = 1865
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 159 x 1 x 3.41 = 542
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10130
SAFETY PERCENTAGE 7.5 = 760
ROOM SENSIBLE HEAT (RSH) = 10890
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11000
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13376
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 15282
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-3 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 160 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 56 WB - OF 82 WB - OF 64
PARTITION AREA 86 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 160 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 160 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1280 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1280 x 0.0166 = 21
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 56 x 0.33 x 31 = 573
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.82
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 548
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.28
PARTITION WALL 86 x 0.42 x 24 = 867 DEHUMIDIFIED CFM TR = 1.37
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 160
x 0.51 x 23 = 1877
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 160 x 1 x 3.41 = 546
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10166
SAFETY PERCENTAGE 7.5 = 762
ROOM SENSIBLE HEAT (RSH) = 10928
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11038
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13414
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 15320
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-4 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 135 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 42 WB - OF 82 WB - OF 64
PARTITION AREA 72 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 135 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 135 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1080 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1080 x 0.0166 = 18
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 42 x 0.33 x 31 = 430
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.81
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 513
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.22
PARTITION WALL 72 x 0.42 x 24 = 726 DEHUMIDIFIED CFM TR = 1.28
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 135
x 0.51 x 23 = 1584
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 135 x 1 x 3.41 = 460
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 9503
SAFETY PERCENTAGE 7.5 = 713
ROOM SENSIBLE HEAT (RSH) = 10216
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 10326
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 12701
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 14608
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-5 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 135 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 42 WB - OF 82 WB - OF 64
PARTITION AREA 72 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 135 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 135 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1080 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1080 x 0.0166 = 18
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 42 x 0.33 x 31 = 430
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.81
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 513
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.22
PARTITION WALL 72 x 0.42 x 24 = 726 DEHUMIDIFIED CFM TR = 1.28
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 135
x 0.51 x 23 = 1584
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 135 x 1 x 3.41 = 460
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 9503
SAFETY PERCENTAGE 7.5 = 713
ROOM SENSIBLE HEAT (RSH) = 10216
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 10326
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 12701
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 14608
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA O/P-6 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 165 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 48 WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 165 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 165 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1320 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1320 x 0.0166 = 22
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 48 x 0.33 x 31 = 491
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.82
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 549
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.28
PARTITION WALL 88 x 0.42 x 24 = 887 DEHUMIDIFIED CFM TR = 1.37
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 165
x 0.51 x 23 = 1935
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 165 x 1 x 3.41 = 563
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10180
SAFETY PERCENTAGE 7.5 = 763
ROOM SENSIBLE HEAT (RSH) = 10943
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11053
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13429
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 15335
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA LABOR-1 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 165 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 48 WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 165 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 165 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1320 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1320 x 0.0166 = 22
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 48 x 0.33 x 31 = 491
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.82
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 549
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.28
PARTITION WALL 88 x 0.42 x 24 = 887 DEHUMIDIFIED CFM TR = 1.37
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 165
x 0.51 x 23 = 1935
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 165 x 1 x 3.41 = 563
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10180
SAFETY PERCENTAGE 7.5 = 763
ROOM SENSIBLE HEAT (RSH) = 10943
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11053
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13429
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 15335
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA LABOR-2 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 165 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 50 WB - OF 82 WB - OF 64
PARTITION AREA 80 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 165 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 165 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1320 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1320 x 0.0166 = 22
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 50 x 0.33 x 31 = 512
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.82
O
WEST GLASS 30 x 0.37 x 158 = 1754 APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 546
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 1.27
PARTITION WALL 80 x 0.42 x 24 = 806 DEHUMIDIFIED CFM TR = 1.36
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 165
x 0.51 x 23 = 1935
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 165 x 1 x 3.41 = 563
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10120
SAFETY PERCENTAGE 7.5 = 759
ROOM SENSIBLE HEAT (RSH) = 10879
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 10988
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13364
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 15270
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA CONSULTING ROOM TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 155 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 80 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 155 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 155 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1240 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1240 x 0.0166 = 21
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.76
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 366
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.97
PARTITION WALL 80 x 0.42 x 24 = 806 DEHUMIDIFIED CFM TR = 1.31
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 155
x 0.51 x 23 = 1818
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 155 x 1 x 3.41 = 529
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 6754
SAFETY PERCENTAGE 7.5 = 507
ROOM SENSIBLE HEAT (RSH) = 7260
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7370
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 9746
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 11652
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA NURSH TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 143 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 143 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 143 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1144 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1144 x 0.0166 = 19
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.73
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 313
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.88
PARTITION WALL x 0.42 x 24 = DEHUMIDIFIED CFM TR = 1.12
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 143
x 0.51 x 23 = 1677
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 143 x 1 x 3.41 = 488
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 5766
SAFETY PERCENTAGE 7.5 = 432
ROOM SENSIBLE HEAT (RSH) = 6198
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 6308
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8684
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 10590
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA SCAN TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 146 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 80 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 146 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 146 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1168 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1168 x 0.0166 = 19
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.79
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 450
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.11
PARTITION WALL 80 x 0.42 x 24 = 806 DEHUMIDIFIED CFM TR = 1.61
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 146
x 0.51 x 23 = 1713
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 146 x 1 x 3.41 = 498
EQUIPMENT 1.0 x 1 x 3410 = 3410
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 8322
SAFETY PERCENTAGE 7.5 = 624
ROOM SENSIBLE HEAT (RSH) = 8947
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9056
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 11432
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 13339
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA END ROOM TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 237 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 126 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 237 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 237 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1896 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1896 x 0.0166 = 31
TOTAL VENTILATION CFM 31

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.79
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 460
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.14
PARTITION WALL 126 x 0.42 x 24 = 1270 DEHUMIDIFIED CFM TR = 1.64
FLOOR x 0.32 x 23 = SELECTED TR 1.60
CEILING 237
x 0.51 x 23 = 2780
ROOF x 0.14 x 32 =
VENTILATION 31 x 28 x 1.09 = 961
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 237 x 1 x 3.41 = 808
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 8504
SAFETY PERCENTAGE 7.5 = 638
ROOM SENSIBLE HEAT (RSH) = 9142
OUTDOOR AIR (CFM) 31 x 28 x 0.13 = 115
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9257
LATENT HEAT
VENTILATION 31 x 61.3 x 0.68 = 1312
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2132
SAFETY PERCENTAGE 7.5 160
ROOM LATENT HEAT (RLH) = 2292
OUTDOOR AIR (CFM) 31 x 61.3 x 0.08 157
EFFECTIVE ROOM LATENT HEAT (ERLH) 2449
EFFECTIVE ROOM TOTAL HEAT (ERTH) 11706
OUTDOOR AIR HEAT
SENSIBLE 31 x 28 x 0.96 = 845
LATENT 31 x 61.3 x 0.60 = 1155
GRAND TOTAL HEAT (GTH) = 13706
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA ROOM TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 124 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 124 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 124 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 992 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 992 x 0.0166 = 16
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.72
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 298
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.86
PARTITION WALL x 0.42 x 24 = DEHUMIDIFIED CFM TR = 1.06
FLOOR x 0.32 x 23 = SELECTED TR 1.00
CEILING 124
x 0.51 x 23 = 1455
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 124 x 1 x 3.41 = 423
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 5478
SAFETY PERCENTAGE 7.5 = 411
ROOM SENSIBLE HEAT (RSH) = 5889
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 5999
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8375
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 10281
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA AUDIO TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 82 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 82 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 82 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 656 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 656 x 0.0166 = 11
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.69
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 264
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.80
PARTITION WALL x 0.42 x 24 = DEHUMIDIFIED CFM TR = 0.88
FLOOR x 0.32 x 23 = SELECTED TR 0.80
CEILING x82 0.51 x 23 = 962
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 82 x 1 x 3.41 = 280
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 4842
SAFETY PERCENTAGE 7.5 = 363
ROOM SENSIBLE HEAT (RSH) = 5205
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 5315
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 7691
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 9597
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA GYNO TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 220 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 226 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 220 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 220 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1760 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1760 x 0.0166 = 29
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.83
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 588
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.34
PARTITION WALL 226 x 0.42 x 24 = 2278 DEHUMIDIFIED CFM TR = 2.10
FLOOR x 0.32 x 23 = SELECTED TR 2.00
CEILING 220
x 0.51 x 23 = 2581
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 220 x 1 x 3.41 = 750
EQUIPMENT 1.0 x 1 x 3410 = 3410
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10914
SAFETY PERCENTAGE 7.5 = 819
ROOM SENSIBLE HEAT (RSH) = 11733
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11843
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 14219
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 16125
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA XRAY TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 247 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 129 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 247 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 247 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1976 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1976 x 0.0166 = 33
TOTAL VENTILATION CFM 33

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.82
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 563
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.33
PARTITION WALL 129 x 0.42 x 24 = 1300 DEHUMIDIFIED CFM TR = 2.01
FLOOR x 0.32 x 23 = SELECTED TR
CEILING 247
x 0.51 x 23 = 2897
ROOF x 0.14 x 32 =
VENTILATION 33 x 28 x 1.09 = 1001
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 247 x 1 x 3.41 = 842
EQUIPMENT 1.0 x 1 x 3410 = 3410
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10431
SAFETY PERCENTAGE 7.5 = 782
ROOM SENSIBLE HEAT (RSH) = 11213
OUTDOOR AIR (CFM) 33 x 28 x 0.13 = 120
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11333
LATENT HEAT
VENTILATION 33 x 61.3 x 0.68 = 1367
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2187
SAFETY PERCENTAGE 7.5 164
ROOM LATENT HEAT (RLH) = 2351
OUTDOOR AIR (CFM) 33 x 61.3 x 0.08 164
EFFECTIVE ROOM LATENT HEAT (ERLH) 2515
EFFECTIVE ROOM TOTAL HEAT (ERTH) 13849
OUTDOOR AIR HEAT
SENSIBLE 33 x 28 x 0.96 = 881
LATENT 33 x 61.3 x 0.60 = 1203
GRAND TOTAL HEAT (GTH) = 15933
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA STORE TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 237 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 111 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 237 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 237 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1896 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1896 x 0.0166 = 31
TOTAL VENTILATION CFM 31

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.79
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 451
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.13
PARTITION WALL 111 x 0.42 x 24 = 1119 DEHUMIDIFIED CFM TR = 1.61
FLOOR x 0.32 x 23 = SELECTED TR 1.60
CEILING 237
x 0.51 x 23 = 2780
ROOF x 0.14 x 32 =
VENTILATION 31 x 28 x 1.09 = 961
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 237 x 1 x 3.41 = 808
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 8353
SAFETY PERCENTAGE 7.5 = 626
ROOM SENSIBLE HEAT (RSH) = 8979
OUTDOOR AIR (CFM) 31 x 28 x 0.13 = 115
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 9094
LATENT HEAT
VENTILATION 31 x 61.3 x 0.68 = 1312
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2132
SAFETY PERCENTAGE 7.5 160
ROOM LATENT HEAT (RLH) = 2292
OUTDOOR AIR (CFM) 31 x 61.3 x 0.08 157
EFFECTIVE ROOM LATENT HEAT (ERLH) 2449
EFFECTIVE ROOM TOTAL HEAT (ERTH) 11544
OUTDOOR AIR HEAT
SENSIBLE 31 x 28 x 0.96 = 845
LATENT 31 x 61.3 x 0.60 = 1155
GRAND TOTAL HEAT (GTH) = 13543
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA PO-7 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 230 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 240 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 230 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 230 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1840 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1840 x 0.0166 = 31
TOTAL VENTILATION CFM 31

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.81
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 514
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.22
PARTITION WALL 240 x 0.42 x 24 = 2419 DEHUMIDIFIED CFM TR = 1.83
FLOOR x 0.32 x 23 = SELECTED TR 2.00
CEILING 230
x 0.51 x 23 = 2698
ROOF x 0.14 x 32 =
VENTILATION 31 x 28 x 1.09 = 932
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 230 x 1 x 3.41 = 784
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 9519
SAFETY PERCENTAGE 7.5 = 714
ROOM SENSIBLE HEAT (RSH) = 10232
OUTDOOR AIR (CFM) 31 x 28 x 0.13 = 112
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 10344
LATENT HEAT
VENTILATION 31 x 61.3 x 0.68 = 1273
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2093
SAFETY PERCENTAGE 7.5 157
ROOM LATENT HEAT (RLH) = 2250
OUTDOOR AIR (CFM) 31 x 61.3 x 0.08 153
EFFECTIVE ROOM LATENT HEAT (ERLH) 2403
EFFECTIVE ROOM TOTAL HEAT (ERTH) 12747
OUTDOOR AIR HEAT
SENSIBLE 31 x 28 x 0.96 = 820
LATENT 31 x 61.3 x 0.60 = 1120
GRAND TOTAL HEAT (GTH) = 14688
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA LABOR-3 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 80 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 220 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 80 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 80 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 640 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 640 x 0.0166 = 11
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.76
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 381
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.00
PARTITION WALL 220 x 0.42 x 24 = 2218 DEHUMIDIFIED CFM TR = 1.27
FLOOR x 0.32 x 23 = SELECTED TR 1.00
CEILING x80 0.51 x 23 = 938
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 80 x 1 x 3.41 = 273
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 7029
SAFETY PERCENTAGE 7.5 = 527
ROOM SENSIBLE HEAT (RSH) = 7557
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7666
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10042
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 11949
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA EXCUT TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 134 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 134 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 134 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1072 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1072 x 0.0166 = 18
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.72
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 306
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.87
PARTITION WALL x 0.42 x 24 = DEHUMIDIFIED CFM TR = 1.09
FLOOR x 0.32 x 23 = SELECTED TR 1.00
CEILING 134
x 0.51 x 23 = 1572
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 134 x 1 x 3.41 = 457
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 5629
SAFETY PERCENTAGE 7.5 = 422
ROOM SENSIBLE HEAT (RSH) = 6052
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 6161
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8537
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 10443
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA DENTAL TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 134 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 134 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 134 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1072 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1072 x 0.0166 = 18
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.77
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 397
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.02
PARTITION WALL x 0.42 x 24 = DEHUMIDIFIED CFM TR = 1.42
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 134
x 0.51 x 23 = 1572
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 134 x 1 x 3.41 = 457
EQUIPMENT 1.0 x 1 x 3410 = 3410
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 7334
SAFETY PERCENTAGE 7.5 = 550
ROOM SENSIBLE HEAT (RSH) = 7884
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7994
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 10370
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 12276
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA OPTHO TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 162 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 162 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 162 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1296 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1296 x 0.0166 = 22
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.76
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 376
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.99
PARTITION WALL 88 x 0.42 x 24 = 887 DEHUMIDIFIED CFM TR = 1.34
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 162
x 0.51 x 23 = 1900
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 162 x 1 x 3.41 = 552
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 6940
SAFETY PERCENTAGE 7.5 = 521
ROOM SENSIBLE HEAT (RSH) = 7461
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7571
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 9947
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 11853
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA OPTHOMOLOGY - 2 TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 162 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 88 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 0.5 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 162 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 162 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1296 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1296 x 0.0166 = 22
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.75
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 361
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.96
PARTITION WALL 88 x 0.42 x 24 = 887 DEHUMIDIFIED CFM TR = 1.29
FLOOR x 0.32 x 23 = SELECTED TR 1.30
CEILING 162
x 0.51 x 23 = 1900
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 81 x 1 x 3.41 = 276
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 6664
SAFETY PERCENTAGE 7.5 = 500
ROOM SENSIBLE HEAT (RSH) = 7164
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 7274
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 9650
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 11556
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA WORK STATION TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 2200 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 78
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 66
PARTITION AREA 1124 SQ.FT TH - BTU/LB 46 TH - BTU/LB 31.5
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 80
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 30 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 2.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 2200 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 2200 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 17600 CU.FT INSIDE 78 55 66 31.5 80
BYPASS FACTOR 0.12
PEOPLE - BASIS 30 x 7.5 = 225 DIFFERENCE 25 16 14.5 52
EXHAUST =
AIR CHANGE BASIS 1 x 17600 x 0.0166 = 292
TOTAL VENTILATION CFM 292

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.78
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 21.12
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 3002
ALL GLASS x 1.13 x 25 = REFRIGERATION LOAD TR 8.68
PARTITION WALL 1124 x 0.42 x 24 = 11330 DEHUMIDIFIED CFM TR = 12.01
FLOOR x 0.32 x 20 = SELECTED TR 4.0TR x 3 Nos
CEILING 2200x 0.51 x 20 = 22440
ROOF x 0.14 x 32 =
VENTILATION 292 x 25 x 1.09 = 7961
INTERNAL HEAT
PEOPLE 30 x 245 x 1 = 7350
LIGHTS 2200 x 1 x 3.41 = 7502
EQUIPMENT 2.0 x 1 x 3410 = 6820
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 63403
SAFETY PERCENTAGE 7.5 = 4755
ROOM SENSIBLE HEAT (RSH) = 68159
OUTDOOR AIR (CFM) 292 x 25 x 0.13 = 955
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 69114
LATENT HEAT
VENTILATION 292 x 52 x 0.68 = 10331
PEOPLE 30 x 205 x 1 = 6150
MISCELLANEOUS 1 x 1
SUB TOTAL 16481
SAFETY PERCENTAGE 7.5 1236
ROOM LATENT HEAT (RLH) = 17717
OUTDOOR AIR (CFM) 292 x 52 x 0.08 1240
EFFECTIVE ROOM LATENT HEAT (ERLH) 18957
EFFECTIVE ROOM TOTAL HEAT (ERTH) 88070
OUTDOOR AIR HEAT
SENSIBLE 292 x 25 x 0.96 = 7006
LATENT 292 x 52 x 0.60 = 9091
GRAND TOTAL HEAT (GTH) = 104167
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA CASUALITY TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 546 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 224 WB - OF 82 WB - OF 64
PARTITION AREA 448 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 8 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 546 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 546 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 4368 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 8 x 7.5 = 60 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 4368 x 0.0166 = 73
TOTAL VENTILATION CFM 73

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 224 x 0.33 x 31 = 2292
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.81
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 1131
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 2.73
PARTITION WALL 448 x 0.42 x 24 = 4516 DEHUMIDIFIED CFM TR = 4.04
FLOOR x 0.32 x 23 = SELECTED TR 2.0TR x 2 Nos
CEILING 546
x 0.51 x 23 = 6405
ROOF x 0.14 x 32 =
VENTILATION 73 x 28 x 1.09 = 2213
INTERNAL HEAT
PEOPLE 8 x 245 x 1 = 1960
LIGHTS 546 x 1 x 3.41 = 1862
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 20952
SAFETY PERCENTAGE 7.5 = 1571
ROOM SENSIBLE HEAT (RSH) = 22523
OUTDOOR AIR (CFM) 73 x 28 x 0.13 = 266
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 22789
LATENT HEAT
VENTILATION 73 x 61.3 x 0.68 = 3022
PEOPLE 8 x 205 x 1 = 1640
MISCELLANEOUS 1 x 1
SUB TOTAL 4662
SAFETY PERCENTAGE 7.5 350
ROOM LATENT HEAT (RLH) = 5012
OUTDOOR AIR (CFM) 73 x 61.3 x 0.08 363
EFFECTIVE ROOM LATENT HEAT (ERLH) 5375
EFFECTIVE ROOM TOTAL HEAT (ERTH) 28164
OUTDOOR AIR HEAT
SENSIBLE 73 x 28 x 0.96 = 1947
LATENT 73 x 61.3 x 0.60 = 2660
GRAND TOTAL HEAT (GTH) = 32771
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA ACCOUNT TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 120 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 120 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 120 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 960 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 960 x 0.0166 = 16
TOTAL VENTILATION CFM 30

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.71
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 295
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 0.85
PARTITION WALL x 0.42 x 24 = DEHUMIDIFIED CFM TR = 0.98
FLOOR x 0.32 x 23 = SELECTED TR 1.00
CEILING 120
x 0.51 x 23 = 1408
ROOF x 0.14 x 32 =
VENTILATION 30 x 28 x 1.09 = 916
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 120 x 1 x 3.41 = 409
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 5417
SAFETY PERCENTAGE 7.5 = 406
ROOM SENSIBLE HEAT (RSH) = 5824
OUTDOOR AIR (CFM) 30 x 28 x 0.13 = 110
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 5934
LATENT HEAT
VENTILATION 30 x 61.3 x 0.68 = 1251
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2071
SAFETY PERCENTAGE 7.5 155
ROOM LATENT HEAT (RLH) = 2226
OUTDOOR AIR (CFM) 30 x 61.3 x 0.08 150
EFFECTIVE ROOM LATENT HEAT (ERLH) 2376
EFFECTIVE ROOM TOTAL HEAT (ERTH) 8309
OUTDOOR AIR HEAT
SENSIBLE 30 x 28 x 0.96 = 806
LATENT 30 x 61.3 x 0.60 = 1100
GRAND TOTAL HEAT (GTH) = 10216
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA OPTICAL TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 336 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** WB - OF 82 WB - OF 64
PARTITION AREA 320 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 4 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 1.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 336 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 336 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 2688 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 4 x 7.5 = 30 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 2688 x 0.0166 = 45
TOTAL VENTILATION CFM 45

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.83
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 759
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.77
PARTITION WALL 320 x 0.42 x 24 = 3226 DEHUMIDIFIED CFM TR = 2.81
FLOOR x 0.32 x 23 = SELECTED TR 3.00
CEILING 336
x 0.51 x 23 = 3941
ROOF x 0.14 x 32 =
VENTILATION 45 x 28 x 1.09 = 1362
INTERNAL HEAT
PEOPLE 4 x 245 x 1 = 980
LIGHTS 336 x 1 x 3.41 = 1146
EQUIPMENT 1.0 x 1 x 3410 = 3410
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 14064
SAFETY PERCENTAGE 7.5 = 1055
ROOM SENSIBLE HEAT (RSH) = 15119
OUTDOOR AIR (CFM) 45 x 28 x 0.13 = 163
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 15283
LATENT HEAT
VENTILATION 45 x 61.3 x 0.68 = 1860
PEOPLE 4 x 205 x 1 = 820
MISCELLANEOUS 1 x 1
SUB TOTAL 2680
SAFETY PERCENTAGE 7.5 201
ROOM LATENT HEAT (RLH) = 2881
OUTDOOR AIR (CFM) 45 x 61.3 x 0.08 223
EFFECTIVE ROOM LATENT HEAT (ERLH) 3104
EFFECTIVE ROOM TOTAL HEAT (ERTH) 18387
OUTDOOR AIR HEAT
SENSIBLE 45 x 28 x 0.96 = 1198
LATENT 45 x 61.3 x 0.60 = 1637
GRAND TOTAL HEAT (GTH) = 21222
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA WAITING AREA TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 2138 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 78
GLASS AREA -SQ.FT 30 180 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 190 620 WB - OF 82 WB - OF 66
PARTITION AREA 1424 SQ.FT TH - BTU/LB 46 TH - BTU/LB 31.5
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 80
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 42 FACTORS
CFM/PERSON 10 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 2.0 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 2138 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 2137.5 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 17100 CU.FT INSIDE 78 55 66 31.5 80
BYPASS FACTOR 0.12
PEOPLE - BASIS 42 x 10 = 420 DIFFERENCE 25 16 14.5 52
EXHAUST =
AIR CHANGE BASIS 1 x 17100 x 0.0166 = 284
TOTAL VENTILATION CFM 420

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL 190 x 0.33 x 37 = 2320 FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL 620 x 0.33 x 31 = 6343 RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS 30 x 0.37 x 11 = 122
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS 180 x 0.37 x 11 = 733
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.78
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 21.12
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 4144
ALL GLASS 210 x 1.13 x 25 = 5933 REFRIGERATION LOAD TR 12.13
PARTITION WALL 1424 x 0.42 x 24 = 14354 DEHUMIDIFIED CFM TR = 15.94
FLOOR x 0.32 x 20 = SELECTED TR 8.0TR x 2 Nos
CEILING 2138x 0.51 x 20 = 21808
ROOF x 0.14 x 32 =
VENTILATION 420 x 25 x 1.09 = 11445
INTERNAL HEAT
PEOPLE 42 x 245 x 1 = 10290
LIGHTS 2138 x 1 x 3.41 = 7289
EQUIPMENT 2.0 x 1 x 3410 = 6820
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 87455
SAFETY PERCENTAGE 7.5 = 6559
ROOM SENSIBLE HEAT (RSH) = 94014
OUTDOOR AIR (CFM) 420 x 25 x 0.13 = 1373
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 95388
LATENT HEAT
VENTILATION 420 x 52 x 0.68 = 14851
PEOPLE 42 x 205 x 1 = 8610
MISCELLANEOUS 1 x 1
SUB TOTAL 23461
SAFETY PERCENTAGE 7.5 1760
ROOM LATENT HEAT (RLH) = 25221
OUTDOOR AIR (CFM) 420 x 52 x 0.08 1782
EFFECTIVE ROOM LATENT HEAT (ERLH) 27003
EFFECTIVE ROOM TOTAL HEAT (ERTH) 122391
OUTDOOR AIR HEAT
SENSIBLE 420 x 25 x 0.96 = 10072
LATENT 420 x 52 x 0.60 = 13069
GRAND TOTAL HEAT (GTH) = 145531
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA PHARMACY TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 435 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT 30 RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 270 WB - OF 82 WB - OF 64
PARTITION AREA 480 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 5 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 435 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 435 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 3480 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 5 x 7.5 = 37.5 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 3480 x 0.0166 = 58
TOTAL VENTILATION CFM 58

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL 270 x 0.33 x 37 = 3297 FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL x 0.33 x 31 =
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS 30 x 0.37 x 11 = 122
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.85
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 1104
ALL GLASS 30 x 1.13 x 28 = 949 REFRIGERATION LOAD TR 2.49
PARTITION WALL 480 x 0.42 x 24 = 4838 DEHUMIDIFIED CFM TR = 4.09
FLOOR x 0.32 x 23 = SELECTED TR 2.0TR x 2 Nos
CEILING 435
x 0.51 x 23 = 5103
ROOF x 0.14 x 32 =
VENTILATION 58 x 28 x 1.09 = 1763
INTERNAL HEAT
PEOPLE 5 x 245 x 1 = 1225
LIGHTS 435 x 1 x 3.41 = 1483
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 20485
SAFETY PERCENTAGE 7.5 = 1536
ROOM SENSIBLE HEAT (RSH) = 22022
OUTDOOR AIR (CFM) 58 x 28 x 0.13 = 212
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 22233
LATENT HEAT
VENTILATION 58 x 61.3 x 0.68 = 2408
PEOPLE 5 x 205 x 1 = 1025
MISCELLANEOUS 1 x 1
SUB TOTAL 3433
SAFETY PERCENTAGE 7.5 257
ROOM LATENT HEAT (RLH) = 3690
OUTDOOR AIR (CFM) 58 x 61.3 x 0.08 289
EFFECTIVE ROOM LATENT HEAT (ERLH) 3979
EFFECTIVE ROOM TOTAL HEAT (ERTH) 26213
OUTDOOR AIR HEAT
SENSIBLE 58 x 28 x 0.96 = 1552
LATENT 58 x 61.3 x 0.60 = 2119
GRAND TOTAL HEAT (GTH) = 29883
INTELLECT AIR SYSTEMS

JOB NO:
INPUT DATA
CUSTMOR NAME SRM-OP BLOCK
ADDRESS CHENNAI DAILY RANGE 18
AREA MANAGER ACCOUNTANT TIME OF PEAK 1600 HRS
MONTH OF PEAK MAY
CONDITIONED AREA 200 SQ.FT
TOTAL WALL HEIGHT 10 FT. OUTSIDE DESIGN INSIDE DESIGN
CEILING HEIGHT (FC) 8 FT. CONDITIONS CONDITIONS
EXPOSURE N N-E E S-E S S-W W N-W DB - OF 103 DB - OF 75
GLASS AREA -SQ.FT RH - % 41 RH - % 55
WALL AREA- SQ.FT ** 200 WB - OF 82 WB - OF 64
PARTITION AREA 150 SQ.FT TH - BTU/LB 46 TH - BTU/LB 29
SKY GLASS AREA SQ.FT GRAINS/LB 132 GRAINS/LB 70.7
NO OF AIR CHANGES 1 PER HOUR
NO. OF PEOPLE 5 FACTORS
CFM/PERSON 7.5 WALL 0.33
EXHAUST AIR QTY. CFM GLASS 0.37
LIGHTING LOAD 1 WATT/SQ.FT ALL GLASS 1.13
EQUIPMENT LOAD 0.5 KW PARTITION 0.42
MISCELLANEOUS-SENS BTU/HR CEILING 0.51
MISCELLANEOUS-LATE BTU/HR FLOOR 0.32
EXPOSED FLOOR SQ.FT ROOF 0.14
ROOF GAIN SQ.FT SKY GLASS 0.56
CEILING GAIN 200 SQ.FT
SH PER PERSON 245 BTU/HR
LH PER PERSON 205 BTU/HR
BYPASS FACTOR 0.12
HEAT LOAD ESTIMATE
CONDITIONED AREA 200 SQ.FT DB %RH WB TH GR/LB
CEILING HEIGHT (FC) 8 FT. OUTSIDE 103 41 82 46 132
VOLUME 1600 CU.FT INSIDE 75 55 64 29 70.7
BYPASS FACTOR 0.12
PEOPLE - BASIS 5 x 7.5 = 37.5 DIFFERENCE 28 18 17 61.3
EXHAUST =
AIR CHANGE BASIS 1 x 1600 x 0.0166 = 27
TOTAL VENTILATION CFM 38

NORTH WALL x 0.33 x 23 = RETURN


= ((WALL GAIN) x (HEIGHT ABOVE CEILING))
NORTH EAST WALL x 0.33 x 29 = AIR GAIN
EAST WALL x 0.33 x 37 = FOR WALLS (CEILING HEIGHT (FC))
SOUTH EAST WALL x 0.33 x 37 =
SOUTH WALL x 0.33 x 31 = RETURN AIR GAIN ****
SOUTH WEST WALL x 0.33 x 33 =
BY DEFAULT THIS WORK SHEET CONSIDERS RETURN AIR
WEST WALL 200 x 0.33 x 31 = 2046
GAIN FOR WALLS ONLY. IF CEILING/ ROOF/ SKY GLASS
NORTH WEST WALL x 0.33 x 25 =
LOADS HAVE TO BE RECKONED AS PART OF RETURN AIR
NORTH GLASS x 0.37 x 39 =
GAIN, THEN THE SAME WILL HAVE TO BE REMOVED FROM
NORTH EAST GLASS x 0.37 x 11 =
SPACE LOAD AND ADDED TO RETURN AIR GAIN
EAST GLASS x 0.37 x 11 =
SOUTH EAST GLASS x 0.37 x 11 =
SOUTH GLASS x 0.37 x 11 =
SOUTH WEST GLASS x 0.37 x 66 = SENSIBLE HEAT RATIO (ESHF) = 0.80
O
WEST GLASS x 0.37 x 158 = APPARATUS DEW POINT F = 54
NORTH WEST GLASS x 0.37 x 148 = DEHUMIDIFIED RISE = 18.48
SKY GLASS x 0.56 x 107 = DEHUMIDIFIED AIR CFM 576
ALL GLASS x 1.13 x 28 = REFRIGERATION LOAD TR 1.41
PARTITION WALL 150 x 0.42 x 24 = 1512 DEHUMIDIFIED CFM TR = 1.99
FLOOR x 0.32 x 23 = SELECTED TR 1.0TR x 2 Nos
CEILING 200
x 0.51 x 23 = 2346
ROOF x 0.14 x 32 =
VENTILATION 38 x 28 x 1.09 = 1145
INTERNAL HEAT
PEOPLE 5 x 245 x 1 = 1225
LIGHTS 200 x 1 x 3.41 = 682
EQUIPMENT 0.5 x 1 x 3410 = 1705
MISCELLANEOUS x 1 x 1 =
SUB TOTAL = 10661
SAFETY PERCENTAGE 7.5 = 800
ROOM SENSIBLE HEAT (RSH) = 11460
OUTDOOR AIR (CFM) 38 x 28 x 0.13 = 137
EFFECTIVE ROOM SENSIBLE HEAT (ERSH) 11597
LATENT HEAT
VENTILATION 38 x 61.3 x 0.68 = 1563
PEOPLE 5 x 205 x 1 = 1025
MISCELLANEOUS 1 x 1
SUB TOTAL 2588
SAFETY PERCENTAGE 7.5 194
ROOM LATENT HEAT (RLH) = 2782
OUTDOOR AIR (CFM) 38 x 61.3 x 0.08 188
EFFECTIVE ROOM LATENT HEAT (ERLH) 2970
EFFECTIVE ROOM TOTAL HEAT (ERTH) 14567
OUTDOOR AIR HEAT
SENSIBLE 38 x 28 x 0.96 = 1007
LATENT 38 x 61.3 x 0.60 = 1376
GRAND TOTAL HEAT (GTH) = 16950