Академический Документы
Профессиональный Документы
Культура Документы
Modes (eigen-values) of Wind power State Space multiple dispatchable DG units are used in a microgrid. In such
. a system with multiple DG units, dispatchable DG units share
their power based on droop, and consequently, frequency devi-
Virtual Inertia time constant 1.
ation is unavoidable [11].
Virtual Inertia time constant 2. Using batteries is not economical and conventional DGs are
slow; adding small-capacity storage devices, which are not ex-
DFIG rotational speed.
pensive, to the synchronous generators can compensate short
Angular Frequency of microgrid. term for any limitations the dynamic behavior conflicts of the
Air density. system [7].
The concept of using a storage device short-term beside a
Denoting the small signal perturbation of a conventional generator, long-term, is used in various models.
variable. [12] has tried using a storage device to compensate for the wind
0 Subscript denoting the initial value. power variation in short-term disturbances, while a diesel is re-
sponsible for steady state mode. The main problem in using a
storage device and inverter separate from the wind generator is
imposing additional costs. [4] has used GSC to reduce power
output variations with respect to prediction. The storage de-
I. INTRODUCTION vice is used to compensate DFIG in the short term, lead to the
use of lower capacity storage devices, such as super-capacitors,
which are more economic. However, the method proposed in [4]
ARANI AND EL-SAADANY: IMPLEMENTING VIRTUAL INERTIA IN DFIG-BASED WIND POWER GENERATION 3
(3)
(4)
Fig. 1. Wind power generator.
TABLE I
DG1 COMPLETE MODEL EIGEN-VALUES
(12)
(13)
(14)
appropriate control parameter tuning, the right side of (8) will
be zero. This equation can be represented by (9):
III. STABILITY ANALYSIS
(9) To prove that virtual inertia can improve system stability, fur-
ther analysis is needed. Due to relatively short time frame of sta-
On the other hand, the inertia relation in machines, introduced bility analyses, small signal analysis seems suitable. Thus, the
by (4), can be simplified as (10). This simplification seems to be typical rural distribution system shown in Fig. 2 is considered.
reasonable, since the frequency always remains very close to its The segment after the circuit breaker B2 has the ability to work
nominal value. The derivative term will be zero in steady-state, in islanding mode and constitutes the microgrid. The overall
while the frequency is constant but not necessarily at its nominal load of this section is 3.77 MW plus 1.24 MVAR. It contains two
value: DG units: DG1, is a variable-speed wind turbine connected to
a 2.5 MVA DFIG with its rotor interfaced by back-to-back con-
(10)
verter; and DG2, representing a 2.5 MVA conventional gas-tur-
bine generator equipped with droop and excitation control sys-
To implement virtual inertia in the GSC controller, , which
tems.
is the output power of the machine, should be replaced by ,
which is the output power of GSC. Further, , which is the A. Rotating Mass as the Source of Virtual Inertia
input power of the machine, should be replaced by , which
is the power extracted from the rotor terminals of DFIG. The 1) Deriving a Simplified Model: Table I shows the
super-capacitor will be responsible for mimicking the rotating eigen-values of the complete DG1 model, wind power gener-
mass behavior. This new relation is shown in (11). , as in ator without virtual inertia. It consists of 15 states. Obviously,
(6), is an emulation of a derivative: the detailed model of the microgrid including two DG units,
6 loads and several lines is much more complicated. In the
(11) simplified form, DG1 has one dominant pole which is far from
the other modes. This situation may lead to simplifying DG1 as
It should be mentioned here that the GSC is utilized to work a first order system, but before this we need to know the state
always at the unity power factor. The rest of GSC controller to which this mode belongs.
which is based on [7] is discussed in detail in [24]. Participation factor analysis shows that the modes to
are impacted by the DC-link, GSC and its controller, while
C. Implementing the rest of the modes are more related to DFIG, RSC and its
As mentioned, due to practical concerns about producing controller. Particularly, is influenced by , the rotational
simple derivative, is represented as in (12). At low speed of DFIG. The sensitivity analysis reveals that the effect of
frequencies, behaves similar to the derivative, but at , the moment of inertia of the DFIG rotating mass on this
high frequencies it performs differently: mode is significant [24]. On the other hand, the only equation
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
ARANI AND EL-SAADANY: IMPLEMENTING VIRTUAL INERTIA IN DFIG-BASED WIND POWER GENERATION 5
(15)
(16)
(19)
(20)
The rest of the system, consisting of a synchronous machine, its
prime mover, governor and the system loads, will be modeled This new relation for can be replaced in Fig. 3 to obtain
as a simplified model, discussed in [27]. The block diagram of the new system block diagram.
the whole system is shown in Fig. 3. 2) Impact on Frequency Regulation: Fig. 6 shows the root
2) Studying the Behavior: Fig. 5 shows the microgrid dom- locus of the microgrid dominant poles while is increasing.
inant poles root-locus by increasing from zero. Obviously, The system without virtual inertia is introduced by .
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
Fig. 7. Frequency response overshoot to step change in the load versus DFIG
Fig. 5. Microgrid dominant poles Root-Locus when DFIG Rotating mass is rotor initial speed. is constant and equals 14 sec for both cases.
the source of virtual inertia.
(21)
(22)
Fig. 6. Microgrid dominant poles Root-Locus when super-capacitor mass is
the source of virtual inertia. (23)
ARANI AND EL-SAADANY: IMPLEMENTING VIRTUAL INERTIA IN DFIG-BASED WIND POWER GENERATION 7
Fig. 10. Wind Power Generator (DG1) Schematic Block Diagram at high wind speeds (enabled Pitch Angle Controller).
Fig. 11. depicts the overshoot in frequency if a step change in A. Constant Wind Speed
load occurs. This figure reveals that in presence of pitch angle First, wind speed is set as a constant to avoid any confusion.
controller, in contrast to normal situation discussed in part B, Since the analysis in the last section shows some dependency
the initial wind speed has on significant impact on virtual in- on wind speed, this part is divided to three different cases.
ertia performance. It can be illustrated by considering the elec- 1) High Wind Speed (Less Than Rated Speed): In this part,
trical control part which is persuading the constant rated power the wind speed is set constant at 11 m/sec. While all loads are
instead of the maximum available wind power at each speed. In connected, DG1 works at 1.52 MW/0 MVAR and DG2 operates
pervious mode, impact of increasing the virtual inertia was neu- at 1.74 MW and very close to the unity power factor. The rest
tralized by the other part of controller (extracting the maximum of the loads are supplied by the grid. An intentional islanding
available wind power). Besides, the mechanical pitch angle con- takes place at sec.
troller is too slow to oppose the virtual inertia. The frequency is shown in Fig. 12. As expected, virtual in-
While these analyses show no conflicts between pitch angle ertia improves the frequency overshoot and settling time signif-
controller and rotating-mass-based virtual inertia in high speeds, icantly. It also verifies the pervious analysis which claims that
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
ARANI AND EL-SAADANY: IMPLEMENTING VIRTUAL INERTIA IN DFIG-BASED WIND POWER GENERATION 9
Fig. 12. Frequency versus time when wind speed is constantly 11 m/sec
for rotating mass and super-capacitor-based virtual inertia is the same.
Fig. 14. Frequency versus time when wind speed is constantly 0 m/sec. Imple-
menting virtual inertia by the DFIG rotating mass in this condition is impossible.
Fig. 15. DG1 active and reactive power output at zero wind speed when super-
capacitor is the source of virtual inertia.
Fig. 16. Frequency versus time when wind speed is over the rated speed and
consequently the pitch angle controller is enabled. Different wind speeds (with
m/sec unit) are examined.
ARANI AND EL-SAADANY: IMPLEMENTING VIRTUAL INERTIA IN DFIG-BASED WIND POWER GENERATION 11
V. CONCLUSION
Since virtual inertia does not participate in power sharing,
no mass energy storage device is needed. This finding leads to
Fig. 20. Intentional islanding with and without virtual inertia. economic advantages: either the rotating mass connected to the
DFIG shaft or a super-capacitor connected via a DC/DC con-
vertor to a back-to-back inverter DC-link could be used. Both
these sources are discussed in detail.
The modification needed in a conventional wind power to in-
corporate each of the sources was explained. Eigen-value anal-
ysis was used to introduce a simplified model for a microgrid.
This model shows the advantages and disadvantages of each in-
ertia source.
Although virtual inertia based on any of these sources im-
proves the system stability, their impacts are different. It was
shown that while rotating-mass-based virtual inertia does not
need any new part or de-rating, its performance is highly depen-
dent on DFIG rotating speed at the disturbance moment. This ro-
tating speed is a function of wind speed which is unpredictable.
On the other hand, super-capacitor-based virtual inertia
which can improve system behavior much more and is inde-
pendent of wind speed, needs an additional super-capacitor,
DC/DC convertor and rerating of GSC. Some formulas and
Fig. 21. Microgrid frequency during the islanding mode when wind speed
diagram for showing the relation of virtual inertia and size of
change from 16 m/sec to 18 m/sec at sec. these elements were introduced.
It was also discussed that while virtual inertia does not partici-
pate directly in long-term power and frequency regulation, it can
state response of the system, which is controlled by droop-based influence the steady-state performance of the system by decou-
governor, still fluctuates widely, which is undesirable. As dis- pling the steady-state and transient control parameters. Theo-
cussed, for better long-term performance, should be de- retical analyses and time domain simulation were used to verify
creased, but lowering the in the system without virtual in- the papers claims.
ertia makes the system unstable. For instance, in this case, the
system without virtual inertia with % becomes un- APPENDIX
stable in the case of an intentional islanding. The presence of
virtual inertia can change the situation and result in further de- A. Loads
crease of . Fig. 20 shows the system with virtual inertia in
LP1:47 KW j15.61 KVAR, LP2:2565 KW j843.06 KVAR,
which is as low as 0.33%. Clearly, not only is the system
LP3:289.75 KW j95.24 KVAR, LP4: 152 KW j49.96 KVAR,
stable, but the frequency fluctuation is much less.
LP5: 517.8 KW j170.18 KVAR, LP6:194.8 KW j64.01
The maximum frequency deviation in the system with
KVAR.
% after sec is less than Hz, while with
% for a similar time period is more than 0.36 Hz. In other
B. Generators
words, it proves the previous claim that virtual inertia can be
used for a better steady-state performance in addition to its main 1) DG1: 2.5 MVA DFIG,
functionality of system stabilization. .
3) Pitch Angle Controller: Changing the wind speed, when it 2) DG2: 2.5 MVA Synchronous Generator, AVR Parame-
still remains higher than rated speed after changes, is expected ters: Non-reheat Thermal Turbine [27],
to have no impact on wind generator output power and speed [29]: ms, s.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.