Вы находитесь на странице: 1из 43

Chapter 4

LIVE LOADS

4.1 DEFINITIONS Section 4.2 or the concentrated load, in pounds or kilonewtons


I BALCONY (EXTERIOR): An exterior floor projecting from (kN), given in Table 4-1, whichever produces the greater load
effects. Unless otherwise specified, the indicated concentration
and supported by a structure without additional shall be assumed to be uniformly distributed over an area 2.5 ft
independent sup-ports. (762 mm) square [6.25 ft2 (0.58 m2)] and shall be located so as
I DECK: An exterior floor supported on at least two opposing to produce the maximum load effects in the structural members.
sides by an adjacent structure and/or posts, piers, or other inde-
pendent supports. 4.4 LOADS ON HANDRAILS, GUARDRAIL
FIXED LADDER: A ladder that is permanently attached to a SYSTEMS, GRAB BAR SYSTEMS, VEHICLE
structure, building, or equipment. BARRIER SYSTEMS, AND FIXED LADDERS
GRAB BAR SYSTEM: A bar provided to support body 4.4.1 Loads on Handrails and Guardrail Systems. All
weight in locations such as toilets, showers, and tub enclosures. handrail assemblies and guardrail systems shall be designed to
resist a single concentrated load of 200 lb (0.89 kN) applied in
GUARDRAIL SYSTEM: A system of building components any direction at any point along the top and to transfer this load
near open sides of an elevated surface for the purpose of through the supports to the structure.
minimiz-ing the possibility of a fall from the elevated surface by
people, equipment, or material. Further, all handrail assemblies and guardrail systems shall be
designed to resist a load of 50 lb/ft (pound-force per linear foot)
HANDRAIL: A rail grasped by hand for guidance and sup-
(0.73 kN/m) applied in any direction at the top and to transfer
port. A handrail assembly includes the handrail, supporting at-
this load through the supports to the structure. This load need not
tachments, and structures.
be assumed to act concurrently with the load specified in the
LIVE LOAD: A load produced by the use and occupancy of preceding paragraph, and this load need not be considered for the
the building or other structure that does not include construction following occupancies:
or environmental loads, such as wind load, snow load, rain load,
earthquake load, flood load, or dead load. I . One- and two-family dwellings.

ROOF LIVE LOAD: A load on a roof produced (I ) during 2. Factory, industrial, and storage occupancies, in areas that
maintenance by workers, equipment, and materials and (2) during are not accessible to the public and that serve an occupant
the life of the structure by movable objects, such as planters or load not greater than 50.
other similar small decorative appurtenances that are not occu- Intermediate rails (all those except the handrail), balusters, and
pancy related. panel fillers shall be designed to withstand a horizontally applied
VEHICLE BARRIER SYSTEM: A system of building normal load of 50 lb (0.22 kN) on an area not to exceed 1 ft
com-ponents near open sides of a garage floor or ramp, or square (305 mm square) including openings and space between
building walls that act as restraints for vehicles. rails. Reactions due to this loading are not required to be
superimposed with those of either preceding paragraph.

4.2 UNIFORMLY DISTRIBUTED LOADS 4.4.2 Loads on Grab Bar Systems. Grab bar systems shall be
designed to resist a single concentrated load of 250 lb (1.11 kN)
4.2.1 Required Live Loads. The live loads used in the design applied in any direction at any point.
of buildings and other structures shall be the maximum loads
expected by the intended use or occupancy, but shall in no case 4.4.3 Loads on Vehicle Barrier Systems. Vehicle barrier sys-
be less than the minimum uniformly distributed unit loads tems for passenger cars shall be designed to resist a single load of
required by Table 4-1. 6,000 lb (26.70 kN) applied horizontally in any direction to the
barrier system, and shall have anchorages or attachments capable
4.2.2 Provision for Partitions. In office buildings or other build- of transferring this load to the structure. For design of the system,
ings where partitions will be erected or rearranged, provision for the load shall be assumed to act at a minimum height of 1 ft 6 in.
partition weight shall be made, whether or notpartitions are shown on (460 mm) above the floor or ramp surface on an area not to
the plans. Partition load shall not be less than 15 psf. exceed 1 foot square (305 mm square), and is not required to be
EXCEPTION: A partition live load is not required where the minimum assumed to act concurrently with any handrail or guardrail
specified live load exceeds 80 psf (3.83 k ~ l m ~ ) . loadings speci-fied in Section 4.4.1. Garages accommodating
trucks and buses shall be designed in accordance with an
4.3 CONCENTRATED LOADS approved method, which contains provision for traffic railings.

Floors, roofs, and other similar surfaces shall be designed to 4.4.4 Loads on Fixed Ladders. The minimum design live load
support safely the uniformly distributed live loads prescribed in on fixed ladders with rungs shall be a single concentrated load

Minimum Design Loads for Buildings and Other Structures 9


of 300 lb (1.33 kN), and shall be applied at any point to produce where
the maximum load effect on the element being considered. The
L = reduced design live load per ft2 (m2) of area supported by
number and position of additional concentrated live load units
the member
shall be a minimum of 1 unit of 300 lb (1.33 kN) for every 10 ft
(3,048 mm) of ladder height. L, = unreduced design live load per ft2 (m2) of area supported
by the member (see Table 4-1)
Where rails of fixed ladders extend above a floor or platform KLL= live load element factor (see Table 4-2)
at the top of the ladder, each side rail extension shall be designed AT = tributary area in ft2 (m2)
to resist a concentrated live load of 100 lb (0.445 kN) in any
direction at any height up to the top of the side rail extension. L shall not be less than 0.50L,, for members supporting one
Ship ladders with treads instead of rungs shall have minimum floor and L shall not be less than 0.40L,, for members supporting
design loads as stairs, defined in Table 4-1. two or more floors.
4.8.2 Heavy Live Loads. Live loads that exceed 100 lb/ft2
(4.79 kN/m2) shall not be reduced.
4.5 LOADS NOT SPECIFIED
EXCEPTION: Live loads for members supporting two or more floors
For occupancies or uses not designated in Sections 4.2 or 4.3, the may be reduced by 20 percent.
live load shall be determined in accordance with a method 4.8.3 Passenger Car Garages. The live loads shall not be re-
approved by the authority having jurisdiction. duced in passenger car garages.
EXCEPTION: Live loads for members supporting two or more floors
may be reduced by 20 percent.
4.6 PARTIAL LOADING
4.8.4 Special Occupancies. Live loads of 100 lb/ft2 (4.79 kN/
The full intensity of the appropriately reduced live load applied m2) or less shall not be reduced in public assembly occupancies.
only to a portion of a structure or member shall be accounted for
if it produces a more unfavorable effect than the same intensity 4.8.5 Limitations on One-Way Slabs. The tributary area, AT,
applied over the full structure or member. Roof live loads are to for one-way slabs shall not exceed an area defined by the slab
be distributed as specified in Table 4-1. span times a width normal to the span of 1.5 times the slab span.

4.9 REDUCTION IN ROOF LlVE LOADS

I
4.7 IMPACT LOADS
The live loads specified in Sections 4.2.1 and 4.4.2 shall be as- The minimum uniformly distributed roof live loads, L , in Table 4-1,
sumed to include adequate allowance for ordinary impact condi- are permitted to be reduced according to the following provisions.
tions. Provision shall be made in the structural design for uses
and loads that involve unusual vibration and impact forces. 4.9.1 Flat, Pitched, and Curved Roofs. Ordinary flat, pitched,
and curved roofs are permitted to be designed for a reduced roof live
4.7.1 Elevators. All elevator loads shall be increased by 100 load, as specified in Eq. 4-2 or other controlling combina-tions of
percent for impact and the structural supports shall be designed loads, as discussed in Chapter 2, whichever produces the greater
within the limits of deflection prescribed by ANSI A17.2 and load. In structures such as greenhouses, where special scaffolding is
ANSIIASME A17.1. used as a work surface for workmen and materials during
maintenance and repair operations, a lower roof load than specified
4.7.2 Machinery. For the purpose of design, the weight of ma- in Eq. 4-2 shall not be used unless approved by the au-thority having
chinery and moving loads shall be increased as follows to allow jurisdiction. On such structures, the minimum roof live load shall be
for impact: (I ) elevator machinery, 100 percent; (2) light 12 psf (0.58 kNlm2).
machinery, shaft- or motor-driven, 20 percent; (3) reciprocating
machinery or power-driven units, 50 percent; and (4) hangers for
floors or balconies, 33 percent. All percentages shall be increased In SI:
where specified by the manufacturer.
L, = L , R lRz where 0.58 5 L, 5 0.96
where
4.8 REDUCTION IN LlVE LOADS
L, = reduced roof live load per ft2 (m2) of horizontal projection
I
Except for roof uniform live loads, all other minimum uniformly distributed in pounds per ft2 (kNlm2)
live loads, L , in Table 4-1, may be reduced according to the following The reduction factors R 1 and R2 shall be determined as follows:
provisions.

4.8.1 General. Subject to the limitations of Sections 4.8.2 1 for A, 5 200 ft2
through 4.8.5, members for which a value of KLLATis 400 ft2 0.6 for A, 1 600 ft2
(37.16 m2) or more are permitted to be designed for a reduced
live load in accordance with the following formula:
In SI:

1 for A, 5 18.58 m2
In SI:
R1 = 1.2 O.O1lAt
- for 18.58m2 < A, < 55.74m2
0.6 for A, 2 55.74m2

ASCE 7-05
where A, = tributary area in ft2 (m2) supported by any structural 4.10.3 Lateral Force. The lateral force on crane runway beams
member and with electrically powered trolleys shall be calculated as 20
percent of the sum of the rated capacity of the crane and the
1 for F 5 4 weight of the hoist and trolley. The lateral force shall be assumed
to acthorizon-tally at the traction surface of a runway beam, in
either direction perpendicular to the beam, and shall be
distributed with due re-gard to the lateral stiffness of the runway
where, for a pitched roof, F = number of inches of rise per foot beam and supporting structure.
(in SI: F = 0.12 x slope, with slope expressed in percentage 4.10.4 Longitudinal Force. The longitudinal force on crane
points) and, for an arch or dome, F = rise-to-span ratio multiplied run-way beams, except for bridge cranes with hand-geared
by 32. bridges, shall be calculated as 10 percent of the maximum wheel
loads of the crane. The longitudinal force shall be assumed to act

I 4 .9.2 Special Purpose Roofs. Roofs that have an occupancy function,


such as roof gardens, assembly purposes, or other special purposes are
horizon-tally at the traction surface of a runway beam in either
direction parallel to the beam.
permitted to have their uniformly dis-tributed live load reduced in
accordance with the requirements of Section 4.8. 4.1 1 CONSENSUS STANDARDS AND
OTHER REFERENCED DOCUMENTS
4.10 CRANE LOADS This section lists the consensus standards and other documents
The crane live load shall be the rated capacity of the crane. De-sign which are adopted by reference within this chapter:
loads for the runway beams, including connections and sup-port ANSI
brackets, of moving bridge cranes and monorail cranes shall include American National Standards Institute
the maximum wheel loads of the crane and the vertical im-pact, 25 West 43rd Street, 4'" Floor
lateral, and longitudinal forces induced by the moving crane. New York, NY 10036
4.10.1 Maximum Wheel Load. The maximum wheel loads ANSI A17.2
shall be the wheel loads produced by the weight of the bridge, as Section 4.7.1
applicable, plus the sum of the rated capacity and the weight of American National Standard Practice for the
the trolley with the trolley positioned on its runway at the Inspection of Elevators, Escalators, and Moving
location where the resulting load effect is maximum. Walks (Inspectors' Manual), 1988.
4.10.2 Vertical Impact Force. The maximum wheel loads of the ASME
crane shall be increased by the percentages shown in the following American Society of Mechanical
text to determine the induced vertical impact or vibration force: Engineers
Monorail cranes (powered) 25 Three Park Avenue
Cab-operated or remotely operated bridge cranes 25 New York, NY 10016-5900
(powered) ANSIIASME A17.1
Pendant-operated bridge cranes (powered) 10 Section 4.7.1
Bridge cranes or monorail cranes with hand-geared 0 American National Standard Safety Code for
bridge, trolley, and hoist Elevators and Escalators, 1993.

Minimum Design Loads for Buildings and Other Structures


TABLE 4-1 MINIMUM UNIFORMLY DISTRIBUTED LlVE LOADS, Lo, AND MINIMUM CONCENTRATED LlVE LOADS
Occupancy or Use Uniform Conc.
sf ( k ~ i m ~ ) Ib (kN)
I . . . I . .

Apartments (see Residential)

Assembly areas and theaters


Fixed seats (fastened to floor)
Lobbies
Movable seats
Platforms (assembly)
Stage floors
Balconies (exterior)
I On one- and two-familv residences onlv. and not exceeding 100 ft2 19.3 m2) I I
Bowling allevs. ooolrooms. and similar recreational areas 75 13.59) I

I Catwalks for maintenance access I 40 (1.92) 1 300 (1.33) 1

Corridors
First floor
I Other floors. same as occuoancv served exceot as indicated I I
Dance halls and ballrooms 100 (4.79) I

I
Decks (patio and roof)
Same as area served. or for the type of occupancv accommodated I I
-
100 (4.79) I
Dining rooms and restaurants
Dwellings (see Residential)
Elevator machine room grating (on area of 4 in.2 [2,580 mm2]) 300 (1.33)
Finish light floor plate construction 200 (0.89)
(on area of 1 in.2 [645 mm2])
Fire escapes 100 (4.79)
On single-family dwellings only 40 (1.92)
Fixed ladders See Section 4.4
Garages (passenger vehicles only) 40 (1.92)'.~
Trucks and buses
Grandstands (see Stadi~tmsand arenas. Bleachers) I I I

I Gvmnasiums-main floors and balconies I 100 (4.79) I I

I Handrails. guardrails. and grab bars I See Section 4.4 I

Hospitals
Operating rooms, laboratories
Patient rooms
Corridors above first floor
I Hotels (see Residential) I I I

Libraries
Reading rooms
Stack rooms
Corridors above first floor
Manufacturing
Light
Heavv
I Marauees I 75 (3.59) I I

Office Buildings
File and computer rooms shall be designed for heavier loads
based on anticipated occupancy
Lobbies and first-floor corridors
Offices
Corridors above first floor
Penal Institutions
Cell blocks
Corridors
Residential
Dwellings (one- and two-family)
Uninhabitable attics without storage
Uninhabitable attics with storage
Habitable attics and sleeping areas
All other areas except stairs and balconies
Hotels and multifamily houses
Private rooms and corridors serving them
Public rooms and corridors serving them
Reviewing stands, grandstands, and bleachers 100 (4.79)d

12 ASCE 7-05
TABLE 4-1 MINIMUM UNIFORMLY DISTRIBUTED LlVE LOADS, Lo, AND MINIMUM CONCENTRATED LlVE LOADS (continued)
Occupancy or Use Uniform Conc.
psi ( k ~ i m ~ ) Ib (kN)
Roofs
Ordinary flat, pitched, and curved roofs
Roofs used for promenade purposes
Roofs used for roof gardens or assembly purposes
Roofs used for other special purposes
Awnings and canopies
Fabric construction supported by a lightweight rigid skeleton structure
All other construction
Primary roof members, exposed to a work floor
Single panel point of lower chord of roof trusses or any point along primary
structural members supporting roofs over manufacturing, storage warehouses,
and repair garages
All other occupancies
All roof surfaces subiect to maintenance workers
Schools
Classrooms
Corridors above first floor
First-floor corridors
Scuttles, skylight ribs, and accessible ceilings 1 200 (0.89 )
Sidewalks, vehicular driveways, and yards subiect to trucking 250 (1 1.97)"
1 8,000 (35.60)f
Stadiums and arenas
Bleachers
Fixed seats (fastened to floor)
I Stairs and exit ways
One- and two-familv residences onlv
I I I
I

Storage areas above ceilings 20 10.96)


Storage warehouses (shall be designed for heavier loads if required for anticipated storage)
Light
Heavv
Stores
Retail
First floor
Upper floors
Wholesale. all floors
I

I Vehicle barriers
I See Section 4.4
I I I
I

Walkwavs and elevated olatforms lother than exit wavs) 60 12.87)


I Yards and terraces. oedestrian I I
I

100 14.79)
'Floors in garages or portions of a building used for the storage of motor vehicles shall be designed for the uniformly distributed live loads of Table 4-1 or the
following concentrated load: (1) for garages restricted to passenger vehicles accommodating not more than nine passengers, 3,000 lb (13.35 kN) acting on an area
of 4.5 in. by 4.5 in. (1 14 mm by 114 mm) footprint of a jack; and (2) for mechanical parking structures without slab or deck that are used for storing passenger
car only, 2,250 lb (10 kN) per wheel.
'carages accommodating trucks and buses shall be designed in accordance with an approved method, which contains provisions for truck and bus loadings. 'The
loading applies to stack room floors that support nonmobile, double-faced library book stacks subject to the following limitations: (1) The nominal book
stack unit height shall not exceed 90 in. (2290 mm); (2) the nominal shelf depth shall not exceed 12 in. (305 mm) for each face; and (3) parallel rows of double-
faced book stacks shall be separated by aisles not less than 36 in. (914 mm) wide.
d ~ addition to the vertical live loads, the design shall include horizontal swaying forces applied to each row of the seats as follows: 24 lb per linear ft of seat applied
in a direction parallel to each row of seats and 10 lb per linear ft of seat applied in a direction perpendicular to each row of seats. The parallel and perpendicular
horizontal swaying forces need not be applied simultaneously.
"Other uniform loads in accordance with an approved method, which contains provisions for truck loadings, shall also be considered where appropriate.
f The concentrated wheel load shall be applied on an area of 4.5 in. by 4.5 in. (1 14 mm by 114 mm) footprint of a jack.
gMinimum concentrated load on stair treads (on area of 4 in.2 [2,580 mm2]) is 300 lb (1.33 kN).
'where uniform roof live loads are reduced to less than 20 lb/ft2 (0.96 kN/m2) in accordance with Section 4.9.1 and are applied to the design of structural members
arranged so as to create continuity, the reduced roof live load shall be applied to adjacent spans or to alternate spans, whichever produces the greatest unfavorable
effect.
"oafs used for other special purposes shall be designed for appropriate loads as approved by the authority having jurisdiction.
I
I
TABLE 4-2 LlVE LOAD ELEMENT FACTOR, KLL
Element I KLL~ I

Interior columns
Exterior columns without cantilever slabs
I Edge columns with cantilever slabs 1 3 1
Corner columns with cantilever slabs
Edge beams without cantilever slabs
Interior beams
All other members not identified
including:
Edge beams with cantilever slabs
Cantilever beams
One-way slabs
Two-way slabs
Members without provisions for continuous
shear transfer normal to their soan
'In lieu of the preceding values, K L L is permitted to be calculated.

Minimum Design Loads for Buildings and Other Structures


Chapter 5
FLOOD LOADS

5.1 GENERAL Mitigation Administration has delineated both special flood haz-ard
areas and the risk premium zones applicable to the community.
The provisions of this section apply to buildings and other struc-
tures located in areas prone to flooding as defined on a flood SPECIAL FLOOD HAZARD AREA (AREA OF SPE-
hazard map. CIAL FLOOD HAZARD): The land in the floodplain subject to
a 1 percent or greater chance of flooding in any given year. These
5.2 DEFINITIONS areas are delineated on a community's FIRM as A-Zones (A, AE, Al-
30, A99, AR, AO, or AH) or V-Zones (V, VE, VO, or Vl-30).
The following definitions apply to the provisions of this chapter:
APPROVED: Acceptable to the authority having jurisdiction.
5.3 DESIGN REQUIREMENTS
BASE FLOOD: The flood having a 1 percent chance of
being equaled or exceeded in any given year. 5.3.1 Design Loads. Structural systems of buildings or other
structures shall be designed, constructed, connected, and an-
BASE FLOOD ELEVATION (BFE): The elevation of chored to resist flotation, collapse, and permanent lateral
flood-ing, including wave height, having a 1 percent chance of displace-ment due to action of flood loads associated with the
being equaled or exceeded in any given year. design flood (see Section 5.3.3) and other loads in accordance
BREAKAWAY WALL: Any type of wall subject to flooding with the load combinations of Chapter 2.
that is not required to provide structural support to a building or 5.3.2 Erosion and Scour. The effects of erosion and scour shall
other structure, and that is designed and constructed such that, be included in the calculation of loads on buildings and other
under base flood or lesser flood conditions, it will collapse in structures in flood hazard areas.
such a way that: (I ) it allows the free passage of floodwaters, and
(2) it does not damage the structure or supporting foundation 5.3.3 Loads on Breakaway Walls. Walls and partitions
system. required by ASCEISEI 24, to break away, including their
COASTAL A-ZONE: An area within a special flood hazard connections to the structure, shall be designed for the largest of
area, landward of a V-Zone or landward of an open coast without the following loads acting perpendicular to the plane of the wall:
mapped V-Zones. To be classified as a Coastal A-Zone, the prin- I . The wind load specified in Chapter 6.
cipal source of flooding must be astronomical tides, storm surges,
seiches, or tsunamis, not riverine flooding, and the potential for 2. The earthquake load specified in Chapter 9.
breaking wave heights greater than or equal to 1.5 ft (0.46 m) 3. 10 psf (0.48 k ~ / m ' ) .
must exist during the base flood.
The loading at which breakaway walls are intended to collapse
COASTAL HIGH HAZARD AREA (V-ZONE): An area shall not exceed 20 psf (0.96 kN/m2) unless the design meets the
within a Special Flood Hazard Area, extending from offshore to following conditions:
the inland limit of a primary frontal dune along an open coast,
and any other area that is subject to high-velocity wave action I . Breakaway wall collapse is designed to result from a flood
from storms or seismic sources. This area is designated on Flood load less than that which occurs during the base flood.
Insurance Rate Maps (FIRMS) as V, VE, VO, or Vl-30. 2. The supporting foundation and the elevated portion of the
building shall be designed against collapse, permanent lat-
DESIGN FLOOD: The greater of the following two flood eral displacement, and other structural damage due to the
events: (I ) the Base Flood, affecting those areas identified as effects of flood loads in combination with other loads as
Special Flood Hazard Areas on the community's FIRM; or specified in Chapter 2.
(2) the flood corresponding to the area designated as a Flood
Hazard Area on a community's Flood Hazard Map or otherwise
legally designated.
5.4 LOADS DURING FLOODING

DESIGN FLOOD ELEVATION (DFE): The elevation of 5.4.1 Load Basis. In flood hazard areas, the structural design
shall be based on the design flood.
the design flood, including wave height, relative to the datum
speci-fied on a community's flood hazard map. 5.4.2 Hydrostatic Loads. Hydrostatic loads caused by a depth
FLOOD HAZARD AREA: The area subject to flooding of water to the level of the DFE shall be applied over all surfaces
dur-ing the design flood. involved, both above and below ground level, except that for sur-
faces exposed to free water, the design depth shall be increased
FLOOD HAZARD MAP: The map delineating Flood by 1 ft (0.30 m).
Hazard Areas adopted by the authority having jurisdiction.
Reduced uplift and lateral loads on surfaces of enclosed spaces
FLOOD INSURANCE RATE MAP (FIRM): An official below the DFE shall apply only if provision is made for entry
map of a community on which the Federal Insurance and
and exit of floodwater.

Minimum Design Loads for Buildings and Other Structures


5.4.3 Hydrodynamic Loads. Dynamic effects of moving water 5.4.4.1 Breaking Wave Loads on Vertical Pilings and
shall be determined by a detailed analysis utilizing basic concepts Columns. The net force resulting from a breaking wave acting
of fluid mechanics. on a rigid vertical pile or column shall be assumed to act at the
EXCEPTION: Where water velocities do not exceed 10 ft/s (3.05 mls), still water elevation and shall be calculated by the following:
dynamic effects of moving water shall be permitted to be converted into
equivalent hydrostatic loads by increasing the DFE for design purposes by
an equivalent surcharge depth, d h ,on the headwater side and above the where
ground level only, equal to
FD = net wave force, in lb (kN)
y,, = unit weight of water, in lb per cubic ft (kN/m3), = 62.4 pcf
(9.80 kN/m3) for fresh water and 64.0 pcf (10.05 W m 3 )
for salt water
where CD = coefficient of drag for breaking waves, = 1.75 for round
V = average velocity of water in ft/s (mls) piles or columns, and = 2.25 for square piles or columns
g = acceleration due to gravity, 32.2 ft/s (9.81 m/s2) D = pile or column diameter, in ft (m) for circular sections, or
for a square pile or column, 1.4 times the width of the pile
a = coefficient of drag or shape factor (not less than 1.25)
or column in ft (m)
The equivalent surcharge depth shall be added to the DFE de- HI, = breaking wave height, in ft (m)
sign depth and the resultant hydrostatic pressures applied to, and 5.4.4.2 Breaking Wave Loads on Vertical Walls. Maximum
uniformly distributed across, the vertical projected area of the pressures and net forces resulting from a normally incident
building or structure that is perpendicular to the flow. Surfaces break-ing wave (depth-limited in size, with HI, = 0.78d,) acting
parallel to the flow or surfaces wetted by the tail water shall be on a rigid vertical wall shall be calculated by the following:
subject to the hydrostatic pressures for depths to the DFE only.
5.4.4 Wave Loads. Wave loads shall be determined by one of
the following three methods: (I ) by using the analytical and
procedures outlined in this section, (2) by more advanced where
numerical mod-eling procedures, or (3) by laboratory test
procedures (physical modeling).
Pmax=maximum combined dynamic (C[,y,,d,) and static
Wave loads are those loads that result from water waves uroua-
(1.2y,,d,) wave pressures, also referred to as shockpres-
1 1

gating over the water surface and striking a building or other


structure. Design and construction of buildings and other struc- sures in lb/ft2 (kN/m2)
tures subject to wave loads shall account for the following loads: Ft = net breaking wave force per unit length of structure, also
waves breaking on any portion of the building or structure; up-lift referred to as shock, impulse, or wave impact force in
forces caused by shoaling waves beneath a building or struc-ture, lb/ft (kN/m), acting near the still water elevation
or portion thereof; wave runup striking any portion of the CI, = dynamic pressure coefficient (1.6 < CI, < 3.5) (see
building or structure; wave-induced drag and inertia forces; and Table 5-1)
wave-induced scour at the base of a building or structure, or its y,, = unit weight of water, in lb per cubic ft (kN/m3), = 62.4
foundation. Wave loads shall be included for both V-Zones and pcf (9.80 k ~ / mfor~ )fresh water and 64.0 pcf (10.05 W m
A-Zones. In V-Zones, waves are 3 ft (0.91 m) high, or higher; in 3 ) for salt water
coastal floodplains landward of the V-Zone, waves are less than 3 d, = still water depth in ft (m) at base of building or other
ft high (0.91 m). structure where the wave breaks
Nonbreaking and broken wave loads shall be calculated using This procedure assumes the vertical wall causes a reflected or
the procedures described in Sections 5.4.2 and 5.4.3 that show standing wave against the waterward side of the wall with the
how to calculate hydrostatic and hydrodynamic loads. crest of the wave at a height of 1.2d, above the still water level.
Thus, the dynamic static and total pressure distributions against
Breaking wave loads shall be calculated using the procedures the wall are as shown in Fig. 5-1.
described in Sections 5.4.4.1 through 5.4.4.4. Breaking wave
heights used in the procedures described in Sections 5.4.4.1 This procedure also assumes the space behind the vertical wall
through 5.4.4.4 shall be calculated for V-Zones and Coastal A- is dry, with no fluid balancing the static component of the wave
Zones using Eqs. 5-2 and 5-3. force on the outside of the wall. If free water exists behind the
wall, a portion of the hydrostatic component of the wave
pressure and force disappears (see Fig. 5-2) and the net force
shall be computed by Eq. 5-7 (the maximum combined wave
where pressure is still computed with Eq. 5-5).
HI, = breaking wave height in ft (m)
d, = local still water depth in ft (m)
where
The local still water depth shall be calculated using Eq. 5-3,
unless more advanced procedures or laboratory tests permitted by Ft = net breaking wave force per unit length of structure, also
this section are used. referred to as shock, impulse, or wave impact force in lb/ft
(kN/m), acting near the still water elevation
CI, = dynamic pressure coefficient (1.6 < C1, < 3.5) (see Table
5-1)
where
BFE = BFE in ft (m) y,, = unit weight of water, in lb per cubic ft (kN/m3), = 62.4 pcf
G = ground elevation in ft (m) (9.80 kN/m3) for fresh water and 64.0 pcf (10.05 kN/m3)
for salt water

ASCE 7-05
d , = still water depth in ft (m) at base of building or other struc- Ft = net breaking wave force (normally incident waves) acting
ture where the wave breaks on a vertical surface in lblft (kN1m)
5.4.4.3 Breaking Wave Loads on Nonvertical Walls. Break- a = horizontal angle between the direction of wave approach and
ing wave forces given by Eqs. 5-6 and 5-7 shall be modified in the vertical surface
instances where the walls or surfaces upon which the breaking
waves act are nonvertical. The horizontal component of breaking 5.4.5 Impact Loads. Impact loads are those that result from
wave force shall be given by debris, ice, and any object transported by floodwaters striking
against buildings and structures, or parts thereof. Impact loads
FIX,= Ft sin2 a (5-8) shall be determined using a rational approach as concentrated
loads acting horizontally at the most critical location at or below
where
the DFE.
FIX,= horizontal component of breaking wave force in lblft
(kNlm)
Ft = net breaking wave force acting on a vertical surface in
lblft (kN1m) 5.5 CONSENSUS STANDARDS AND
a = vertical angle between nonvertical surface and the hori-
OTHER REFERENCED DOCUMENTS
-
zontal This section lists the consensus standards and other documents
which are adopted by reference within this chapter:
5.4.4.4 Breaking Wave Loads from Obliquely Incident Waves.
Breaking wave forces given by Eqs. 5-6 and 5-7 shall be modified in ASCEISEI
instances where waves are obliquely incident. Breaking wave forces American Society of Civil Engineers
from non-normally incident waves shall be given by Structural Engineering Institute
1801 Alexander Bell Drive
F,,, = Ft sin2 a (5-9) Reston, VA 20191-4400
where ASCEISEI 24
F,,, = horizontal component of obliquely incident breaking wave Section 5.3.3
force in lblft ( W m ) Flood Resistant Design and Construction, 1998

TABLE 5-1 VALUE OF DYNAMIC PRESSURE COEFFICIENT, Cp


Building Category

111 3.2
IV 3.5

Minimum Design Loads for Buildings and Other Structures


Vertical Wall

Crest of reflected wave

Dynamic pressure
1.2 d, Crest of incident wave
0.55 d,

---------

I
Stillwater level

ds pressure

Ground elevation

FIGURE 5-1 NORMALLY INCIDENT BREAKING WAVE PRESSURES AGAINST A VERTICAL WALL (space behind
vertical wall is dry)

ASCE 7-05
Vertical Wall

Crest of reflected wave

Dynamic pressure
Crest of incident wave

Stillwater level

Net hydrostatic pressure

Ground elevation

FIGURE 5-2 NORMALLY INCIDENT BREAKING WAVE PRESSURES AGAINST A VERTICAL WALL (still
water level equal on both sides of wall)

Minimum Design Loads for Buildings and Other Structures


Chapter 6
WIND LOADS
6.1 GENERAL BUILDING AND OTHER STRUCTURE, FLEXIBLE:
Slender buildings and other structures that have a fundamental
6.1.1 Scope. Buildings and other structures, including the Main
natural frequency less than 1 Hz.
Wind-Force Resisting System (MWFRS) and all components and
cladding thereof, shall be designed and constructed to resist wind BUILDING, LOW-RISE: Enclosed or partially enclosed
loads as specified herein. buildings that comply with the following conditions:
1. Mean roof height h less than or equal to 60 ft (18 m).
6.1.2 Allowed Procedures. The design wind loads for buildings
and other structures, including the MWFRS and component and 2. Mean roof height h does not exceed least horizontal dimen-
cladding elements thereof, shall be determined using one of the sion.
following procedures: (1) Method 1-Simplified Procedure as
specified in Section 6.4 for buildings meeting the requirements BUILDING, OPEN: A building having each wall at least 80
specified therein; (2) Method 2-Analytical Procedure as speci- percent open. This condition is expressed for each wall by
fied in Section 6.5 for buildings meeting the requirements speci- the equation A, 0.8AR where
fied therein; (3) Method 3-Wind Tunnel Procedure as specified in A, = total area of openings in a wall that receives positive
Section 6.6. external pressure, in ft2 (m2)
6.1.3 Wind Pressures Acting on Opposite Faces of Each Ax = the gross area of that wall in which A, is identified, in
ft2 (m2)
Building Surface. In the calculation of design wind loads for
the MWFRS and for components and cladding for buildings, the BUILDING, PARTIALLY ENCLOSED: A building that
algebraic sum of the pressures acting on opposite faces of each complies with both of the following conditions:
building surface shall be taken into account. 1. The total area of openings in a wall that receives positive
external pressure exceeds the sum of the areas of openings
6.1.4 Minimum Design Wind Loading. The design wind in the balance of the building envelope (walls and roof) by
load, determined by any one of the procedures specified in Sec-
more than 10 percent.
tion 6.1.2, shall be not less than specified in this section.
2. The total area of openings in a wall that receives positive
6.1.4.1 Main Wind-Force Resisting System. The wind load external pressure exceeds 4 ft2 (0.37 m2) or 1 percent of
to be used in the design of the MWFRS for an enclosed or the area of that wall, whichever is smaller, and the
partially enclosed building or other structure shall not be less percentage of openings in the balance of the building
than 10 lb/ft2 (0.48 kN/m2) multiplied by the area of the building envelope does not exceed 20 percent.
or structure projected onto a vertical plane normal to the assumed
wind direc-tion. The design wind force for open buildings and These conditions are expressed by the following equations:
other struc-tures shall be not less than 10 lb/ft2 (0.48 kN/m2) 1. A, > l.lOA,;
multiplied by the area Af .
2. A, > 4 sq ft (0.37 m2) or >O.OIAR, whichever is smaller,
6.1.4.2 Components and Cladding. The design wind pressure and A,;/A, 5 0.20
for components and cladding of buildings shall not be less than a where
net pressure of 10 lb/ft2 (0.48 kN/m2) acting in either direction
A,, Ax are as defined for Open Building
normal to the surface.
A,; = the sum of the areas of openings in the building en-
velope (walls and roof) not including A,, in ft2 (m2)
Ax; = the sum of the gross surface areas of the building en-
6.2 DEFINITIONS
velope (walls and roof) not including Ax, in ft2 (m2)
The following definitions apply only to the provisions of BUILDING OR OTHER STRUCTURE, REGULAR-
Chapter 6: SHAPED: A building or other structure having no unusual geo-
APPROVED: Acceptable to the authority having jurisdiction. metrical irregularity in spatial form.
BASIC WIND SPEED, V: Three-second gust speed at 33 ft BUILDING OR OTHER STRUCTURES, RIGID: A
(10 m) above the ground in Exposure C (see Section 6.5.6.3) as build-ing or other structure whose fundamental frequency is
determined in accordance with Section 6.5.4. greater than or equal to 1 Hz.
BUILDING, ENCLOSED: A building that does not comply with BUILDING, SIMPLE DIAPHRAGM: A building in
the requirements for open or partially enclosed buildings. which both windward and leeward wind loads are transmitted
through floor and roof diaphragms to the same vertical MWFRS
BUILDING ENVELOPE: Cladding, roofing, exterior (e.g., no structural separations).
walls, glazing, door assemblies, window assemblies, skylight
assem-blies, and other components enclosing the building. COMPONENTS AND CLADDING: Elements of the
build-ing envelope that do not qualify as part of the MWFRS.

Minimum Design Loads for Buildings and Other Structures


DESIGN FORCE, F : Equivalent static force to be used in RECOGNIZED LITERATURE: Publishedresearchfindings
the determination of wind loads for open buildings and other and technical papers that are approved.
structures. RIDGE: With respect to topographic effects in Section 6.5.7
DESIGN PRESSURE, p: Equivalent static pressure to an elongated crest of a hill characterized by strong relief in two
beused in the determination of wind loads for buildings. directions (see Fig. 6-4).

I EAVE HEIGHT, h: The distance from the ground surface adjacent


to the building to the roof eave line at a particular wall. If the height of
WIND-BORNEDEBRIS
withinhurricane prone regions located:
REGIONS: Areas

1. Within 1 mile of the coastal mean high water line where the
the eave varies along the wall, the average height shall be used. basic wind speed is equal to or greater than 110 milh and in
EFFECTIVE WIND AREA, A: The area used to determine Hawaii, or
GCp .For component and cladding elements, the effective wind 2. In areas where the basic wind speed is equal to or greater
area in Figs. 6- 1 1 through 6- 17 and Fig. 6- 19 is the span length than 120 mi/h.
multiplied by an effective width that need not be less than one-
third the span length. For cladding fasteners, the effective wind 6.3 SYMBOLS AND NOTATION
area shall not be greater than the area that is tributary to an indi-
vidual fastener. The following symbols and notation apply only to the provisions
of Chapter 6:
ESCARPMENT: Also known as scarp, with respect to topo-
graphic effects in Section 6.5.7, a cliff or steep slope generally A = effective wind area, in ft2 (m2)
separating two levels or gently sloping areas (see Fig. 6-4). A = area of open buildings and other structures either nor-
FREE ROOF: Roof with a configuration generally conform- mal to the wind direction or projected on a plane nor-
ing to those shown in Figs. 6- 18A through 6- 18D (monoslope, mal to the wind direction, in ft2 (m2)
pitched, or troughed) in an open building with no enclosing walls Ax = the gross area of that wall in which A, is identified, in
underneath the roof surface. ft2 (m2)
GLAZING: Glass or transparent or translucent plastic sheet Ax; =the sum of the gross surface areas of the build-ing
used in windows, doors, skylights, or curtain walls. envelope (walls and roof) not including Ax, in ft2
(m2)
GLAZING, IMPACT RESISTANT: Glazing that has been
shown by testing in accordance with ASTM El886 and ASTM A, = total area of openings in a wall that receives positive
El996 or other approved test methods to withstand the impact of external pressure, in ft2 (m2)
wind-borne missiles likely to be generated in wind-borne debris A,; = the sum of the areas of openings in the building enve-
regions during design winds. lope (walls and roof) not including A,, in ft2 (m2)
HILL: With respect to topographic effects in Section 6.5.7, a AOx= total area of openings in the building envelope in ft2
land surface characterized by strong relief in any horizontal (m2)
direction (see Fig. 6-4). A, = gross area of the solid freestanding wall or solid sign,
in ft2 (m2)
HURRICANE PRONE REGIONS: Areas vulnerable to
hur-ricanes; in the United States and its territories defined as a = width of pressure coefficient zone, in ft (m)
1. The U.S. Atlantic Ocean and Gulf of Mexico coasts where B = horizontal dimension of building measured normal to
the basic wind speed is greater than 90 mi/h, and wind direction, in ft (m)
-
2. Hawaii, Puerto Rico, Guam, Virgin Islands, and American h =mean hourly wind speed factor in Eq. 6-14 from Table
Samoa. 6-2
IMPACT RESISTANT COVERING: A covering designed
to protect glazing, which has been shown by testing in accor- h = 3-s gust speed factor from Table 6-2
dance with ASTM El886 and ASTM El996 or other approved test C = force coefficient to be used in determination of wind
methods to withstand the impact of wind-borne debris mis-siles loads for other structures
likely to be generated in wind-borne debris regions during design C N = net pressure coefficient to be used in determination
winds. of wind loads for open buildings
IMPORTANCE FACTOR, I: A factor that accounts for the C p = external pressure coefficient to be used in determina-
degree of hazard to human life and damage to property. tion of wind loads for buildings
MAIN WIND-FORCE RESISTING SYSTEM (MWFRS): c = turbulence intensity factor in Eq. 6-5 from Table 6-2
An assemblage of structural elements assigned to provide sup-
port and stability for the overall structure. The system generally D = diameter of a circular structure or member, in ft (m)
receives wind loading from more than one surface.
D' = depth of protruding elements such as ribs and spoilers,
MEAN ROOF HEIGHT, h: The average of the roof eave in ft (m)
height and the height to the highest point on the roof surface, F = design wind force for other structures, in lb (N)
except that, for roof angles of less than or equal to lo", the mean
roof height shall be the roof heave height. G = gust effect factor
OPENINGS: Apertures or holes in the building envelope that G = gust effect factor for MWFRSs of flexible buildings
allow air to flow through the building envelope and that are and other structures
designed as "open" during design winds as defined by these GCp,, = combined net pressure coefficient for a parapet
provisions. GCp =product of external pressure coefficient and gust-
effect factor to be used in determination of wind
loads for buildings

ASCE 7-05
GCp j = product of the equivalent external pressure coef- q = velocity pressure, in lb/ft2 (IV/m2)
ficient and gust-effect factor to be used in deter-
qj, = velocity pressure evaluated at height z = h , in
mination of wind loads for MWFRS of low-rise
lb/ft2 (IV/m2)
buildings
q; = velocity pressure for internal pressure determi-
GCpi = product of internal pressure coefficient and gust-
effect factor to be used in determination of wind nation, in lb/ft2 (IV/m2)
loads for buildings q p =velocity pressure at top of parapet, in lb/ft2
gg = peak factor for background response in Eqs. 6-4 (IV/m2)
and 6-8 q, =velocity pressure evaluated at height z above
g~ = peak factor for resonant response in Eq. 6-8
ground, in lb/ft2 (IV/m2)
g,. = peak factor for wind response in Eqs. 6-4 and 6-
R = resonant response factor from Eq. 6-10
8 R s , Rj,, R L = values from Eq. 6-13
H = height of hill or escarpment in Fig. 6-4, in ft (m) R; = reduction factor from Eq. 6-16
h = mean roof height of a building or height of other R,, = value from Eq. 6- 11
structure, except that eave height shall be used s = vertical dimension of the solid freestanding wall I
for roof angle B of less than or equal to loo, in or solid sign from Fig. 6-20, in ft (m)
ft (m) r = rise-to-span ratio for arched roofs
he = roof eave height at a particular wall, or the aver-
V = basic wind speed obtained fromFig. 6- 1, inmilh
age height if the eave varies along the wall
(m/s). The basic wind speed corresponds to a 3-
I = importance factor s gust speed at 33 ft (10 m) above ground in
I, = intensity of turbulence from Eq. 6-5 exposure Category C
K I ,K z , K 3 = multipliers in Fig. 6-4 to obtain K,, V; = unpartitioned internal volume ft3 (m3)
Kd = wind directionality factor in Table 6-4 & = mean hourly wind speed at height 7 , ft/s (m/s)
Kj, = velocity pressure exposure coefficient evaluated W = width of building in Figs. 6-12 and 6-14A and B
at height z = h and width of span in Figs. 6-13 and 6-15, in ft
K , = velocity pressure exposure coefficient evaluated (m)
at height z X = distance to center of pressure from windward
K,, = topographic factor as defined in Section 6.5.7 edge in Fig. 6-18, in ft (m)
L =horizontal dimension of a building measured x =distance upwind or downwind of crest in Fig. 6-
parallel to the wind direction, in ft (m) 4, in ft (m)
Lj, = distance upwind of crest of hill or escarpment in z = height above ground level, in ft (m)
Fig. 6-4 to where the difference in ground 7 = equivalent height of structure, in ft (m)
elevation is half the height of hill or
zR =nominal height of the atmospheric boundary
escarpment, in ft (m)
layer used in this standard. Values appear in
L , = integral length scale of turbulence, in ft (m) Table 6-2
L , = horizontal dimension of return comer for a solid
freestanding wall or solid sign from Fig. 6-20, ~ , ~ i =,, exposure constant from Table 6-2
in ft (m)
a = 3-s gust-speed power law exponent from Table
L = integral length scale factor from Table 6-2, ft (m) 6-2
N I = reduced frequency from Eq. 6-12
6 = reciprocal of a from Table 6-2
n 1 = building natural frequency, Hz
a = mean hourly wind-speed power law exponent in
p = design pressure to be used in determination of Eq. 6-14 from Table 6-2
wind loads for buildings, in lb/ft2 (IV/m2) ,f3 = damping ratio, percent critical for buildings or
p~ = wind pressure acting on leeward face in Fig. 6-9, other structures
in lb/ft2 (IV/m2)
E = ratio of solid area to gross area for solid free-
p,,,, = net design wind pressure from Eq. 6-2, in lb/ft2 standing wall, solid sign, open sign, face of a
(IV/m2) trussed tower, or lattice structure
piLet3o= net design wind pressure for Exposure B at h = h = adjustment factor for building height and expo-
30 ft and I = 1.0 from Fig. 6-3, in lb/ft2 (IV/m2) sure from Figs. 6-2 and 6-3
p p =combined net pressure on a parapet from Eq. 6- E = integral length scale power law exponent in Eq.
20, in lb/ft2 (IV/m2) 6-7 from Table 6-2
p, = net design wind pressure from Eq. 6-1, in lb/ft2 '7= value used in Eq. 6-13 (see Section 6.5.8.2)
(IV/m2)
0 = angle of plane of roof from horizontal, in de-
p,30 = simplified design wind pressure for Exposure B grees
at h = 30 ft and I = 1.0 from Fig. 6-2, in lb/ft2
(IV/m2) v = height-to-width ratio for solid sign
pw =wind pressure acting on windward face in Fig. 6-
9, in lb/ft2 (IV/m2)
6.4 METHOD 1-SIMPLIFIED PROCEDURE
Q = background response factor from Eq. 6-6
6.4.1 Scope. A building whose design wind loads are determined in
accordance with this section shall meet all the conditions of

Minimum Design Loads for Buildings and Other Structures


6.4.1.1 or 6.4.1.2. If a building qualifies only under 6.4.1.2 for of building surfaces as shown in Fig. 6-2. For the horizontal
design of its components and cladding, then its MWFRS shall be pres-sures (zones A, B, C, D), p, is the combination of the
designed by Method 2 or Method 3. windward and leeward net pressures. p, shall be determined by
6.4.1.1 Main Wind-Force Resisting Systems. For the design of
the following equation:
MWFRSs the building must meet all of the following conditions:
1. The building is a simple diaphragm building as defined in where
Section 6.2.
h = adjustment factor for building height and exposure
2. The building is a low-rise building as defined in Section 6.2.
from Fig. 6-2
3. The building is enclosed as defined in Section 6.2 and con-
forms to the wind-borne debris provisions of Section6.5.9.3.
K,, = topographic factor as defined in Section 6.5.7 evaluated
I
4. The building is a regular-shaped building or structure as at mean roof height, h
defined in Section 6.2. I = importance factor as defined in Section 6.2
5. The building is not classified as a flexible building as defined p~30= simplified design wind pressure for Exposure B, at h =
30 ft, and for I = 1.0, from Fig. 6-2
in Section 6.2.
6. The building does not have response characteristics making 6.4.2.1.1 Minimum Pressures. The load effects of the
design wind pressures from Section 6.4.2.1 shall not be less than
it subject to across wind loading, vortex shedding, instability
the minimum load case from Section 6.1.4.1 assuming the
due to galloping or flutter; and does not have a site location
pressures, p,, for zones A, B, C, and D all equal to +10 psf, while
for which channeling effects or buffeting in the wake of
assuming zones E, F, G, and H all equal to 0 psf.
upwind obstructions warrant special consideration.
7. The building has an approximately symmetrical cross- 6.4.2.2 Components and Cladding. Net design wind pressures, p,,,,
,for the components and cladding of buildings designed using
section in each direction with either a flat roof or a gable or

I
Method 1 represent the net pressures (sum of internal and external)
hip roof with H 5 45". to be applied normal to each building surface as shown in Fig. 6-3.
8. The building is exempted from torsional load cases as in- p,,,, shall be determined by the following equation:
dicated in Note 5 of Fig. 6-10, or the torsional load cases
defined in Note 5 do not control the design of any of the
MWFRSs of the building. where
6.4.1.2 Components and Cladding. For the design of compo- h = adjustment factor for building height and exposure from
nents and cladding the building must meet all the following
conditions:
Fig. 6-3
K,, = topographic factor as defined in Section 6.5.7 evaluated I
at mean roof height, h
1. The mean roof height h must be less than or equal to 60 ft I = importance factor as defined in Section 6.2
(h I60 ft) . p,,,,3() = net design wind pressure for exposure B, at h = 30 ft,
2. The building is enclosed as defined in Section 6.2 and con- and for I = 1.0, from Fig. 6-3
forms to the wind-borne debris provisions of Section6.5.9.3. 6.4.2.2.1 Minimum Pressures. The positive design wind
3. The building is a regular-shaped building or structure as pressures, p,,,,, from Section 6.4.2.2 shall not be less than +10
defined in Section 6.2. psf, and the negative design wind pressures, p,,,,, from Section
6.4.2.2 shall not be less than 10 psf.
-

4. The building does not have response characteristics making it


subject to across wind loading, vortex shedding, instability due 6.4.3 Air Permeable Cladding. Design wind loads determined
to galloping or flutter; and does not have a site location for from Fig. 6.3 shall be used for all air permeable cladding unless
which channeling effects or buffeting in the wake of upwind approved test data or the recognized literature demonstrate lower
obstructions warrant special consideration. loads for the type of air permeable cladding being considered.

5. The building has either a flat roof, a gable roof with 0 5


45", or a hip roof with H 5 27'. 6.5 METHOD 2-ANALYTICAL PROCEDURE
6.4.2 Design Procedure. 6.5.1 Scope. A building or other structure whose design wind
loads are determined in accordance with this section shall meet
1. The basic wind speed V shall be determined in accordance all of the following conditions:
with Section 6.5.4. The wind shall be assumed to come 1. The building or other structure is a regular-shaped building
from any horizontal direction. or structure as defined in Section 6.2.
2. An importance factor I shall be determined in accordance 2. The building or other structure does not have response
with Section 6.5.5. char-acteristics making it subject to across wind loading,
3. An exposui-e categoi-y shall be determined in accordance vortex shedding, instability due to galloping or flutter; or
with Section 6.5.6. does not have a site location for which channeling effects
or buf-feting in the wake of upwind obstructions warrant
4. A height and exposure adjustment coefficient, h, shall be special consideration.
determined from Fig. 6-2.
6.5.2 Limitations. The provisions of Section 6.5 take into con-
6.4.2.1 Main Wind-Force Resisting System. Simplified design sideration the load magnification effect caused by gusts in reso-
wind pressures, p,, for the MWFRSs of low-rise simple dia-phragm nance with along-wind vibrations of flexible buildings or other
buildings represent the net pressures (sum of internal and external) to structures. Buildings or other structures not meeting the require-
be applied to the horizontal and vertical projections ments of Section 6.5.1, or having unusual shapes or response

ASCE 7-05
the anemometer have been taken into account. Reduction in basic

characteristics, shall be designed using recognized literature


I
documenting such wind load effects or shall use the wind tunnel wind speed below that of Fig. 6-1 shall be permitted.
procedure specified in Section 6.6. In hurricane-prone regions, wind speeds derived from simula-
6.5.2.1 Shielding. There shall be no reductions in velocity pres- tion techniques shall only be used in lieu of the basic wind speeds
sure due to apparent shielding afforded by buildings and other given in Fig. 6- 1 when (1) approved simulation and extreme value
structures or terrain features. statistical analysis procedures are used (the use of regional wind
speed data obtained from anemometers is not permitted to define
6.5.2.2 Air Permeable Cladding. Design wind loads deter- the hurricane wind-speed risk along the Gulf and Atlantic coasts,
mined from Section 6.5 shall be used for air permeable cladding the Caribbean, or Hawaii) and (2) the design wind speeds result-
unless approved test data or recognized literature demonstrate ing from the study shall not be less than the resulting 500-year
lower loads for the type of air permeable cladding being
considered. return period wind speed divided by a.
In areas outside hurricane-prone regions, when the basic wind
6.5.3 Design Procedure. speed is estimated from regional climatic data, the basic wind
speed shall be not less than the wind speed associated with an
1. The basic wind speed V and wind dii-ectionalityfactor Kd
annual probability of 0.02 (50-year mean recurrence interval),
shall be determined in accordance with Section 6.5.4.
and the estimate shall be adjusted for equivalence to a 3-s gust
2. An importance factor I shall be determined in accordance wind speed at 33 ft (10 m) above ground in exposure Category
with Section 6.5.5. C. The data analysis shall be performed in accordance with this
chapter.
3. An exposui-e categoi-y or exposui-e categories and 6.5.4.3 Limitation. Tornadoes have not been considered in de-
velocity pi-essui-e exposui-e coeficient K, or Kj,, as
applicable, shall be determined for each wind direction in veloping the basic wind-speed distributions.
accordance with Section 6.5.6. 6.5.4.4 Wind Directionality Factor. The wind directionality
4. A topogi-aphic factor K,, shall be determined in accor- factor, K d , shall be determined from Table 6-4. This factor shall
dance with Section 6.5.7. only be applied when used in conjunction with load combinations
specified in Sections 2.3 and 2.4.
5. A gust effect factor G or Gj, as applicable, shall be deter- 6.5.5 Importance Factor. An importance factor, I, for the build-
mined in accordance with Section 6.5.8.
ing or other structure shall be determined from Table 6-1 based
6. An enclosui-e classification shall be determined in accor- on building and structure categories listed in Table 1- 1.

I
dance with Section 6.5.9. 6.5.6 Exposure. For each wind direction considered, the upwind
7. Internal pi-essui-e coeficient GCp, shall be determined in exposure category shall be based on ground surface roughness
accordance with Section 6.5.11.1. that is determined from natural topography, vegetation, and con-
structed facilities.
8. External pi-essui-e coeficients C , or G C D for, for-ce coefi-
6.5.6.1 Wind Directions and Sectors. For each selected wind
cients C j,as applicable, shall be.determ&ed in accordance
direction at which the wind loads are to be evaluated, the expo-
with Section 6.5.1 1.2 or 6.5.1 1.3, respectively.
sure of the building or structure shall be determined for the two
9. Velocity pi-essui-e q, or qj,, as applicable, shall be deter- upwind sectors extending 45" either side of the selected wind di-
mined in accordance with Section 6.5.10. rection. The exposures in these two sectors shall be determined
in accordance with Sections 6.5.6.2 and 6.5.6.3 and the exposure
10. Design wind load p or F shall be determined in accor- resulting in the highest wind loads shall be used to represent the
dance with Sections 6.5.12, 6.5.13, 6.5.14, and 6.5.15, as winds from that direction.
applicable. 6.5.6.2 Surface Roughness Categories. A ground surface
6.5.4 Basic Wind Speed. The basic wind speed, V , used in the roughness within each 45" sector shall be determined for a dis-
determination of design wind loads on buildings and other tance upwind of the site as defined in Section 6.5.6.3 from the
structures shall be as given in Fig. 6-1 except as provided in categories defined in the following text, for the purpose of
Sections 6.5.4.1 and 6.5.4.2. The wind shall be assumed to come assign-ing an exposure category as defined in Section 6.5.6.3.
from any horizontal direction.
Surface Roughness B: Urban and suburban areas, wooded ar-
6.5.4.1 Special Wind Regions. The basic wind speed shall be in- eas, or other terrain with numerous closely spaced obstructions
creased where records or experience indicate that the wind speeds are having the size of single-family dwellings or larger.
higher than those reflected in Fig. 6- 1. Mountainous terrain, gorges, Surface Roughness C: Open terrain with scattered obstructions
and special regions shown inFig. 6- 1 shall be examined for unusual having heights generally less than 30 ft (9.1 m). This category
wind conditions. The authority having jurisdiction shall, if necessary, includes flat open country, grasslands, and all water surfaces in
adjust the values given in Fig. 6-1 to account for higher local wind hurricane prone regions.
speeds. Such adjustment shall be based on me-teorological
information and an estimate of the basic wind speed obtained in Surface Roughness D: Flat, unobstructed areas and water sur-
accordance with the provisions of Section 6.5.4.2. faces outside hurricane prone regions. This category includes
smooth mud flats, salt flats, and unbroken ice.
6.5.4.2 Estimation of Basic Wind Speeds from Regional
Climatic Data. In areas outside hurricane-prone regions, re- 6.5.6.3 Exposure Categories
gional climatic data shall only be used in lieu of the basic wind Exposure B: Exposure B shall apply where the ground surface
speeds given in Fig. 6-1 when (1) approved extreme-value roughness condition, as defined by Surface Roughness B, prevails
statistical-analysis procedures have been employed in reducing in the upwind direction for a distance of at least 2,600 ft (792 m)
height of the building, whichever is greater.
I or 20 times the
the data; and (2) the length of record, sampling error, averaging
time, anemometer height, data quality, and terrain exposure of

Minimum Design Loads for Buildings and Other Structures


EXCEPTION: For buildings whose mean roof height is less than or 4. HILj, 2 0.2.
equal to 30 ft, the upwind distance may be reduced to 1,500 ft (457 m).
Exposure C: Exposure C shall apply for all cases where Expo- 5. H is greater than or equal to 15 ft (4.5 m) for Exposures C
sures B or D do not apply. and D and 60 ft (18 m) for Exposure B.

Exposure D: Exposure D shall apply where the ground surface 6.5.7.2 Topographic Factor. The wind speed-up effect shall be
roughness, as defined by Surface Roughness D, prevails in the included in the calculation of design wind loads by using the
upwind direction for a distance greater than 5,000 ft (1,524 m) or factor K,,:
20 times the building height, whichever is greater. Exposure
Dshall extend into downwind areas of Surface Roughness B or C
for a distance of 600 ft (200 m) or 20 times the height of the where K I , K2, and K3 are given in Fig. 6-4.
building, whichever is greater. If site conditions and locations of structures do not meet all the
For a site located in the transition zone between exposure cate- conditions specified in Section 6.5.7.1 then K, = 1.0.
gories, the category resulting in the largest wind forces shall be 6.5.8 Gust Effect Factor.
used.
EXCEPTION: An intermediate exposure between the preceding cate- 6.5.8.1 Rigid Structures. For rigid structures as defined in Sec-
gories is pennitted in a transition zone provided that it is detennined by a tion 6.2, the gust-effect factor shall be taken as 0.85 or calculated
rational analysis method defined in the recognized literature. by the formula:
6.5.6.4 Exposure Category for Main Wind-Force Resisting
System.
6.5.6.4.1 Buildings and Other Structures. For each wind
direction considered, wind loads for the design of the MWFRS
de-termined from Fig. 6-6 shall be based on the exposure
categories defined in Section 6.5.6.3.
6.5.6.4.2 Low-Rise Buildings. Wind loads for the design of
the MWFRSs for low-rise buildings shall be determined using a
where I: = the intensity of turbulence at height 7 where 7 = the
velocity pressure qj, based on the exposure resulting in the high-
equivalent height of the structure defined as 0.6h, but not less
est wind loads for any wind direction at the site where external
than z,,, for all building heights h. z,,, and c are listed for each
pressure coefficients GCPjgiven in Fig. 6-10 are used.
exposure in Table 6-2; g g and g , shall be taken as 3.4. The
I6Components
.5.6.5 Exposure Category for Components and Cladding.
and cladding design pressures for all buildings and other
background response Q is given by
structures shall be based on the exposure resulting in the highest wind
loads for any direction at the site.

6.5.6.6 Velocity Pressure Exposure Coefficient. Based on the


exposure category determined in Section 6.5.6.3, a velocity pres-
sure exposure coefficient K, or Kj,, as applicable, shall be de- where B, h are defined in Section 6.3; and L: = the integral length
termined from Table 6-3. For a site located in a transition zone scale of turbulence at the equivalent height given by
between exposure categories, that is, near to a change in ground
surface roughness, intermediate values of K, or Kj,, between
those shown in Table 6-3, are permitted, provided that they are
de-termined by a rational analysis method defined in the
recognized literature. InSI: L: = l -
6.5.7 Topographic Effects. (fo) ?
in which ! and C are constants listed in Table 6-2.
6.5.7.1 Wind Speed-Up over Hills, Ridges, and Escarpments.
Wind speed-up effects at isolated hills, ridges, and escarpments 6.5.8.2 Flexible or Dynamically Sensitive Structures.
constituting abrupt changes in the general topography, located in Forflex-ible or dynamically sensitive structures as defined in
any exposure category, shall be included in the design when Section 6.2, the gust-effect factor shall be calculated by
buildings and other site conditions and locations of structures
meet all of the following conditions:
G j = 0.925 (6-8)
1. The hill, ridge, or escarpment is isolated and unobstructed /

upwind by other similar topographic features of comparable g g and g , shall be taken as 3.4 and g ~ is given by
height for 100 times the height of the topographic feature
(100H) or 2 mi (3.22 km), whichever is less. This distance R , the resonant response factor, is given by
shall be measured horizontally from the point at which the
height H of the hill, ridge, or escarpment is determined.
2. The hill, ridge, or escarpment protrudes above the height of
R = / $ i i E z l (6- 10)
upwind terrain features within a 2-mi (3.22 km) radius in
any quadrant by a factor of two or more.
3. The structure is located as shown in Fig. 6-4 in the upper one- (6- 11)
half of a hill or ridge or near the crest of an escarpment.

ASCE 7-05
6.5.10 Velocity Pressure. Velocity pressure, q,, evaluated at
height z shall be calculated by the following equation:
q, = o . o o ~ ~ ~ K , K , ~ K(lb/ft2)~v~ I (6-15)
[In SI: q, = o . ~ ~ ~ K , K , , K (~~v/ m~ 'I) ;V in m/s]
where Kd is the wind directionality factor defined in Section
6.5.4.4, K, is the velocity pressure exposure coefficient defined in
Section 6.5.6.6, K,, is the topographic factor defined in Section
where the subscript L in Eq. 6-13 shall be taken as h, B, and L,
6.5.7.2, and qj, is the velocity pressure calculated using Eq. 6-15
respectively, where h, B, and L are defined in Section 6.3.
at mean roof height h.
n 1 = building natural frequency
The numerical coefficient 0.00256 (0.613 in SI) shall be used
Rt = Rj, setting q = 4.6nlh/& except where sufficient climatic data are available to justify the
Rr = Rs setting q = 4 . 6 n l ~ ~ / & selection of a different value of this factor for a design application.
Re = RL setting 11 = 1 5 . 4 n l ~ / K 6.5.11 Pressure and Force Coefficients.
= damping ratio, percent of critical 6.5.11.1 Internal Pressure Coefficient. Internal pressure
V: = mean hourly wind speed (ft/s) at height i determined from Eq. coeffi-cients, GCp;, shall be determined from Fig. 6-5 based on
6- 14. building enclosure classifications determined from Section 6.5.9.
6.5.11.1.1 Reduction Factor for Large Volume Buildings,
Ri.For a partially enclosed building containing a single,
unparti-tioned large volume, the internal pressure coefficient,
GCp, , shall be multiplied by the following reduction factor, R, :

where h and 6 are constants listed in Table 6-2 and V is the basic
wind speed in mi/h.
6.5.8.3 Rational Analysis. In lieu of the procedure defined in
Sections 6.5.8.1 and 6.5.8.2, determination of the gust-effect fac-
tor by any rational analysis defined in the recognized literature is where
permitted.
AOx = total area of openings in the building envelope (walls and
6.5.8.4 Limitations. Where combined gust-effect factors and roof, in ft2)
pressure coefficients (GCp, GCpi, and GCpj) are given in fig- V; = unpartitioned internal volume, in ft3
ures and tables, the gust-effect factor shall not be determined
separately. 6.5.11.2 External Pressure Coefficients.
6.5.11.2.1 Main Wind-Force Resisting Systems. External
6.5.9 Enclosure Classifications.
pressure coefficients for MWFRSs Cp are given in Figs. 6-6, 6-7,
6.5.9.1 General. For the purpose of determining internal pres- and 6-8. Combined gust effect factor and external pressure
sure coefficients, all buildings shall be classified as enclosed, par- coefficients, GCpj, are given in Fig. 6-10 for low-rise buildings.
tially enclosed, or open as defined in Section 6.2. The pressure coefficient values and gust effect factor in Fig. 6- 10
shall not be separated.
6.5.9.2 Openings. A determination shall be made of the amount
6.5.11.2.2 Components and Cladding. Combined gust-effect
of openings in the building envelope to determine the enclosure
factor and external pressure coefficients for components and cladding
classification as defined in Section 6.5.9.1.
GCp are given in Figs. 6- 11 through 6- 17. The pressure coefficient
6.5.9.3 Wind-Borne Debris. Glazing in buildings located in values and gust-effect factor shall not be separated.
wind-borne debris regions shall be protected with an impact- 6.5.11.3 Force Coefficients. Force coefficients C are given in
resistant covering or be impact-resistant glazing according to the Figs. 6-20 through 6-23.
requirements specified in ASTM El886 and ASTM El996 or
other approved test methods and performance criteria. The levels 6.5.11.4 Roof Overhangs.
of impact resistance shall be a function of Missile Levels and 6.5.11.4.1 Main Wind-Force Resisting System. Roof over-
Wind Zones specified in ASTM El886 and ASTM E1996. hangs shall be designed for a positive pressure on the bottom
EXCEPTIONS: surface of windward roof overhangs corresponding to Cq = 0.8 in
1. Glazing in Category 11,111, or IV buildings located over 60 ft (18.3 m) combination with the pressures determined from using Figs. 6-6
above the ground and over 30 ft (9.2 m) above aggregate surface roofs and 6-10.
located within 1,500 ft (458 m) of the building shall be pennitted to be
unprotected.
6.5.11.4.2 Components and Cladding. For all buildings,
roof overhangs shall be designed for pressures determined from
2. Glazing in Category I buildings shall be pennitted to be unprotected. pres-sure coefficients given in Figs. 6-1 lB,C,D.

6.5.9.4 Multiple Classifications. If a building by definition 6.5.11.5 Parapets.


complies with both the "open" and "partially enclosed" defini- 6.5.11.5.1 Main Wind-Force Resisting System. The pres-
tions, it shall be classified as an "open" building. A building that sure coefficients for the effect of parapets on the MWFRS loads
does not comply with either the "open" or "partially enclosed" are given in Section 6.5.12.2.4
definitions shall be classified as an "enclosed" building.

Minimum Design Loads for Buildings and Other Structures


6.5.11.5.2 Components and Cladding. The pressure coeffi- 6.5.12.2.3 Flexible Buildings. Design wind pressures for the
cients for the design of parapet component and cladding elements MWFRS of flexible buildings shall be determined from the fol-
are taken from the wall and roof pressure coefficients as specified lowing equation:
in Section 6.5.12.4.4.

6.5.12 Design Wind Loads on Enclosed and


Partially Enclosed Buildings. where q , q;, Cp, and (GCpi) are as defined in Section 6.5.12.2.1
and G = gust effect factor is defined as in Section 6.5.8.2.
6.5.12.1 General.
6.5.12.2.4 Parapets. The design wind pressure for the effect
6.5.12.1.1 Sign Convention. Positive pressure acts toward of parapets on MWFRSs of rigid, low-rise, or flexible buildings
the surface and negative pressure acts away from the surface. with flat, gable, or hip roofs shall be determined by the following
equation:
6.5.12.1.2 Critical Load Condition. Values of external and
internal pressures shall be combined algebraically to determine
the most critical load.
where
6.5.12.1.3 Tributary Areas Greater than 700 ft2 (65 m2). p p = combined net pressure on the parapet due to the combi-
Component and cladding elements with tributary areas greater nation of the net pressures from the front and back para-
than 700 ft2 (65 m2) shall be permitted to be designed using the pet surfaces. Plus (and minus) signs signify net pressure
provisions for MWFRSs. acting toward (and away from) the front (exterior) side
of the parapet
6.5.12.2 Main Wind-Force Resisting Systems. qp = velocity pressure evaluated at the top of the parapet
GCp,, = combined net pressure coefficient
6.5.12.2.1 Rigid Buildings of All Heights. Design wind
pres-sures for the MWFRS of buildings of all heights shall be = + 1.5 for windward parapet
deter-mined by the following equation: = 1.0 for leeward parapet
-

6.5.12.3 Design Wind Load Cases. The MWFRS of buildings


of all heights, whose wind loads have been determined under the
where provisions of Sections 6.5.12.2.1 and 6.5.12.2.3, shall be
designed for the wind load cases as defined in Fig. 6-9. The
q = qr for windward walls evaluated at height z above the eccentricity e for rigid structures shall be measured from the
mound u geometric center of the building face and shall be considered for
q = qj, for leeward walls, side walls, and roofs, evaluated at each principal axis (ex, ey). The eccentricity e for flexible
height h structures shall be determined from the following equation and
q; = qj, for windward walls, side walls, leeward walls, and shall be considered for each principal axis (ex, ey):
roofs of enclosed buildings and for negative internal
pressure evaluation in partially enclosed buildings
q; = qr for positive internal pressure evaluation in partially
enclosed buildings where height z is defined as the
level of the highest opening in the building that could where
affect the positive internal pressure. For buildings
sited in wind-borne debris regions, glazing that is not eg = eccentricity e as determined for rigid structures in Fig. 6-9 e~ =
impact resistant or protected with an impact resistant distance between the elastic shear center and center of mass
cover-ing, shall be treated as an opening in accordance of each floor
with Section 6.5.9.3. For positive internal pressure I z , g g , Q , g ~R , shall be as defined in Section 6.5.8
evalua-tion, q; may conservatively be evaluated at The sign of the eccentricity e shall be plus or minus,
height h (q; = q11) whichever causes the more severe load effect.
G = gust effect factor from Section 6.5.8
EXCEPTION: One-story buildings with lz less than or equal to 30 ft,
- buildings two stories or less framed with light-frame construction, and
Cp = external pressure coefficient from Fig. 6-6 or 6-8 buildings two stories or less designed with flexible diaphragms need only
(GCpi) = internal pressure coefficient from Fig. 6-5 be designed for Load Case 1 and Load Case 3 in Fig. 6-9.
q and q; shall be evaluated using exposure defined in Section
6.5.6.3. Pressure shall be applied simultaneously on windward 6.5.12.4 Components and Cladding.
and leeward walls and on roof surfaces as defined in Figs. 6-6
and 6-8.
6.5.12.4.1 Low-Rise Buildings and Buildings with h <
60 ft (18.3 m). Design wind pressures on component and cladding
elements of low-rise buildings and buildings with h 5 60 ft
6.5.12.2.2 Low-Rise Building. Alternatively, design wind
(18.3 m) shall be determined from the following equation:
pressures for the MWFRS of low-rise buildings shall be deter-
mined by the following equation:

where
where qj, = velocity pressure evaluated at mean roof height h using
exposure defined in Section 6.5.6.3
qj, = velocity pressure evaluated at mean roof height h using (GCp) = external pressure coefficients given in Figs. 6- 11
exposure defined in Section 6.5.6.3 through 6-16
(GCpj) = external pressure coefficient from Fig. 6-10
(GCp;) = internal pressure coefficient from Fig. 6-5 (GCp;) = internal pressure coefficient given in Fig. 6-5

ASCE 7-05
6.5.12.4.2 Buildings with h > 60 ft (18.3 m). Design wind 6.5.13.1.1 Sign Convention. Plus and minus signs signify
pressures on components and cladding for all buildings with h > pressure acting toward and away from the top surface of the roof,
60 ft (18.3 m) shall be determined from the following equation: respectively.
6.5.13.1.2 Critical Load Condition. Net pressure coeffi-
cients C N include contributions from top and bottom surfaces.
where
All load cases shown for each roof angle shall be investigated.
q = q, for windward walls calculated at height z above the
ground 6.5.13.2 Main Wind-Force Resisting Systems. The net
design pressure for the MWFRSs of monoslope, pitched, or
q = qj, for leeward walls, side walls, and roofs, evaluated at
troughed roofs shall be determined by the following equation:
height h
q, = qj, for windward walls, side walls, leeward walls, and
roofs of enclosed buildings and for negative internal
pressure evaluation in partially enclosed buildings where
q, = q, for positive internal pressure evaluation in partially qj, = velocity pressure evaluated at mean roof height h using the
enclosed buildings where height z is defined as the level exposure as defined in Section 6.5.6.3 that results in the
of the highest opening in the building that could affect the highest wind loads for any wind direction at the site
positive internal pressure. For buildings sited in wind- G = gust effect factor from Section 6.5.8
borne debris regions, glazing that is not impact resistant C N = n e t pressure coefficient determined from Figs. 6-18A
or protected with an impact-resistant cover-ing, shall be through 6-18D
treated as an opening in accordance with Section 6.5.9.3.
For positive internal pressure evalua-tion, q, may For free roofs with an angle of plane of roof from horizontal
conservatively be evaluated at height h 0 less than or equal to 5' and containing fascia panels, the fascia
(q, = YI,) panel shall be considered an inverted parapet. The contribution of
(GCp) = external pressure coefficient from Fig. 6-17 loads on the fascia to the MWFRS loads shall be determined
(GC,,,) = internal pressure coefficient given in Fig. 6-5. using Section 6.5.12.2.4 with qp equal to qj,.
q and q; shall be evaluated using exposure defined in Section 6.5.13.3 Component and Cladding Elements. The net design
6.5.6.3. wind pressure for component and cladding elements of mono-
slope, pitched, and troughed roofs shall be determined by the
6.5.12.4.3 Alternative Design Wind Pressures for following equation:
Compo-nents and Cladding in Buildings with 60 ft (18.3
m) < h < 90 ft (27.4 m). Alternative to the requirements of
Section 6.5.12.4.2, the design of components and cladding for where
buildings with a mean roof height greater than 60 ft (18.3 m) and
less than 90 ft (27.4 m) values from Figs. 6- 11 through 6- 17 qj, = velocity pressure evaluated at mean roof height h using the
shall be used only if the height to width ratio is one or less exposure as defined in Section 6.5.6.3 that results in the
(except as permitted by Note 6 of Fig. 6-17) and Eq. 6-22 is used. highest wind loads for any wind direction at the site
G = gust-effect factor from Section 6.5.8
6.5.12.4.4 Parapets. The design wind pressure on the
C N = n e t pressure coefficient determined from Figs. 6-19A
compo-nents and cladding elements of parapets shall be designed
by the following equation: through 6-19C
6.5.14 Design Wind Loads on Solid Freestanding Walls and Solid
Signs. The design wind force for solid freestanding walls and solid
where signs shall be determined by the following formula:
qp = velocity pressure evaluated at the top of the parapet
GCp = external pressure coefficient from Figs. 6-1 1 through
6-17 where
GCp; = internal pressure coefficient from Fig. 6-5, based on the qj, = the velocity pressure evaluated at height h (defined in Fig.
porosity of the parapet envelope 6-20) using exposure defined in Section 6.5.6.4.1
Two load cases shall be considered. Load Case A shall consist of G = gust-effect factor from Section 6.5.8
applying the applicable positive wall pressure from Fig. 6-1 1A or C = net force coefficient from Fig. 6-20
Fig. 6-17 to the front surface of the parapet while applying the A, = the gross area of the solid freestanding wall or solid sign, in
applicable negative edge or corner zone roof pressure from Figs. 6- ft2 (m2)
11 through 6- 17 to the back surface. Load Case B shall consist of
applying the applicable positive wall pressure from Fig. 6-1 1A or 6.5.15 Design Wind Loads on Other Structures. The design
Fig. 6-17 to the back of the parapet surface, and applying the wind force for other structures shall be determined by the follow-
applicable negative wall pressure from Fig. 6-1 l A or Fig. 6-17 to the
ing equation:
front surface. Edge and corner zones shall be arranged as shown in
Figs. 6-1 1 through 6-17. GCp shall be determined for appropriate
roof angle and effective wind area from Figs. 6-1 1 through 6- 17. If where
internal pressure is present, both load cases should be evaluated q, = velocity pressure evaluated at height z of the centroid of
under positive and negative internal pressure. area A using exposure defined in Section 6.5.6.3
I6 .5.13 Design Wind Loads on Open Buildings with Monoslope, G = gust-effect factor from Section 6.5.8
C j = force coefficients from Figs. 6-21 through 6-23
Pitched, or Troughed Roofs.
A = projected areanormal to the wind except where C is spec-
6. 5.13.1 General. ified for the actual surface area, ft2 (m2)

Minimum Design Loads for Buildings and Other Structures


6.5.15.1 Rooftop Structures and Equipment for Buildings 7. Response characteristics of the wind tunnel instrumentation
with h < 60 ft (18.3 m). The force on rooftop structures and are consistent with the required measurements.
equipment with A less than (0.1B h) located on buildings with
h 5 60 ft (18.3 m) shall be determined from Eq. 6-28, increased 6.6.3 Dynamic Response. Tests for the purpose of determining
by a factor of 1.9. The factor shall be permitted to be reduced the dynamic response of a building or other structure shall be in
linearly from 1.9 to 1.0 as the value of A is increased from accordance with Section 6.6.2. The structural model and associ-
ated analysis shall account for mass distribution, stiffness, and
(O.1Bh) to (Bh).
damping.

6.6.4 Limitations.
6.6 METHOD 3-WIND TUNNEL PROCEDURE 6.6.4.1 Limitations on Wind Speeds. Variation of basic wind
6.6.1 Scope. Wind tunnel tests shall be used where required by speeds with direction shall not be permitted unless the analysis
Section 6.5.2. Wind tunnel testing shall be permitted in lieu of for wind speeds conforms to the requirements of Section 6.5.4.2.
Methods 1 and 2 for any building or structure.
6.6.2 Test Conditions. Wind tunnel tests, or similar tests em-
ploying fluids other than air, used for the determination of design
6.6.5 Wind-Borne Debris. Glazing in buildings in wind-borne I
debris regions shall be protected in accordance with Section 6.5.9.3.
wind loads for any building or other structure, shall be conducted
in accordance with this section. Tests for the determination of
mean and fluctuating forces and pressures shall meet all of the 6.7 CONSENSUS STANDARDS AND
following conditions: OTHER REFERENCED DOCUMENTS
1. The natural atmospheric boundary layer has been modeled This section lists the consensus standards and other documents
to account for the variation of wind speed with height. which are adopted by reference within this chapter:
2. The relevant macro- (integral) length and micro-length ASTM
scales of the longitudinal component of atmospheric tur- ASTM International
bulence are modeled to approximately the same scale as 100 Barr Harbor Drive
that used to model the building or structure. West Conshohocken, PA 19428-2959
3. The modeled building or other structure and surrounding ASTM El886
structures and topography are geometrically similar to their Section 6.5.9.3
full-scale counterparts, except that, for low-rise buildings Standard Test Method for Performance of Exterior
meeting the requirements of Section 6.5.1, tests shall be Windows, Curtain Walls, Doors and Storm
permitted for the modeled building in a single exposure site Shutters Impacted by Missile(s) and Exposed to
as defined in Section 6.5.6.3. Cyclic Pressure Differentials, 2002.
4. The projected area of the modeled building or other structure
and surroundings is less than 8 percent of the test section ASTM El996
cross-sectional area unless correction is made for blockage. Section 6.5.9.3
Standard Specification for Performance of Exterior
5. The longitudinal pressure gradient in the wind tunnel test Windows, Curtain Walls, Doors and Storm
section is accounted for. Shutters Impacted by Windborne Debris in
6. Reynolds number effects on pressures and forces are mini- Hurricanes, 2003.
mized.

ASCE 7-05
This page intentionally left blank.

Minimum Design Loads for Buildings and Other Structures


FIGURE 6-1 BASIC WIND SPEED

ASCE 7-05
11O(49) 120(54) Hawaii V mph (rnls)
105 (47)
Puerto Rico 145 (65j
Guam 170 (76)
Virgin Islands 145 (65)
American Samoa 125 (56)
Notes:
1. Values are nominal design 3-second gust wind speeds in miles per hour
(rnls) at 33 ft (10 m) above ground for Exposure C category.
2. Linear interpolation between wind contours is permitted.
3. Islands and coastal areas outside the last contour shall use the last wind
speed contour of the coastal area.
4. Mountainous terrain, gorges, ocean promontories, and special wind
regions shall be examined for unusual wind conditions.

FIGURE 6-1 continued


BASIC WIND SPEED

Minimum Design Loads for Buildings and Other Structures


-..... - .
j$!jii.$ Special Wind Region
;:;:::;:;:>
1. Values are nominal design 3-second gust wind
speeds in miles per hour (mls)at 33 ft (10 m)
above ground for Exposure C category.
2. Linear interpolation between wind contours
is permitted.
3. Islands and coastal areas outside the last
contour shall use the last wind speed
contour of the coastal area.
4. Mountainous terrain, gorges, ocean
1IO(49) 120(55) promontories, and special wind regions shall
be examined for unusual wind conditions.
FIGURE 6-1A BASIC WIND SPEED-WESTERN GULF OF MEXICO HURRICANE COASTLINE
Minimum Design Loads for Buildings and Other Structures
ASCE 7-05
Main Wind Force Resisting System - Method 1 h I60 ft.
Figure 6-2 Design Wind Pressures
I Walls & Roofs
Enclosed Buildings

Notes
1 Pressures shown are appl~edto the hor~zontaland vert~calprojections, for exposure B, at h=30 f l ( 9 l n ~ )1=1, 0, and K,, = 1 0 Adjust to
other c o n d ~ t ~ o uslngs Equat~on6 - 1
2 The load patterns shown shall be appl~edto each comer of the bulldlng In turn as the reference corner (See Flgure 6-10)
3 For the deslgn of the long~tudlnalMWFRS use 0 = 0, and locate the zone EIF, GIH boundary at the m~d-lengthof the bulldlng
4 Load cases 1 and 2 must be checked for 25" < 0 5 45' Load case 2 at 25' 1s prov~dedonly for lnterpolatlon between 25' to 30'
5 Plus and mlnus slgns slgnlfy pressures actlng toward and away from the projected surfaces, respectively
6 For roof slopes other than those shown, h e a r lnterpolatlon 1s pernutted
7 The total hor~zontalload shall not be less than that deternlrned by assunllng p, = 0 In zones B & D
8 The zone pressures represent the following
Hor~zontalpressure zones Sun1 of the wlndward and leeward net (sun1 of Internal and external) pressures on vert~calprojectlon of
-

A - End zone of wall C - Interlor zone of wall


B - End zone of roof D - Interlor zone of roof
Vert~calpressure zones Net (sun1 of Internal and external) pressures on hor~zontalprojectlon of
-

E - End zone of w~ndwardroof G - Interlor zone of w~ndwardroof


F - End zone of leeward roof H - Interlor zone of leeward roof
9 Where zone E or G falls on a roof overhang on the wlndward s ~ d ofe the bulldmg, use EOHand GOHfor the pressure on the hor~zontal
projectlon of the overhang Overhangs on the leeward and s ~ d edges shall have the b a s ~ czone pressure appl~ed
10 Notat~on
a 10 percent of least hor~zontaldlmens~onor 0 4h, wh~chever1s smaller, but not less than e~ther4% of least hor~zontaldlmens~on or 3
ft (0 9 n ~ )
h Mean roof helght, In feet (meters), except that eave helght shall be used for roof angles < l o o 0
Angle of plane of roof from hor~zontal,In degrees

Minimum Design Loads for Buildings and Other Structures


Unit Conversions-1.0 ft = 0.3048 m; 1.0 psf = 0.0479 kN/m2

38 ASCE 7-05
1 Main Wind Force Resisting Svstem - Method 1 1 h I 60 ft.
I
Figure 6-2 (cont'd) Design Wind Pressures
Walls & Roofs
Enclosed Buildings

Simplified Design Wind Pressure, Ps30 (psf) (Exposure B at h = 30 ft., K,, = 1.0, with I = 1.0)

I 1- 1
Zones
I
I Basic Wind

Speed
Roof

Angle
Horizontal Pressures Vertical Pressures Overhangs

E F G H EOH GOH
-29.7 -13.1 -32.7
1 -16.9 1 -20.7 1 -41.7 1

Unit Conversions-1.0 ft = 0.3048 m; 1.0 psf = 0.0479 k ~ / m ~

Minimum Design Loads for Buildings and Other Structures 39


ASCE 7-05
Interior Zones Corner Zones
Roofs - Zone 21Walls - Zone 5

1. Pressures shown are applied nomlal to the surface, for exposure B, at h = 30 ft (9.ln1), 1 = 1.0, and K,, = 1.0. Adjust to other
conditions using Equation 6-2.
2. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
3. For hip roofs with 6 1;:25', Zone 3 shall be treated as Zone 2.
4. For effective wind areas between those given, value may be interpolated, otherwise use the value associated with the lower
effective wind area.
5. Notation:
a: 10 percent of least horizontal dimension or 0.4h, whichever is smaller, but not less than either 4 % of least horizontal
dimension or 3 ft (0.9 n ~ ) .
h: Mean roof height, in feet (meters), except that eave height shall be used for roof angles <loo .
6: Angle of plane of roof from horizontal, in degrees.

Minimum Design Loads for Buildings and Other Structures 41


Net Design Wind Pressure, Pnea0(psf) {Exposure B a f h = 30 f t with I = l.0and K2t = 1.0)

Unit Conversions - 1.0 ft = 0.3048 m; 1.0 psf = 0.0479 kN/mz

ASCE 7-05
Net Design Wind Pressure, pnet3~(psf) (Exposure B at h = 30 ft. with I = 1.0 and KZt= 1.0)

Unit Conversions - 1.0 ft = 0.3048 m; 1.0 psf = 0.0479 kN/m2

Minimum Design Loads for Buildings and Other Structures 43


Walls & Roofs

Adjustment Factor
for Building Height and Exposure, h

Unit Conversions - 1.0 ft = 0.3048 m; 1.0 sf = 0.0929 m2; 1.0 psf = 0.0479 kN/m

ASCE 7-05
Topographic Factor, Ka - Method 2 I
Figure 6-4 I

ESCARPMENT 2-D RIDGE OR 3-0


AXISYMMETRICAL HILL

Notes:
1. For values of H/Lh, x/Lh and z/Lh other than those shown, linear interpolation is permitted.
2. For H/Lh > 0.5, assume H/Lh = 0.5 for evaluating KI and substitute 2H for Lh for evaluating K2 and K3.
3. Multipliers are based on the assumption that wind approaches the hill or escarpment along the direction
of maximum slope.
4. Notation:
H:Height of hill or escarpment relative to the upwind terrain, in feet (meters).
Lh: Distance upwind of crest to where the difference in ground elevation is half the height of
hill or escarpment, in feet (meters).
K,: Factor to account for shape of topographic feature and maximum speed-up effect.
KZ: Factor to account for reduction in speed-up with distance upwind or downwind of crest.
K3: Factor to account for reduction in speed-up with height above local terrain.
x: Distance (upwind or downwind) from the crest to the building site, in feet (meters).
z: Height above local ground level, in feet (meters).
P: Horizontal attenuation factor.
Y Height attenuation factor.

Minimum Design Loads for Buildings and Other Structures


Topographic Factor, Kfi - Method 2
I
Figure 6-4 (cont'd)

E~uations:

K, = ( I + K1 K 2 IC312

K1 determined from table below


1x1
Kz =(I --)
PLh

K~ = e-'FJLh

Parameters for Speed-Up Over Hills and Escarpments

K14HL3 P
Hill Shape B Exposure D 7 Upwind Downwind
C of Crest of Crest
2-dimensional ridges
(or valleys with negative 1.30 1.45 1.55 3 1.5 1.5
H in K1/(H/Lh)
2-dimensional escarpments 0.75 0.85 0.95 2.5 1.5
4
3-dimensional axisym. hili 0.95 1.05 1.15 4 1.5
1.5

ASCE 7-05
Main Wind Force Res. Sys. I Comp and Clad. - Method 2 All Heights
Figure 6-5
I
Internal Pressure Coefficient, GCpi Walls & Roofs
Enclosed, Partially Enclosed, and Open Buildings

Enclosure Classification WP~


Open Buildings 0.00

Partially Enclosed Buildings +0.55

-0.55
Enclosed Buildings +O. 18

-0.18

Notes:
I . Plus and minus signs signify pressures acting toward and
away from the internal surfaces, respectively.
2. Values of GC,; shall be used with q, or qh as specified in 6.5.12.
3. Two cases shall be considered to determine the critical
load requirements for the appropriate condition:
(i) a positive value of GCPiapplied to all internal surfaces
fii) a negative value of GCpiapplied to all internal surfaces

Minimum Design Loads for Buildings and Other Structures


Main Wind Force Resisting System - Method 2 All Heights
Figure 6-6
I External Pressure Coefficients, Cp Walls & Roofs
Enclosed, Partially Enclosed Buildings
B qzG

WlND
r
qzGcp
L
PLAN ELEVATION

GABLE, HIP ROOF

WIND
f
1
-E
qzGC.

PLAN ELEVATION ELEVATION

MONOSLOPE ROOF (NOTE 4)

WlND fl l GCp
-
4 z Ccp

L-i
PLAN ELEVATION

MANSARD ROOF (NOTE [o

ASCE 7-05
Main Wind Force Resisting System - Method 2 All Heights
Figure 6-6 (con't) I
External Pressure Coefficients, Cp Walls & Roofs
Enclosed, Partially Enclosed Buildings
Wall Pressure Coefficients, Cp
Surface LIB C, Use With
Windward Wall All values 0.8 q~
0- 1 -0.5
qh
Leeward Wall 2 -0.3
24 -0.2
Side Wall All values -0.7 qh

Roof Pressure Coefficients, C,, for use with qh


Windward Leeward
Wid Angle, 0 (degrees) Angle, 0 (degrees)
Direction 35 45 260# 10 15 220
h/L 1 10 [ 15 ] 20 25 30
Normal '-0.7 ' -0.5 ' -0.3 -0.2 -0.2 0.0* 0.01 8 -0'3
50.25 -0.18 0.0* 0.2 0.3 0.3 0.4 0.4
to -0.9 -0.7 -0.4 -0.3 -0.2 -0.2 O.O* -OS O"
ridge for 0.5 -0.18 -0.18 0.0" 0.2 0.2 -'" 0.01 0 -0.7 -0.6
-0.6
0.3 0.4 ,
0 2 lo0 -1,3** -1.0 -0.7 -0.5 -0.3
0.2
21.0 -0.18-0.18-0.18 O.O* 0.2 *
Horiz distance from CP *Value is provided for
Normal windward edge interpolation purposes.
to < 0.5 0 tohi2 -0.9, -0.18
ridge for h/2 to h -0.9, -0.18 **Value can be reduced linearly with area
8<10 hto2h -0.5, -0.18 over which it is applicable as follows
and > 2h -0.3, -0.18
.
Parallel 0 to hi2 -1.3**, -0.18 Area (sq ft) Reduction Factor
< 100 (9.3 sq m) 1. O
to ridge
for all 0
2 1.0
;. hi2
-0'7' -" 200 (23.2 sq m 0.9 -
i)
0.8
Notes: ' 2 1000 (92.9 sq
1 .Plus and minus signs signifL pressures acting toward and away from the surfaces, respectively.
2. Linear interpolation is permitted for values of L/B. WL and Q other than shown. Interpolation shall only
be carried out between values of the same sign. Where no value of the same sign is given, assume 0.0
for interpolation purposes.
3. Where two values of C, are listed, this indicates that the windward roof slope is subjected to either positive
or negative pressures and the roof structure shall be designed for both conditions. Interpolation for
intermediate ratios of hiL in this case shall only be carried out between C, values of like sign.
4. For monoslope roofs, entire roof surface is either a windward or leeward surface.
5. For flexible buildings use appropriate Gfas determined by Section 6.5.8.
6. Refer to Figure 6-7 for domes and Figure 6-8 for arched roofs.
7. Notation:
B: Horizontal dimension of building, in feet (meter), measured normal to wind direction.
L: Horizontal dimension of building, in fcet (meter), mcasurcd parallel to wind direction.
h: Mean roof height in feet (meters): except that eave height shall be used for 8 2 10 degrees.
z: Height above ground, in feet (meters).
G: Gust effect factor.
q,qh: Velocity pressure, in pounds per square foot (N/m2), evaluated at respective height.
8: Angle of plane of roof from horizontal, in degrees.
8. For mansard roofs, the top horizontal surface and leeward inclined surface shall be treated as
leeward surfaces from the table.
9. Except for MWFRS's at the roof consisting of moment resisting frames, the total horizontal shear shall
not be less than that determined by neglecting wind forces on roof surfaces.
#For roof slopes greater than SO0, use C, = 0.8

Minimum Design Loads for Buildings and Other Structures 49


Main Wind Porce Resisting System - Method 2 All Heights
Figure 6-7 I External Pressure Coefficients, Cp.-.o
Domed Roofs
L
Enclosed, Partially Enclosed Buildings and Structures
?r/*~t:~
C D
4 B

+0.8
+0,6

+0.4

P
0 to2
u-
s 0.0
-a 42
8
0 -0.4
E
7"
a. 0.8
-

8
-1.0
$ 2
U1 -1A

-1.6

-1.8

0 0.1 0.2 0.3 0.4 0.5


Ratio of Rise to Diameter, flD
External Pressure Coefficients for Domes with a Circular Base.
Notes: (Adapted from Eurocode, 1995)
1. Two load cases shall be considered:
Case A. C, values between A and B and between B and C shall be determined by linear
interpolation along arcs on the dome parallel to the wind direction;
Case B. C, shall be the constant value of A for 6 1 25 degrees, and shall be determined by linear
interpolation from 25 degrees to B and from B to C.
2. Values denote C, to be used with q @ * ~where h D + f is the height at the top of the dome.
3. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
4. C, is constant on the dome surface for arcs of circles perpendicular to the wind direction; for
example, the arc passing through B-B-B and all arcs parallel to B-B-B.
5. For values of h a between those listed on the graph curves, linear interpolation shall be permitted.
6. 0 = 0 degrees on dome springline, 0 = 90 degrees at dome center top point. f is memured
from springline to top.
7. The total horizontal shear shall not be less than that determined by neglecting w~ndforces on
roof surfaces.
8. For flD values less than 0.05, use Figure 6-6.

ASCE 7-05
Main Wind Force Res. Sys. I Comp and Clad. - Method 2 All Heights
Figure 6-8
1
External Pressure CwfMents, Cp Arched Roofs
Enclosed, Partially Enclosed Buildings and Structures

Conditions Rise-to-span C~
ratio, r Windward Center Leeward

quarter half quarter


0 < r < 0.2 -0.9 -0.7 - r -0.5

Roof on elevated structure 0.2Ir<0.3* 13-0.3 -0.7 - r -0.5

0.3 2 r 2 0.6 2.75r - 0.7 -0.7 -0.5


-r
Roof springing from ground level 0 < r S 0.6 1.4r -0.7 - r -0.5

*When the rise-to-spn ratio is 0.2 2 r 2 0.3, alternate coefficients given by 6r - 2.1 shall also be used
for the windward quarter.

Notes:
1. Values listed are for the determination of average loads on main wind force resisting systems.
2. Plus and minus signs signify pressures acting toward and away from the surfaces, respectively.
3. For wind directed parallel to the axis of the arch, use pressure coefficients from Fig. 6-6 with
wind directed parallel to ridge.
4. For components and cladding: (1) At roof perimeter, use the external pressure coefficients in Fig.
6-1 1 with 8 based on spring-line slope and (2) for remaining roof areas, use external pressure
coefficients of this table multiplied by 0.87.

II

Minimum Design Loads for Buildings and Other Structures

Вам также может понравиться