Вы находитесь на странице: 1из 1

Addressable Fire Alarm Systems /

Zeta Common Addressable Input Unit


(ZIU)

The Zeta addressable input unit (ZIU) is used


to interface external equipment which has a
volt free normally open relay output to any
Zeta addressable fire alarm system. The input
is monitored with a 47K end of line resistor.
The unit has a built in loop short circuit isolator to help
keep the unit operational in the event of a problem on
the addressable loop wiring.

The unit has internal LED indications for loop isolator


active, fault on input and alarm (panel controlled).
During the system set-up, the led can be removed from
this box to allow these LEDs to be viewed.

Model ZIU
Part No. 48-100
Interface Unit
Operating Voltage 17 33V DC Loop

Quiescent Current 900uA - - + + -


In Out
Alarm Current 2.9mA

Serial No
Fault Current 2.8mA
Isolating Current 7.3mA ZIU Pt No: 48-100
ZIOU Pt No: 48-105
Input End Of Line 47K Resistor ZSCC Pt No: 48-110

Device Normal Resistance


10K to 75K
(Return Value 16) Hundreds Tens Units
901 901 901
Device Open CCT Fault
78

78

78
23

23

23

85K to open circuit


456 456 456

Resistance (Return Value 4) Address

Device Alarm Resistance


0K to 5K
(Return Value 64)
Operating Temperature 0C to 50C
Maximum Humidity 95% RH Non Condensing
IP Rating IP 43
Size, Width x Height x Depth 127 x 88 x 57mm
Weight 220g

Issue #1 Issue Date 05/07/2010 Revision #4