Technical Datasheet Offer number: 27099587 Attachment

________________________________________________________________________________
Siemens H-Pos: 100; 3EP6 360-3PJ43-2DR1-Z X07 D91 X81
System Information
Nominal System Voltage (Un) 400 kV
Highest Voltage of Equipment (Um) 420 kV
Basic Insulation Level (BIL) 1 425 kV
Maximum altitude of installation (a.s.l.) 1000 m
Neutral system earthing solid
Power Frequency 50 Hz
Ambient temperature range -40 ... 55 C
Electrical data
Applied Standard IEC 60099-4
Rated voltage (Ur) 360 kV
Maximum continuous operating voltage (Uc / MCOV) 288 kV
Nominal discharge current (In, 8/20 s) 20 kA
Line discharge class 4
Long duration impulse current withstand (2 ms) 1 600 A
High current impulse withstand (4/10 s) 100 kA
Rated short circuit current (0,2 s) 65,0 kA
Maximum residual voltage at :
20 kA 1/2 s 1 139 kV
5 kA 8/20 s 810 kV
10 kA 8/20 s 861 kV
20 kA 8/20 s 947 kV
40 kA 8/20 s 1 033 kV
500 A 30/60 s 698 kV
1 kA 30/60 s 715 kV
2 kA 30/60 s 749 kV
Temporary overvoltage for 1 s 387 kV
Temporary overvoltage for 10 s 360 kV
Energy discharge capability - thermal 10,0 kJ/kVr
Energy discharge capability - impulse 6,50 kJ/kVr
1
Switching Impulse withstand voltage (250/2500 s, wet) 2 190 kV
2
Switching Impulse withstand voltage (250/2500 s, wet) 1 450 kV
1
Lightning Impulse withstand voltage (1,2/50 s) 3 348 kV
2
Lightning Impulse withstand voltage (1,2/50 s) 2 579 kV
Mechanical data
Height (H) 6 579 mm
Minimum creepage distance 23 004 mm
Number of units 3
Weight (G) 490 kg
Color of housing brown
Specified long-term load SLL (Fstat) 1090 N
Specified short-term load SSL (Fdyn) 2740 N
Grading ring diameter (d) 1 800 mm
Distance from grading ring to top (l) 1 200 mm
Drawing number E T HP AR 27099587.0100
Accessories
Line terminal Bolt 30 x 80 mm, A2
Ground terminal Insulated, 240x240 mm
Accessory 1 Earth lead 0,45 m / 35 mm

Accessory 2 3EX6031 Line clamp DIN/NEMA


Accessory 6 The Arrester Condition Monitor (ACM) in the advanced version reveals the
arrester conditions by indicating the following operating parameters:

- Total leakage current (peak value) in turns with


- Number of (surge) impulses,
_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 1/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
- Resistive (leakage) current visualized by a "traffic light" system.

The "traffic light" visualisation of the resistive current is based on a


3rd-harmonic-evaluation of the leakage current considering the specific
surge arrester configuarion. Moreover, with a harmonic compensation in
the system voltage and considering the influence of the temperature of
the measurement the resistive current value is rectified.

General technical data:

- Measuring frequency range: 50 or 60 Hz


- Ambient temperature range: -40C to +60C

- Power supply: Solar panel


- Unlimited application field: latitude < 60
- Operational readiness after deep discharge of the solar battery: <(>
<<)> 2
days, placed in direct sunlight < 3 hours

Leakage current measurement:


- Measuring range of total leakage current (peak level): 0,15...15 mA
- Measuring range of resistive leakage current (peak level): 25...5000
A

Impulse current measurement:


- Counting threshold: > 50 A
- Surge counting time resolution: 2 Impulse per second
- Measuring range:
- High current (4/10 s): 1...100 kA
- Lightning impulse current (8/20 s): 1...40 kA
- Switching impulse current (30/60 s): 0,25...3 kA
- Long-duration current (T=500...5000 s): 0,2...2,1 kA

The included license key (arrester specific) enables the user to access
the following features, using the free of charge software and a
PC/laptop:
- Leakage current measurement (Itotal und Ires) daily for trend
analysis,
- Detailed Surge data history: date, time, surge current peak value,
equivalent of surge energy.

Memory capacity:
- Detailed surge data history: 448 entries
- Trend analysis data: 2000 (> 5 years)

Sensor/Transceiver data communication:


- Frequency: 2,4 GHz
- Transmitting power: <3 dBm
- Operating range:
- horizontal: up to 50 m
- vertical: up to 50 m

To establish a wireless remote connection between laptop and ACM one


USB-wireless module (3EX5 086) will be needed and has to be ordered
seperately.
1
withstand voltages acc. to IEC 60099-4: sum of the withstand voltages per empty housing
2
withstand voltages, arrester complete: measured on the mounted arrester, incl. grading ring

AL: N
ECCN: N

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 2/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
Siemens H-Pos: 200; 3EP6 240-3PJ42-2TR1-Z H1E X81
System Information
Nominal System Voltage (Un) 275 kV
Highest Voltage of Equipment (Um) 300 kV
Basic Insulation Level (BIL) 1 050 kV
Maximum altitude of installation (a.s.l.) 1000 m
Neutral system earthing solid
Power Frequency 50 Hz
Ambient temperature range -40 ... 55 C
Electrical data
Applied Standard IEC 60099-4
Rated voltage (Ur) 240 kV
Maximum continuous operating voltage (Uc / MCOV) 192 kV
Nominal discharge current (In, 8/20 s) 20 kA
Line discharge class 4
Long duration impulse current withstand (2 ms) 1 600 A
High current impulse withstand (4/10 s) 100 kA
Rated short circuit current (0,2 s) 65,0 kA
Maximum residual voltage at :
20 kA 1/2 s 759 kV
5 kA 8/20 s 540 kV
10 kA 8/20 s 574 kV
20 kA 8/20 s 632 kV
40 kA 8/20 s 689 kV
500 A 30/60 s 465 kV
1 kA 30/60 s 477 kV
2 kA 30/60 s 499 kV
Temporary overvoltage for 1 s 276 kV
Temporary overvoltage for 10 s 258 kV
Energy discharge capability - thermal 10,0 kJ/kVr
Energy discharge capability - impulse 6,50 kJ/kVr
1
Switching Impulse withstand voltage (250/2500 s, wet) 1 344 kV
2
Switching Impulse withstand voltage (250/2500 s, wet) 1 100 kV
1
Lightning Impulse withstand voltage (1,2/50 s) 2 232 kV
2
Lightning Impulse withstand voltage (1,2/50 s) 1 747 kV
Mechanical data
Height (H) 4 384 mm
Minimum creepage distance 15 336 mm
Number of units 2
Weight (G) 451 kg
Color of housing brown
Specified long-term load SLL (Fstat) 1640 N
Specified short-term load SSL (Fdyn) 4100 N
Grading ring diameter (d) 1 200 mm
Distance from grading ring to top (l) 800 mm
Drawing number E T HP AR 27099587.0200
Accessories
Line terminal DIN/NEMA flat 40...50 mm, Al
Ground terminal Insulated, 240x240 mm
Accessory 6 The Arrester Condition Monitor (ACM) in the advanced version reveals the
arrester conditions by indicating the following operating parameters:

- Total leakage current (peak value) in turns with


- Number of (surge) impulses,
- Resistive (leakage) current visualized by a "traffic light" system.

The "traffic light" visualisation of the resistive current is based on a


_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 3/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
3rd-harmonic-evaluation of the leakage current considering the specific
surge arrester configuarion. Moreover, with a harmonic compensation in
the system voltage and considering the influence of the temperature of
the measurement the resistive current value is rectified.

General technical data:

- Measuring frequency range: 50 or 60 Hz


- Ambient temperature range: -40C to +60C

- Power supply: Solar panel


- Unlimited application field: latitude < 60
- Operational readiness after deep discharge of the solar battery: <(>
<<)> 2
days, placed in direct sunlight < 3 hours

Leakage current measurement:


- Measuring range of total leakage current (peak level): 0,15...15 mA
- Measuring range of resistive leakage current (peak level): 25...5000
A

Impulse current measurement:


- Counting threshold: > 50 A
- Surge counting time resolution: 2 Impulse per second
- Measuring range:
- High current (4/10 s): 1...100 kA
- Lightning impulse current (8/20 s): 1...40 kA
- Switching impulse current (30/60 s): 0,25...3 kA
- Long-duration current (T=500...5000 s): 0,2...2,1 kA

The included license key (arrester specific) enables the user to access
the following features, using the free of charge software and a
PC/laptop:
- Leakage current measurement (Itotal und Ires) daily for trend
analysis,
- Detailed Surge data history: date, time, surge current peak value,
equivalent of surge energy.

Memory capacity:
- Detailed surge data history: 448 entries
- Trend analysis data: 2000 (> 5 years)

Sensor/Transceiver data communication:


- Frequency: 2,4 GHz
- Transmitting power: <3 dBm
- Operating range:
- horizontal: up to 50 m
- vertical: up to 50 m

To establish a wireless remote connection between laptop and ACM one


USB-wireless module (3EX5 086) will be needed and has to be ordered
seperately.
1
withstand voltages acc. to IEC 60099-4: sum of the withstand voltages per empty housing
2
withstand voltages, arrester complete: measured on the mounted arrester, incl. grading ring

AL: N
ECCN: N

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 4/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
Siemens H-Pos: 300; 3EP6 132-3PJ41-2DR1-Z X07 D91 X81
System Information
Nominal System Voltage (Un) 132 kV
Highest Voltage of Equipment (Um) 145 kV
Basic Insulation Level (BIL) 650 kV
Maximum altitude of installation (a.s.l.) 1000 m
Neutral system earthing solid
Power Frequency 50 Hz
Ambient temperature range -40 ... 55 C
Electrical data
Applied Standard IEC 60099-4
Rated voltage (Ur) 132 kV
Maximum continuous operating voltage (Uc / MCOV) 106 kV
Nominal discharge current (In, 8/20 s) 20 kA
Line discharge class 4
Long duration impulse current withstand (2 ms) 1 600 A
High current impulse withstand (4/10 s) 100 kA
Rated short circuit current (0,2 s) 65,0 kA
Maximum residual voltage at :
20 kA 1/2 s 413 kV
5 kA 8/20 s 297 kV
10 kA 8/20 s 316 kV
20 kA 8/20 s 347 kV
40 kA 8/20 s 379 kV
500 A 30/60 s 256 kV
1 kA 30/60 s 262 kV
2 kA 30/60 s 275 kV
Temporary overvoltage for 1 s 142 kV
Temporary overvoltage for 10 s 132 kV
Energy discharge capability - thermal 10,0 kJ/kVr
Energy discharge capability - impulse 6,50 kJ/kVr
Power Frequency withstand voltage (1min, wet) 452 kV
Lightning Impulse withstand voltage (1,2/50 s) 1 116 kV
Mechanical data
Height (H) 2 189 mm
Minimum creepage distance 7 668 mm
Number of units 1
Weight (G) 227 kg
Color of housing brown
Specified long-term load SLL (Fstat) 3280 N
Specified short-term load SSL (Fdyn) 8220 N
Drawing number E T HP AR 27099587.0300
Accessories
Line terminal Bolt 30 x 80 mm, A2
Ground terminal Insulated, 240x240 mm
Accessory 1 Earth lead 0,45 m / 35 mm

Accessory 2 3EX6031 Line clamp DIN/NEMA


Accessory 6 The Arrester Condition Monitor (ACM) in the advanced version reveals the
arrester conditions by indicating the following operating parameters:

- Total leakage current (peak value) in turns with


- Number of (surge) impulses,
- Resistive (leakage) current visualized by a "traffic light" system.

The "traffic light" visualisation of the resistive current is based on a


3rd-harmonic-evaluation of the leakage current considering the specific

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 5/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
surge arrester configuarion. Moreover, with a harmonic compensation in
the system voltage and considering the influence of the temperature of
the measurement the resistive current value is rectified.

General technical data:

- Measuring frequency range: 50 or 60 Hz


- Ambient temperature range: -40C to +60C

- Power supply: Solar panel


- Unlimited application field: latitude < 60
- Operational readiness after deep discharge of the solar battery: <(>
<<)> 2
days, placed in direct sunlight < 3 hours

Leakage current measurement:


- Measuring range of total leakage current (peak level): 0,15...15 mA
- Measuring range of resistive leakage current (peak level): 25...5000
A

Impulse current measurement:


- Counting threshold: > 50 A
- Surge counting time resolution: 2 Impulse per second
- Measuring range:
- High current (4/10 s): 1...100 kA
- Lightning impulse current (8/20 s): 1...40 kA
- Switching impulse current (30/60 s): 0,25...3 kA
- Long-duration current (T=500...5000 s): 0,2...2,1 kA

The included license key (arrester specific) enables the user to access
the following features, using the free of charge software and a
PC/laptop:
- Leakage current measurement (Itotal und Ires) daily for trend
analysis,
- Detailed Surge data history: date, time, surge current peak value,
equivalent of surge energy.

Memory capacity:
- Detailed surge data history: 448 entries
- Trend analysis data: 2000 (> 5 years)

Sensor/Transceiver data communication:


- Frequency: 2,4 GHz
- Transmitting power: <3 dBm
- Operating range:
- horizontal: up to 50 m
- vertical: up to 50 m

To establish a wireless remote connection between laptop and ACM one


USB-wireless module (3EX5 086) will be needed and has to be ordered
seperately.

AL: N
ECCN: N

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 6/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
Siemens H-Pos: 400; 3EP5 036-2PH31-1DR1-Z H1E
System Information
Nominal System Voltage (Un) 33,0 kV
Highest Voltage of Equipment (Um) 36,0 kV
Basic Insulation Level (BIL) 200 kV
Maximum altitude of installation (a.s.l.) 1000 m
Neutral system earthing impedance
Power Frequency 50 Hz
Ambient temperature range -40 ... 55 C
Electrical data
Applied Standard IEC 60099-4
Rated voltage (Ur) 36,0 kV
Maximum continuous operating voltage (Uc / MCOV) 28,8 kV
Nominal discharge current (In, 8/20 s) 10 kA
Line discharge class 3
Long duration impulse current withstand (2 ms) 1 100 A
High current impulse withstand (4/10 s) 100 kA
Rated short circuit current (0,2 s) 50,0 kA
Maximum residual voltage at :
10 kA 1/2 s 103 kV
5 kA 8/20 s 84,5 kV
10 kA 8/20 s 89,9 kV
20 kA 8/20 s 99,7 kV
40 kA 8/20 s 113 kV
500 A 30/60 s 71,9 kV
1 kA 30/60 s 73,7 kV
2 kA 30/60 s 77,3 kV
Temporary overvoltage for 1 s 41,4 kV
Temporary overvoltage for 10 s 38,7 kV
Energy discharge capability - thermal 8,00 kJ/kVr
Energy discharge capability - impulse 5,00 kJ/kVr
Power Frequency withstand voltage (1min, wet) 160 kV
Lightning Impulse withstand voltage (1,2/50 s) 375 kV
Mechanical data
Height (H) 764 mm
Minimum creepage distance 1 871 mm
Number of units 1
Weight (G) 37,8 kg
Color of housing brown
Specified long-term load SLL (Fstat) 1040 N
Specified short-term load SSL (Fdyn) 2610 N
Drawing number E T HP AR 27099587.0400
Accessories
Line terminal Bolt 30 x 80 mm, A2

Ground terminal Insulated, 3 holes, PCD 200 - 254


mm(7.87"-10"), A2

AL: N
ECCN: N

_______________________________________________________________________________________________________________
11.12.2015 EM HP AR / 27099587.01 / MA 7/8
Technical Datasheet Offer number: 27099587 Attachment
________________________________________________________________________________
Siemens H-Pos: 500; USB TRANSMITTER 3EX5 086 W. ANTENNA, CPL
USB wireless module is used to establish a wireless connection between
PC/Laptop and ACM-device.

PC/Laptop requirements:
- one free USB-Port;
- system software: Windows XP or Win7
- ACM-software: Siemens Arrester Monitoring System -Service Tool
(provided for free with the USB wireless module).

Wireless connection data:


- Frequency: 2,4 GHz
- transmitting power: <3 dBm
- range (horizontal): up to 50 m
- range (vertical): up to 50 m

The required Siemens-software is for free and it is included in the


delivery of the license key needed to upgrade to ACM-advanced and to
connect to a particular ACM.

AL: N
ECCN: N

_______________________________________________________________________________________________________________