Вы находитесь на странице: 1из 4

DIgSILENT Project:

PowerFactory
2017 SP3 Date: 10/25/2017

Harmonics Calculation Balanced, positive sequence Busbars/Terminals


Nominal Frequency 50.00 Hz Output Frequency 50.00 Hz Calculate HD and THD Based on rated voltage/current

Grid: CLUSTERS System Stage: CLUSTERS Study Case: Study Case Annex: / 1
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
Single Busbar(1)
PLAT-1 LV 0.41 1.00 0.00 1.00 1.07 4.74 7.52
Single Busbar(10)
PLAT-9 LV 0.41 0.95 0.00 0.95 1.01 3.52 5.82
Single Busbar(11)
PLAT-8 LV 0.41 0.98 0.00 0.99 1.06 4.88 7.32
Single Busbar(15)
PLAT-14 LV 0.41 0.97 0.00 0.97 1.01 1.78 3.75
Single Busbar(16)
PLAT-4 LV 0.41 1.00 0.00 1.00 1.03 1.69 3.43
Single Busbar(17)
PLAT-12 LV 0.41 0.98 0.00 0.98 1.02 1.83 3.80
Single Busbar(2)
PLAT-6_LV 0.41 1.01 0.00 1.01 1.07 3.26 5.43
Single Busbar(3)
PLAT-7 LV 0.41 1.01 0.00 1.01 1.09 5.13 7.87
Single Busbar(4)
PLAT-2 LV 0.41 1.00 0.00 1.00 1.06 3.39 5.60
Single Busbar(5)
PLAT-11 LV 0.41 1.00 0.00 1.00 1.03 1.70 3.47
Single Busbar(6)
PLAT-15_LV 0.41 0.97 0.00 0.97 1.01 2.08 4.06
Single Busbar(7)
PLAT-5_LV 0.41 1.00 0.00 1.00 1.04 2.39 4.67
Single Busbar(8)
L6 LV 0.41 0.94 0.00 0.95 1.00 3.42 5.74
Single Busbar(9)
PLAT-10 LV 0.41 0.99 0.00 0.99 1.06 4.87 7.34
CLS-55_1
3.30 1.01 0.00 1.01 1.04 1.75 3.35
CLS-55_2
3.30 1.01 0.00 1.01 1.04 1.89 3.53
CLS-57_1
3.30 1.02 0.00 1.02 1.06 3.03 4.75
CLS-57_2
3.30 1.02 0.00 1.02 1.07 3.29 5.07
CLS-58_1
3.30 1.01 0.00 1.01 1.04 1.37 2.77
CLS-58_2
3.30 1.01 0.00 1.01 1.04 1.48 2.93
CLS-59_1
3.30 1.01 0.00 1.01 1.04 1.37 2.77
CLS-59_2
3.30 1.01 0.00 1.01 1.04 1.48 2.93
CLS-60_1
3.30 0.99 0.00 0.99 1.02 1.50 3.14
CLS-60_2
3.30 1.02 0.00 1.02 1.05 1.65 3.28
CLS-62_1
3.30 1.00 0.00 1.00 1.06 3.99 5.98
CLS-62_2
3.30 1.00 0.00 1.00 1.06 4.35 6.39
CLS-63_1
3.30 0.99 0.00 1.01 1.06 2.44 4.24
CLS-63_2
3.30 1.01 0.00 1.01 1.06 2.70 4.56
LV_CLS-55
0.41 1.01 0.00 1.01 1.04 1.70 3.24
LV_CLS-57
0.41 0.99 0.00 1.00 1.04 2.87 4.60
LV_CLS-58
Grid: CLUSTERS System Stage: CLUSTERS Study Case: Study Case Annex: / 2
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
0.41 1.02 0.00 1.02 1.04 1.33 2.68
LV_CLS-59
0.41 1.02 0.00 1.02 1.04 1.33 2.68
LV_CLS-60(1)
0.41 1.00 0.00 1.00 1.03 1.46 3.04
LV_CLS-62
0.41 1.00 0.00 1.00 1.06 3.88 5.79
LV_CLS-63
0.41 0.99 0.00 1.02 1.06 2.37 4.11
DIgSILENT Project:
PowerFactory
2017 SP3 Date: 10/25/2017

Harmonics Calculation Balanced, positive sequence Busbars/Terminals


Nominal Frequency 50.00 Hz Output Frequency 50.00 Hz Calculate HD and THD Based on rated voltage/current

Grid: TRANSCO GRID System Stage: TRANSCO GRID Study Case: Study Case Annex: / 3
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
Double Busbar
AWBU220S_BB1 220.00 0.95 0.00 0.95 1.00 1.85 4.86
AWBU220S_BB2 220.00 0.95 0.00 0.95 1.00 1.85 4.86
Single Busbar with Tie(1)
ADBU33SN_A 33.00 0.99 0.00 0.99 1.01 0.86 2.37
ADBU33SN_B 33.00 0.99 0.00 0.99 1.01 0.86 2.37
Single Busbar with Tie(10)
MSWG-4401_A 0.41 1.00 0.00 1.00 1.04 1.49 3.44
MSWG-4402_B 0.41 1.00 0.00 1.00 1.04 1.49 3.44
Single Busbar with Tie(11)
HSWG-4301-02_A 3.30 0.99 0.00 0.99 1.03 1.34 3.11
HSWG-4301-02_B 3.30 0.99 0.00 0.99 1.03 1.33 3.11
Single Busbar with Tie(12)
MSWG-4401-01_B 0.41 1.00 0.00 1.00 1.03 1.29 2.98
MSWG-4405-01_A 0.41 1.00 0.00 1.00 1.03 1.29 2.99
Single Busbar with Tie(2)
HWSG-4301-01_A 11.00 0.99 0.00 0.99 1.03 1.54 3.58
HWSG-4301-01_B 11.00 0.99 0.00 0.99 1.03 1.54 3.58
Single Busbar with Tie(3)
12-30-HSWG-4303 33.00 0.99 0.00 0.99 1.02 1.44 2.99
12-30-HSWG-4303 33.00 0.99 0.00 0.99 1.02 1.44 2.99
Single Busbar with Tie(4)
12-30-HSWG-4304 33.00 0.99 0.00 0.99 1.02 1.44 2.99
12-30-HSWG-4304 33.00 0.99 0.00 0.99 1.02 1.44 2.99
Single Busbar with Tie(5)
12-30-HSWG-4305 3.30 0.99 0.00 0.99 1.02 1.31 2.72
12-30-HSWG-4305 3.30 1.00 0.00 1.00 1.03 1.37 2.83
Single Busbar with Tie(6)
12-30-MSWG-4408 0.41 1.00 0.00 1.00 1.03 1.28 2.64
12-30-MSWG-4408 0.41 1.00 0.00 1.01 1.03 1.34 2.75
Single Busbar with Tie(7)
12-30-MSWG-4409 0.41 1.00 0.00 1.00 1.03 1.28 2.65
12-30-MSWG-4409 0.41 1.01 0.00 1.01 1.03 1.34 2.75
Single Busbar with Tie(8)
12-30-MSWG-4410 0.41 1.00 0.00 1.00 1.03 1.28 2.65
12-30-MSWG-4410 0.41 1.01 0.00 1.01 1.03 1.34 2.76
Single Busbar with Tie(9)
12-30-MSWG-4411 0.69 1.00 0.00 1.00 1.03 1.28 2.65
12-30-MSWG-4411 0.69 1.00 0.00 1.00 1.03 1.34 2.76
Single Busbar with Tie
ADBU33PSN_A 33.00 0.99 0.00 0.99 1.03 1.71 3.98
ADBU33PSN_B 33.00 0.99 0.00 0.99 1.03 1.71 3.98
Single Busbar(1)
WI_CL-61_1 3.30 1.00 0.00 1.00 1.03 1.84 3.49
Single Busbar(2)
WI_CL-61_2 3.30 0.97 0.00 0.97 1.01 1.94 3.68
Single Busbar(3)
WI_CLS-61 0.41 0.97 0.00 0.97 1.01 1.75 3.38
Single Busbar(4)
WI_CL-56_2 3.30 1.00 0.00 1.00 1.04 2.36 4.06
Single Busbar(5)
PLAT-3 0.41 0.95 0.00 0.95 0.99 2.17 4.20
Single Busbar(6)
WI_CL-56_1 3.30 1.00 0.00 1.00 1.04 2.18 3.90
Single Busbar(7)
WI_CLS-56 0.41 1.01 0.00 1.01 1.04 2.12 3.78
AC Terminal_1
6.60 1.00 0.00 1.02 1.50 16.99 49.79
AC Terminal_2
6.60 1.00 0.00 1.06 1.99 34.59 99.19
AC Terminal_3
Grid: TRANSCO GRID System Stage: TRANSCO GRID Study Case: Study Case Annex: / 4
Rated Bus-voltage Distortion
Voltage ( 50.00 Hz) ( 50.00 Hz) RMS Sum ( 50.00 Hz) Total
[kV] [p.u.] [deg] [p.u.] [p.u.] [%] [%]
6.60 1.00 0.00 1.02 1.50 16.99 49.79
AC Terminal_4
6.60 1.00 0.00 1.06 1.99 34.59 99.19
AC Terminal_5
6.60 0.99 0.00 1.00 1.49 16.99 50.42
AC Terminal_6
6.60 1.00 0.00 1.06 1.99 34.59 99.19
DC Terminal_1
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_2
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_3
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_4
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_5
7.50 0.00 0.00 0.00 0.00 0.00 0.00
DC Terminal_6
7.50 0.00 0.00 0.00 0.00 0.00 0.00