Академический Документы
Профессиональный Документы
Культура Документы
GROUNDING
AND
GROUND GRID
DESIGN
1
SUB-TOPIC
GROUNDING?
EARTHING?
BONDING?
3
BONDING
Bonding is intentional electrical interconnecting of conductive
path in order to ensure common electrical potential between
the bounded parts.
Bonding is simply the act of joining two electrical
conductors together.
These may be two wires, a wire and a pipe, or these may be
two equipments.
Bonding has to be done by connecting of all the metal parts
that are not supposed to be carrying current during normal
operations to bringing them to the same electrical potential
4
BONDING
Example of bonding
5
EARTHING
Earthing means connecting the dead part (it means
the part which does not carries current under normal
condition) to the earth for example electrical equipments
frames, enclosures, supports etc.
The purpose of earthing is to minimize the risk of
receiving an electric shock if touching metal parts
when a fault is present.
Generally green wire is used for this as a nomenclature.
6
GROUNDING
Grounding means connecting the live part (it means
the part which carries current under normal condition) to
the earth for example neutral of power transformer.
It is done for the protections of power system equipment
and to provide an effective return path from the machine
to the power source.
Because of lightning, line surges or unintentional contact
with other high voltage lines, dangerously high voltages
can develop in the electrical distribution system wires.
Grounding provides a safe, alternate path around the
electrical system of your house thus minimizing damage
from such occurrences.
7
Grounding vs Earthing
8
Micro Difference between Earthing and
Grounding
1. Difference in Terminology
In USA term Grounding is used but in UK term Earthing is
used.
2. Balancing the Load VS Safety
Ground is a source for unwanted currents and also as a
return path for main current some times. While earthing is
done not for return path but only for protection of delicate
equipments. It is an alternate low resistance path for current.
When we take out the neutral for a three phase unbalanced
connection and send it to ground, it is called grounding.
Grounding is done to balance unbalanced load. While
earthing is used between the equipment and earth pit so as to
avoid electrical shock and equipment damage.
9
Micro Difference between Earthing and
Grounding
3. Equipment Protection Vs Human Safety
Earthing is to protect the circuit elements whenever high
voltage is passed by thunders or by any other sources while
Grounding is the common point in the circuit to maintain the
voltage levels.
4. System Zero Potential Vs Circuit Zero Potential
Earthing and Grounding both is refer to zero potential, but
the system connected to zero potential is differ than
equipment connected to zero potential .If a neutral point of a
generator or transformer is connected to zero potential then it
is known as grounding.
At the same time if the body of the transformer or generator is
connected to zero potential then it is known as earthing.
10
Grounding Terms
11
The reasons for grounding :
Personal safety by limiting potentials between
all non-current-carrying metal parts of electrical power system.
Personal safety and control of electrostatic discharge (ESD)
by limiting potentials between all non current-carrying metal
parts of an electrical power system and the ground.
12
System Grounding:
Ungrounded System
Grounded System
- Solid grounding
- Resistance grounding
- Reactance grounding
- Ground fault neutralizer
- Distribution Transformer, etc
There is no one best system grounding method. In
choosing among the various options, the designer
must consider the requirements for safety, continuity
of service, and cost. 13
Figure 1: Equipment Grounding and System
Grounding
14
Ungrounded means that there is no intentional
Between a current-carrying conductor and ground
15
Criteria of System Grounding
Low Resistance : Ro 2 Xo and IFG = (10% - 25%) I3
16
Figure 2: Solid Grounded Wye System
17
Figure 3: Ungrounded Delta System
18
The basic reasons for system neutral grounding
To limit over voltage
To limit electric potential difference
To isolate faulty equipment and circuits
To provide low-impedance return path from the
Load back to the source and improve fault protection.
To hold system neutral point equal ground point
19
Table Comparison of system Grounding Methods
No. Characteristic assuming No System Grounding Method
Fault
Escalation Solidly Ungrounded High
Ground resistance
ed
1. Operation of over-current Yes No No
device on First ground fault
2. Control of internally generated Yes No Yes
transient Over-voltage
3. Control of steady state over- Yes No Yes
voltage
4. Flash Hazard No Yes No
5. Equipment damage from arcing No Yes No
ground fault (can be controlled)
6. Over-voltage (on un-faulted L-N >> L-L L-L
phases) from Ground Voltage Voltage Voltage
7. Can serve line to neutral load Yes No No
20
Ground Rod and Grounding Electrode ?
Ground rod is an electrode rod buried in the earth for
purpose of grounding systems.
Grounding conductor is conductor that connect the grounding
system to earth for purpose to keep the entire grounding
system at the earth potential.
Grounding electrode is a conductor can be as wires/rod, strips,
plates in intimate contact with the earth for the purpose
of providing a connection with the grounding
and bonding.
21
Grounding conductor
Grounding electrode
Ground rod
22
23
Ground rod made of :
Ion or steel rods must be at least 5/8 in (15 mm) diameter;
Copper-clad stainless-steel, or stainless steel-clad rod
must be at least -in (12 mm).
Rods should be driven to at least 8 ft (2.45m).
If a driven rod hits a rock bottom, the depth may < 8 feet.
25
The main factors that influence the resistance are
the number of rods (paralel) , resistivity of the soil
and the length.
8l
R= ln 1 Ohm
2l d
26
Soil Resistivity
Soil resistivity is one of the most important factors,
in designing, grounding system of a substation.
The characteristic of the soil resistivity are primarily
affected by:
Soil type (size, variability and density),
Moisture
Temperature
Salt content
Compactness
27
Typical Values of Resistivity of Some Soils
Resistivity (Ohm-m)
Type of soils
Loam, garden 5 50
soil
Clay 8 50
Sand and gravel 60 100
Sandstone 10 500
Rocks 200 10,000
28
Figure 4: Effect of salt, moisture, and temperature on Soil
resistivity
29
Permissible Ground Resistance
IEEE recommend a ground resistance
value of 5 ohms or less for domestic user
30
Soil Resistivity Measurement
31
Wenner Method
=2 -m
36
Ground Resistance Measurement
Consists of measuring the resistance of a body of earth
surrounding a grounding electrode.
Normally the fall of potential method (sometime called as the
three-point technique) is the practical and reliable method for
measuring the ground resistance.
37
Figure 8: The fall of potential method arrangement
Fall of Potential Method
In this method, a current I is injected into the earth using
current probe.
The potential probe which is inserted at intervals within
the current path will measure the voltage drop produce
by the current.
The form of fall of potential method is obtained when the
ground electrode, potential probe and current probe are
on a straight line and potential probe is located between
ground electrode and current probe.
When Vx/I is plotted as a function of the potential probe
distance, the curve as shown in Figure 9 are produced.
It is usually accepted that the flat section of the curve
give the correct magnitude of the resistance measured.
38
Fall of Potential Method
8l
R= ln 1
2l d
41
Grid Substation Grounding
A common method for obtaining a low ground
resistance at high voltage substation is to use
interconnected ground grid.
The substation grounding provides the ground
connection for the neutral system, the discharge
path for surge arresters and ensure safety to
operating personal.
It also provides a low resistance path to ground
to minimize the rise in ground potential.
Many utilities add ground rods for further
reduction of the resistance. 42
Grid Substation Grounding
43
The arrangement of the grounding grid with 72 meshes.
44
There are two conditions that person within or
round the substation may be experience
Touch voltage
Step voltage
46
47
Z(system)
If
V
Ig
Ib
Rb
Vth
Rbody
Touch voltage Circuit Equivalent Zth
Terminal F 48
Vth : Touch voltage
Z(system)
If
V
Ig
Terminal F2
49
Permissible Body Current Limit
Dalziel concludes of all men could withstand,
without ventricular fibrillation,
k
Ib = A
ts
50
Table limitations of the electric currents flow through the body
51
Permissible Step and Touch Voltages (Volt)
0.116
Vtouch(50) = (1000 + 1.5C s s )
ts
0.157
Vtouch( 70) = (1000 + 1.5C s s )
ts
53
Steps of grid calculation analysis:
Investigation of soil characteristics
Determination of maximum ground fault current
Preliminary design of the ground system
Calculation of resistance of the ground system
Calculation of step voltage at periphery
Calculation of internal step and touch voltages
Refinement of preliminary design.
54
The maximum grid current IG.
IG = SfIf
where
IG : Symmetrical ground fault current (3I0), A
If : Rms value of symmetrical fault current, A
Sf : Ratio of grid current to fault current.
55
A single line to ground fault,
V
I0 =
X1 + X 2 + X 0
X2
I0 = V
X1(X 0 + X 2 ) + X 2 X 0
56
Selection of Conductor
Conductors are used for grounding system, grid conductors,
connections, connecting lead, and all primary electrodes must
be adequate criteria as below;
i). Have sufficient conductivity
ii). Resist fusing and mechanical deterioration under short
circuit.
iii).Be mechanically reliable and rugged to a high degree.
iv).Be able to maintain its function even exposed to corrosion
or physical abuse
57
Conductor materials may be used:
Cooper is used for grounding.
Copperclad steel is used for underground rods and
occasionally for grid conductors, especially where
theft is a problem.
Aluminum is used for ground grids less frequently.
Steel can be used for ground grid conductor and rods.
58
The calculation tolerable Step, and mesh
voltage based up on IEEE standard 80-1986.
Vstep = K S Ki (IG / L)
1 1 1 1 1
Ks = ( + + + )
2h D + h 2 D 3D
Ki = 0.172 N + 0.656
N = number of grid conductors
59
L = Lc + 1.15 LT (with ground grid and rods)
60
The mesh voltage tends to be highest in
the mesh rectangle nearest to the perimeter.
K m I G Ki
Vmesh =
L
1 D 2 1 3 5 7
K m = ln + ln
2 16hd 4 6 8
61
The ground resistance of grounding grid,
R=
4
R : substation ground resistance,
: soil resistivity, m
A : area of the grounding grid m2
62
According to Laurent and Nieman
or
63
The calculation tolerable Step, and mesh voltage
based up on IEEE standard 80-2000.
Mesh Voltage
64
For grids with no ground rods or grids with only a few ground rods, none located in
the corners or on the perimeter.
65
Step Voltage
66
67
The required data for the program for analysis/design
The soil resistivity at the substation location
Fault duration Current division factor
System impedance
Line to line voltage at worst-fault location
Crushed rock resistivity
Thickness of crushed rock surface
Depth of grid
Span distance of conductor
Available ground area
Conductor type in use
Fault Clearing 68
Improving The Performance of The Grounding Grids
Increasing the grounding area; the most effective way to
decrease ground resistance is by increasing the area
occupied by the grid.
Improvement of gradient control; If mesh voltage is higher
than the allowed touch voltage, a modified grid can be
designed by subdividing the meshes.
Addition of a relatively high resistance surface layer.
A layer of crushed rock can be added on the surface of
the substation to increase the resist.in series with the body.
The available fault current magnitude may be reduced by
connecting overhead ground wires of transmission lines.
Limiting of short-circuit current to the ground grid.
69
1400
800
600
400
200
0
0 300 600 900 1200
Tahanan Jenis Tanah (ohm -m )
71
Example 1.
A grid substations have parameter are
given as below
Number of parallel conductor, n = 16
Soil resistivity, = 750 ohm-m
S = 3,000 ohm-m
Fault current, IG = 1,200 A and clearing time, t = 0.75 sec.
Total length of conductor, L = 1,600 m
Conductor spacing in parallel, D = 4 m
Conductor diameter, d = 0.016 m
Depth of grid conductor, h = 0.8 m
For the above condition, the values of factors such as
Km = 0.3695, Ki = 3.042 , and Ks = 0.4014.
Body resistance is 1,000 ohm
(i) Calculate mesh voltage and step voltage
(ii) Calculate allowable step voltage and touch voltage 72