Вы находитесь на странице: 1из 5

Differences Between Indoor and Maintenance : Maintenance of Indoor

Outdoor Sub Station substation is not easy. It require both time


Capital Cost : The Capital and specialized labor so it is costly while
required to install indoor substation maintenance of outdoor substation is
is very high because a lot of cheap.
buildings are to be manufactured in Distribution Feeder Systems
case of Indoor substation while the Lets take a look at the four most
capital required for outdoor sub common distribution feeder systems
station is small as compare to applied nowdays. There are few other
Indoor sub station. variations, but we will stick to the basic
Civil Work : In case of Indoor ones.
substation, first we have to prepare Its very important to understand why and
building to host larger electrical where each of distribution feeder systems
equipments like Transformers and have to (topologies) are used, because whatever
make cut outs for power cables that are you do (design of secondary substations,
bringing power to the sub station. these performing testing of secondary
requires a lot of civil work and hence switchgears or transformers or planning
increasing time required to install the sub etc.) this would be the very first thing to
station in opposition to this only a small know.
construction work is required in outdoor So, these are the distribution feeder
sub stations. systems well speak about //
Fault Location : Indoor substations are 1. Radial
very compact in arrangement and hence if 2. Parallel feeders
there is any fault then the location of fault 3. Ring main
become very difficult while in outdoor sub 4. Meshed systems
stations the equipments are placed at 1. Radial
different locations so the fault can be Many distribution systems operate using a
sensed easily. radial feeder system. A typical radial
Future Expansion : In Indoor sub feeder system is shown schematically in
stations the buildings are constructed Figure 2. Radial feeders are the simplest
according to the size of present and least expensive, both to construct and
transformer so if in future we want to for their protection system.
increase the rating of sub station then we This advantage however is offset by the
have to demolish or make some civil difficulty of maintaining supply in the
works in the building to host new event of a fault occurring in the feeder.
transformer while in outdoor substations A fault would result in the loss of supply
transformers are placed outside so they to a number of customers until the fault
may be replaced by just increasing the area is located and cleared. The next level of
of fencing. reliability is given by a parallel feeder
Safety : Indoor substations are more system.
safe as they restrict the entry of animals or
any unauthorized person near the
transformer while outdoor substations are
not much safe.
Appearance : Indoor sub stations looks
good because there is not and electrical
equipment that is visible from outside
while in outdoor sub stations appearance is
not very good.
3. Ring main distribution systems. For all the power
A similar level of system reliability to that system operations, substations are
of the parallel arrangement can be required for their course of action.
achieved by using ring main feeders. This Substations are congregation of electrical
usually results from the growth of load equipment through which consumers get
supplied by a parallel feeder where the supply of electrical power from generating
cabling has been installed along different stations. By varying the voltage levels or
routes. These are most common in urban frequency or any other aspects, the
and industrial environments. required electrical quantity can be altered
Whilst the start and finish ends of the ring in substations to provide quality power to
are at the same location, power is delivered
consumers
by both pathways of the ring into
Based on the application of substations,
substations located around the ring.
they are classified into different types:
Should a fault occur on a feeder cable at
Generation substation, Indoor substation,
any point around the ring the faulty Outdoor substation, Pole mounted
section may be isolated by the operation substation, Switching substation,
of the protecting circuit breakers, at the Transmission substation, Converter
same time maintaining supply to all substation and Distribution substation. In
rare cases like wind farm power generation
substations on the ring. system, multiple hydroelectric and thermal
In typical urban / suburban ring main power plants one can observe the collector
arrangements, the open ring is operated substation which is used for transferring
manually and loss of supply restored by power from multiple turbines into one
manual switching. transmission unit.
The substation is an assembly of the
following major electrical equipments:
Electrical Power transformers
Instrument transformers
Conductors& Insulators
Isolators
Bus bars
Lightning arresters
Circuit breakers
Relays
Capacitor banks and miscellaneous
Figure 4 A ring main feeder system
equipment
Current practice is to use distribution
Electrical Power Transformer
automation, where operation and supply
restoration in the feeder rings is done
automatically by centrally controlled
supervisory systems.
This gives the advantages of ring main
systems as line voltage drops are reduced
at the various load substations there is a
firm supply (i.e. an alternative path is
available if the primary one fails) to each
load substation.
Equipment for substations :-
The power system is a constituent Electrical Power transformer
of power generation, transmission and
A static electrical machine used for copper) and that allows the flow of
transforming power from one circuit to electric charge is called conductor.
another circuit without changing frequency
Conductors permit free movement of the
is termed as Power transformer. The
transformers are generally used to step flow of electrons through them. These are
down or step up the voltage levels of a used for the transmission of power or
system for transmission and generation electrical energy from one place
purpose. These transformers are classified (generating station) to another place
into different types based on their design,
utilization purpose, installation methods, (consumer point where power is
and so on. consumed by the loads) through
Instrument Transformers: substations. Conductors are of different
types and mostly aluminum conductors
are preferred in practical power systems.
Insulators
The metal which does not allow free
movement of electrons or electric charge
Instrument transformers is called as an insulator. Hence, insulators
The current and voltage transformers are resist electricity with their high resisting
together called as the property. There are different types of
Instrument transformers.
insulators such as suspension type, strain
Current Transformer
Current transformer is used for the type, stray type, shackle, pin type and so
measurement of the alternating current by on. A few types of insulators are shown in
taking samples of the higher currents of the above figure. Insulators are used for
the system. These reduced samples are in insulation purpose while erecting electric
accurate proportions with the actual high
poles with conductors to avoid short
currents of the system. These are used for
installation and maintenance of the current circuit and for other insulation
relays in substations for protection purpose requirements.
which are normally have low-current Isolators
ratings for their operation. Isolator is a manually operated
Potential Transformer mechanical switch that isolates the faulty
Potential transformer is quite similar to the section or the section of a conductor or a
current transformer, but it is used for part of a circuit of substation meant for
taking samples of high voltages of a repair from a healthy section in order to
system for providing low-voltage to the
avoid occurrence of more severe faults.
relays of protection system and also to the
Hence, it is also called as a disconnector or
low-rating meters for voltage
measurement. From this low-voltage disconnecting switch. There are different
measurement, the actual systems high types of isolators used for different
voltage can be calculated without applications such as single-break isolator,
measuring high voltages directly to avoid double-break isolator, bus isolator, line
the cost of the measurement system. isolator, etc.
Conductors Bus bars
The material or object that obeys the The conductor carrying current and having
multiple numbers of incoming and
electrical property conductance (mostly
outgoing line connections can be called as
made of metals such as aluminum and
bus bar, which is commonly used in Capacitor banks
substations. These are classified into A Capacitor bank is a set of many identical
different types like single bus, double bus capacitors connected in series or parallel
and ring bus. within a enclosure and is used for the
Lightening Arresters power factor correction and basic
The substation equipments such as protection of substation.These capacitor
conductors, transformers, etc., are always banks are acts as a source of reactive
erected outdoor. Whenever light surges power, and thus, the phase difference
occur then, a high-voltage pass through between voltage and current can be
these electrical components causing reduced by the capacitor banks. They will
damage to them (either temporary or increase the ripple current capacity of the
permanent damage based on the amount of supply. It avoids undesirable
voltage surge). Therefore, to avoid this characteristics in the power system. It is
difficulty, lightening arresters are placed to the most economical method for
pass the entire lightening surges to earth. maintaining power factor and of correction
There are other arresters which are used to of the power lag problems.
ground the switching surges called as The electric power can be transmitted
surge arresters. either by means of d.c. or a.c. Each
Circuit Breakers system has its own merits and demerits.
For the protection of substation and its 1. D.C. transmission.
components from the over currents or over For some years past, the transmission of
load due to short circuit or any other fault electric power by d.c. has been receiving
the faulty section is disconnected from the the active consideration of engineers due
healthy section either manually or to its numerous advantages.
automatically. If once the fault is rectified,
then again the original circuit can be Advantages. The high voltage d.c.
rebuilt by manually or automatically. transmission has the following
Different types of circuit breakers are advantages over high voltage a.c.
designed based on different criteria and transmission :
usage. But in general mostly used circuit 1. It requires only two conductors as
breakers are Oil circuit breaker, Air circuit compared to three for a.c.
breaker, SF6 circuit breaker, Vacuum transmission.
Circuit Breaker, and so on. 2. There is no inductance,
Relays capacitance, phase displacement
Relays are used for disconnecting the and surge problems in d.c.
circuits by manual or automatic operation. transmission.
Relay consists of the coil which is excited 3. Due to the absence of inductance,
or energized and such that making the the voltage drop in a d.c.
contacts of relay closed activates the relay transmission line is less than the
to break or make the circuit connection. a.c. line for the same load and
There are different types of relays such as sending end voltage. For this
over current relays, definite time over reason, a d.c. transmission line has
current relays, voltage relays, auxiliary better voltage regulation.
relays, reclosing relays, solid state relays,
4. There is no skin effect in a d.c.
directional relays,inverse time over current
system. Therefore, entire cross-
relays, microcontroller relays, etc. The
above figure shows some basic relays and section of the line conductor
their operation. is utilized.
5. For the same working voltage, the
potential stress on the insulation is
less in case of d.c. system than that 4. An a.c. line has capacitance.
in a.c. system. Therefore, a d.c. Therefore, there is a continuous
line requires less insulation. loss of power due to charging
6. A d.c. line has less corona loss and current even when the line is
reduced interference with open.
communication circuits.
7. The high voltage d.c. transmission
is free from the dielectric losses,
particularly in the case of cables.
8. In d.c. transmission, there are no
stability problems
and synchronizing difficulties.
Disadvantages
1. Electric power cannot be
generated at high d.c. voltage due
to commutation problems.
2. The d.c. voltage cannot be stepped
up for transmission of power at
high voltages.
3. The d.c. switches and circuit
breakers have their own
limitations.
2. A.C. transmission.
Now-a-days, electrical energy is almost
exclusively generated, transmitted and
distributed in the form of a.c.
Advantages
1. The power can be generated at
high voltages.
2. The maintenance of a.c. sub-
stations is easy and cheaper.
3. The a.c. voltage can be stepped up
or stepped down by transformers
with ease and efficiency. This
permits to transmit power at high
voltages and distribute it at safe
potentials.
Disadvantages
1. An a.c. line requires more copper
than a d.c. line.
2. The construction of a.c.
transmission line is more
complicated than a d.c.
transmission line.
3. Due to skin effect in the a.c.
system, the effective resistance of
the line is increased.

Вам также может понравиться