Over the past 45 years, Hawke has built a world-wide reputation in the Hazardous Area and Hostile Environment markets,
with an innovative range of cable connection, termination and barrier products.
The underlying philosophy behind our Corporate Strategy has been a recognition of the fundamental principle that our
products are concerned with safety, in an environment where failure can have catastrophic consequences to human life, the
environment, expensive plant and valuable production - and in situations where the replacement of faulty components is often
difficult.
This philosophy requires an enthusiastic participation in the development of new Safety Standards and Codes of Practice, and a
product development programme which embraces these, together with advances in cable construction and materials. It
requires that our products should be easy to select and install, because these activities are not only expensive but also affect
the safety of the assembly. It requires that we provide informed technical advice, that our staff and customers are thoroughly
trained, and that we have quality systems and a manufacturing plant which ensure Zero Defects. It means that we must
transcend the mere requirements of having the "appropriate certification" and that we exceed the undemanding requirement
that products be "fit for purpose" - whose purpose?
All the products we make (from Fire Barrier Transit systems to Fieldbus Power Supply systems) have a common underlying
theme, which forms the basis of our Product Development Strategy :-
Product Development is an ongoing process, in which Hawke continues to invest heavily, and the cable glands described within
are the culmination of a particularly concentrated effort over recent years.
An example from our new range of cable glands illustrate these principles :-
The new rear sealing system not only meets the new ATEX Directive, but also uses a unique clamping system, giving
higher retention forces than any other similar product on the market. It uses a new thermoset elastomer compound
which provides superb resistance to high and low temperatures, to the ageing effects of Oxygen and Ozone, and
Compression Set. It has the added benefit of being halogen-free, with low smoke and fume emission . . . . but, above all,
it is safe.The system has the versatility to seal the entire range of cable sizes that can be accommodated by a
particular entry size, without the need for special outer seals.This makes the cable gland easier and quicker to use,
with less likelihood of an installer using the wrong seal. It also means easier product selection, and fewer items for our
distributors to keep in stock, which should in turn mean improved stock availability.The cable acceptance range is
marked on the rear nut, affording easier inspectability.
As a company, we have all the obvious targets in terms of On-Time Delivery and Customer Service, Zero Defects, Investment
in Manufacturing Facilities, and in the Training and Development of our People - and we perform to World-Class Standards,
but . . . .
Smarter products
www.ehawke.com
1
Contents
Page No.
Cable Gland Selection Chart 4-6
Smarter products
www.ehawke.com
International
2
Contents
Page No.
7.0 CE Marking 49
7.1 EMC, Electromagnetic Compatibility Directive 49
7.2 Low Voltage Directive 49
8.0 Certification/Listing/Approvals 49
Smarter products
www.ehawke.com
International
3
Cable Gland Selection Chart
Colour
Coded Cable Gland Certification Ingress
Pictorial View Certification Application/Cable Type Sealing
Catalogue Type Options Protection
Page No.
ATEX
EExd IIC/EExe II
501/421 Indoor/outdoor IP66/67/68 Outer cable
7 II 2 GD
Non-armoured cable Deluge sheath seal
Zone 1, 2, 21 & 22
IEC
ATEX
EExd IIC/EExe II Indoor/outdoor Two outer
8 IP66/67/68
501/423 II 2 GD Non-armoured cable Deluge cable sheath seals
Zone 1, 2, 21 & 22 IEC
ATEX
EExd IIC/EExe II Indoor/outdoor IP66/67/68 Inner and outer
9 501/453/RAC II 2 GD Armoured/braided cable with (Deluge cable sheath seals
Zone 1, 2, 21 & 22 IEC inner and outer sheath option)
ATEX
EExd IIC/EExe II Indoor/outdoor Inner (diaphragm)
IP66/67/68
11 501/453/UNIV II 2 GD Armoured/braided cable with and outer
Deluge
Zone 1, 2, 21 & 22 inner and outer sheath cable sheath seals
IEC
ATEX
EExd IIC/EExe II Indoor/outdoor Individual
IP66/67/68
12 II 2 GD IEC Armoured/braided cable with conductor seal
PSG 553/RAC (Deluge
Zone 1, 2, 21 & 22 inner (optional) and outer sheath option) and outer
cable sheath seal
ATEX
EExd IIC/EExe II
13
Indoor/outdoor IP66/67/68 Inner (compound)
ICG 623 II 2 GD and outer
Non-armoured cable Deluge
Zone 1, 2, 21 & 22 IEC cable sheath seals
ATEX
EExd IIC/EExe II Indoor/outdoor Inner (compound)
IP66/67/68
14 ICG 653/UNIV II 2 GD Armoured/braided cable with and outer
Deluge
Zone 1, 2, 21 & 22 IEC inner (optional) and outer sheath cable sheath seals
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 4
Cable Gland Selection Chart
Colour
Coded Cable Gland Certification Ingress
Pictorial View Certification Application/Cable Type Sealing
Catalogue Type Options Protection
Page No.
ATEX
EExd IIC/EExe II Indoor/outdoor IP66/67/68 Individual
17 SB 474 II 2 GD IEC Individual conductors, Deluge conductor
Zone 1, 2, 21 & 22 conduit system seal
ATEX
EExd IIC/EExe II Indoor/outdoor Individual
18 CSB 656 II 2 GD Individual conductors, IP66/67/68 conductor
conduit system Deluge (compound) seal
Zone 1, 2, 21 & 22 IEC
ATEX
501/453 IEC Indoor/outdoor
EExd IIC/EExe II IP66/67/68 Inner and outer
ICG 653 Armoured/braided cable with
19 II 2 GD (Deluge cable sheath seals
153 inner and outer sheath
Zone 1, 2, 21 & 22 option)
Sizes G, H & J
ATEX
EExe II Indoor/outdoor IP66
351/RAC Armoured/braided cable with Outer cable
20 II 2 GD (Deluge
inner (optional) and outer sheath sheath seal
Zone 1, 2, 21 & 22 IEC option)
Indoor/outdoor
EN 50262 IP66 Outer cable
24 151/RAC IEC Armoured/braided cable with
(Deluge sheath seal
inner (optional) and
option)
outer sheath
EN 50262 Indoor/outdoor
IP66/67 Inner (diaphragm)
25 153/RAC IEC Armoured/braided cable
(Deluge and outer
with inner and outer
option) cable sheath seal
cable sheath
EN 50262 Indoor/outdoor
IP66/67/68 Outer cable
27 114 IEC Non-armoured cable,
Deluge sheath seal
conduit system
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 5
Cable Gland Selection Chart
Colour
Coded Cable Gland Certification Ingress
Pictorial View Certification Application/Cable Type Sealing
Catalogue Type Options Protection
Page No.
UL/cUL
Indoor/outdoor IP66/67/68 Inner (compound)
31 Class 1 Division 1
753 Armored Marine (Deluge and outer cable
Groups
Shipboard cable option) jacket seals
A, B, C & D C
33 - 36 Accessories
33 - 36 Accessories
33 - 36 Accessories
ATEX
Adaptors/ EExd IIC/EExe II
Indoor/outdoor IP66/67/68
37 Reducers II 2 GD
Deluge
Zone 1, 2, 21 & 22
IEC
Cable Gland
38 Variations
& Options
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 6
ATEX 15.0mm
Metric
Entry
'G' Approx
Entry Thread
'B'
501/421
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the
customer's responsibility to ensure that the
or publication of the document may be made and no
article may be manufactured or assembled in accordance
International
product is suitable for their application. with information contained in the document without prior
written consent of the owner. 7
ATEX
15.0mm 'G' Approx
Metric
Entry
Entry Thread
'B'
501/423
Flameproof and Increased Safety
Materials & Finishes All Metric entry threads are 1.5mm pitch medium fit.
Hawke cable glands are manufactured as All dimensions in millimetres (except*).
standard in brass. Sizes Os and O are available with an M16 thread size. For O size with M16 thread,
Alternative materials and plating are available. the maximum cable outer sheath diameter is 10.9mm.
Assembly instruction data sheet No. A.I. 306. For sizes Os to F.
Assembly instruction data sheet No. A.I. 334. For sizes G to J.
Technical Data
Flameproof EExd and Increased Safety EExe.
Alternative thread sizes available. See page 38
II 2 GD
Accessories including locknuts, sealing washers, shakeproof washers, shrouds,
BASEEFA Certificate No. BAS 01 ATEX 2071X.
adaptors and reducers available. See pages 33 - 37
For sizes Os - F.
BASEEFA Certificate No. BAS 01 ATEX 2295X.
For sizes G - J.
Suitable for use in Zone 1, Zone 2, ATEX Cable Gland
Zone 21 and Zone 22. Ordering Examples
Suitable for use in Gas Groups IIA, IIB and IIC. Cable Gland Type/Size/Thread
Construction and test standards
EN 50014, EN 50018, EN 50019 and e.g. 501/423/C/M32
EN 50281-1-1. 501/423/C/1" NPT
IEC 60079-0, IEC 60079-1 and IEC 60079-7.
IP66, IP67 and IP68 ingress protection to
Cable Gland with Alternative Seal (S)
IEC 60529, EN 60529 and NEMA 4X.
DTS01 deluge protection certified by ITS. e.g. 501/423/C/M32/S
Additional deluge protection seal also available. 501/423/C/1" NPT/S
Operating temperature range
-60C to +80C as standard.
Option available, Exd IIC, Exe II.
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 8
ATEX 15.0mm 'G' Approx
Metric Armour/Braid
Entry 'C'
Entry Thread
'A'
501/453/RAC
'B'
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 9
ATEX 15.0mm
Metric
Entry
Lead Sheath
Bond
'G' Approx
Armour/Braid
'C'
Entry Thread
501/453/RAC/L
'A'
'B'
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 10
ATEX 15.0mm
Metric
Entry
Deluge
Boot
'G' Approx
Diaphragm
Seal
Armour/Braid
'C'
Entry Thread
501/453/UNIV
'A'
'B'
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the
customer's responsibility to ensure that the
or publication of the document may be made and no
article may be manufactured or assembled in accordance
International
product is suitable for their application. with information contained in the document without prior
written consent of the owner. 11
ATEX 15.0mm
Metric
Entry
'G' Approx
Armour/Braid
'C'
Entry Thread
PSG 553/RAC
'B'
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 12
ATEX
15.0mm 'G' Approx
Metric Inspectable
Entry Compound
Entry Thread
'D'
ICG 623
'E'
'B'
Flameproof and Increased Safety
Function Construction and design standards All Metric entry threads are 1.5mm pitch
EN 50014, EN 50018, EN 50019 and medium fit.
Provides a barrier seal between the individual
EN 50281-1-1. All dimensions in millimetres (except*).
insulated cores within the cable and prevent
IEC 60079-0, IEC 60079-1 and Two part sealing compound and
entry of the products of an explosion into
IEC 60079-7. assembly instructions are supplied with
the cable.
IP66, IP67 and IP68 ingress protection the cable gland.
Assembly of the cable gland compresses
to IEC 60529, EN 60529 and NEMA 4X. Assembly instruction data sheet
and distributes the compound evenly to
DTS01 deluge tested by ITS. No. A.I. 305.
effect a barrier seal at the point of entry
Operating temperature range
into the enclosure. Alternative thread sizes available. See page 38
-60C to +80C as standard.
The compound chamber may be
Option available, Exd IIC, Exe II. Accessories including locknuts,
seperated from the compound to sealing washers, shakeproof washers,
ensure that the chamber has been shrouds, adaptors and reducers available.
effectively filled. See pages 33 - 37
Provides a high pullout resistance and ATEX Cable Gland
low smoke and fume, zero halogen
seal onto the cables outer sheath. Ordering Examples
Cable Gland Type/Size/Thread
Materials & Finishes e.g. ICG 623/C/M32
Hawke cable glands are manufactured ICG 623/C/1" NPT
as standard in brass.
Alternative materials and plating are Cable Gland with Alternative Seal (S)
available.
e.g. ICG 623/C/M32/S
ICG 623/C/1" NPT/S
Technical Data
Flameproof EExd and Increased Safety EExe.
II 2 GD
BASEEFA Certificate No. BAS 01 ATEX 2079X.
Suitable for use in Zone 1, Zone 2,
Zone 21 and Zone 22.
Suitable for use in Gas Groups IIA, IIB and IIC.
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the
customer's responsibility to ensure that the
or publication of the document may be made and no
article may be manufactured or assembled in accordance
International
product is suitable for their application. with information contained in the document without prior
written consent of the owner. 13
ATEX
15.0mm 'G' Approx
Inspectable Deluge Armour/Braid
Metric Compound Boot 'C'
Entry
Entry Thread
'D'
'E'
ICG 653/UNIV
'B'
Flameproof and Increased Safety
International
errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the article may be manufactured or assembled in accordance
product is suitable for their application. with information contained in the document without prior
written consent of the owner. 14
ATEX
15.0mm 'G' Approx
Entry Thread
ICG 653/UNIV/L
'E'
'D'
'B'
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Metric
Entry
'G' Approx
Entry Thread
Entry Thread
501/414
Female
'B'
Male
Flameproof and Increased Safety
Materials & Finishes All Metric entry threads are 1.5mm pitch medium fit.
All dimensions in millimetres (except*).
Hawke cable glands are manufactured as
Assembly instruction data sheet No. A.I. 310.
standard in brass.
Alternative materials and plating are available.
Alternative thread sizes available. See page 38
Accessories including locknuts, sealing washers, shakeproof washers,
Technical Data adaptors and reducers available. See pages 33 - 37
Flameproof EExd and Increased Safety EExe.
II 2 GD
BASEEFA Certificate No. BAS 01 ATEX 2076X.
Suitable for use in Zone 1, Zone 2,
Zone 21 and Zone 22.
ATEX Cable Gland
Suitable for use in Gas Groups IIA, IIB and IIC. Ordering Examples
Construction and test standards Cable Gland Type/Size/Male Thread/Female Thread
EN 50014, EN 50018, EN 50019 and
EN 50281-1-1. e.g. 501/414/C/M32/M32
IEC 60079-0, IEC 60079-1 and IEC 60079-7. 501/414/C/1" NPT/M32
IP66, IP67 and IP68 ingress protection to
IEC 60529 and EN 60529. Cable Gland with Alternative Seal (S)
Operating temperature range
-60C to +80C as standard. e.g. 501/414/C/M32/M32/S
501/414/C/1" NPT/M32/S
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Metric
Entry
'G' Approx
Entry Thread
Entry Thread
SB 474
Female
Male
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 17
ATEX 15.0mm
Metric
Entry
Inspectable
Compound
'G' Approx
Allen Grub Screw
2mm A/F A-C
2.5mm A/F C2-F
Entry Thread
Entry Thread
'D'
Female
'E'
Male
CSB 656
Flameproof and Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
'B'
J M100 4" 75.0 91.6 88.0 104.5 # 121
G M80 -
62.8 74.0 140 75.0 89.5 # 121
Entry Thread
'D'
'E'
'B'
Metric
Entry
'G' Approx
Armour/Braid
'C'
Entry Thread
'A'
351/RAC
'B'
Increased Safety
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 20
15.0mm 'G' Approx
Metric
Entry
Entry Thread
'B'
121
Industrial general purpose
Technical Data
All Metric entry threads are 1.5mm pitch medium fit.
Construction and test standards All dimensions in millimetres (except*).
EN 50262. BS 6121 Part 1. Type A2. Sizes Os and O are available with an M16 thread size. For O size with M16 thread,
IP66, IP67 and IP68 ingress protection to the maximum cable outer sheath diameter is 10.9mm.
IEC 60529 and EN60529. Assembly instruction data sheet No. A.I. 307. For sizes Os to F.
DTS01 deluge protection certified by ITS. Assembly instruction data sheet No. A.I. 326. For sizes G to J.
Operating temperature range
-60C to +80C as standard.
Alternative entry thread types and sizes available. See page 38
Accessories including locknuts, sealing washers, shakeproof washers, shrouds,
adaptors and reducers available. See pages 33 - 37
Cable Gland
Ordering Examples
Cable Gland Type/Size/Thread
e.g. 121/C/M32
121/C/1" NPT
Cable Gland with Alternative Seal (S)
e.g. 121/C/M32/S
121/C/1" NPT/S
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 21
15.0mm 'G' Approx
Metric
Entry
Entry Thread
'B'
123
Industrial general purpose
Technical Data All Metric entry threads are 1.5mm pitch medium fit.
Construction and test standards All dimensions in millimetres (except*).
EN 50262. BS 6121 Part 1. Type A2. Sizes Os and O are available with an M16 thread size. For O size with M16 thread,
IP66, IP67 and IP68 ingress protection to the maximum cable outer sheath diameter is 10.9mm.
IEC 60529 and EN 60529. Assembly instruction data sheet No. A.I. 306. For sizes Os to F.
DTS01 deluge protection certified by ITS. Assembly instruction data sheet No. A.I. 334. For sizes G to J.
Additional deluge protection seal also available.
Operating temperature range
Alternative thread sizes available. See page 38
-60C to +80C as standard.
Accessories including locknuts, sealing washers, shakeproof washers, shrouds,
adaptors and reducers available. See pages 33 - 37
Cable Gland
Ordering Examples
Cable Gland Type/Size/Thread
e.g. 123/C/M32
123/C/1" NPT
Cable Gland with Alternative Seal (S)
e.g. 123/C/M32/S
123/C/1" NPT/S
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 22
15.0mm 'G' Approx
Metric Armour/Braid
Entry 'C'
Entry Thread
150/RAC
'B'
'A'
Industrial general purpose
Cable Gland
Ordering Examples
Cable Gland Type/Size/Thread
e.g. 150/RAC/C/M32
150/RAC/C/1" NPT
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 23
ATEX 15.0mm
Metric
Entry
'G' Approx
Armour/Braid
'C'
Entry Thread
'A'
151/RAC
'B'
Industrial general purpose
e.g. 151/RAC/C/M32
151/RAC/C/1" NPT
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 24
15.0mm 'G' Approx
Diaphragm Armour/Braid
Metric
Seal 'C'
Entry
Entry Thread
'A'
153/RAC
'B'
Industrial general purpose
e.g. 153/RAC/C/M32
153/RAC/C/1" NPT
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 25
15.0mm 'G' Approx
Entry Thread
153/RAC/L
'A'
'B'
Industrial general purpose
e.g. 153/RAC/C/M32/L
153/RAC/C/1" NPT/L
e.g. 153/RAC/C/M32/K
153/RAC/C/1" NPT/K
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 26
15.0mm 'G' Approx
Metric
Entry
Entry Thread
Entry Thread
114
Female
'B'
Male
Industrial general purpose
Cable Gland
Ordering Examples
Cable Gland Type/Size/Male Thread/Female Thread
e.g. 114/C/M32/M32
114/C/1" NPT/M32
e.g. 114/C/M32/M32/S
114/C/1" NPT/M32/S
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 27
Armor Stop 'G' Approx
Entry Thread
701
'E'
'B'
Industrial general purpose
Technical Data
Construction and test standards
UL 514B. UL Listing pending. Cable Gland
IP66, IP67 and IP68 ingress protection to Ordering Example
IEC 60529, EN60529 and NEMA 4X. Cable Gland Type/Size/Thread
DTS01 deluge tested by ITS.
e.g. 701/C/1" NPT
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the
customer's responsibility to ensure that the
or publication of the document may be made and no
article may be manufactured or assembled in accordance
International
product is suitable for their application. with information contained in the document without prior
written consent of the owner. 28
'G' Approx
Entry Thread
'D'
'E'
711
'B'
Explosion Proof
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the
customer's responsibility to ensure that the
or publication of the document may be made and no
article may be manufactured or assembled in accordance
International
product is suitable for their application. with information contained in the document without prior
written consent of the owner. 29
'G' Approx
Compound
C
Entry Thread
710
'D'
'E'
'B'
Explosion Proof
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
Entry Thread
753
'D'
'E'
'B'
Explosion Proof
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
www.ehawke.com
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 31
'G' Approx
Entry Thread
'D'
755
'E'
'B'
Explosion Proof
Os " 0.35" 0.39" 6 0.22" 0.47" 0.036"/0.049" 0.008"/0.013" 0.008"/0.031" 3.19" 0.94" 1.09"
Function O " 0.35" 0.39" 6 0.37" 0.63" 0.036"/0.049" 0.008"/0.013" 0.008"/0.031" 3.19" 0.94" 1.09"
Provides a barrier seal between A " 0.43" 0.49" 10 0.49" 0.81" 0.036"/0.049" 0.008"/0.013" 0.008"/0.031" 3.27" 1.18" 1.36"
the individual insulated cores B " 0.64" 0.72" 21 0.66" 1.02" 0.049"/0.062" 0.008"/0.017" 0.008"/0.039" 3.43" 1.42" 1.64"
within the cable and prevent
C 1" 0.86" 0.97" 42 0.87" 1.30" 0.062"/0.078" 0.008"/0.017" 0.008"/0.055" 3.62" 1.81" 2.09"
entry of the products of an
C2 1" 1.04" 1.16" 60 1.10" 1.61" 0.062"/0.078" 0.012"/0.017" 0.008"/0.070" 3.90" 2.17" 2.50"
explosion into the cable.
Assembly of the cable gland D 2" 1.46" 1.64" 80 1.42" 2.07" 0.078"/0.098" 0.016"/0.017" 0.008"/0.070" 4.45" 2.56" 2.96"
compresses and distributes the E 2" 1.88" 2.11" 100 1.81" 2.57" 0.098" 0.016"/0.017" 0.008"/0.070" 4.61" 3.15" 3.64"
compound evenly to effect a F 3" 2.32" 2.61" 120 2.24" 3.07" 0.098" 0.016"/0.017" 0.008"/0.070" 4.72" 3.74" 4.31"
barrier seal at the point of entry
into the enclosure.
* Metric entry threads are available, please ask for details.
Deluge protection option available.
Two part sealing compound and assembly instructions are
Provides a high pullout resistance supplied with the cable gland.
and low smoke and fume, zero
Assembly instruction data sheet No. A.I. 319. For sizes O to F.
halogen seal onto the cables outer
Assembly instruction data sheet No. A.I. 340. For size H.
sheath.
Alternative thread sizes available. See page 38
Materials & Finishes Accessories including locknuts, sealing washers, shakeproof washers, shrouds,
Hawke cable glands are manufactured adaptors and reducers available. See pages 33 - 37
as standard in brass with nickel plated
entry.
Alternative materials and plating are
available.
Cable Gland
Technical Data
UL Listing pending for use in Class 1, Ordering Example
Division 2, Gas Groups A, B, C and D. Cable Gland Type/Size/Thread
UL Listing pending for use in Class 1,
Zone 1 and Zone 2, e.g. 755/C/1" NPT
Gas Groups IIA, IIB and IIC.
Construction and test standards
UL 2225 and UL 2279.
IP66, IP67 and IP68 ingress protection
to IEC 60529, EN60529 and NEMA 4X.
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 33
Earth Tags
and Cable Gland Accessories
Locknuts
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 34
PVC and LSFZH Shrouds
Insulated Adaptor Types Cable Gland
478, 378 and 178 Accessories
Flameproof, Increased Safety and Industrial
O/Os O/Os
A A
B B
C C
LSFZH Shrouds C2
D
C2
D
E E
F F
G
Ordering Examples
H Shroud Type/Size
J
e.g. PVC Shroud/C
Materials & Finishes LSFZH Shroud/C
Hawke PVC shrouds are supplied in
Application black as standard. Hawke Low smoke
Outdoor or Indoor use. and fume zero halogen (LSFZH) shrouds
For fitting over cable glands when additional are supplied in black as standard. Other
environmental and corrosion protection is required. colours available, details on request.
Metric
Entry Thread
Female
Thread
* Flats Corners
Male
'Z'
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 36
ATEX
Adaptors and
Reducers
Type 476 & 376
Adaptor Reducer
Flameproof and Increased Safety
M20
M25
Metric
M32
M40
M50
M63
Female Thread
M75
"
"
1"
NPT *
1"
1"
2"
2"
3"
All Metric entry threads are 1.5mm pitch medium fit.
Suitable for use in Gas Groups
+ Alternative entry thread types and sizes available. Materials & Finishes IIA, IIB and IIC.
Hawke components are manufactured
Construction and test standards
Application/Function as standard in brass.
EN 50014, EN 50018, EN 50019 and
Provides a means of connection between Alternative materials and plating
EN 50281-1-1.
the equipment and cable glands with are available.
IEC 60079-0, IEC 60079-1 and
dissimilar thread sizes or types.
* Only metric female thread types are Technical Data IEC 60079-7.
Option available,
permitted by the ATEX Directive for Flameproof EExd and Increased Safety EExe.
BR-Exd IIC/Exe II.
flameproof EExd applications. II 2 GD IP66.
Flameproof adaptors/reducers are BASEEFA Certificate No. BAS 01 ATEX 2249X.
permitted with female thread types other BASEEFA Certificate No. BAS 01 ATEX 2241U ATEX Adaptor/Reducer
than metric, providing the equipment has (see*). (Component approval only). Ordering Examples
been certified for use with the BASEEFA Certificate No. BAS 01 ATEX 2242X 476/Adaptor or Reducer/Male Thread
adaptor/reducer. (EExe II only). Size/Female Thread Size.
EExe adaptors/reducers have no ATEX Suitable for use in Zone 1, Zone 2, e.g. 476/R/M25/M20
thread type restriction. Zone 21 and Zone 22. 476/A/M25/" NPT.
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
NON-STANDARD SIZE
SELECTION TABLE NPT Threads
Entry Thread Type For gland sizes D, E and F,
the maximum inner sheath size is reduced
Size
Metric NPT GLAND TYPE
Ref.
O M16 - Diaphragm Inner Seal
Size
A M16 " Compression Inner Seal Compound Inner Seal
Ref.
B - 1" No Innner Seal
C - 1" Max. Inner Sheath Diameter Max. Inner Sheath Diameter
C2 - 1" D 42.3 N/A
D - 1" E 54.3 N/A
E - 2" F 65.3 65.3
F - 2"
To the best of our knowledge the information All copyright reserved-Hawke Cable Glands Ltd 2001.
contained in this brochure, is accurate at the This document and all copyright therein is the property of:
Smarter products
time of going to print and the company reserves Hawke International a trading name of Hawke Cable Glands
the right to improve or modify any product Ltd (A member of the McKechnie Group of Companies).
illustrated without notification. The company is Copyright Condition: This document shall be used only for
unable to accept liability for any inaccuracies, the purpose for which it is provided and no reproduction
www.ehawke.com errors or omissions that may exist. It is the or publication of the document may be made and no
customer's responsibility to ensure that the
product is suitable for their application.
article may be manufactured or assembled in accordance
with information contained in the document without prior International
written consent of the owner. 38
Technical Data
The intent of this section of the catalogue is to identify important features that may be useful in the selection and installation
of explosion protected electrical equipment.
There are numerous different regulations, codes, guidelines and standards for the design, installation and maintenance of
electrical and non-electrical systems for use in potentially explosive atmospheres. The type of operational facility, geographic
location, operator practice, local and national legislation, authority having jurisdiction etc. will determine many of the design and
installation rules permitted. A fixed or floating petroleum facility located offshore, for example, would not be designed or
classified in the same manner as an onshore petrochemical facility.
An area in which an explosive atmosphere is not likely to occur in normal operation and if it
Zone 2 occurs, it will exist only for a short time.
(Rough Guide: Less than 10 hours / year)
Smarter products
www.ehawke.com
39
Technical Data
Combustible Dusts
An area in which combustible dust, as a cloud, is present continuously or frequently, during normal
Zone 20 operation, in sufficient quantity to be capable of producing an explosive concentration of
combustible dust in a mixture with air
An area, in which combustible dust, as a cloud, is occasionally present during normal operation, in a
Zone 21 sufficient quantity to be capable of producing an explosive concentration of combustible dust in a
mixture with air.
An area, in which combustible dust, as a cloud, may occur infrequently and persist for only a short
Zone 22 period, or in which accumulations of layers of combustible dust may give rise to an explosive
concentration of combustible dust in mixture with air.
IEC 60079-10 - Electrical Apparatus for Explosive Gas Atmospheres, Classification of Hazardous Areas
PR EN 50281-3 - Classification of areas where dusts are, or may be, present
Institute of Petroleum - Model Code of Safe Practice in the Petroleum Industry, Part 15: Area Classification
Code for Petroleum Installations, IP 15
3.3 Design and Installation of Electrical Systems for Hazardous (Classified) Areas
There are numerous regulation codes, guidelines and standards for the design, selection and installation of
electrical installation in potentially explosive atmospheres. These requirements are in addition to the
requirements for installations in non-hazardous areas.
There are several types of protection, i.e. construction techniques, available for electrical apparatus in hazardous
areas. The type of protection permitted will depend upon the applicable installation codes and rules to be
adopted.
Smarter products
www.ehawke.com
40
Technical Data
3.5 Apparatus selection according to the ignition temperature of the gas or vapour
The equipment must be selected so that its maximum surface temperature will not reach the ignition temperature of
any gas or vapour that may be present.
If the marking of the electrical apparatus does not include an ambient temperature range, the apparatus is only for use
within an ambient temperature range from -20C to +40C.
For further information regarding data for flammable gases and vapours, see PD IEC 60079-20.
Smarter products
www.ehawke.com
41
Technical Data
Smarter products
www.ehawke.com
42
Technical Data
To ensure compliance with the Directive, equipment must meet with the essential requirements specified in the
Directive and be marked with the CE marking.
The process of ensuring that equipment complies with the Directive, conformity assessment procedure(s) must be
complied with. These procedures may involve a Notified Body. A Notified body is a body that is independent of the
product manufacturer and assesses conformity of the products and the manufacturer with the Directive. The Notified
Body has to be approved and appointed by its government. EECS is a Notified Body for the ATEX Directive.
Smarter products
www.ehawke.com
43
Technical Data
The Directive classifies equipment into eight categories depending on the equipment's area of use: -
Category M1 - equipment intended for mining use and is required to remain functional in the presence of an
explosive atmosphere.
Category M2 - equipment intended for mining use but is intended to be de-energised in the event of an
explosive atmosphere.
Category 1G - non-mining equipment for use in Zone 0.
In places where potentially explosive atmospheres may occur in such quantities as to endanger the health and
safety of workers, the point of entry must be marked with the sign shown below in accordance with Section II,
Article 7 of the Directive.
Smarter products
www.ehawke.com
44
Technical Data
No cable damage due to Hawke 501/453 Cable damage as found with cable gland designs
Universal diaphragm seal cable gland design. incorporating compression / displacement
seals.
The IEC and CELELEC installation standards, IEC 60079-14 and EN 60079-14 address "cold flow" in Clause 9.1.3.
Smarter products
www.ehawke.com
45
Technical Data
Cable glands may also be designed, tested and certified for use with a particular cable construction type e.g.
for use with trace heating flat form cable types. The cable gland approval certificates, if applicable, will refer to
the appropriate cable type description.
Cable glands may also be designed for use with a particular cable construction and be tested and certified
with the equipment. Reference to these cable gland types will be given in the equipment approval certification
documents, if applicable.
The IEC and CENELEC design, selection and installation standards, IEC 60079-14 and EN 60079-14 offers
guidance on the selection of flameproof cable gland types.
Where cables enter flameproof equipment directly, they should comply with the following: -
a) Application:
an enclosure in Zone 1 or 2, Group IIA or IIB that contains terminals only or an enclosure that does
not contain equipment with an ignition source such as arcing or sparking devices (e.g. relays, contactors,
etc) or equipment that in normal operation will not cause temperatures that can cause ignition.
b) Application:
an enclosure in Zone 1 or 2, Group IIC with an enclosure volume greater than 2-litres, that contains
terminals only or an enclosure that does not contain equipment with an ignition source such as arcing
or sparking devices (e.g. relays, contactors, etc) or equipment that in normal operation will not cause
temperatures that can cause ignition.
Cable Gland Selection:
a certified cable gland suitable for use with the particular type of cable and incorporating a sealing
ring(s) that acts upon the appropriate cable sheath(s), with an uncompressed length of 20mm for
circular cables with a diameter not greater than 20mm and 25mm for circular cables with a diameter
greater than 20mm, is permitted for use.
Smarter products
www.ehawke.com
46
Technical Data
c) Application:
an enclosure that contains equipment with an ignition source such as arcing or sparking devices (e.g.
relays, contactors, etc) or equipment that in normal operation will cause temperatures that can cause
ignition in Zone 2, gas group IIA or IIB
d) Application:
an enclosure that contains equipment with an ignition source such as arcing or sparking devices (e.g.
relays, contactors, etc) or equipment that in normal operation will cause temperatures that can cause
ignition in Zone 1, gas group IIA or IIB and an enclosure volume less than 2-litres.
e) Application:
an enclosure that contains equipment with an ignition source such as arcing or sparking devices (e.g.
relays, contactors, etc) or equipment that in normal operation will cause temperatures that can cause
ignition in Zone 1, gas group IIA or IIB and an enclosure volume greater than 2-litres.
f) Application:
an enclosure that contains equipment with an ignition source such as arcing or sparking devices (e.g.
relays, contactors, etc) or equipment that in normal operation will cause temperatures that can cause
ignition in Zone 1 or 2, gas group IIC.
Smarter products
www.ehawke.com
47
Technical Data
A minimum ingress protection rating of IP54 is required for increased safety equipment. To meet with this
requirement it may be necessary to provide a seal between the cable gland and the equipment, for example,
by the use of a sealing washer or thread sealant. Where cable glands are fitted into non-metallic enclosures,
metallic enclosures with a painted type finish or enclosures with non-threaded clearance holes, additional
ingress and earthing / bonding considerations may be necessary. Please refer to the sealing washer, earthtag,
serrated washer and locknut accessories shown in the catalogue.
Manufacturers type The symbol to indicate The group of When the equipment is
identification, e.g. that the electrical the electrical designed for use in an
catalogue number apparatus corresponds apparatus ambient temperature range
with one or more other than -20 oC to +40 oC,
explosion protection the symbol Ta or Tamb
The group
techniques together with the special
sub-division, if
range of ambient
applicable
Year of Marking to indicate special temperatures must be
certification conditions for safe use marked.
BAS 01 2070 X
Smarter products
www.ehawke.com
48
Technical Data
7.0 CE Marking
The CE Marking is intended to facilitate the free movement of products within the European Union. By affixing CE
marking to products, the manufacturer is making a legal declaration that the product meets with the appropriate
requirements of all relevant European Directives. CE marking only applies to products within the scope of the
Directives. It should not be applied to products if they are outside the scope of the Directives.
Smarter products
www.ehawke.com
49
Technical Data
1 Protected against
objects of 50mm
An object probe, sphere of 50mm
diameter, shall not fully penetrate
1 Protected against
vertically falling
Vertically falling drops shall have no
harmful effects
diameter and water drops
greater
50
2 Protected against
solid foreign
An object probe, sphere of
12.5mm diameter, shall not fully
2 Protected against
vertically falling
Vertically falling drops shall have no
harmful effects when the enclosure
objects of 12.5mm penetrate water drops when is tilted at any angle up to 15 on
12.5 diameter and enclosure tilted up either side of the vertical
greater to 15
3 Protected against
solid foreign
An object probe, sphere of 2.5mm
diameter, shall not penetrate at all
3 Protected against
spraying water
Water sprayed at an angle up to
60 on either side of the vertical
objects of 2.5mm shall have no harmful effects
diameter and
greater
4 Protected against
solid foreign
An object probe, sphere of 1.0mm
diameter, shall not penetrate at all
4 Protected against
splashing water
Water splashed against the
enclosure from any direction shall
objects of 1.0mm have no harmful effects
diameter and
greater
Ingress of dust is not totally Protected against Water projected in jets against the
5 Dust-protected
prevented, but dust shall not
5 water jets enclosure from any direction shall
penetrate in a quantity to interfere have no harmful effects
with satisfactory operation of
apparatus or to impair safety
Smarter products
www.ehawke.com
50
Technical Data
7.0 CE Marking The protection of the enclosure and the equipment inside against external influences or conditions, such as:
mechanical impacts, corrosion, corrosive solvents, solar radiation, icing moisture (e.g. produced by condensation), and
explosive atmospheres, are matters that should be dealt with by the relevant product Standard.
There are additional and supplementary optional letters to the above coding; these designators are A, B, C & D and H,
M, S & W, and further information can be found in the relevant Standard(s).
9.1 Deluge Ingress Protection
On offshore facilities, equipment may be located in areas subject to emergency deluge systems. Equipment
that has been evaluated as certified for use in hazardous areas may not be suitable for use in these locations.
A testing method for electrical equipment to be installed in areas subject to deluge systems, DTS01, has been
prepared by the Explosion and Fire Hazards Group of ERA Technology (now known as ITS) in collaboration
with Shell UK Exploration and Production Ltd.
Testing includes: -
Energising the equipment (where appropriate) for 60 minutes prior to the deluge test, then interrupting
the electrical power at the start of the deluge test and resuming after 60 minutes until the completion of
the deluge test.
Carrying out insulation resistance testing before and after pre-conditioning and after the deluge test,
where applicable.
Carrying out pre-conditioning by exposure to vibration and thermal ageing at 90% relative humidity and
at a temperature 20k above the equipments maximum service temperature and/or at least 80C of any
appropriate seals.
Carrying out deluge test using a deluge chamber fitted with deluge nozzles that apply a salt water
solution deluge pressure within the range of 3.5 bar to 4.5 bar at a water temperature in the range of
5C to 10C for 3-hours.
7.2 LowVoltage Directive 10.0 IECEx Scheme
The objective of the IECEx Scheme is to facilitate international trade in electrical equipment intended for use in
potentially explosive atmospheres by eliminating the need for multiple national certification. The IECEx Scheme
provides a means for manufacturers to obtain Certificates of Conformity that will be accepted at national level in all
participating countries. A Certificate of Conformity may be obtained from any certification body accepted into the
scheme. The objective of the IECEx Scheme is world-wide acceptance of one standard, one certificate, and one mark.
For the IEC scheme to achieve its objective, every applicable national standard will need to be identical to the
corresponding IEC standard. A transition period will be necessary to allow time for participating IECEx Scheme
countries to align their national standards with the IEC standards and work towards national acceptance of IECEx
Certificates of Conformity and the IECEx mark.
Smarter products
www.ehawke.com
51
Technical Data
In the United States of America, hazardous (classified) locations are sub-divided into three Zones or two
Divisions, as follows: -
Zone 1:
Where ignitable concentrations of flammable
gases, vapors or liquids can exist some of the time
under normal operating conditions.
Division 2: Zone 2:
Where ignitable concentrations of flammable Where ignitable concentrations of flammable
gases, vapors or liquids are not likely to exist gases, vapors or liquids are not likely to exist
under normal operating conditions under normal operating conditions.
Division 1:
Where ignitable concentrations of ignitable fibres
and flyings can exist all of the time or some of the
time under normal operating conditions
Division 2:
Where ignitable concentrations of ignitable fibres
and flyings are not likely to exist under normal
operating conditions
Smarter products
www.ehawke.com
52
Technical Data
Equipment listed as classified for use in Class I locations is not necessarily acceptable for Class II locations as
it may not be dust-tight or operate at a safe temperature with a dust covering.
Smarter products
www.ehawke.com
53
Technical Data
11.3 Apparatus selection according to the ignition temperature of the gas or vap
The equipment must be selected so that its maximum surface temperature will not reach the ignition
temperature of any gas or vapor that may be present.
Maximun surface
Temperature class of Ignition temperature
temperature of
electrical apparatus of gas or vapour
electrical apparatus
T1 450C >450C
T2 300C >300C
T2A 280C >280C
T2B 260C >260C
T2C 230C >230C
T2D 215C >215C
T3 200C >200C
T3A 180C >180C
T3B 165C >165C
T3C 160C >160C
T4 135C >135C
T4A 120C >120C
T5 100C >100C
T6 85C >85C
Low ambient conditions require special consideration. Explosion proof of dust ignition proof equipment may
not be suitable for use at temperatures lower than -25C (-13F) unless they are identified for low
temperature service. Unless the equipment is marked otherwise, it is for use only in an ambient temperature
range of -25C (-13F) to +40C (+104F).
Equipment that is approved for Class I and Class II should be marked with the maximum safe operating
temperature.
For information regarding data for flammable gases and vapors, see NFPA 497 and NFPA 325.
Smarter products
www.ehawke.com
54
Technical Data
The grouping of Class I gases and vapors are The grouping of Class II dusts are classified
classified into categories A, B, C and D. into categories E, F, and G.
A E
(typical gas - acetylene) (typical atmospheres containing
combustible metal dusts)
B F
(typical gas - hydrogen) (typical atmospheres containing
coal dusts)
C G
(typical gas - ethylene) (typical atmospheres containing
grain dusts)
D
(typical gas - propane)
ANSI / ISA - S12.12 - Non-incendive Electrical Equipment for use in Class I and II, Division 2 and Class
III, Divisions 1 and 2 Hazardous (Classified) Locations.
ANSI / NFPA 496 - Standard for Purged and Pressurised Enclosures for Electrical Equipment.
ANSI / UL 913 - Intrinsically Safe Apparatus and Associated Apparatus for use in Class I, II and III,
Division 1, Hazardous Locations.
ANSI / UL 698 - Industrial Control Equipment for use in Hazardous (Classified) Locations.
ANSI / UL 2225 - Metal-Clad Cables and Cable-Sealing Fittings for use in Hazardous (Classified)
Locations.
UL 1604 - Electrical Equipment for use in Class I and II, Division 2 and Class III Hazardous
(Classified) Locations.
ANSI / UL 2279 - Electrical Equipment for use in Class I, Zone 0, 1 and 2 Hazardous (Classified)
Locations.
ISA S12.0.01 - Electrical Apparatus for use in Class I, Zone 0, 1 Hazardous (Classified)
Locations, General Requirements.
ISA S12.22.01 - Electrical Apparatus for use in Class I, Zone 1 and 2 Hazardous (Classified)
Locations, Type of Protection - Flameproof 'd'
ISA S12.16.01 - Electrical Apparatus for use in Class I, Zone 1 and 2 Hazardous (Classified)
Locations, Type of Protection - Increased Safety 'e'.
Smarter products
www.ehawke.com
55
Technical Data
Type MC, MV, ITC, PLTC, TC or MI cable with approved termination fittings in accordance with Section
501-4 of the NEC.
Threaded rigid metal conduit, threaded steel intermediate metal conduit.
Non-incendive field wiring using any of the methods suitable for wiring in ordinary locations in
accordance with Section 501-4 of the NEC.
Boxes, fittings and joints need not be explosion-proof except as required by the NEC code.
Smarter products
www.ehawke.com
56
Technical Data
Smarter products
www.ehawke.com
57
Technical Data
The equipment grounding path should be carefully considered when using Shipboard Cables or type TC
cables, as these may not inherently provide a grounding means. The armor of Shipboard Cables should be
grounded but can not be used as the grounding conductor. An appropriate sized grounding conductor should
be included in each cable.
12.5 American Petroleum Institute - Wiring Methods
Class 1, Division 1
The API RP 14F Recommended Practice for the design and installation of electrical systems for fixed and
floating offshore petroleum facilities recommends the following wiring methods for hazardous (classified)
locations.
Type MC-HL metal clad cables as defined in UL 2225.
Armored marine shipboard cable with an overall impervious sheath over the armor, constructed in
accordance with UL 1309, and listed as "Shipboard Cable Marine" by a National Recognised Testing
Laboratory (NRTL). This wiring method is a departure from the NEC.
Type ITC cable that is NRTL - listed for use in Class I, Division 1 locations with a gas / vapor tight
continuous corrugated aluminum sheath and with an overall PVC or other suitable polymeric jacket.
Threaded rigid copper-free aluminum conduit.
Threaded rigid steel, hot dipped galvanized conduit, coated with PVC, or other suitable material, and with
the interior protected by an additional means.
An NRTL approved cable sealing fitting, e.g. barrier type cable gland complying with UL 2225, must be fitted
onto cables where they enter explosion-proof enclosures.
For further information and other wiring methods acceptable for Division 1, refer to Clause 6.4.2.2 of the
API RP14F.
For fitting requirements of cables with multi-conductors, twisted pairs or shielded conductors into explosion
proof equipment. See clause 12.4.1.
Class 1, Division 2
Wiring methods as recommended for use in Division 1.
Type MC cable with a gas / vapour tight continuous corrugated aluminum sheath, an overall PVC or
other suitable polymeric jacket, and grounding conductors in accordance with NEC 250-122.
Non-armored marine shipboard cable, with an overall impervious jacket in accordance with UL 1309 and
listed as "Shipboard Cable Marine" by a NRTL. This wiring method is a departure from the NEC.
HawkeType 710 Additional wiring methods acceptable for Division 2 include type PLTC, ITC, TC and MV cables. It is
Cable Gland
recommended that an overall PVC or other suitable polymeric material jacket is included for these cable
types.
For additional information, refer to Clause 6.4.2.3 of API RP14F.
In Division I locations, all electrical equipment (except intrinsically safe systems and equipment inside purged
enclosures) should be explosion-proof.
In Division 2 locations, the equipment does not need to be explosion-proof, except where necessary to
maintain the integrity of the installation.
Further information on the use of equipment is given in Clause 6.4.7 of API RP14F.
An NRTL approved cable sealing fitting, e.g. barrier type cable gland complying with UL 2225, must be fitted
onto cables where they enter explosion-proof enclosures.
Smarter products
www.ehawke.com
58
Technical Data
For fitting requirements of cables with multi-conductors, twisted pairs or shielded conductors into explosion
proof equipment. See clause 12.4.1.
Class 1, Zones 0, 1 and 2
The API RP 14 FZ, Recommended Practice for the design and installation of electrical systems for fixed and
floating offshore petroleum facilities for unclassified and Class I, Zone 0, Zone 1 and Zone 2 locations,
recommends the following wiring methods for hazardous (classified) locations.
Class 1, Zone 1
Type MC-HL metal clad cables as defined in UL 2225.
Armored marine shipboard cable with an overall impervious sheath over the armor, constructed in
accordance with UL 1309, and listed as "Shipboard Cable Marine" by a National Recognised Testing
Laboratory (NRTL). This wiring method is a departure from the NEC.
Type ITC cable that is NRTL - listed for use in Class 1, Division 1 locations with a gas / vapor tight
continuous corrugated aluminum sheath and with an overall PVC or other suitable polymeric jacket.
Threaded rigid copper-free aluminum conduit.
Threaded rigid steel, hot dipped galvanized conduit, coated with PVC, or other suitable material, and with
the interior protected by an additional means.
Non-armored marine shipboard cable, with an overall impervious jacket in accordance with UL 1309 and
listed as "Shipboard Cable Marine" by a NRTL. This wiring method is a departure from the NEC.
For further information and other wiring methods acceptable for Zone 1, refer to Clause 6.4.2.2 of the API
RP14FZ.
For fitting requirements of cables with multi-conductors, twisted pairs or shielded conductors into explosion
proof equipment. See clause 12.4.1.
Class 1, Zone 2
Wiring methods as recommended for use in Zone 1.
Type MC cable with a gas / vapor tight continuous corrugated aluminum sheath, an overall PVC or other
suitable polymeric jacket, and grounding conductors in accordance with NEC 250-122.
Non-armored marine shipboard cable, with an overall impervious jacket in accordance with UL 1309 and
listed as "Shipboard Cable Marine" by a NRTL. This wiring method is a departure from the NEC.
Additional wiring methods acceptable for Zone 2 include type PLTC, ITC, TC and MV cables. It is
recommended that an overall PVC or other suitable polymeric material jacket is included for these cable
types.
For additional information, refer to Clause 6.4.2.3 of API RP14FZ.
Further information on the use of equipment is given in Clause 6.4.7 of API RP14FZ.
An NRTL approved cable sealing fitting, e.g. barrier type cable gland complying with UL 2225, must be fitted
onto cables where they enter explosion-proof enclosures.
For fitting requirements of cables with multi-conductors, twisted pairs or shielded conductors into explosion
proof equipment. See clause 12.4.1.
Smarter products
www.ehawke.com
59
Technical Data
Where cables enter equipment which is permitted for use in Zone 2 or unclassified areas and that is not
explosion-proof, a suitable cable fitting e.g. cable gland design, need not be explosion-proof, except when
necessary to maintain the integrity of the enclosure and as required by the Recommended Practice.
In unclassified and Zone 2 locations, when the metallic sheath is approved as a grounding conductor, the
continuous metal sheath of the MC cable or the combined metallic sheath and grounding conductors may be
used as the grounding conductor when used with termination fittings that are NRTL-listed to UL 514B.
Temperature
Area classification Type(s) of protection classification
Smarter products
www.ehawke.com
60
NEMA
Enclosure
Type Number
Technical Data
Smarter products
www.ehawke.com
61
Technical Data
Hazardous Locations
Further information can be found in NEMA Standard Publication 250 and UL 50 Standard Publication.
The enclosures are designed to protect and to provide additional protection as stated below: -
NEMA Enclosure
IEC and CENELEC
Type Number
1 IP10
2 IP11
3 IP54
3R IP14
3S IP54
4 and 4X IP56
5 IP52
6 and 6P IP67
The IEC and CENELEC 60529 Standards and NEMA degrees of protection can not be fully compared as
equivalent ratings. The NEMA Standard includes tests for environmental conditions such as mechanical
damage, corrosion, rusting, ice formation, etc.
Smarter products
www.ehawke.com
62
Technical Data
Certain types of cable employ materials that can exhibit "cold flow" characteristics
that could have adverse effects on the protection of the apparatus. Where such cable
Cold Flow is used, a suitable cable entry device should be employed, for example cable entry
devices not employing compression seals that act upon the part(s) of the cable
having "cold flow" characteristics. "Cold flow" can be more fully described as
thermoplastic materials that flow when subjected to pressure at ambient
temperature.
Canadian Standards Association. A service they offer includes testing and
CSA certification services to US and Canadian Standards, as well as international
certification through agreements with other approval authorities.
DNV Det Norske Veritas
Electrical Equipment Certification Service (UK). They provide a range of testing and
EECS certification services primarily related to equipment and systems intended for use in
potentially explosive atmospheres. EECS has two divisions, the Mining Equipment
Certification Services (MECS), and BASEEFA. The EECS is a branch of the Health &
Safety Executive, UK.
A marking prefix for apparatus complying with one or more types of explosion
EEx
protection techniques in accordance with CENELEC standards.
Explosionproof A term used to describe equipment that is capable of withstanding an explosion of a
specified gas or vapour that may occur within it and preventing the ignition of a
specified gas or vapour surrounding it.
Smarter products
www.ehawke.com
63
Technical Data
Smarter products
www.ehawke.com
64
Technical Data
Smarter products
www.ehawke.com
65