Вы находитесь на странице: 1из 10

ARTICLE IN PRESS

WAT E R R E S E A R C H 40 (2006) 3695 3704

Available at www.sciencedirect.com

journal homepage: www.elsevier.com/locate/watres

Comparison of the efficiency of dOH radical formation


during ozonation and the advanced oxidation processes
O3/H2O2 and UV/H2O2

Erik J. Rosenfeldta,b, Karl G. Lindenb, Silvio Canonicaa, Urs von Guntena,


a
Swiss Federal Institute of Aquatic Science and Technology, Eawag, 8600 Dubendorf, Switzerland
b
Department of Civil and Environmental Engineering, Duke University, Durham, NC 27708-0287, USA

art i cle info A B S T R A C T

Article history: Comparison of advanced oxidation processes (AOPs) can be difficult due to physical and
Received 6 June 2006 chemical differences in the fundamental processes used to produce dOH radicals. This
Received in revised form study compares the ability of several AOPs, including ozone, ozone+H2O2, low pressure UV
4 September 2006 (LP)+H2O2, and medium pressure UV (MP)+H2O2 in terms of energy required to produce dOH
Accepted 12 September 2006 radicals. Bench scale dOH radical formation data was generated for each AOP using para-
Available online 31 October 2006 chlorobenzoic acid (pCBA) as an d
OH radical probe compound in three waters, Lake
Keywords: Greifensee water, Lake Zurich water, and a simulated groundwater. Ozone-based AOPs
Advanced oxidation were found to be more energy efficient than the UV/H2O2 process at all H2O2 levels, and the
d
OH radical addition of H2O2 in equimolar concentration resulted in 35% greater energy consumption
Ozone over the ozone only process. Interestingly, the relatively high UV/AOP operational costs
O3/H2O2 were due almost exclusively to the cost of hydrogen peroxide while the UV portion of the
UV/H2O2 UV/AOP process typically accounted for less than 10 percent of the UV/AOP cost and was
always less than the ozone energy cost. As the dOH radical exposure increased, the energy
gap between UV/H2O2 AOP and ozone processes decreased, becoming negligible in some
water quality scenarios.
& 2006 Elsevier Ltd. All rights reserved.

1. Introduction During ozonation, organic contaminants are oxidized in


two ways. Ozone itself can directly react with dissolved
Advanced oxidation processes (AOPs) have been defined as the chemicals, at varying rates, and is a highly selective
aqueous phase chemical oxidation of target organic or inorganic oxidant (Hoigne and Bader, 1983a, b; Hoigne et al., 1985).
pollutants by a process involving hydroxyl free radicals (Singer In addition to direct oxidation, ozone decomposes via a
and Reckhow, 1999). Hydroxyl radical (dOH) reacts very quickly chain reaction mechanism to form dOH radicals, which in
with many organic species, displaying kinetic constants in the turn can oxidize the pollutant (Hoigne, 1982). The two
range from 108 to 1010 M1 s1 (Haag and Yao, 1992). AOPs can be pathways can lead to different products and display different
generated via a number of aqueous treatment scenarios transformation kinetics (von Gunten, 2003a). When hydrogen
including ozone, ozone/H2O2, UV/ozone, UV/H2O2, UV/H2O2/O3, peroxide is added to the ozone system, the decomposition of
Fentons processes, and photocatalysis. Previous reviews de- O3 into dOH radicals is accelerated, essentially shifting
scribe these AOPs, including ozone-based (von Gunten, 2003a) the process entirely to an AOP. This is recommended for
and UV- based (Legrini et al., 1993) processes. waters in which ozone is stable and resulting pollutant

Corresponding author. Tel.: +41 44 823 5270; fax: +41 44 823 5210.
E-mail address: vongunten@eawag.ch (U. von Gunten).
0043-1354/$ - see front matter & 2006 Elsevier Ltd. All rights reserved.
doi:10.1016/j.watres.2006.09.008
ARTICLE IN PRESS
3696 WAT E R R E S E A R C H 40 (2006) 3695 3704

Nomenclature kOH,N second order rate constant for the reaction of dOH
radicals with species N (M1 s1)
AOP advanced oxidation process LP low pressure mercury vapor UV lamp
CO3 ;i initial ozone concentration (mg L1) MP medium pressure mercury vapor UV lamp
[CO23 ] concentration of carbonate in water ZUV UV lamp efficiency (30% for LP, 15% for MP (USEPA,
DOC dissolved organic carbon (mg L1) 2003))
E0 a OH
d
average UV fluence rate (mW L1) hydroxyl radical
E0 a(l) wavelength specific average fluence rate in the [RdOH] concentration of dOH radical (M)
reactor (mW L1) OHdt dOH radical exposure (M s)
E$ local cost of electricity ($ kWh1) O3 ozone
EH2 O2 hydrogen peroxide energy requirement (kWh L1) pCBA para-chlorobenzoic acid
E0 lamp(l) wavelength specific fluence rate at the surface %dOHpCBA percent of dOH radical available for oxidation
of the lamp (mW L1) of pCBA in ozone or UV/H2O2 experiments
EEO electrical efficiency per order Rct ratio of dOH radical exposure to ozone exposure
EO3 energy of the ozone process (kWh L1) in ozone processes
[HCO ]
3 concentration of bicarbonate in water RF reflection factor of air/quartz/water interface
H0 UV fluence (mJ L1) ROH,UV dOH radical exposure per UV fluence in the UV/
H$ local cost of hydrogen peroxide ($ kg1 H2O2) H2O2 AOP (M s L mJ1)
H2O2 hydrogen peroxide [S] concentration of scavengers in water (M)
HPLC high performance liquid chromatography t time (s)
k0 D
d observed fluence based pCBA direct photolysis Ufluence UV lamp energy requirement for a given fluence
pseudo-first order rate constant (L mJ1) (kWh L1)
kd0
direct photolysis time based pseudo-first order UV ultraviolet
rate constant (s1) WF water factor used to calculate the average fluence
k0 obs observed pseudo-first order rate constant for rate from the incident fluence rate WF 1 
pCBA oxidation (s1) e2:303alb =2:303alb (Bolton and Stefan, 2002)
k0 D
obs observed pseudo-first order fluence based rate a(l) wavelength specific UV energy absorbance (cm1)
constant for pCBA oxidation (L mJ1) b reactor pathlength (cm)

degradation is slow (Acero and von Gunten, 2001; Griffini and water being treated. Therefore, the comparison between the
Iozzelli, 1996). technologies could not be generalized, and was not applicable
UV-based AOPs also transform pollutants in two ways. to different water matrices. Bolton and Cater (1994) indicated
Some organic chemicals absorb UV light directly, and that under optimum conditions, the energy required to
absorption of this high-energy radiation can cause destruc- produce one mole of dOH radicals by the UV/H2O2 process
tion of chemical bonds and subsequent breakdown of the was 0.54 kWh as opposed to the 1.05 kWh needed to create
contaminant (Schwarzenbach et al., 2003). However, some one mole by the ozone/peroxide process. They also deter-
organic species do not degrade very quickly or efficiently by mined that the comparative efficiency is dependent upon UV
direct UV photolysis. Therefore, addition of H2O2 to the UV absorbance of the water, and in waters with high UV
process creates AOP conditions, often increasing the rate of absorbance, the UV process can become more energy
contaminant degradation significantly. H2O2 absorbs UV light, consumptive than the ozone process.
and breaks down into dOH radicals (Bolton and Cater, 1994), The amount of dOH radical produced and a fraction thereof
degrading the contaminant via dOH radical oxidation. The used for targeted oxidation for each process are important
quantum yield for the process is 1 mol dOH per Einstein comparative parameters for evaluation of different AOPs. The
absorbed by H2O2. goal of this study was to directly compare the energy of dOH
There has been little research comparing AOPs for their radical oxidation by ozone, ozone/H2O2, low-pressure (LP) UV/
potential to form dOH radicals. Several attempts to compare H2O2, and medium pressure (MP) UV/H2O2. To address this
different AOPs for their effectiveness at destroying target goal, ozone and UV/H2O2 bench scale experiments were
pollutants include Muller and Jekel (2001), Muller et al. (2001) performed, examining the degradation of a commonly
who used the concept of EEO put forth by Bolton and Bircher utilized dOH radical probe compound, para-chlorobenzoic
(1996) to compare the electrical energy needed to degrade acid (pCBA) (Elovitz and von Gunten, 1999, 2000; Pines and
atrazine by one order of magnitude via the UV/H2O2, UV/O3, Reckhow, 2003; Han et al., 2002; Acero et al., 2003), in three
and O3/H2O2 processes. The results of these studies indicated distinct waters.
that for Berlin tap water and a model water, the ozone based Rct, defined as the steady state ratio of dOH radical exposure
processes were an order of magnitude more energy efficient to O3 exposure was determined by pCBA as the probe
than the UV based processes. However, these results were compound for dOH radical exposure. pCBA is an ideal probe
dependent upon reactor geometry and upon the specific compound for ozone AOP studies because it displays slow
ARTICLE IN PRESS
WAT E R R E S E A R C H 4 0 (200 6) 369 5 370 4 3697

reaction rates with ozone (kO3o1 M1 s1), but rapid oxidation The indigo method (Hoigne and Bader, 1981) was used for
kinetics with the dOH radical (kOH,pCBA 5  109 M1 s1) ozone residual analysis, and the I3 method (Klassen et al.,
(Elovitz and von Gunten, 1999). pCBA is also an ideal probe 1994) was used to measure residual H2O2.
compound for UV AOP studies for similar reasons. The Atrazine and pCBA were detected using a Hewlett-Packard
quantum yield of pCBA was determined to be 0.026 using Series 1050 HPLC with UV/vis detection. A Macherey-Nagel
UV light in the wavelength range of 250350 nm (Chen et al., CC125/4 Nucleosil 100-5 C-18 column was used for pCBA
1998), indicating that direct photolysis of pCBA will likely be detection, and a Hewlett Packard LichroCART 250-4 reverse
slow compared to the advanced oxidation pathway. phase C-18 column (5 mm) for atrazine separation. An eluent
Utilizing this approach, the energy for dOH radical oxidation consisting of 60%:40% methanol: H2O (adjusted to pH 2 with
between AOPs was compared, independent of reaction time H3PO4) was used for pCBA and 50:50 methanol:H2O was used
and reactor geometry, but accounting for water matrix for atrazine. UV absorbance at 240 and 220 nm was used for
properties. pCBA and atrazine measurement, respectively. Quantification
limits of 0.05 mM for pCBA and atrazine were achieved.

2. Materials and methods


2.3. Experimental setup
2.1. Reagents and waters
Two ozone experimental setups were employed. To determine
All chemicals for these experiments were purchased from the Rct in Lake Greifensee water and Lake Zurich water,
Fluka (Buchs, Switzerland) or Merck (Darmstadt, Germany), dynamic experiments were performed in a 500 mL batch
with the exception of the Indigo trisulfonate potassium salt, reactor spiked to the following final concentrations: 5 mM
which was obtained from Riedel-de Haen (Hanover, Ger- borate (pH 8 experiments) or phosphate buffer (pH 6.5
many). HPLC reagent grade methanol was from Scharlau experiments), and 0.5 mM pCBA. The solution was kept at
Chemie S.A. (Barcelona, Spain). 15 1C and pH was adjusted using 1 M HCl or 1 M NaOH. Ozone
Pure water was obtained from a Millipore Quantum EX stock solution was added to the proper concentration (62.5 mM
system with Ultrapure Organex Cartridge and Q-Guard 2 in Lake Greifensee water, and 20.8 mM in Lake Zurich waters)
cartridges, and a Millipore 0.22 micron Millipak Express filter via an inlet tube, and samples were taken at time predeter-
(Billerica, MA). The experimental waters were collected raw mined intervals for ozone and pCBA analysis. For ozone
from Lake Greifensee and Lake Zurich in Switzerland. dosage experiments, a vial was filled with the water to be
Additionally, Lake Zurich water was spiked with NaHCO3 to tested, and then spiked to achieve the buffer and pCBA
increase alkalinity to a concentration of approximately 8 mM concentrations above. The solution was kept at 15 1C and pH
(Table 1). Natural waters were filtered with a 0.45 mm filter, and was adjusted using 1 M HCl or 1 M NaOH. Ozone stock was
stored at 4 1C in glass containers prior to use. Water quality added at the proper concentration (2.08, 4.17, 10.4, 20.8, and
parameters (alkalinity, DOC, and nitrate) were determined 104 mM O3) at time zero. Samples were quenched with Na2SO3
using standard methods (APHA, AWWA and WEF, 2000). Table after 30 min and 15 h for pCBA analysis via HPLC. Ozone/H2O2
1 displays the water quality parameter measurements. experiments were performed exactly as the ozone experi-
Ozone was generated in a Fischer Model 502 Ozon- ments with the addition of H2O2 (1:2 or 1:1 on a molar basis
Generator (Germany), with direct O2 feed from Carbagas H2O2:O3 ratio) to the reaction mixture before the addition of
(Bern, Switzerland). The ozone-enriched oxygen gas was ozone.
bubbled into one liter of water on ice to create an approxi- UV experiments were performed in a DEMA model 125
mately 1 mM saturated ozone stock solution. The concentra- merry-go-round photoreactor (Hans Mangels GmbH, Born-
tion of the ozone stock solution was determined via UV heim-Roisdorf, Germany), equipped with either a 15 W
absorbance at 258 nm (e258 3000 M1 cm1). Heraeus Noblelight TNN 15/32 low pressure mercury vapor
lamp (Hanau, Germany), or a 150 W Heraeus Noblelight TQ
2.2. Analytical methods 150 medium pressure mercury lamp (Hanau, Germany)
surrounded by two square mesh stainless steel wire cloths,
A Cary 100 Bio UVvis spectrophotometer (VarianPalo Alto, open area 53% and 40%, respectively, resulting in approxi-
CA), and a UVIKON 940 spectrophotometer (Kontron Instru- mately 21% light transmission. Reactor rotation and time was
ments, Watford, UK) were used to measure UV absorption. begun upon placement of the sample-filled, UV transparent

Table 1 Water quality of the waters examined in this study

Water pH DOC (mg L1) Alkalinity (mM as HCO 2


3 /CO3 ) Nitrate (mg N L1) UV 254 (cm1)

Lake Greifensee 8.0 3.5 3.4 1.6 0.067


Lake Zurich 7.9 1.4 2.7 0.8 0.032
Lake Zurich+alkalinity 8.2 1.3 8.2 0.8 0.036
ARTICLE IN PRESS
3698 WAT E R R E S E A R C H 40 (2006) 3695 3704

quartz tubes. At the predetermined irradiation time to and included DOC (kOH,DOC 2.5  104 L mg1 s1) (Larson
6
achieve a target fluence, a tube was removed for pCBA and and Zepp, 1988), HCO 3 kOH;HCO3 8:5  10 M

1 1
s ,
2 8 1 1
H2O2 analysis. CO3 kOH;CO2 3:9  10 M s (Hoigne et al., 1985; Buxton
3
The UV experiments were performed in three stages. First, et al., 1988) along with incorporating the spiked pCBA
atrazine actinometry experiments were performed to deter- kOH,pCBA 5  109 M1 s1) (Elovitz and von Gunten, 1999) and
mine the irradiance incident to the surface of the tube for H2 O2 kOH;H2 O2 2:7  107 M1 s1 (Buxton et al., 1988). Percent
each lamp. Once this irradiance was determined, direct UV available dOH radical data is tabulated (Table 2) for each
experiments were run without the addition of H2O2 to process and will be utilized to aid in the discussion of
determine the rate of direct photolysis of pCBA. Finally, UV/ differences in the processes between water matrices. The
H2O2 experiments were performed to determine oxidation of scavenging of dOH radicals by ozone can also be a significant
pCBA by UV in combination with H2O2 concentrations of 2, 10, sink for dOH radicals. However, the kinetics of the reaction
and 50 mg L1. between ozone and dOH radicals are not well defined, and a
sensitivity analysis showed that for most of the conditions
2.4. Atrazine actinometry for UV fluence calculation tested in this study, inclusion of this parameter resulted in
less than a 0.5% difference in %OHpCBA . Rather than to include
Atrazine actinometry experiments were performed to deter- the significantly variable kOH,O3 rate constant, which has been
mine the fluence rate in the quartz tube for each lamp at the measured between 108 M1 s1 to 2  109 M1 s1 (von Gunten,
limit of negligible optical density. Next, the average UV 2003a), the effect of dOH radical scavenging by ozone was
fluence rate (mW L1) in the completely mixed sample was neglected in this study.
determined using an integrated form of the Beer-Lambert law These calculated values are utilized for qualitative compar-
including UV absorbance, and sample depth (Linden and ison purposes only, and are presented acknowledging that
Darby, 1997). The UV fluence delivered to a sample was discrepancies within the reported data exists regarding reaction
calculated as the average UV fluence rate multiplied by the rate constants, that errors in measurement of water quality
exposure time. For the LP UV source, UV fluence was parameters can significantly alter the parameter, and that this
calculated as the radiation emitted at 254 nm. For the broad- discussion is only valid for the initial conditions. Even with
band MP UV source, the fluence was calculated as the sum of these qualifications, the percent available dOH radical will be a
the total UV output in the 200300 nm region. useful qualitative tool to illustrate differences between waters
For experiments performed using the LP lamp, a fluence and discuss underlying reasons for these differences.
rate of 4.55  109 Einstein cm2 s1 for 254 nm radiation was
determined by atrazine actinometry, employing a quantum 3.2. Using Rct and ROH,UV to characterize the waters under
yield for atrazine depletion of 0.05 mol Einstein1 (Beltran typical treatment conditions
et al., 1993). For the MP lamp, atrazine actinometry yielded a
fluence rate of 9.3  109 Einstein cm2 s1 for UV light in the The steady state parameters Rct and ROH,UV were utilized to
wavelength range of 200300 nm. The latter fluence rate was characterize ozone-based and UV/H2O2 AOPs for each water
calculated using the above quantum yield value, which under typical operating conditions. These typical conditions
should be a good approximation for the average quantum consist of an ozone dose of 1 mg L1 per 1 mg L1 DOC, and LP
yield (the main spectral contribution to atrazine photolysis or MP UV+0.29 mM (10 mg L1) H2O2. Rct is defined as the ratio
with the MP lamp is given by the range of 250270 nm, which of dOH radical exposure to ozone exposure (Elovitz and von
has a wavelength-independent quantum yield (Sharpless Gunten, 1999), and ROH,UV is a new concept, defined as the
et al., 2003)).
d
OH radical exposure (Ms) per UV fluence (mJ L1). (Rosenfeldt
and Linden, 2005).

3. Results and discussion 3.2.1. Ozone processes


Bench scale testing was performed in Lake Greifensee, Lake
3.1. Theoretical efficiency of AOPs Zurich, and Lake Zurich+alkalinity waters to characterize the
waters using the Rct concept, fully developed in Elovitz and
One of the major factors governing AOPs is the fraction of dOH
radicals available for the oxidation of the target contaminant
as compared to the fraction of dOH radicals scavenged by the
Table 2 Percent OH radical available for oxidation of
background water matrix. To determine the theoretical effect
0.5 lM pCBA in water treated with ozone and
of the scavenging in each water, the percent of dOH radical UV+0.29 mM H2O2
available for oxidation of pCBA was calculated using Eq. (1).
The value considers only the theoretical ratio of the rate of
Ozone UV+0.29 mM H2O2
oxidation of pCBA as compared to the rate of oxidation of all
d
OH radical scavengers (S) in the water. Water pH 6.5 pH 8 pH 6.5 PH 8
kOH;pCBA pCBA
%OHpCBA 100 P . (1) Lake Greifensee 1.8 1.6 1.7 1.5
fkOH;pCBA pCBA kOH;S Sg Lake Zurich 3.2 2.9 2.9 2.6
The scavenging rate in the system was calculated Lake Zurich+alkalinity 1.6 1.3 1.5 1.3

from the water quality information listed in Table 1,


ARTICLE IN PRESS
WAT E R R E S E A R C H 4 0 (200 6) 369 5 370 4 3699

von Gunten (1999). To determine the Rct, the oxidation of into one equation.
pCBA as a function of ozone exposure (M min) is measured, to   Z
pCBAo
calculate the production of hydroxyl radicals per unit ln k0d t kOH;pCBA OHdt k0obs t (3)
pCBA
consumption of ozone. Fig. 1 displays the Rct values deter-
mined in Lake Greifensee water with an ozone dose of and
R
62.5 mM, and Lake Zurich water and Lake Zurich+alkalinity OHdt
k0obs k0d kOH;pCBA . (4)
water with an ozone dose of 20.8 mM. t
The Rct values in Fig. 1 correspond well to those found by To generalize the kinetics of a UV system, it is necessary to
Elovitz and von Gunten (2000), where Rct values were reported convert time based rate constants into UV fluence based rate
for decarbonated Lake Zurich water (pH 6.5 at 15 1C) of constants (Bolton and Stefan, 2002). In this case, dividing both
1.1  108, and for Lake Zurich water (pH 7.8) of 1.5  108. sides of Eq. (4) by the volume-based UV average fluence rate,
They also agree with scavenging rates as described by the E0 a (mW L1), converts the rate constants and results in Eq. (5).
percent of dOH radicals available for pCBA oxidation (Table 2). R
D D kOH;pCBA OH dt
First, as scavenging increases, it is expected that the fraction k0 obs  k0 d . (5)
E0a t
of dOH radicals available for oxidation of pCBA will decrease.
The Rct values in Fig. 1 agree with trends regarding the Because UV fluence (H0 ) is simply the product of average
available dOH radical after scavenging by the background fluence rate and time, upon rearrangement of Eq. (5), ROH,UV
matrix. Secondly, ozone decomposition to dOH radical is (mol mW1) can be determined (Eq. (6)).
enhanced at high pH values (Hoigne, 1982). This enhanced R D D
OH dt k0 obs  k0 d
decomposition dominated the process at pH 8, resulting in ROH;UV . (6)
H0 kOH;pCBA
greater Rct values than at pH 6.5, despite the fact that the dOH
radical scavenging is elevated at pH 8, resulting in lower ROH,UV values for each water treated with the LP UV and MP
% OHpCBA values in Table 2. The ozone/H2O2 process displays UV+0.29 mM H2O2 AOPs are presented in Fig. 2.
the highest Rct. This is due to the enhanced initiation of the These ROH,UV values can be compared to examine the effect
ozone transformation to dOH radical by HO 2. of water quality on the dOH radical exposure by the UV/H2O2
system. In the UV/H2O2 system, three factors affect dOH
radical availability: formation rate and scavenging rate of dOH
3.2.2. The UV/H2O2 process
radical and UV absorbance of the water. By definition, ROH,UV
Bench scale testing was also performed to determine the
already contains a correction accounting for water absor-
ROH,UV for each water at 0.29 mM initial hydrogen peroxide.
bance, which leaves the formation and scavenging rates of
This new steady state parameter is analogous to Rct used for d
OH radical as the only determining factors of ROH,UV. At
ozonation, and was developed as follows. Eq. (2) is the
constant H2O2 concentration, formation rates of dOH radical
governing equation describing transformation of pCBA by
based on average fluence rate should have constant values for
the UV/H2O2 process.
LP or MP irradiation conditions and ROH,UV values should be
dpCBA    influenced only by dOH radical scavenging kinetics. For Lake
 k0d kOH;pCBA OH pCBA . (2)
dt Greifensee and Lake Zurich waters, %OHpCBA values from
Eq. (3) is the result of the integration of Eq. (2). Dividing both Table 2 correspond well with the experimental results of Fig.
sides by time results in Eq. (4), incorporating the overall 2. However, the ROH,UV values of Lake Zurich+alkalinity water
observed, direct photolysis, and dOH radical rate constants presents a more complicated picture. Even though the

5 3.9
Ozone / H O AOP
2 2
4

pH 6.5
Rct (10-8)

3 pH 8
2.0

2 1.4
1.2
1.2

1 0.69
0.64

0
Lake Greifensee Lake Zurich Lake Zurich + alkalinity

Fig. 1 Rct values for Lake Greifensee, Lake Zurich, and Lake Zurich+alkalinity waters during ozonation for all conditions
tested (95% confidence intervals). The ozone dose is 62.5 lM (Lake Greifensee water), or 20.8 lM (Lake Zurich waters), initial
pCBA is 0.5 lM.
ARTICLE IN PRESS
3700 WAT E R R E S E A R C H 40 (2006) 3695 3704

5.0
LP UV, pH 6.5

ROH,UV (10-13 M s L mJ-1)


4.0 LP UV, pH 8
MP UV, pH 6.5

3.0 MP UV, pH 8

2.0

1.0

0.0
Lake Greifensee Lake Zurich Lake Zurich + alkalinity

Fig. 2 ROH,UV values for Lake Greifensee, Lake Zurich, and Lake Zurich+alkalinity waters for LPUV+0.29 mM H2O2, with 95%
confidence intervals.

0.5
Lake Greifensee Medium Pressure UV
Absorbance (cm-1) and Relative

Low Pressure UV Lamp Lamp Emission


Emission
0.4

0.3 Lake Zurich


Emission

+ alkalinity

0.2
Lake Zurich

0.1
0.29mMH2O2

0
200 220 240 260 280 300 320 340 360 380 400
Wavelength (nm)

Fig. 3 Background water absorbance of Lake Greifensee, Lake Zurich and Lake Zurich+alkalinity water, absorbance of
0.29 mM H2O2, and relative emission spectra (normalized to the maximum emission) for typical LP and MP UV lamps.

%OHpCBA is less than in the Lake Greifensee or Lake Zurich treated water and under the same irradiation conditions, the
water, the ROH,UV values are comparable or higher under all production rate of dOH radical for Lake Greifensee water will
tested conditions in the Lake Zurich+alkalinity water. This be reduced by a factor of E2 with respect to the same rate in
observation is magnified at lower pH, indicating that a Lake Zurich water. This means that, in terms of energy
plausible explanation of this behavior may be attributed to consumption for the production of UV light, the differences
possible presence of a transition metal impurity in the added between the waters given in Fig. 2 will be amplified by a
NaHCO3 salts, which might lead to an enhanced production of maximum factor of E2 depending on reactor geometry. The
d
OH radical (for instance through a photo-fenton type reduced effectiveness of the MP system, compared to the LP
mechanism). system, is mainly due to a smaller spectral overlap of emitted
Nevertheless, the UV absorbance of the water must be UV radiation with the absorption spectrum of hydrogen
taken into account for energy calculations presented further peroxide.
on in this paper. Absorbance varies depending on the average
path length of UV light, which is defined by the photochemi-
3.3. d
OH radical exposure for ozone doses and applied UV
cal reactor geometry. Background water absorption becomes
fluences
increasingly important at longer path lengths and its max-
imum effect is reached for total absorption of UV light by the
To provide a context for comparing the technologies, the dOH
treated water. Fig. 3 displays the relevant absorption and
radical exposure (similar to a Ct concept) for each system was
emission spectra involved and shows that UV absorbance is
determined, with the second set of ozone experiments, which
dominated by the background water absorption (mainly
measured the pCBA degradation after complete ozone con-
organic matter over the whole spectral range and nitrate
sumption. This pCBA degradation was directly related to the
below E230 nm). R 
d
OH radical exposure OH dt , using Eq. (7).
Hydrogen peroxide at the concentration levels in our study  
Z
(0.29 mM) absorbs only a small fraction of the available UV ln pCBAo =pCBA
OHdt . (7)
light. In the limiting case of total UV light absorption by the kOH;pCBA
ARTICLE IN PRESS
WAT E R R E S E A R C H 4 0 (200 6) 369 5 370 4 3701

R
Fig. 4 displays OHdt as a function of initial ozone of the water absorbance, and an assumed pathlength) and the
concentration, for ozone doses of 2.08, 4.17, 10.4, 20.8, and reflection factor, according to Eq. (8).
104 mM O3 (0.1, 0.2, 0.5, 1, 2, 5 mg L1), in Lake Greifensee and
Lake Zurich waters at pH 6.5 and pH 8. Also displayed in Fig. 4 E0a lt
R E0lamp lt . (8)
is OHdt when hydrogen peroxide is added to the ozone RF  WF
process in Lake Zurich water at pH 8. Although the Rct is
Eq. (9) converts the quartz sleeve fluence to the energy
increased with the addition of hydrogen peroxide (shown for
required by the UV lamp.
Lake Zurich+alkalinity water in Fig. 2), Fig. 4 clearly displays
that there is no significant improvement in overall dOH 3P
00
1h 1 kW
radical exposure with the addition of hydrogen peroxide, E0lamp lt 3600 s 1106 mW
consistent with the findings presented in von Gunten (2003a). Ulamp 200 . (9)
ZUV
However, the faster rates of dOH formation will result in
smaller system size compared to ozone alone. Another energy consideration in the UV system is the
R
OHdt was also plotted as a function of UV fluence for hydrogen peroxide energy EH2 O2 . The local EH2 O2 was
varying initial hydrogen peroxide concentrations, corre- calculated for four regions, California, USA average, Germany,
sponding to approximately 0.08, 0.29, and 1.45 mM (2, 10, and France. Table 3 displays the local costs of hydrogen
and 50 mg L1) initial H2O2 (Fig. 5). It is important to note that peroxide (H$), electricity cost (E$), the calculated ratio of these
the UV fluence to achieve similar dOH radical exposures is values for each region and the average of this ratio. The
approximately double in the MP UV systems as compared to energy requirements of the two processes are compared for
the LP UV systems. This can be attributed, as discussed Lake Greifensee and Lake Zurich waters in Fig. 6, which
earlier, to a better overlap between lamp emission spectrum displays the ratio of the energy required for the UV processes
and absorption spectrum of hydrogen peroxide for the LP to that of the ozone processes.
systems than for the MP systems. As the dOH radical exposure increases, the energy ratio of
UV to ozone processes decreases dramatically. To increase
d
OH radical exposure with an ozone process involves
3.4. Energy comparison of ozone and UV processes increasing the ozone dose, and therefore the ozone energy.
However, for the UV AOPs, a higher dOH radical exposure
The theoretical electrical energy needed for ozone and UV/ occurs with the addition of UV fluence, which is negligible in
H2O2 processes to yield a certain dOH exposure was calculated the peroxide energy dominated process. This results in a UV
and compared to evaluate the energy requirements for AOP energy that is essentially constant with increasing dOH
formation of dOH radicals. The energy required for an ozone radical exposure. In certain cases, the energy ratio can be very
exposure in a model reactor EO3 can be calculated by close to or less than one (zero on the log scale shown in Fig. 6),
multiplying the ozone close by the energy efficiency of ozone implying the UV process is near to or less energy intensive
generation (1826 kWh kg1 USEPA, 1999). than the ozone process. This situation occurs only at 0.1 and
To calculate the theoretical energy required for the UV 0.3 mM initial peroxide concentrations and high dOH radical
processes, the kWh for the fluence required to yield a certain exposure. Interestingly, the UV portion of the UV/H2O2 AOP
R
d
OH radical exposure OHdt, as well as the energy of the energy cost is a small fraction of the total UV/H2O2 cost. For
hydrogen peroxide production must be considered. Once the instance, for an dOH radical exposure of 1  1012 M min in
UV fluence level has been established, the mJ L1 emitted Lake Greifensee water at pH 6.5, the LP UV energy is only 10%
from the lamp at the surface of the quartz sleeve in a model of the total UV/H2O2 AOP (at 2 mg L1 H2O2) energy. For MP UV
reactor can be calculated using the water factor (with inputs these numbers are similar. As the concentration of H2O2 is

Ozone dose (mg L-1)


0.0 1.0 2.0 3.0 4.0 5.0 6.0
14
OH radical exposure (1011 M min)

Lake Zurich, pH 6.5


12 Lake Zurich, pH 8
Lake Zurich, ozone + H2O2, pH 8
10 Lake Greifensee, pH 6.5
Lake Greifensee, pH 8
8
6
4
2
0
0 20 40 60 80 100 120
Ozone dose (M)

Fig. 4 OH radical exposure as a function of the ozone dose in Lake Greifensee and Lake Zurich waters, pH 6.5 and pH 8.
ARTICLE IN PRESS
3702 WAT E R R E S E A R C H 40 (2006) 3695 3704

70

OH Radical Exposure (1013 M min)


60

50
1.43mM H2O2
40

30
0. 29 mM H2O2
20

10 0.06 mM H2O2

0
0 100 200 300 400 500
(a) UV Fluence (mJ L-1)

70
OH Radical Exposure (1013 M min)

60

50
1.52mM H2O2
40

30
0.30mM H2O2
20

10
0.10mM H2O2
0
0 200 400 600 800 1000

(b) UV Fluence (mJ L-1)

Fig. 5 OH radical exposure as a function of UV fluence for (a) LP UV+0.06, 0.29, and 1.43 mM H2O2, and (b) MP UV+0.10, 0.30,
and 1.52 mM H2O2 in Lake Greifensee water. Note the MP UV fluence scale is double the LP UV fluence scale, but the y-axes are
scaled the same. Solid symbols are pH 6.5 data, and open symbols represent pH 8.

Table 3 Local energy cost of hydrogen peroxide in four locations

50% H2O2 30% H2O2 50% H2O2 Germanyd 100% H2O2 Average
California, California, USA Francee
USA USA

H2O2 cost (H$) ($ kg1 H2O2) 0.60a 0.90a 0.68b n/a 1 Euro
Local electricity cost (E$) ($ 0.065a 0.065a 0.074c n/a 0.085 Euro
kWh1)
Energy cost of H2O2 (H$/E$) 9.23 13.85 9.19 10.00 11.76 10.81
(kWh kg1 H2O2)

a
-Patel (2004).b-Tramposch (2004).c-Moody (2003).d-Muller (2001).e-Atofina (2004).

increased, the fraction of total energy of the UV/H2O2 process hydrogen peroxide to the ozone process increases the energy
due to UV energy is less than 1%. requirement by 35%, compared to O3 only. Consequently, the
The addition of hydrogen peroxide to the ozone process energy ratios for the UV processes to the equimolar O3/H2O2
does not improve the overall dOH radical exposure of the in Lake Zurich water process are parallel to the lines in
ozone process, as shown in Fig. 4. and with the addition of Fig. 6(b), but shifted down by 35%.
hydrogen peroxide energy to the process, one would expect
the process to be more energy intensive than the simple 3.4.1. Disregarded costs
ozone process for production of dOH radical. This is indeed This study focused on quantifying the energy costs associated
the case, as the addition of equimolar concentrations of with different advanced oxidation technologies for the
ARTICLE IN PRESS
WAT E R R E S E A R C H 4 0 (200 6) 369 5 370 4 3703

3.0

2.5

2.0

log [E(UV)/E(O3)]
1.5

1.0

0.5

0.0

-0.5

-1.0
-14.5 -13.5 -12.5 -11.5 -10.5 -13.0 -12.5 -12.0 -11.5 -11.0 -10.5

(a) log(OHCt(M min)) (b) log(OHCt(M min))

Fig. 6 Energy Ratio of UV to ozone processes as a function of OH radical exposure in (a) Lake Greifensee and (b) Lake Zurich
water at pH 6.5. Solid lines and symbols indicate MP UV data, and dashed indicate LP UV data. The square symbols represent
0.06 mM H2O2 data, triangles are for 0.30 mM data, and circles are for 1.48 mM H2O2 data.

formation of dOH radicals, by using bench scale data to energy intensive than the ozone processes. However, in most
predict steady state trends. However, many other issues must situations, the ozone process will require less energy to
be considered when comparing the design of ozone and UV/ produce dOH radicals.
H2O2 systems. Neglected cost considerations in this study Although energy costs are a key component in comparing
included: costs associated with storage, handling, and UV and ozone systems, it is just one of many considerations.
pumping of added chemicals (ozone and H2O2), reactor Ultimate technology analysis must also weigh issues related
footprint considerations, destruction or removal of excess to chemical storage, handling, and pumping, reactor footprint
ozone and H2O2 remaining after the treatment process, and size, destruction or removal of excess chemicals, and
potential formation of undesired byproducts, such as bromate potential for formation of undesirable byproducts.
(von Gunten, 2003b). While the complete costs and benefits of
each technology are of importance in engineering advanced
oxidation technology for a specific water treatment situation, Acknowledgements
the data presented in this study provides a fundamental
understanding of dOH radical generation efficiency for ozone This work was funded in part by EPA Grant #R-829412-01,
and UV AOPs, to augment some of the practical cost Michael Elovitz project manager. Support from Eawag for both
considerations. Karl Linden and Erik Rosenfeldt while in Switzerland is
gratefully acknowledged. The authors would like to acknowl-
edge Elisabeth Salhi, Marc Huber, Marc-Olivier Buffle, Michael
4. Conclusions Dodd, Laurence Meunier, and Gretchen Onstad at Eawag for
their gracious assistance and patient teaching of some of the
Utilizing a method to directly compare the oxidative ability of bench scale techniques utilized in this study.
ozone and UV/H2O2 processes, the energy required for each
technology to form dOH radicals was determined for distinct R E F E R E N C E S
water qualities. Under most of the tested conditions, ozone is
a more energy efficient technology for production of dOH
radical in the waters tested. For UV/H2O2 AOPs, hydrogen Acero, J., von Gunten, U., 2001. Characterization of oxidation
peroxide was the most energy intensive portion of the processes: ozonation and the AOP O3/H2O2. J. Am. Water
processes. The MP UV systems were consistently less efficient Works Assoc. 93 (10), 90100.
for dOH radical production than were the LP UV systems, due Acero, J., Benitez, F., Real, F., Maya, C., 2003. Oxidation of
acetamide herbicides in natural waters by ozone and by the
to the relative inefficiency associated with UV output of MP
combination of ozone/hydrogen peroxide: kinetic study and
lamps and UV light absorption by hydrogen peroxide. Also, process modeling. Ind. Eng. Chem. Res. 42 (23), 57625769.
addition of peroxide to the ozone process resulted in a faster APHA, AWWA, WEF, 2000. Standard Methods for the Examination
formation of dOH radical, but did not significantly increase of Water and Wastewater, 20th Ed. United Book Press, Inc.,
the ultimate dOH radical exposure. The addition of hydrogen Baltimore.
peroxide increased the energy of the process by 35% over the Atofina, 2004. France. Personal Communication.
Beltran, F., Ovejero, G., Acedo, B., 1993. Oxidation of atrazine in
ozone only process, but reduced contact times to achieve an
water by ultraviolet radiation combined with hydrogen per-
d
OH radical exposure.
oxide. Water Res. 27 (6), 10131021.
When a large amount of contaminant oxidation is required, Bolton, J., Bircher, K., 1996. Figures-of-merit for the technical
our results indicate that at low peroxide levels, and high dOH development and application of advanced oxidation pro-
radical exposure, the UV process can be comparable or less cesses. J. Adv. Oxidat. Technol. 1, 1317.
ARTICLE IN PRESS
3704 WAT E R R E S E A R C H 40 (2006) 3695 3704

Bolton, J., Cater, S., 1994. Homogeneous photodegradation of Klassen, N.V., Marchington, D., McGowan, H.C.E., 1994. H2O2
pollutants in contaminated water: an introduction. In: Aquatic determination by the I 3 method and by KMnO4 titration.
and Surface Photochemistry. CRC Press, Inc., Boca Raton, Fl. Analyt. Chem. 66 (18), 29212925.
Bolton, J., Stefan, M., 2002. Fundamental photochemical approach Larson, R., Zepp, R., 1988. Reactivity of the carbonate radical with
to the concepts of fluence (UV dose) and electrical energy aniline derivatives. Environ. Toxicol. Chem. 7 (4), 265274.
efficiency in photochemical degradation reactions. Res. Chem. Legrini, O., Oliveros, E., Braun, A., 1993. Photochemical processes
Interm. 28 (7-9), 857870. for water treatment. Chem. Rev., 671698.
Buxton, G., Greenstock, C., Helman, W., Ross, A., 1988. Critical Linden, K., Darby, J., 1997. Estimating effective germicidal dose
review of rate constants for reactions of hydrated electrons, from medium pressure UV lamps. ASCE J. Environ. Eng. 123
hydrogen atoms and hydroxyl radicals (dOH/O) in aqueous (11), 11421149.
solution. J. Phys. Chem. Ref. Data 17 (2), 513886. Moody, D., 2003. Electricity Price Trends. American Public Power
Chen, J.W., Peijnenburg, W., Quan, X., Zhao, Y.Z., Xue, D.M., Yang, Association September.
F.L., 1998. The application of quantum chemical and statistical Muller, J., Jekel, M., 2001. Comparison of advanced oxidation
technique in developing quantitative structureproperty re- processes in flow-through pilot plants (Part I). Water Sci.
lationships for the photohydrolysis quantum yields of sub- Technol. 44 (5), 303309.
stituted aromatic halides. Chemosphere 37, 11691186. Muller, J., Gottschalk, C., Jekel, M., 2001. Comparison of advanced
Elovitz, M., von Gunten, U., 1999. Hydroxyl radical/ozone ratios oxidation processes in flow-through pilot plants (Part II).
during the ozonation processes. I. The Rct Concept. Ozone Sci. Water Sci. Technol. 44 (5), 311315.
Eng. 21, 239260. Patel, M., 2004. Orange County Water District. Personal Commu-
Elovitz, M., von Gunten, U., 2000. Hydroxyl radical/ozone ratios nication
during ozonation processes. II. The effect of temperature, pH, Pines, D., Reckhow, D., 2003. Solid phase catalytic ozonation
alkalinity, and DOM properties. Ozone Sci. Eng. 22, 123150. process for the destruction of a model pollutant. Ozone Sci.
Griffini, O., Iozzelli, P., 1996. The influence of H2O2 in ozonation Eng. 25 (1), 2539.
treatment: experience of the water supply service of Florence, Rosenfeldt, E.J., Linden, K.G., 2005. The ROH,UV Concept to
Italy. Ozone Sci. Eng. 18, 117. Characterize and Model UV/H2O2 Processes in Natural
Haag, W., Yao, C., 1992. Rate constants for reaction of hydroxyl Waters. IUVA 2005: Third International Congress on Ultraviolet
radicals with several drinking water contaminants. Environ. Technologies, Whistler, British Columbia, May 2427, 2005.
Sci. Technol. 26, 10051013. Sharpless, C.M., Seibold, D.A., Linden, K.G., 2003. Nitrate photo-
Han, S., Nam, S., Kang, J., 2002. dOH radical monitoring sensitized degradation of atrazine during UV water treatment.
technologies for AOP advanced oxidation process. Water Sci. Aquat. Sci. 65, 359366.
Technol. 46 (11-12), 712. Schwarzenbach, R., Gschwend, P., Imboden, D., 2003. Photoche-
Hoigne, J., 1982. Mechanisms, rates, and selectivities of oxidations mical transformation reactions. In: Environ. Organ. Chem.
of organic compounds initiated by ozonation of water. In: Wiley, New York.
Handbook of Ozone Technology and Applications. Ann Arbor Singer, P., Reckhow, D., 1999. Chemical oxidation. In: Water
Science, Ann Arbor. Quality and Treatment: A Handbook of Community Water
Hoigne, J., Bader, H., 1981. Determination of ozone in water by the Supplies. McGraw-Hill, Inc., New York.
indigo method. Water Res. 15, 449456. Tramposch, W., 2004. Calgon carbon. Personal communication.
Hoigne, J., Bader, H., 1983a. Rate constants of reactions of ozone USEPA, 1999. EPA Guidance Manual Alternative Disinfectants and
with organic and inorganic compounds in waterI: not Oxidants, Table 33, pp. 310.
dissociating organic compounds. Water Res. 17, 173183. USEPA, 2003. EPA Draft UV Disinfection Guidance Manual
Hoigne, J., Bader, H., 1983b. Rate constants of reactions of ozone Proposal Draft, Table 2.1, pp. 215.
with organic and inorganic compounds in waterII: disso- von Gunten, U., 2003a. Ozonation of drinking water: part I.
ciating organic compounds. Water Res. 17, 185194. oxidation kinetics and product formation. Water Res. 37,
Hoigne, J., Bader, H., Haag, W., Staehelin, J., 1985. Rate constants of 14431467.
reactions of ozone with organic and inorganic compounds in von Gunten, U., 2003b. Ozonation of drinking water: part II.
waterIII: inorganic compounds and radicals. Water Res. 19, Disinfection and By-product formation in presence of bro-
9031004. mide, iodide and chlorine. Water Res. 37, 14691487.

Вам также может понравиться