TABLE 3:

BNG U CP NH TH CHO NGN E01

U CP NGUN
Cable Type - Cores x
Order Cable Wire From Ref. To Ref.
Section
REMARK
Nr. Number Name Item Item Designation
Drawing Drawing
Designation
C101 DC /CRP 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm DCBD = CRP E01
1 X1:11 /23 X03:07 /36
2 X1:12 /23 X03:08 /36 DC supply Source -01
C102 DC /CRP 1-02 Cu/PVC/PVC-2Cx4.0 sq.mm DCBD = CRP E01
1 X1:59 /27 X03:09 /36
2 X1:60 /27 X03:10 /36 DC supply Source -02
C103 AC /CRP 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm ACDB = CRP E01
1 X14:3 /26 X03:5 /40
2 X14:4 /26 X03:6 /40 AC supply 230V
CA101 AC /MK 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm ACDB = MK E01
1 X14:1 /26 X1:1 /11
2 X14:2 /26 X1:3 /11 AC supply 230V to MCB F201
C1201 MK 1/MK 2-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = MK E02
1 X1:2 /11 X1:1 /10
2 X1:4 /11 X1:3 /10 AC Supply to BMK-02
C104 MK 1/Q0 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = CB Q0 E01
1 MK1-X12:1 /12 X1:7
230V AC supply for Q0
2 MK1-X12:11 /12 X1:8
C105 MK 1/Q7 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = DS Q7 E01
1 MK1-X12:2 /12 401
230V AC supply for Q7
2 MK1-X12:12 /12 403
C106 MK 1/Q761-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = ES Q76 E01
1 MK1-X12:3 /12 401
230V AC supply for Q76
2 MK1-X12:13 /12 403
C107 MK 1/Q751-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = ES Q75 E01
1 MK1-X12:4 /12 401
230V AC supply for Q75
2 MK1-X12:14 /12 403
C108 MK 1/Q1 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = DS Q1 E01
1 MK1-X12:5 /13 401
230V AC supply for Q1
2 MK1-X12:15 /13 403
C109 MK 1/Q151-01 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = ES Q15 E01
1 MK1-X12:6 /13 401
230V AC supply for Q15
2 MK1-X12:16 /13 403
C110 DC /MK 1-01 Cu/PVC/PVC-2Cx4.0 sq.mm DCDB = MK E01
1 X2:1 /23 X2:1 /14
2 X2:2 /23 X2:3 /14 DC DUPPLY TO BMK-01
C111 MK 1/Q0 1-02 Cu/PVC/PVC-2Cx4.0 sq.mm = MK E01 = CB Q0 E01
1 MK1-X21:1 /14 X1:5
110V DC Q0 Breaker Spring charge Motor
2 MK1-X21:6 /14 X1:6
U CP DNG, P
C113A1 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX A E01
MK1/CTA2-02 1 CTTB2:1 /41 1S4
R-Phase- Core-1 Distance protection(REL670)
2 CTTB2:3 /41 1S1
3
Core -02 Spare, 2S4-2S1 Spare and Ground
4
C113A2 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX A E01
A2-01 1 CTTB4:1 /44 3S4
R-Phase- Core-3 Back Up protection(REF615)
2 CTTB4:3 /44 3S1
3 CTTB1:1 /40 4S4
R-Phase -Core-04 Metering Protection
4 CTTB1:3 /40 4S1
C113B1 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX B E01
B2-02 1 CTTB2:4 /41 1S4
Y-Phase- Core-1 Distance protection(REL670)
2 CTTB2:6 /41 1S1
3
Core -02 Spare, 2S4-2S1 Spare and Ground
4
C113B2 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX B E01
B2-01 1 CTTB4:4 /44 3S4
Y-Phase- Core-3 Back Up protection(REF615)
2 CTTB4:6 /44 3S1
3 CTTB1:4 /40 4S4
Y-Phase -Core-04 Metering Protection
4 CTTB1:6 /40 4S1
C113C1 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX C E01
C2-02 1 CTTB2:7 /41 1S4
B-Phase- Core-1 Distance protection(REL670)
2 CTTB2:9 /41 1S1
3
Core -02 Spare, 2S4-2S1 Spare and Ground
4
C113C2 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = CT BOX C E01
C2-01 1 CTTB4:7 /44 3S4 B-Phase- Core-3 Back Up protection(REF615)
2 CTTB4:9 /44 3S1
3 CTTB1:7 /40 4S4
B-Phase -Core-04 Metering Protection
4 CTTB1:9 /40 4S1
C114 CRP 3/CRP 1-01 CVV-S -4Cx4.0 sq.mm = CRP E03 = CRP E01
1 L-X12:1 /43 X12:1 /41
2 L-X12:2 /43 X12:2 /41
BUS PT Voltage Metering Core-02
3 L-X12:3 /43 X12:3 /41
4 L-X12:4 /43 X12:4 /41
C115 CRP 3/CRP 1-02 CVV-S -4Cx4.0 sq.mm = CRP E03 = CRP E01
1 L-X12:5 /43 X12:5 /41
2 L-X12:6 /43 X12:6 /41
BUS PT Voltage Protection Core-03
3 L-X12:7 /43 X12:7 /41
4 L-X12:8 /43 X12:8 /41
C116 MK 1/CRP 1-01 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 CTTB1:1 /40 X01:11 /42
2 CTTB1:4 /40 X01:12 /42
Metering Core4 - CRP-01
3 CTTB1:7 /40 X01:13 /42
4 CTTB1:9 /40 X01:14 /42
C117 MK 1/CRP 1-02 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 CTTB2:1 /41 X01:1 /46
2 CTTB2:4 /41 X01:2 /46
REL670 Distance protection Core-01
3 CTTB2:7 /41 X01:3 /46
4 CTTB2:9 /41 X01:4 /46
C118 MK 1/CRP 1-03 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 MK1-X8:1 /43 X02:1 /47
Line CVT Incomer-01
2 MK1-X8:2 /43 X02:2 /47
3
4
C119 MK 1/CRP 1-04 CVV-S -4Cx4.0 sq.mm = MK E01 = CRP E01
1 CTTB4:1 /44 X01:6 /60
2 CTTB4:4 /44 X01:7 /60
REF615 Back Up Protection Core-03
3 CTTB4:7 /44 X01:8 /60
4 CTTB4:9 /44 X01:9 /60
C120 #N/A CVV-S -4Cx4.0 sq.mm = MK E01 = VTB BOX B E01
1 MK1-X8:1 /43 1a
2 MK1-X8:2 /43 1n Line-01 CVT Core-01
3
4
U CP IU KHIN
C121 MK 1/CRP 1-05 CVV-S -12Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X1:13 /17 52X04:15 /80 Common positive +DC
2 MK1-X1:16 /17 52X04:16 /80 Breaker open position NC
3 MK1-X1:17 /17 52X04:17 /80 Breaker open position NO
4 MK1-X1:15 /17 52X04:18 /80 Spring charge indication
5 MK1-X1:14 /17 52X04:19 /80 SF6 Pressure Blocking
6 MK1-X1:18 /17 52X04:12 /50 Common positive +DC
7 MK1-X1:19 /17 52X04:13 /50 Breaker open position NC to REL670
8 MK1-X1:20 /17 52X04:14 /50 Breaker open position NO TO REL670
9 MK1-X1:21 /17 X04:01 /48
SF6 Gas Replisnish ment Alarm
10 MK1-X1:22 /17 X04:02 /48
11
12
C122 MK 1/CRP 1-06 CVV-S -7Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X7:1 /39 X04:6 /48
Field MCB TRIP/OFF
2 MK1-X7:11 /39 X04:7 /48
3 MK1-X4:14 /29 X04:114 /86
4 MK1-X4:15 /29 X04:115 /86 OVH LINE DEAD IOM BO.12
5 MK1-X1:27 /14 52X04:22 /83
Breaker Local position Indication LAMP
6 MK1-X1:29 /14 52X04:23 /83
7
C123 CRP 3/CRP 1-03 CVV-S -12Cx1.5 sq.mm = CRP E01 = CRP E03
1 X04:36 /54 X04:27 /73
2 X04:37 /54 X04:28 /73 CRP-01,50 BF OPERATED to CRP-03 Trip coil-01
3 X04:38 /54 X04:29 /74
4 X04:39 /54 X04:30 /74 CRP-01,50 BF OPERATED to CRP-03 Trip coil-02
5 X04:77 /70 LBB-X04:1 /59
6 X04:78 /70 LBB-X04:2 /59 CRP-03,50 BF OPERATED to CRP-01 Trip coil-01
7 X04:83 /71 LBB-X04:3 /59
8 X04:84 /71 LBB-X04:4 /59 CRP-03,50 BF OPERATED to CRP-01 Trip coil-02
9
10
11
12
C124 MK 1/CRP 1-07 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X5:1 /31 X03:1 /65
2 MK1-X5:3 /31 X03:2 /65 DC Supply 110V - Q1
3 MK1-X5:7 /31 89X04:1 /65 Common
4 MK1-X5:6 /31 89X04:2 /65 Remote open
5 MK1-X5:5 /31 89X04:3 /65 Remote Close
6 MK1-X5:8 /32 89X04:4 /65
7 MK1-X5:9 /32 89X04:5 /65 Interlock coil
C125 MK 1/CRP 1-08 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X2:1 /19 X03:3 /67
2 MK1-X2:3 /19 X03:4 /67 DC Supply 110V - Q7
3 MK1-X2:7 /19 89X04:11 /67 Common
4 MK1-X2:6 /19 89X04:12 /67 Remote open
5 MK1-X2:5 /19 89X04:13 /67 Remote Close
6 MK1-X2:8 /20 89X04:14 /67
7 MK1-X2:9 /20 89X04:15 /67 Interlock coil
C126 MK 1/CRP 1-09 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X6:7 /35 89X04:6 /66 Common ------Q15
2 MK1-X6:6 /35 89X04:7 /66 Remote open
3 MK1-X6:5 /35 89X04:8 /66 Remote Close
4 MK1-X6:8 /36 89X04:9 /66
5 MK1-X6:9 /36 89X04:10 /66 Interlock coil
6
7
C127 MK 1/CRP 1-010 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X3:7 /23 89X04:16 /68 Common ------Q75
2 MK1-X3:6 /23 89X04:17 /68 Remote open
3 MK1-X3:5 /23 89X04:18 /68 Remote Close
4 MK1-X3:8 /24 89X04:19 /68
5 MK1-X3:9 /24 89X04:20 /68 Interlock coil
6
7
C128 MK 1/CRP 1-011 CVV-S -7Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X4:7 /27 89X04:21 /69 Common ------Q76
2 MK1-X4:6 /27 89X04:22 /69 Remote open
3 MK1-X4:5 /27 89X04:23 /69 Remote Close
4 MK1-X4:8 /28 89X04:24 /69
5 MK1-X4:9 /28 89X04:25 /69 Interlock coil
6
7
C129 MK 1/CRP 1-012 CVV-S -12Cx2.5 sq.mm = MK E01 = CRP E01
1 MK1-X1:1 /15 52X04:1 /72
2 MK1-X1:2 /15 52X04:2 /72 DC Supply 110vdc breaker Q0
3 MK1-X1:8 /16 52X04:3 /72 Remote Trip /TC-1
4 MK1-X1:10 /16 52X04:4 /72 Pre-Close TC-01 Supervision
5 MK1-X1:9 /16 52X04:5 /72 Post-Close TC-01 Supervision
6 MK1-X1:7 /16 52X04:6 /73 Remote Trip /TC-2
7 MK1-X1:12 /16 52X04:7 /73 Pre-Close TC-02 Supervision
8 MK1-X1:11 /16 52X04:8 /73 Post-Close TC-02 Supervision
9 MK1-X1:30 /15 52X04:25 /73 DC supply-02
10 MK1-X1:04 /15 52X04:10 /74 Auto Recloser
11 MK1-X1:05 /15 52X04:11 /74 Remote/ Manual Close
12
C130 MK 1/CRP 1-013 CVV-S -7Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X5:26 /34 89X04:26 /80 Common
2 MK1-X5:27 /34 89X04:27 /80 Q1-Isolator open position NC
3 MK1-X5:28 /34 89X04:28 /80 Q1- Isolator Close position NC
4 MK1-X2:22 /22 89X04:29 /80 Common
5 MK1-X2:23 /22 89X04:30 /80 Q7-Isolator open position NC
6 MK1-X2:24 /22 89X04:31 /80 Q7- Isolator Close position NC
7
C131 MK 1/CRP 1-014 CVV-S -12Cx1.5 sq.mm = MK E01 = CRP E01
1 MK1-X6:26 /38 89X04:32 /81 Common
2 MK1-X6:27 /38 89X04:33 /81 Q15-Earth Switch open position NC
3 MK1-X6:28 /38 89X04:34 /81 Q15- Earth Switch Close position NC
4 MK1-X3:16 /26 89X04:35 /81 Common
5 MK1-X3:17 /26 89X04:36 /81 Q75-Earth Switch open position NC
6 MK1-X3:18 /26 89X04:37 /81 Q75- Earth Switch Close position NC
7 MK1-X4:16 /30 89X04:38 /81 Common
8 MK1-X4:17 /30 89X04:39 /81 Q76-Earth Switch open position NC
9 MK1-X4:18 /30 89X04:40 /81 Q76- Earth Switch Close position NC
10
11
12
C132 CRP 3/CRP 1-04 CVV-S -7Cx1.5 sq.mm = CRP E03 = CRP E01

C133 MK 1/Q0 1-03 CVV-S -12Cx2.5 sq.mm = MK E01 = CB Q0 E01


1 MK1-X1:1 /15 X1:1
2 MK1-X1:2 /15 X1:2 DC Supply 110vdc breaker Q0
3 MK1-X1:8 /16 X1:10 Remote Trip /TC-1
4 MK1-X1:10 /16 X1:13 Pre-Close TC-01 Supervision
5 MK1-X1:9 /16 X1:12 Post-Close TC-01 Supervision
6 MK1-X1:07 /16 X1:11 Remote Trip /TC-2
7 MK1-X1:12 /16 X1:15 Pre-Close TC-02 Supervision
8 MK1-X1:11 /16 X1:14 Post-Close TC-02 Supervision
9 MK1-X1:30 /15 X1:3 DC Supply -2
10 MK1-X1:04 /15 X1:4 Auto Recloser
11 MK1-X1:05 /15 X1:9 Remote/ Manual Close
12
C134 MK 1/Q0 1-04 CVV-S -12Cx2.5 sq.mm = MK E01 = CB Q0 E01
1 MK2-X1:13 /17 X1:30 Common positive +DC
Loop
(X1:30,X1:32,
X3:106,X3:108)
2 MK2-X1:14 /17 X1:29 Loop SF6 Pressure Blocking
3 MK2-X1:15 /17 X1:31 (X1:30,X1:32, Spring charge indication
4 MK2-X1:16 /17 X3:105 X3:106,X3:108) Breaker open position NC
5 MK2-X1:17 /17 X3:107 Breaker open position NO
6 MK1-X1:18 /17 X3:102 Common positive +DC
Loop
7 MK1-X1:19 /17 X3:101 Breaker open position NC to REL670
(X3:102,X3:104)
8 MK1-X1:20 /17 X3:103 Breaker open position NO TO REL670
9 MK1-X1:21 /17 X1:18
SF6 Gas Replisnish ment Alarm
10 MK1-X1:22 /17 X1:19
11
12
C135 MK 1/Q0 1-05 CVV-S -7Cx2.5 sq.mm = MK E01 = CB Q0 E01
1 MK1-X1:6 /15 X1:46
2 MK1-X1:7 /15 X1:47 Not required
3 MK1-X1:23 /18 X1:26
SH:02 Local Interlock
4 MK1-X1:26 /18 X1:27
5
6
7
C136 MK 1/Q0 1-06 CVV-S -12Cx1.5 sq.mm = MK E01 = CB Q0 E01
1 MK1-X1:27 /15 X3:151 Common
2
3 MK1-X1:29 /15 X3:152 Local Selector switch
4 MK1-X2:19 /21 X3:109 Breaker AUX Contact NC-Normal Condition used for Q7
5 MK1-X2:18 /21 X3:110 Local Interlock
6 MK1-X5:19 /33 X3:113 Breaker AUX Contact NC-Normal Condition used for Q1
7 MK1-X5:18 /33 X3:114 Local Interlock
8 MK1-X7:1 /39 X1:40
9 MK1-X7:11 /39 X1:39 F3 MCB Aux.Contact Trip for Q0 Breaker
10 MK1-X7:2 /39 X1:38
11 MK1-X7:12 /39 X1:37 F11 DC MCB Contact trip for Q0 Breaker
12
C137 MK 1/Q7 1-02 CVV-S -12Cx2.5 sq.mm = MK E01 = DS Q7 E01
1 MK1-X2:1 /19 410
2 MK1-X2:3 /19 418 DC Supply 110V - Q7
3 MK1-X2:7 /19 431 Common
4 MK1-X2:6 /19 432 Remote open
5 MK1-X2:5 /19 430 Remote Close
6 MK1-X2:8 /20 440
7 MK1-X2:9 /20 441 Interlock coil
8 MK1-X2:12 /21 437
9 MK1-X2:19 /21 438 Local Interlock
10
11
12
C138 MK 1/Q7 1-03 CVV-S -7Cx1.5 sq.mm = MK E01 = DS Q7 E01
1
2
3
4 MK1-X7:3 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:13 /39 454
6
7
C139 MK 1/Q7 1-04 CVV-S -12Cx1.5 sq.mm = MK E01 = DS Q7 E01
1 MK1-X1:25 /18 27
Q7 NC contact for LC /Closing CKT Q0
2 MK1-X1:26 /18 28
3 MK1-X2:22 /22 24 Common
4 MK1-X2:23 /22 23 Q7-Isolator open position NC Contact
5 MK1-X2:24 /22 25 Q7- Isolator Close position NC Contact
6 MK1-X3:14 /25 31 Q7 Isolator Aux Contact open position NC contact used for
7 MK1-X3:15 /25 32 Local Interlock Q75
8 MK1-X4:13 /29 35 Q7 Isolator Aux Contact open position NC contact used for
Local Interlock Q76
Q7 Isolator Aux Contact open position NC contact used for
9 MK1-X4:14 /29 36 Local Interlock Q76
10 MK1-X6:14 /37 55 Q7 Isolator Aux Contact open position NC contact used for
11 MK1-X6:15 /37 56 Local Interlock Q15
12
C140 MK 1/Q1 1-02 CVV-S -12Cx2.5 sq.mm = MK E01 = DS Q1 E01
1 MK1-X5:1 /31 410
2 MK1-X5:3 /31 418 DC Supply 110V - Q1
3 MK1-X5:7 /31 431 Common
4 MK1-X5:6 /31 432 Remote open
5 MK1-X5:5 /31 430 Remote Close
6 MK1-X5:8 /32 440
7 MK1-X5:9 /32 441 Interlock coil
8 MK1-X5:12 /33 437
9 MK1-X5:19 /33 438 Local operation Interlock
10
11
12
C141 MK 1/Q1 1-03 CVV-S -7Cx1.5 sq.mm = MK E01 = DS Q1 E01
1 MK1-X5:29 67
2 MK1-X5:30 68 Q1 Aux contact used in E03 Q16 closing CKT.
3
4 MK1-X7:6 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:16 /39 454
6
7
C142 MK 1/Q1 1-04 CVV-S -12Cx1.5 sq.mm = MK E01 = DS Q1 E01
1 MK1-X1:23 /18 27
Q1 NC contact for LC /Closing CKT Q0
2 MK1-X1:24 /18 28
3 MK1-X5:26 /34 24 Common
4 MK1-X5:27 /34 23 Loop 24&26 Q7-Isolator open position NC Contact
5 MK1-X5:28 /34 25 Q7- Isolator Close position NC Contact
6 MK1-X3:12 /25 31
7 MK1-X3:13 /25 32 Isolator OFF position NC contact for Local Interlock
8 MK1-X4:11 /29 35
9 MK1-X4:12 /29 36 Isolator OFF position NC contact for Local Interlock
10 MK1-X6:12 /37 55
11 MK1-X6:13 /37 56 Isolator OFF position NC contact for Local Interlock
12
C143 MK 1/Q751-02 CVV-S -12Cx2.5 sq.mm = MK E01 = ES Q75 E01
1 MK1-X3:7 /23 431 Common ------Q75
2 MK1-X3:6 /23 432 Remote open
3 MK1-X3:5 /23 430 Remote Close
4 MK1-X3:8 /24 440
5 MK1-X3:9 /24 441 Interlock coil
6 MK1-X3:3 /23 418
7 MK1-X3:1 /23 410 DC Supply 110V - Q75
8 MK1-X3:12 /25 437
9 MK1-X3:15 /25 438 Local operation Interlock
10
11
12
C144 MK 1/Q751-03 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q75 E01
1
2
3
4 MK1-X7:4 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:14 /39 454
6
7
C145 MK 1/Q751-04 CVV-S -12Cx1.5 sq.mm = MK E01 = ES Q75 E01
1 MK1-X2:14 /21 27
2 MK1-X2:15 /21 28 Earth Switch OFF position NC contact for Local Interlock
3 MK1-X3:16 /26 24 Common
4 MK1-X3:17 /26 23 Loop 24&26 Q75-Earth switch OFF position NC Contact
5 MK1-X3:18 /26 25 Q75-Earth switch OFF position NO Contact
6 MK1-X5:14 /33 31
7 MK1-X5:15 /33 32 Earth Switch OFF position NC contact for Local Interlock
8
9
10
11
12
C146 MK 1/Q761-02 CVV-S -12Cx2.5 sq.mm = MK E01 = ES Q76 E01
1 MK1-X4:7 /27 431 Common ------Q76
2 MK1-X4:6 /27 432 Remote open
3 MK1-X4:5 /27 430 Remote Close
4 MK1-X4:8 /28 440
5 MK1-X4:9 /28 441 Interlock coil
6 MK1-X3:2 /23 410
7 MK1-X3:4 /23 418 DC Supply 110V - Q76
8 MK1-X4:11 /29 437
9 MK1-X4:15 /29 438 Local operation Interlock
10
11
12
C147 MK 1/Q761-03 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q76 E01
1
2
3
4 MK1-X7:5 /39 455
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:15 /39 454
6
7
C148 MK 1/Q761-04 CVV-S -12Cx1.5 sq.mm = MK E01 = ES Q76 E01
1 MK1-X2:17 /21 27
2 MK1-X2:16 /21 28 Earth Switch OFF position NC contact for Local Interlock
3 MK1-X4:16 /30 24 Common
4 MK1-X4:17 /30 23 Loop 24&26 Q76-Earth switch OFF position NC Contact
5 MK1-X4:18 /30 25 Q76-Earth switch OFF position NO Contact
6
7
8
9
10
11
12
C149 MK 1/Q151-02 CVV-S -12Cx2.5 sq.mm = MK E01 = ES Q15 E01
1 MK1-X6:7 /35 431 Common ------Q15
2 MK1-X6:6 /35 432 Remote open
3 MK1-X6:5 /35 430 Remote Close
4 MK1-X6:8 /36 440
5 MK1-X6:9 /36 441 Interlock coil
6 MK1-X6:3 /35 418
7 MK1-X6:1 /35 410 DC Supply 110V - Q15
8 MK1-X6:12 /37 437
9 MK1-X6:15 /37 438 Local operation Interlock
10
11
12
C150 MK 1/Q151-03 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q15 E01
1
2
3
4 MK1-X7:7 /39 455
Local CONTROL PANEL MCB Trip/OFF
Local CONTROL PANEL MCB Trip/OFF
5 MK1-X7:17 /39 454
6
7
C151 MK 1/Q151-04 CVV-S -12Cx1.5 sq.mm = MK E01 = ES Q15 E01
1 MK1-X2:12 /21 27
2 MK1-X2:13 /21 28 Earth Switch OFF position NC contact for Local Interlock
3 MK1-X6:26 /38 24 Common
4 MK1-X6:27 /38 23 Loop 24&26 Q75-Earth switch OFF position NC Contact
5 MK1-X6:28 /38 25 Q75-Earth switch OFF position NO Contact
6 MK1-X5:12 /33 31
7 MK1-X5:13 /33 32 Earth Switch OFF position NC contact for Local Interlock
8
9
10
11
12
C152 MK 1/Q163-01 CVV-S -7Cx1.5 sq.mm = MK E01 = ES Q16 E03
1 MK1-X5:17 /33 67
2 MK1-X5:16 /33 68 Earth switch OFF POSITION NC contact for Q1 Interlock
3 MK1-X5:29 34A
4 MK1-X5:30 35A Q1 Aux contact used in E03 Q16 closing CKT.
5
6
7