DeltaVElectronicMarshallingDigitalAutomationSystem
(CHARMI/OSubsystem)
Zone2InstallationInstructions

EmersonProcessManagement
FisherRosemountSystems

12P5403
Rev.G22Aug2013
ApprovedbyR.P.T

EmersonProcessManagement
MeridianEast
MeridianBusinessPark
Leicester,LE191UX,UK

Emersona.s.
EuropeanSystemandAssembly
Pieansk1202/44
NovMestonadVhom91528
Slovakia

FisherRosemountSystems,Inc.anEmersonProcessManagementcompany
EmersonProcessManagement
1100WestLouisHennaBlvd.
Bldg.1
RoundRock,TX78681USA


2011,2013FisherRosemountSystems,Inc.AllRightsReserved.
DeltaVandtheDeltaVdesignaremarksofoneoftheEmersonProcessManagementgroupof
companies.Allothermarksarethepropertyoftheirrespectiveowners.
12P5403 Page 2

IntroductionandSystemDefinition
ThesystemshownbelowrepresentsatypicalDeltaVSystem.ThiscomprisesofUnspecified
SafeAreaApparatusandCharmI/Omodulesandallothernecessaryapparatussuchaspower
supplies,carriers,extenders,etc.Eachsystemhasamaximumof8CharmBaseplatesand96
Charms.Additionallyonecableextenderwithamaximumcablelengthof2meterscanbe
utilized(seeFigure1).
GeneralinstallationinstructionsofthesecomponentsarecoveredintheDeltaVTMSSeries
andCHARMsHardwareInstallationandHardwareReferenceManuals.Specialinstallation
requirements,applicabletotheuseinZone2hazardouslocationarecoveredhereandare
definedbelow.ThissystemmayalsobeplacedinaSafeAreaandhaveitsfieldwiringentera
Zone2hazardousareaaslongasallcriterialistedbelowaremet.

ApplicableStandards
EN600790:2012
IEC600790(Ed.6,2011)
EN6007911:2012
IEC6007911(Ed.6,2011)
EN6007915:2010;EN6007915:2005
IEC6007915(Ed.4,2010);IEC6007915(Ed.3,2005)

Referencetofurtherdocumentation
Laws,standards,ordirectivesapplicabletotheintendedusemustbeobserved.Inrelationto
hazardousareas,Directive1999/92/ECmustbeobserved.ThecorrespondingECtype
examinationcertificatesandIECExcertificatesareanintegralpartofthisdocument.
Duetoconstantrevisions,documentationissubjecttopermanentchange.Pleasereferonlyto
themostuptodateversionavailablefromFisherRosemountSystems/EmersonProcess
Management.

IntendedUse
Thedeviceisonlyapprovedforappropriateandintendeduse.Ignoringtheseinstructionswill
voidanywarrantyandabsolvethemanufacturerfromanyliability.
Thedevicemustonlybeoperatedintheambienttemperaturerangeandattherelative
humidity(noncondensing)specified.
TheinputandoutputmoduleslistedinTable1actasaninterfacebetweensignalsfromthe
hazardousarea(Exarea)andthesafearea(NonExarea).
ThemoduleslistedinthisdocumentareusedinC&I(controlandinstrumentation)technology
forthegalvanicisolationofC&Isignalssuchas20mAand10Vstandardsignalsor
alternativelyforadaptingorstandardizingsignals.Devicesthatincorporateintrinsicallysafe
circuitareusedforoperatingintrinsicallysafefielddevicesinhazardousareas.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 3

Avoidimproperuse
Protectionoftheoperatingpersonnelandtheoverallsystemisnotensurediftheproductis
notbeingusedaccordingtoitsintendedpurpose.

Notes,WarningsandLimitations

1. SystemInstallationmustbeinaccordancewithEN/IEC6007915.
Provisionshallbemade,eitherintheapparatusorexternaltotheapparatus,toprovidea
transientprotectiondevice.Thesetprotectionlevelshallnotexceedtheratedvoltageof
thepowersupplybymore40%(asmeasuredattheterminalsoftheapparatus).
ThesystemmustbemountedinanenclosureinaccordancetoEN/IEC6007915,oroneof
theprotectionslistedinClause1inEN/IEC600790withatleastadegreeofprotection
IP54accordingtoEN/IEC60529andpollutiondegree2,asdefinedinEN/IEC606641.
Whenthesystemisinstalledinanenclosure,theenclosuremusthavealabelthatreads,
BeforeopeningpleaseconfertheZone2InstallationDocument.Metalenclosures,
whichareratedIP54,passtherequiredimpactspecificationbydefault.
2. ThecomponentsareidentifiedasnotedinTable1andFigure1a,1b,1c,1d.
3. ThevoltagesourcetotheCSLS,SZ,CIOCorWIOCCarriers(H)viaPowerPlugsKmustnot
generateorcontaininnormaloperationasourceofpotentialinexcessof26.4VDC
4. TheCommunicationNetworkconnectedtotheDeltaVControllerviaSNP,SIP,orI/OPort
(J)cannotberemovedorinsertedwhenpowerisappliedunlesstheareaisknowntobe
nonhazardous.Thisconnectionmustnotbeconnectedtoasource,whichgeneratesor
contains,undernormalconditionapotentialinexcessof50VACor75VDC.
5. SystempowermustbedeenergizedbeforedisconnectingoraddinganyCarriers,
Baseplates,andExtender,ExtenderCablesorterminators.
6. FieldPowersuppliedtotheCharmI/Omoduleseitheratthefieldterminalorasinjected
fieldpowerviatheCharmTerminalGmustberemovedbeforeremovingorconnecting
CharmI/OmodulesfromtheBaseplateexceptwherenotedasacceptableinTable1.
7. CharmModulesBdonothaveinjectedpowerappliedtotheCharmTerminalGandmay
NOTbereplacedwhiletheSystemPowerisenergized.
8. CharmModulesChaveinjectedpowerappliedtotheInjectedPowerCharmTerminalP
andmayNOTbereplacedwhiletheSystemPowerisenergized.SeeNote31.
9. CharmModulesDdonothaveinjectedpowerappliedtotheCharmTerminalGandmay
bereplacedwhilethesystempowerisenergized.WARNING:Foramodule,whichmaybe
removedandinsertedwiththesystempowerenergized,onlyonemoduleistobe
removedorinsertedatatime.SeeTable1.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 4

Figure1aModuleDefinitionCharmI/O

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 5


Figure1bModuleDefinitionWIOC

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 6

+24VDCPower
Supplies(seeNotes
1,3) NONHAZARDOUSLOCATION

HAZARDOUS
Zone2
KK GROUPA,B,C,DLOCATION

JJ

Any simple
apparatus or
approved device
WW L with entity
concept
AA parameters (Ui,
Typical
[ic] Ii, Ci, Li resp.
K BorD G Field Vmax, Imax, Ci,
Circuit Li) appropriate for
C T6 connection to
associated
L apparatus with
R1 S entity concept
V1 T7 parameters listed
in Table 1.
V3
V3 T1
V3
V3 T9
V2
V2 T3
V4
V4 T5
2V3
or2V4 T4

OptionalBottomExtender

Figure1c ModuleDefinitionCSLSandSISCHARMsSubsystem
(Showing[ic]FieldCircuit)

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 7

+24VDC Power
Supplies (see
Notes 1,3)
NONHAZARDOUS LOCATION

HAZARDOUS
Zone 2
GROUP A,B,C,D
K K
LOCATION

J J

A A

Figure1d ModuleDefinitionSZand
Carrier

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 8

10. TheCharmTerminalsGandPcanbeinsertedorremovedwithoutdeenergizingsystem
poweraslongasthereisnoCharminstalledandnofieldwiringconnected.Onceinstalled
theCharmTerminalassumesthefieldcircuitEntityParametersoftheCharmforthat
position.
11. ThespecificoutputcharacteristicsfortheenergylimitedCharmI/Omodulesarelistedin
Table1.Note:InallcasesUmmustbelessthan26.4VDC.

Definitionsforoutputcharacteristicsareasfollows:

EnergyLimitedCircuits
Anenergylimitedcircuitisoneinwhichanyarc,spark,orthermaleffect
producedduringnormaloperationispreventedbyenergylimitationfromigniting
thesurroundingflammableatmosphere.SeeFigure2.


Approved for Zone-2
I/O Charm installation with energy-
(Single channel) limited field wiring
(Refer to Table 1 for parameters:
approved models) V max, I max, Li, Ci
Device
Uo Vmax
Energy-Limited Co Ci + Ccable
Field Circuit Lo Li + Lcable
Parameters Uo, Io, Io Imax*
Lo, Co *If field device Imax is
specified.

Figure2EnergylimitedFieldWiring

NonSparkingCircuit
Nonsparkingcircuitsaretypicallynotenergylimitedandcancontainenergy
levelscapableofignitingtheflammableatmosphereifinterruptedwithoutfurther
meansofprotection.
NormalOperation
Apparatusissaidtobeinnormaloperationwhenitconformselectricallyand
mechanicallytoitsmanufacturer'spublishedspecificationandperformswithout
anyfault.

WARNING:EnergyLimitedandNonSparkingcircuitsmustnotbeinterconnected.

12. ForCharmslabeled(ExnLIICT4orExicIICT4),anI/OloopassessmentMUSTbe
completedonallenergylimitednodes.Ifaloopassessmentisnotpossibleor
practical,anEnergyLimitedcomponentmarked(ExnLoric)maybeusedasanExnA
partsofarasthelivemakingandbreakingofcircuitsisexcluded.Inaddition
provisionsmustbemadetopreventpossibletransientsexceedingthepeakrated
voltagevalueof85Vbymorethan140%asprescribedinthestandard6007915.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 9

Whenasupply[ExnL]isuseditisassumedtheExnLcomponentissufficiently
protectedfromtransientsbythesupply.

13. ExicCircuits

Circuitsoftypeofprotection"Exic"(intrinsicallysafe)whichhavebeenoperatedwith
circuitsofothertypeofprotectionsmustnotbeusedas"Exic"circuitsafterwards.
Therespectivepeakvaluesofthefielddeviceandtheassociatedapparatuswithregardto
explosionprotectionshouldbeconsideredwhenconnectingintrinsicallysafefielddevices
withintrinsicallysafecircuitsofassociatedapparatus(verificationofintrinsicsafety).
MakesuretoobserveIEC/EN6007914andIEC/EN6007925.
Allseparationdistancesbetweennonintrinsicallysafecircuitsandintrinsicallycircuits
needtobeobservedinaccordancewithIEC/EN6007914.Allseparationdistances
betweenadjacentintrinsicallysafecircuitsneedtobeobservedinaccordancewithIEC/EN
6007914.
TheEntityConceptallowsinterconnectionofintrinsicallysafeapparatuswithassociated
apparatusnotspecificallyexaminedincombinationasasystemwhentheapprovedvalues
ofUo(Voc)andIo(Isc)fortheassociatedapparatusarelessthanorequaltoUi(Vmax)
andIi(Imax)fortheintrinsicallysafeapparatus.SeeTable1forEntityParameters.
Capacitanceandinductanceofthefieldwiringbetweenintrinsicallysafeequipmentand
theassociatedapparatusshallbecalculatedandmustbeincludedinthesystem
calculations.CablecapacitanceCcableplusintrinsicallysafeequipmentcapacitanceCi
mustbelessthanthecapacitanceCo(Ca),markedonanyconnectedassociatedapparatus.
Thesameappliesforthevaluesforinductance(Lcable,LiandLoorLarespectively).
Wherethecablecapacitanceandinductanceperfootarenotknown,thefollowingvalues
shallbeused:Ccable=60pF/ft.,Lcable=0.2H/ft.
TheI/OModulesmayalsobeconnectedtosimpleapparatusasdefinedinArticle504.2
andinstalledandtemperatureclassifiedinaccordancewithArticle504.10(B)ofthe
NationalElectricalCode(ANSI/NFPA70),orotherlocalcodes,asapplicable.
14. ACharmTerminalGmustbefittedtoalloccupiedorunoccupiedslotsonaCharm
BaseplateL.
15. AdditionalCharmBaseplatesLoranExtenderEmaybeusedtofurtherdistributethe
systempowerprovidedeachsystemislimitedtoamaximumof8CharmBaseplatesand
one2meterextendercable.SeeFigure1.
CAUTION:Carriers,Baseplates,ExtendersandExtenderCablesmustNOTbeaddedor
unpluggedunlesseither:
A. theSystemhasbeendeenergized,or
B.theareaisknowntobenonhazardous.

16. TheCIOC,WIOC,CSLS,SZ,(A)andPowerModules(W)andallFiberPorts(J)maynotbe
removedorinsertedwithpowerappliedunlesstheareaisknowntobenonhazardous
SeeTable1.

17. PowerPlugsKmaynotberemovedorinsertedwithpowerapplied.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 10

18. WARNING:Equipmentplacedinahazardouslocationshallnothaveanysurfaceexposed
toflammableorcombustiblematerialsthatoperateatatemperatureexceedingthe
temperatureratingmarkedontheapparatus.Thetemperaturemarkingspecifiedshall
notexceedtheignitiontemperatureofthespecificgasorvaportobeencountered.

19. WARNING:TheKL4505X1DA1,EA1,GA1,KL4502X1MA1andKL4502X1LA1cannot
havehazardouslivevoltages(120VACor250VAC)presentontheterminals.Maximum
VoltageisUm<26.4VDC.
20. Thetypeofprotection(nAornL)isnotidentifiedontheCHARMTerminalsmostCHARM
TerminalsaregenericanduniversalandcanbeusedforeithernAornLapplications.The
keyingsystemoneachCHARMTerminalBlockisshippedinaneutralposition.Thetypeof
Terminalfunctionalityisbasedonthekeythatissetduringinstallation.TheTerminalsby
themselvesdonothavefieldcircuitEntityParameters.OnceinstalledtheTerminal
inheritstheEntityParametersoftheCHARMthatisinstalledinthatposition.Consultthe
HardwareReferenceManualforwhichCHARMscanbeusedwithwhichTerminals.
21. TheRelayOutputTerminalBlockKL4502X1MA1isdesignedforhighoutputcurrent
applicationsandrequirestheDO24VDCHighsideCHARMtodrivetherelaycoil.The
RelayOutputTermblocksprovideanormallyopenandnormallyclosed
contact..MaximumVoltageisUm<26.4VDC.
22. TheCIOC,WIOC,CSLSandSZ(A)canonlybeusedwiththeirrespectiveCarriers(H).See
Figure1.
23. TheLSDVCHARTDTACHARM(V1)isusedwiththeLSDVCTerminalBlock(T7).
24. TheRedundantLSDVCCHARMTerminal(T3)isusedwithtwoLSDVCHART(Redundant
DTA)CHARMs(V2).
25. TheLSThermocouple/mVCHARM(R1)mustbeusedwiththeThermocouple/mV
TerminalBlock(S).
26. TheRedundantLSDOCharmTerminalBlock(T4)isusedwitheithertwoLSDOUT24VDC
(RedundantDTA)CHARMs(V3)ortwoLSDOUT24VDC(RedundantETA)CHARMs(V4).
27. TheRelayDTAInjectedPowerLSDOCHARMTerminal(T1)isusedwithtwoLSDO
24VDC(RedundantDTA)CHARMs(V3).
28. TheRedundantDTARelayCHARMTerminal(T9)isusedwithtwoLSDOUT24VDC
(RedundantDTA)CHARMs(V3).
29. TheRedundantETARelayCHARMTerminal(T5)isusedwithtwoLSDOUT24VDC
(RedundantETA)CHARMs(V4).

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 11

30. TheStandardCharmTerminal(G)canusedwiththefollowingLSCHARMs:
LSAI010VDCIsolatedCHARM(D)
LSAI420mAHARTCHARM(D)
LSDI24VDCIsolatedCHARM(B)
LSDI24VDCLowSideCHARM(D)
LSDINAMURCHARM(D)
LSRTD/ResistanceInputCHARM(D)
LSDO24VDCDTACHARM(B)
LSDO24VDCETACHARM(B)

SeetheSISHardwareReferenceManualfordetails.

31. TheFusedInjectedPowerCharmTerminal(T6)canbeusedwiththefollowingLS
CHARMs:
LSDI24VDCIsolatedCHARM(C)
LS24VDCPowerCHARM(C)

32. Theolder(nonfused)InjectedPowerCharmTerminal(P)hasbeenreplacedbytheFused
InjectedPowerCharmTerminal(T6).ThenewFusedInjectedPowerTerminalworkswith
bothLSandnonLSCHARMs.SeetheHardwareReferenceManualfordetails.
33. AmbientTemperature:Ta=40to+70C(unlessnotedinTable1)

34. WARNING:Substitutionofcomponentsmayimpairintrinsicsafety

Marking
FormarkingdetailsrefertotheindividualATEXInstructionSheetforeachmodule.

MountingandInstallationInstructions
Priortomounting,installation,andcommissioningofthedevicetheinstallershouldbe
familiarwiththedeviceandcarefullyreadtheinstructionmanual.
TheinstallationinstructionsspecifiedbyIEC/EN6007914mustbeobserved.
TheECtypeexaminationcertificate,certificatesand/ordeclarationsofconformitieshaveto
beobservedifapplicableespeciallythespecialconditionsofuse.
Ifthedevicehasalreadybeenoperatedingeneralelectricalsystems,itisnotallowedtoinstall
itinelectricalsystemsusedincombinationwithhazardousareas.
ThedevicefulfillsadegreeofprotectionIP20accordingtoIEC/EN60529.
ToensuretheIPdegreeofprotectionallsealsofthedevicehousing(ultrasonicwelding)and
thehousingsthemselvesmustbeundamagedandcorrectlyfitted.
ThedevicemayonlybeinstalledandoperatedinZone2ifithasbeenmountedinan
enclosurewithdegreeofprotectionIP54accordingtoIEC/EN60529.Theenclosuremust
haveadeclarationofconformityaccordingto94/9/ECforatleastcategory3G.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 12

TheSystemmustbesuppliedwithaSELV/PELVorclass2powersupplywithamaximumDC
voltageofUm=26.4VDCattheedgeconnectors.
Carrierterminalscanbeusedtoconnectacablescreenofthefieldwiring.Thescreenbar
itselfmustbeconnectedtotheequipotentialbondingsystemofthehazardousarea.
Thecommunicationnetworkmusthaveaprospectivefaultcurrentof<100A.

Operation,MaintenanceandRepair
Thedevicemustnotberepaired,changedormanipulated.Ifthereisadefect,theproduct
mustalwaysbereplacedwithanoriginaldevice.
Connectionordisconnectionofenergizednonintrinsicallysafeandnonenergylimited
circuitsareonlypermittedintheabsenceofahazardousatmosphere.

TorqueRequirementsforI/OTerminalScrews:
I/Oterminals0.45Nm(4inlb)

Table1ListofApprovedModels
Table1followsonnextpage.TheCHARMslistedinTable1canonlybeusedwiththe
CHARMI/OSubsystemcomponentsalsolistedinTable1.TheCHARMI/OSubsystem
componentslistedinTable1canonlybeusedwiththeCHARMslistedinTable1.
Note:InallcasesUmmustbelessthan26.4VDC.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 13

Removalor
Insertion FieldCircuitClassand
Ref. With
Model Description EntityParameters
Fig.1 System
Power (seeItem11)
Energized
KL1501X1BA1 W CSLSPOWERMODULE No4 NONSPARKING2
KL1601X1BA1 J I/OPort,Copper No4 NONSPARKING2
I/OPort,Fiber
KL1602X1BA1 J No4 NONSPARKING2
Ta:40to+60C
SAFETYNETWORKPORT
KL1603X1BA1 J No4 NONSPARKING2
COPPER
SAFETYISOLATIONPORT
KL1604X1BA1 J No4 NONSPARKING2
COPPER
KL2001X1BA1 A CSLS No4 NONSPARKING2
KL2001X1BB1 A SZCONTROLLER No4 NONSPARKING2
KL2101X1BA1 A CHARMI/OCard(CIOC) No4 NONSPARKING2
KL2102X1BA1 A WirelessI/OCard(WIOC) No4 NONSPARKING2
ENERGYLIMITED
KL3001X1BA1 D DiscreteInNamurCHARM EntityParameters
Po=27mW
YES1
Uo=12.6V,Io=8.5mA,
KL3001X1LS1 D LSDiscreteInNamurCHARM Co=6.8F,
Lo=1000mH
DiscreteOut+24VDCHighSide
KL3002X1BA1 B No4 NONSPARKING2
CHARM
DiscreteIn+24VDCDryContact ENERGYLIMITED
KL3003X1BA1 D
CHARM EntityParameters
YES1 Po=370mW
LSDiscreteIn+24VDCDry Uo=26.4V,Io=14mA,
KL3003X1LS1 D
ContactCHARM Co=0.11F,Lo=75mH
DiscreteOut+24VDCIsolated
KL3004X1BA1 BorC No4 NONSPARKING2
CHARM
DiscreteIn+24VDCIsolated
KL3005X1BA1 BorC
Charm
No4 NONSPARKING2
LSDiscreteIn+24VDCIsolated
KL3005X1LS1 BorC
Charm
ENERGYLIMITED
EntityParameters
DiscreteOut<100mAEnergy
KL3006X1BA1 B YES1 Po=739mW
LimitedCHARM
Uo=26.4V,Io=112mA,
Co=0.02F,Lo=5mH.
KL3007X1BA1 C PowerCHARM,+24VDC
No4 NONSPARKING2
KL3007X1LS1 C LSPowerCHARM,+24VDC
ENERGYLIMITED
AnalogIn,420mA,HART
KL3021X1BA1 D EntityParameters
CHARM
YES1 Po=792mW
LSAnalogIn,420mA,HART Uo=26.4V,Io=30mA,
KL3021X1LS1 D Co=0.03F,Lo=8mH.
CHARM

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 14

Removalor
Insertion FieldCircuitClassand
Ref. With
Model Description EntityParameters
Fig.1 System
Power (seeItem11)
Energized
ENERGYLIMITED
EntityParameters
AnalogOut,420mA,HART Po=217mW
KL3022X1BA1 D YES1
CHARM Uo=26.4V,Io=33mA,
Co=0.333F,
Lo=11mH.
ENERGYLIMITED
KL3023X1BA1 D AnalogIn,010VIsolatedCharm EntityParameters
Po=18mW
YES1
Uo=5.5V,Io=3.18mA,
LSAnalogIn,010VIsolated Co=3.2F,
KL3023X1LS1 D
Charm Lo=0.999mH.
ENERGYLIMITED
KL3031X1BA1 D RTD/ResistanceInputCHARM EntityParameters
Po=18mW
YES1
Uo=5.5V,Io=3.18mA,
LSRTD/ResistanceInput Co=3.2F,
KL3031X1LS1 D
CHARM Lo=0.999mH.
ENERGYLIMITED
Thermocouple/mVInput EntityParameters
KL3032X1BA1 R
CHARM Po=18mW
YES1
Uo=5.5V,Io=3.18mA,
LSThermocouple/mVInput Co=2.1F,
KL3032X1LS1 R1 Lo=0.999mH.
CHARM
KL3302X1BA1 B LSDO24VDCDTACHARM No4 NONSPARKING2
LSDO24VDC (RedundantDTA)
KL3302X1BB1 V3 No4 NONSPARKING2
CHARM
KL3302X1BC1 B LSDO24VDCETACHARM No4 NONSPARKING2
LSDO24VDC(RedundantETA)
KL3302X1BD1 V4 No4 NONSPARKING2
CHARM
ENERGYLIMITED
EntityParameters
Po=792mW
KL3322X1BA1 V1 LSDVCHARTDTACHARM YES1
Uo=26.4V,Io=30mA,
Co=0.05F,
Lo=0.35mH.
ENERGYLIMITED
EntityParameters
LSDVCHART(RedundantDTA) Po=1.584W
KL3322X1BB1 V2 YES1
CHARM Uo=26.4V,Io=60mA,
Co=0.05uF,
Lo=0.3mH.
KL4001X1BA1 H SZCONTROLLERCARRIER No4 N/A
KL4103X1BA1 H CSLSCARRIER No4 N/A
KL4101X1BA1 H CIOCCarrier No4 N/A
KL4102X1BA1 H WIOCCarrier No4 N/A

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 15

Removalor
Insertion FieldCircuitClassand
Ref. With
Model Description EntityParameters
Fig.1 System
Power (seeItem11)
Energized
KL4201X1BA1 L CHARMBaseplate No4 N/A
KL4302X1CA1 Q WIOCTermBlock Redundant No4 N/A
KL4501X1BA1 F CHARMAddressPlug1
KL4501X1BB1 F CHARMAddressPlug2
ENERGYLIMITED
KL4501X1BC1 F CHARMAddressPlug3
EntityParameters
KL4501X1BD1 F CHARMAddressPlug4
YES1 Po=162mW
KL4501X1BE1 F CHARMAddressPlug5
Uo=6.49V,Io=100mA,
KL4501X1BF1 F CHARMAddressPlug6
Co=325F,Lo=5mH.
KL4501X1BG1 F CHARMAddressPlug7
KL4501X1BH1 F CHARMAddressPlug8
CHARMTerminal,Standard
KL4502X1BA1 G YES1,3 SEENOTE5
(Screw)
CHARMTerminal,Injected
KL4502X1CA1 P YES1,3 SEENOTE5
Power(Screw)
CHARMAddressTerminal
KL4502X1DA1 N No4 NONSPARKING2
(Screw)
CHARMColumnTerminator,
KL4502X1EA1 M No4 NONSPARKING2
Bottom
CHARMColumnTerminator,
KL4502X1FA1 M No4 NONSPARKING2
Top
KL4502X1LA1 T6 CHARMTerminal,Fused(Screw) YES1,3 SEENOTE5
KL4502X1
G YES1,3 SEALEDDEVICE2
MA1 CHARMTerminal,Relay(Screw)
KL4502X1NA1 S CharmTerminal,TC/mV No4 SEENOTE5
CHARMColumnExtender,
KL4503X1BA1 E No4 NONSPARKING2
Bottom
KL4503X1CA1 E CHARMColumnExtender,Top No4 NONSPARKING2
KL4505X1BA1 T4 REDLSDOCHARMTERMINAL No4 SEENOTE5
KL4505X1CA1 T3 REDLSDVCCHARMTERMINAL YES1,3 SEENOTE5
RELAYETALSDOCHARM
KL4505X1DA1 T5 No4 SEALEDDEVICE2
TERMINAL
RELAYDTALSDOCHARM
KL4505X1EA1 T9 No4 SEALEDDEVICE2
TERMINAL
KL4505X1FA1 T7 LSDVCCHARMTERMINAL YES1,3 SEENOTE5
RELAYDTAIPLSDOCHARM
KL4505X1GA1 T1 No4 SEALEDDEVICE2
TERMINAL

1
note:
RemovalorinsertionofaCharmI/Omodulewithsystempowerenergizedmayonlybedonewhenusedwiththe
KL2101X1BA1,CIOCoronanLSSystemwiththeKL1501X1BA1CSLSPowerModuleoperatingon24VDCinput
powerpernotes1and3.

2
note:
NonSparkingfieldcircuitsaredesignedsothatignitiondoesnotoccurduringnormaloperation.Nonsparking
fieldcircuitsMUSTbedeenergizedbeforeremovingandinsertingaCharmI/Omodule.Pleaserefertodefinitions
innote11.

2013 Fisher-Rosemount Systems, Inc. All Rights reserved.


TM
DeltaV Charm I/O Zone 2 Installation
Instructions
12P5403 Page 16

3
note:
CharmTerminalscanbeaddedorremovedwithSystemPowerappliedonlywhennoCharmisinstalledandno
fieldwiringisconnectedtotheterminal.Onceinstalled,theCharmTerminalassumesthecircuitparametersofthe
Charmforthatposition.

4
note:
Thesemodulescanonlybeinsertedorremovedwhen:
a. TheSystemhasbeendeenergizedor
b. Theareaisknowntobenonhazardous
5
note:
TheCHARMTerminalsbythemselvesdonothaveEntityParameters.OnceinstalledtheCHARMandtheCHARM
TerminalpairassumetheEntityParametersoftheCHARMforthatposition.SeealsoNote20.