HYDRAULIC TRIP SYSTEM

Over speed trip device 1 (10% RATED SPEED)

Over speed trip device 2( 11% OF RATED SPEED)


CONDENSER VACUUM LO-LO

Thrust Bearing trip device (AXIAL SHIFT)

LOCAL TRIP OPERATED FROM GOVERNING


RACK
ELECTRICAL ELECTRICAL
TRIP TRIP
CONDITIONS CONDITIONS

TRIP TRIP
RELAY 1 RELAY 1
HYDRAULIC
TRIP
DEVICES
TRIP TRIP
SOLENOID 1 SOLENOID 2

TURBINE
TRIP VALVE

STOP
VALVE
Action of Protection & Governing System on Turbine Stop & Control Valves
Steam

Protection TripOil
Turbine Stop
Trip System Valve
Logic

Secondary oil

Governing
Turbine Control Valve
Control
System
Parameter
Gen.
Turbine

Condenser
GOVERNING RACK
GOVERNING RACK
OVERSPEED TRIP BOLTS IN BEARING NO. 1 PEDESTAL
Electrical Trip
FIRE PROTECTION
Fire protection switch either in control room or in
machine hall operated.

Level in main oil tank falls to a very low value


indicating substantial leakage of oil from the system.
HP EXHAUST TEMP HIGH
During startup/shutdown or load rejections,
steam turbines are operated at very low
volumetric flows. Energy transmitted by the
turbine shaft is

converted to thermal energy, which in turn result


in an increase in the temp.of both the exhaust
steam and turbine components.
AXIAL SHIFT VERY HIGH
A too high axial displacement of the turbine
shaft may cause damage to the turbine blades.
The axial shift is measured in both directions ()
using three proximity probes.
HPT/IPT TOP BOTTOM TEMP HIGH
Excessive large temp. differentials within
turbine components cause heat stresses. The
temp. differential between upper & lower parts
of the turbine casing (HP and IP sections) is a
measure of casing distortion.
EXTENDED TURBINE PROTECTION
a. Generator bushing level hi-hi > 90 mm
b. Cold gas temp. behind cooler hi-hi > 55 deg C
c. Warm air temp. behind cooler hi-hi > 80 deg C
d. Seal oil temp. behind cooler hi-hi > 60 deg C
e. Primary water flow stator outlet lo-lo < 13.3 dm3/sec
f. Primary water flow at main bushing phase U,V,W lo-lo
<0.37 dm3/sec
g. H.P. casing T/B 50 % diff. temp hi hi >+45 deg K
h. I.P. casing front T/B 50 % diff. temp hi hi > +45 deg K
j. H.P. casing rear T/B 50 % diff. temp hi hi > +45 deg K
k. H.P. exhaust steam temp. hi-hi > 500 deg C
l. Primary water temp. behind cooler hi-hi > 60 deg C