Вы находитесь на странице: 1из 9

x process data from the function block

displayed in the tuning window and displays them as a graph.

The sampling period is 1 second and the recording span is 48 minutes.

Display time span

Data axis reducing /

enlarging rate

The process data items acquired from the function block and the corresponding display colors are:

Process variable (PV), calculated output value (CPV), feedback input data (FV) [Cyan]

Setpoint value (SV), switch position (SW) [White]

Manipulated output value (MV) [Magenta]

The acquisition of tuning trend begins when the tuning window is called up and stops when the

tuning window is closed. The reserve function can be used to continue the tuning trend data

acquisition after the tuning window is closed. The maximum number of data can be reserved is 16

per HIS. If more than 16 data are reserved, the oldest data are deleted.

TE33Q4T30-01E

86

YOKOGAWA
Control Drawing Window

The control drawing window displays the function blocks defined

in the control drawing builder and displays the controlling status

and connecting status of that function blocks visually.

Toolbar

Show/hide terminal

names and data

status.

Control drawing

display area

TE33Q4T30-01E

87

YOKOGAWA
Control Drawing Window

The sequence table window can be used to monitor the scan

status of the sequence table and the status of conditions.

Status bar color:

Toolbar

Yellow: Non-executing rule

Green: Condition not satisfied

Red: Condition satisfied

Condition pattern color:

Table display

area

TE33Q4T30-01E

Cyan: Condition not satisfied

Red: Condition satisfied

88

YOKOGAWA
Trend Window

The trend window acquires different types of process data

and displays time-series change in a graph. The maximum

number of trend points can be displayed is 8.

Toolbar

Trend data display area

Numerical data

display area

Status bar

TE33Q4T30-01E

89

YOKOGAWA
Structure of Trend

The trend recording consists of the three layers of the trend

blocks, the trend windows and the trend point windows.

Trend block

Trend group

Trend block 01

TR0001

Trend block 02

TR0002

Trend block 03

TR0003

Trend group 1

TG0101

Trend group 2

TG0102

Trend group 3

TG0103

TG0101

Trend group 16

TG0116
Trend point window

LIC300.PV

3 LIC300.PV

Trend block 50

TR0050

Trend window name

TGbbgg

bb: Block number

gg: Group number

Trend window

1 FIC100.PV

2 TIC200.PV

3 LIC300.PV

Each trend block can

specifies trend type and


sampling period.

Maximum number trend blocks for CS1000 is 8.

TE33Q4T30-01E

90

YOKOGAWA
Trend Data