FLOWMETERS MEASUREMENT
9.2 INTRODUCTION
Experimental Stand for Flow Meter is a water process. Water from a sump tank T-501 is pumped
by P-501 through a manifold containing three different types of flow meter which are Orifice Flow
Meter Transmitter FT-503, Magnetic Flowmeter FT-502 and Coriolis Flowmeter FT-501.
Hand valves are used to select the flowmeter for measuring the water flow during the experiment,
which is collected in a calibration tank T-505. The volumetric flowrate over time is checked
against the volumetric scale on the calibration tank to compare the accuracy of each type of
flowmeter.
145
Table 9.1 Instrument function and capabilities
No Instrument Tag No Description Range
1 PID controller FIC-500 Microprocessor based PID -
controller, flow control
2 Flowmeter FT-501 Coriolis flowmeter
FT-502 Magnetic flowmeter
FT-503 Integral orifice with d/p
transmitter
3 Recorder FR-500 Continuous 2 pen chart recorder -
4 Pump P-501 Water circulation tank
5 Control valve FCV-500 1 inch globe type valve with 0-100%
Cv=4.8 linear characterisitic
with I/P positioner and I/P
converter
6 Temperature TI-501 Dial gauge temperature 0-1000C
indicator for local
Indicator
temperature indication
7 Process Tank T-501 Sump tank 120 L
T-505 Calibration tank 80 L
9.4 PROCEDURE
The tank T-505 has been calibrated using volume of 75 litres of water .
146
STEP ACTION REMARKS
147
Check and make sure hand valves position as follows.
Close HV511, HV515, HV516, HV520, HV521, HV522,
HV523, HV525, HV526
1 Open HV512, HV517, HV518, HV519
9.5 REFERENCES
Seborg D.E., T.F. Edgar and D.A. Melliechamp, Process Dynamics and Control, John Wiley and
Sons, New York, 1989, pp 116-118.