General AXR
Specifications Two-wire Magnetic Flowmeter
Integral Flowmeter
GS 01E30D01-01EN [Style: S2]

n GENERAL DESCRIPTION
The ADMAG AXR two-wire magnetic flowmeter can be
installed in the two-wire system without any AC power
source, thus drastically reducing the initial instrumen-
tation cost.
The ADMAG AXR is the worlds first two-wire magnetic
flowmeter which employs the fluid noise free Dual
Frequency Excitation Method, achieving excellent
stability for instrumentation.
Like the AXF four-wire magnetic flowmeter series, the
ADMAG AXR has user-friendly functions such as a
full dot-matrix LCD indicator, electrode adhesion level
diagnosis function, and a multi-lingual display. The l User-friendly Functionality
magnet switches can be used for checking and setting Enhanced Diagnostic Function
parameters without opening the case cover. By checking the level of the insulating substance on
Note: The Dual Frequency Excitation Method is the electrodes, it is possible to determine when main-
Yokogawas unique technology. tenance is required.
Results of mean flow measurement during a given
n FEATURES period, etc. can be checked by using parameters.
Clear and Versatile Indications
lH
 igh Performance and Excellent The full dot-matrix LCD indicator facilitates various
Functionality displays such as one to three lines and multi-lingual
display.
Dual Frequency Excitation Method In an alarm condition, a full description of the coun-
The Dual Frequency Excitation Method combines termeasure is indicated.
two strengths: stability in flow measurement due to
Parameter Setting
low frequency excitation and high noise resistance
Magnet switches and push switches are employed.
due to high frequency excitation. Therefore, the
Magnet switches enable parameters to be set without
method is strong against fluctuations of fluid condition
opening the case cover in the hazardous area.
and is ideal for stable measurement.
Various Output Signals
High Accuracy
In addition to the current output, one output can
The ADMAG AXR performs 0.5% of rate under nor-
be selected among pulse, alarm, and status. Vari-
mal flowrate conditions.
ous functions such as multiple-range, forward and
Electric Noise Resistance reverse flow measurement, and flow rate upper/lower
The ADMAG AXR offers electric noise resistance limit alarm are achieved. The pulse output is a high
compared with the four-wire magnetic flowmeter. speed of 10,000 pps (pulses per second).
High Reliability
The ADMAG AXR complies with SIL2 for safety
requirement. The ADMAG AXR has SIL2 capability CONTENTS
for single flowmeter use and SIL3 capability for dual General description, Features P.1
Standard Specifications P.2
flowmeter use.
Hazardous Area Classification P.7
Standard Performance P.9
l Reducing the Instrumentation Cost Normal Operating Conditions P.11
Reducing the Wiring Cost Cautions for Installation P.12
The two-wire system reduces the wiring cost drasti- Accessories P.13
Terminal Configuration and Terminal Wiring P.13
cally. Wiring Example P.14
Direct Connection with the DCS Model and Suffix Code P.21
AC power sources are not necessary. The ADMAG Optional Specifications P.25
AXR can be connected with almost all distributors, External Dimensions P.28
signal conditioner cards, and input modules. Sizing Data P.35
Ordering Information P.36
Energy Saving
Compared with four-wire magnetic flowmeters, the
ADMAG AXR can drastically decrease power con-
sumption.

Yokogawa Electric Corporation GS 01E30D01-01EN


2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Copyright Aug. 2009 (KP)
Tel.: +81-422-52-4443 Fax.: +81-422-52-2018 6th Edition June 2016 (KP)
<<Contents>> <<Index>> 2
n STANDARD SPECIFICATIONS Connecting device Maximum length of cable
(rough guideline)
l Converter Cable with Cable with
Name Model cross section cross section
The contents of (*1) and (*2) described in the of 2 mm2 of 1.25 mm2
converter specifications are follows.
Signal
*1: One output can be selected from pulse, alarm, or EA1
Conditioner 2 km 2 km
status through the parameter setting. EA2
*2: For models without an indicator, the con-
Card
figuration tool (Such as handheld terminal or AAM11
I/O Module 2 km 2 km
FieldMate, etc.) is necessary to set or change AAM11B
parameters.
AAI143 2 km 2 km
Excitation Method: Analog I/O AAI141
Dual frequency excitation: Size 25 to 200 mm (1 to Module AAI841
8 in.) (for FIO) Not applicable Not applicable
AAI135
Output Signals: AAI835
Current output and digital output can be carried out Analog I/O
simultaneously. Module (for SAI143 1.4 km 0.8 km
Prosafe-RS)
Read WIRING EXAMPLE.
Current output: 4 to 20 mA DC, two-wire system SDBT
Distributor 2 km 2 km
SDBS
Output range: 3.8 to 20.5 mA (1.25 to 103.13%)
Digital output (*1): VJA1
JUXTA VJA4 2 km 2 km
Transistor contact output, open collector VJA7
Contact rating: 30 V DC, 120 mA DC
Low level: 0 to 2 V DC (Read Figure 1) Communication Requirement:
BRAIN
HIGH level
Communication Signal:
0 to 2 V BRAIN communication signal (superimposed on 4 to
LOW level 20 mA DC signals)
0V
F01.ai Conditions of Communication Line:
Supply Voltage: 20.6 to 42 V DC
Figure 1 High and Low levels Load Resistance: 250 to 600 (including cable
(transistor contact output) resistance)
Read Figure 2.
Current Output Status at System Alarms (Burnout) Communication Distance: Up to a distance of 2 km
Up-scale: 110%, 21.6 mA DC or more (standard) when a CEV cable is used
Down-scale: 5%, 3.2 mA DC or less Read WIRING EXAMPLE.
Supply Voltage: Load Capacitance: 0.22 F or less
14.7 to 42 V DC for general-purpose use and explo- Load Inductance: 3.3 mH or less
sion proof type Distance from other Power Line: 15 cm (6 in.) or
14.7 to 32 V DC for lightning protector more (Avoid parallel wiring.)
(optional code A) Input Impedance of Communicating Device:
Note 1: Supply voltage means the voltage necessary to pro- 10 k or more at 2.4 kHz
vide between the power terminals of the magnetic
flowmeter.
Note 2: Connecting with the commercial AC power supply 600
will damage the flowmeter. Be sure to use the DC
power supply in the predetermined range. R= E14.7
Note 3: The ADMAG AXR can be connected with almost 0.0236 Digital
External Communication
all distributors, signal conditioner cards, and I/O Range
Load (BRAIN or HART)
modules except certain devices.
Resistance
Read the following table for Yokogawas devices,
choose an appropriate connecting device and the 250
corresponding length of cable.
For devices other than those in the table, decide on R ()
the connection by reading the supply voltage specifi-
cations and the description in WIRING EXAMPLE.

14.7 20.6 28.9 42


Power supply voltage E (V DC)
F02.ai

Figure 2 R
 elationship Between Power Supply Voltage
And External Load Resistance
HART
Communication Signal:
HART communication signal (superimposed on 4 to
20 mA DC signals)
Note: HART is a registered trademark of the FieldComm
Group.
Conditions of Communication Line:
Supply Voltage: 20.6 to 42 V DC

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 3
Load Resistance: 250 to 600 (including cable Converter Coating:
resistance) Case and Cover: Corrosion-resistant coating
Read Figure 2. Coating Color: Mint-green paint (Munsell 5.6 BG
HART Protocol Revision: 3.3/2.9 or its equivalent)
HART protocol revision can be selected from 5 or 7
Converter Material:
when ordering. (-J only)
Case and Cover: Aluminum alloy
The protocol revision can be changed by user con-
figuration. Mounting/Shapes:
The HART protocol revision at the time of shipment Electrical Connection: ANSI 1/2 NPT female
is shown by the last number at the serial number ISO M20 x 1.5 female
column of the name plate. JIS G1/2 female
Note: Protocol revision supported by HART configuration Direction of Electrical Connection: The direction can
tool must be the same or higher than that of AXR. be changed even after delivery.
Terminal Connection: M4 size screw terminal
Selection of HART 5/ HART 7 Grounding:
Grounding resistance of 100 or less is necessary.
Output Signal When the optional code A is selected, grounding
-E -J
Code
resistance of 10 or less shall be required.
Ordering * In case of TIIS explosion proof type, read descrip-
Specify 5 Specify 7
Information
tion of HAZARDOUS AREA CLASSIFICATION.
HART Protocol * For an explosion proof type except for TIIS, follow
HART 5 HART 7
Revision
the domestic electrical requirements in each coun-
YES try.
Be sure to
Require- confirm the
ment for protocol Functions
HART 7 NO revision of How to Set Parameters (*2):
function- the HART
configura- Both of four push buttons and magnet switches can
ality
tion tool be used for setting. The magnet switches can be
Selec- shown in used to set parameters without opening the case
tion Note 2.
guide cover.
Not avail- Available Available The magnet switches need operational magnets
to switch to switch (optional code BM). These are also available as part
able to to HART to HART number F9840PA.
Other switch to 7 proto- 5 proto-
condi- HART 7 col after col after Users can choose a language on indicator from Eng-
tions protocol delivery lish, Japanese, German, French, Italian, and Span-
by delivery by
after deliv- user-con- ish. Parameters can also be set with the configuration
user-con-
ery. figuration. figuration. tool (Such as HHT (handheld terminal) or FieldMate,
Remarks Note 1 Note 2 Note 2 etc.). The language for the HHT is English only.
Note 1: "-E" is HART5 exclusive model and will be Instantaneous Flow Rate/Totalized Value Display
terminated. "-J" is recommended for HART Functions (for models with an indicator) (*2):
communication. The full dot-matrix LCD enables user selections of
Note 2: HART protocol revision for the device and displays from one line to three lines for:
HART configuration tool Instantaneous flow rate
HART 7 communication is supported by Field- Instantaneous flow rate (%)
Mate R2.04 or later. Instantaneous flow rate (bar graph)
Current output value (mA)
Protocol revision supported by HART Totalized forward-direction flow rate
configuration tool Totalized reverse-direction flow rate
5 7 Totalized differential flow rate
AXR, HART 5 Available Available Tag No.
AXR, HART 7 Not available Available Results of electrode adhesion diagnosis
Communication type
Indicator (*2): Totalizer Display Function (*2):
Full dot-matrix LCD (128 x 64 pixels) The flow rate is counted one count at a time accord-
Operational switch: 4 magnet switches (including ing to the setting of totalization pulse weights. For
push switches) forward and reverse flow measurement functions,
Lightning Protector: the totalized values of the flow direction (forward or
When optional code A is selected, the lightning pro- reverse) and the flow direction are displayed on the
tector is built into the power supply and digital output indicator together with the units. The difference of
terminals. totalized values between the forward and reverse
Protection: flow rate can be displayed. Totalization for the re-
General-purpose Use/TIIS Flameproof type: verse flow rate is carried out only when Forward and
IP66/IP67, Type 4X reverse flow measurement functions is selected.
Explosion proof type except for TIIS: Damping Time Constant (*2):
In the case of explosion proof type except TIIS, The time constant can be set from 1.0 second to
read description of Enclosure in HAZARDOUS 200.0 seconds (63% response). The default is 5
AREA CLASSIFICATION. seconds.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 4
When the damping time is short, the output fluctu- NE-107 Alarm Message (*2):
ates. Set the time to 5 seconds or more for control Alarms are classified into 4 categories by NAMUR
loop. NE-107 and can be displayed.
Span Setting Function (*2): -F: Failure
Span flows can be set in units such as volume flow -C: Function check
rate, mass flow rate, time, or flow rate value. The -S: Out of specification
velocity unit can also be set. -M: Maintenance required
Volume Flow Rate Unit: kcf, cf, mcf, Mgal (US), kgal
(US), gal (US), mgal (US), kbbl (US)*, Alarm Output (*1)(*2):
bbl (US)*, mbbl (US)*, bbl (US)*, Ml Alarms are generated only for the items selected
(megaliter), m3, kl (kiloliter), l (liter), cm3 via the Alarm Selection Function if relevant failures
Mass Flow Rate Unit (Density must be set): klb occur.
(US), lb (US), t (ton), kg, g Self Diagnosis Functions (*2):
Velocity Unit: ft, m (meter) When an alarm is output, details of the System
Time Unit: s (sec), min, h (hour), d (day) Alarms, Process Alarms, Setting Alarms, and Warn-
* US Oil or US Beer can be selected.
ings are displayed together with the specific descrip-
Pulse Output (*1)(*2): tion of corresponding countermeasures.
Scaled pulse is output one by one according to the Results of mean flow measurement during a given
setting of pulse weight. period, etc. can be checked by using parameters.
Pulse Width: Duty 50% or fixed pulse width (0.05, Flow Rate Upper/Lower Limit Alarms (*1)(*2):
0.1, 0.5, 1, 20, 33, 50, 100, 200, 330, If a flow rate becomes out of the predetermined
500, 1000, 2000 ms) can be selected. range, the alarm output is generated.
Output Rate: 0.0001 to 10,000 pps (pulses per
second) Electrode Adhesion Diagnosis Function (*1) (*2):
This function enables checking of the adhesion level
Multi-range Functions (*1)(*2): of insulating substances to the electrodes. Depend-
Automatic range switching ing on the status of adhesion, users are notified by a
When the flow rate exceeds 100% of the range, warning or an alarm via status outputs.
transition to the next range (up to two ranges) is While adhesion diagnosis is being carried out (ap-
carried out automatically. Range switching can be proximately 5 minutes), a current of 4 mA is output
confirmed by the status output and on the indicator. because the flow measurement is not performed.
Forward and Reverse Flow Measurement Func- Adhesion diagnosis should only be carried out when
tions (*1)(*2): the fluid velocity is completely zero by closing the
Flows in both forward and reverse directions can be valve.
measured. The reverse flow measurement can be When adhesion diagnosis is carried out, change the
confirmed by the status output and on the indicator. control loop to the manual mode first.
Totalization Switch (*1)(*2): Data Security during Power Failure:
The status output is carried out when a totalized Data (parameters, totalization value, etc.) storage by
value becomes equal to or greater than the set value. EEPROM. No back-up battery required.
Preset Totalization (*1)(*2): Low Cut (*2):
The parameter setting enables a totalized value to be In this function, the values of the current output along
preset to a setting value or zero. with LCD indication, totalization, and pulse, which are
Alarm Selection Function (*2): corresponding to setting span of 0 to 20%, are fixed
Alarms are classified into the System Alarms (hard- at 0% (including reverse flow). The default setting is
ware failure), Process Alarms (such as Signal 3%.
Overflow and Adhesion Alarm), Setting Alarms, and When the Low Cut point is small, the incorrect output
Warnings. Process Alarms and Setting Alarms can be may occur at the flow rate of zero. Set the Low Cut
activated or deactivated for each item. The current point to 3% or more. If the span is small, the damping
output for an alarm can be selected from the follow- time is short or the fluid is low conductivity, the incor-
ing settings. If any System Alarm occurs, turn the rect output may easily occur at the flow rate of zero.
power off and back on again to return to the normal Zero Adjustment Function (*2):
condition. By using the parameter setting, zero adjustment is
System Alarm: 21.6 mA or more, 3.2 mA or less carried out to ensure that the output for zero flow is
Process Alarm, Setting Alarm: 0%. Zero adjustment should be carried out only when
21.6 mA or more, 20.5 mA, HOLD the flowtube is filled with measurement fluid and the
(fixed to the current value before flow is completely stopped by closing the valves.
the alarm), 4 mA, 3.8 mA, 3.2 During zero adjustment (450 seconds), the current
mA or less output is 10.4 mA.
The default settings of each alarm are as follows:
Optional
Standard
code C1
System Alarm
Process Alarm (Note) 21.6 mA or more 3.2 mA or less
Setting Alarm (Note)
Note: In the case of style:S1 with optional code C1, the
current output is set up to 3.8 mA during Process
Alarms and Setting Alarms.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 5
l Flowtubes Flowtube Material:
Size 25 to 100 mm (1 to 4 in.)
Size of AXR Flowtubes:
Part Name Material
Lay length code 1 Unit: mm (in.)
Stainless steel-JIS
Process
Use Integral Flowmeter SUS304
Connection Housing
(AISI 304 SS/EN 1.4301
80 (3.0), 100 (4.0), equivalent)
Wafer*1
150 (6.0), 200 (8.0)
General-purpose Stainless steel-JIS
Use/Explosion 25 (1.0), 40 (1.5), SUS304 or SUSF304
Flange
Proof Type 50 (2.0), 65 (2.5), (AISI 304 SS/EN 1.4301
Flange*1 equivalent)
80 (3.0), 100 (4.0),
150 (6.0), 200 (8.0)
Size 25 mm
*1: The dimensions of lay length code 1 are the same as Stainless steel-SCS13
(1.0 in.)
those of the PFA lining standard lay length (lay length
code 1) in the AXF series. For details, read EXTERNAL Mini- Wafer Stainless steel-JIS
DIMENSIONS. Flange type SUS430
Size 40 to 100 mm
ASTM 4300/DIN
Lay length code 2 Unit: mm (in.) (1.5 to 4.0 in.)
X6Cr17/ EN 1.4016
equivalent
Process
Use Integral Flowmeter
Connection Size 25 mm
Stainless steel-SCS13
(1.0 in.)
25 (1.0), 40 (1.5),
General-purpose Wafer
50 (2.0), 65 (2.5), Stainless steel-JIS
Use/Explosion Wafer*2 type
80 (3.0), 100 (4.0), Size 40 to 100 mm SUS304
Proof Type
150 (6.0), 200 (8.0) (1.5 to 4.0 in.) (AISI 304 SS/EN 1.4301
*2: Excluding the size of 65 mm, dimensions of lay length equivalent)
Pipe
code 2 are the same as those of PFA lining replacement Size 25 mm
models (lay length code 2) in AXF series. Lay lengths for Stainless steel-SCS13
(1.0 in.)
special gaskets (optional codes GA, GC, GD) are different.
Flange Stainless steel-JIS
For details, read EXTERNAL DIMENSIONS.
type Size 40 to 100 mm SUS304
Coating: (1.5 to 4.0 in.) (AISI 304 SS/
General-purpose Use/Explosion Proof Type: EN 1.4301 equivalent)
Size 25 to 100 mm (1 to 4 in.) (Wafer type),
Size 25 to 100 mm (1 to 4 in.) (Flange type):
Housing: No coating (Stainless steel surface) Size 150 mm (6.0 in.) to 200 mm (8.0 in.)
Flange (Flange type only):
Part Name Material
No coating (Stainless steel surface)
Size 150 to 200 mm (6.0 to 8 in.) (Wafer type), Housing
Carbon steel-JIS SPCC
Size 150 to 200 mm (6.0 to 8 in.) (Flange type): equivalent
Housing, Flange (Flange type only) Stainless steel-JIS
Corrosion-resistant coating SUS304 or SUSF304
Process Connection code: B**
Coating color; Mint green (Munsell 5.6 BG (AISI 304 SS/EN 1.4301
3.3/2.9 or its equivalent) Flange equivalent)
Carbon steel-JIS SS400
Process Connection code: C**
or SFVC 2A
Mini- Carbon steel-JIS SS400
Wafer Type
Flange or SFVC 2A
Stainless steel-JIS SUS
Pipe Flange Type/Wafer Type 304 (AISI 304 SS/EN
1.4301 equivalent)
Wetted Part Material:
Lining;
Fluorocarbon PFA*1 lining
*1: PFA is FDA (U.S. Food and Drug Administration) ap-
proval material.
The inner surface of the PFA lining is mirror-finished to
Ra of 0.05 to 0.15 m. The value of Ra is the average
of measurements at several points. Mirror finished
PFA lining is standard for size 25 to 100 mm (1 to 4 in.)
and optional for size 150 to 200 mm (6 to 8 in.) speci-
fied by optional code PM.
Electrode;
Stainless steel-JIS SUS316L (AISI 316L SS/EN
1.4404 equivalent), Hastelloy*1 C276 equivalent,
Tantalum, Platinum-Iridium

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 6
Grounding Ring/Grounding Electrode; Gaskets Size
Grounding Ring (plate type) Be sure to choose a gasket with an inner and outer
Stainless steel-JIS SUS316 (AISI 316 SS/EN diameter that does not protrude inside the piping
1.4401 equivalent), Stainless steel-JIS SUS316L (Read item of Inner Diameter Of Grounding Ring,
or ASTM 316L (AISI 316L SS/EN 1.4404 equiva- Outer Diameter For Effective Sealing).
lent), Hastelloy*1 C276 equivalent If the inner diameter of the gasket is too large, or
Grounding Electrode (electrode type)*2 outer diameter of the gasket is too small, fluid leak-
Fluorocarbon PFA lining + grounding electrode age may result.
(Tantalum, Platinum-Iridium)
*1: Hastelloy is a registered trademark of Haynes Interna-
tional Inc. Inner Diameter of Grounding Ring, Outer Diameter
*2: The permeable fluids (such as nitric acid, hydrofluoric for Effective Sealing, Recommended Inner Diame-
acid, or sodium hydroxide at high temperature) are ter of Gasket;
unusable.
Lay length code 1; Unit: mm (in.)
Gasket;
PFA lining
Use General-purpose Use/
Explosion Proof Type Wafer, Flange
Recommended Inner
Grounding ring Outer Diameter of Gasket
Inner
Size Diameter PTFE-
Diameter of
for sheathed
Standard Grounding Flat
Effective Non-
Ring Gasket
Sealing asbestos
[A] [C]
[B] Gasket
No gasket within Flowtube [D]
25 (1.0) 28 (1.10) 53 (2.09) 35 (1.38)
Grounding ring 40 (1.5) 41 (1.61) 71 (2.80) 49 (1.93)
50 (2.0) 53 (2.09) 84 (3.31) 61 (2.40)
65 (2.5) 66 (2.60) 103 (4.06) 84 (3.31)
Optional 80 (3.0) 77 (3.03) 114 (4.49) 90 (3.54)
code Gasket within Flowtube
(GA, GC, 100 (4.0) 102 (4.02) 140 (5.51) 115 (4.53)
or GD) Gasket Material (within Flowtube) 150 (6.0) 146.1 (5.75) 190 (7.48) 167 (6.57)
GA: Fluororubber for PVC pipes (Viton) 200 (8.0) 193.6 (7.62) 240 (9.45) 218 (8.58)
GC: Acid-resistant fluororubber for PVC
pipes (Viton) Lay length code 2; Unit: mm (in.)
GD: Alkali-resistant fluororubber for PVC
pipes (Viton) PFA lining
Wafer
Use General-purpose Use/ Recommended Inner
Explosion Proof Type Diameter of Gasket
Outer
Inner
Size Diameter PTFE-
Grounding ring Diameter of
for sheathed
Grounding Flat
Effective Non-
Ring Gasket
Sealing asbestos
[A] [C]
Optional [B] Gasket
code [D]
(BCF, BSF, 25 (1.0) 28 (1.10) 53 (2.09) 35 (1.38)
BCC, or Flange of users pipe Gasket for
BSC) users flange 40 (1.5) 41 (1.61) 71 (2.80) 49 (1.93)

Gasket Material (for users flange) 50 (2.0) 53 (2.09) 84 (3.31) 61 (2.40)

BCF, BSF: PTFE-sheathed non-asbestos 65 (2.5) 66 (2.60) 103 (4.06) 84 (3.31)


BCC, BSC: Chloroprene rubber 80 (3.0) 77 (3.03) 114 (4.49) 90 (3.54)
100 (4.0) 102 (4.02) 140 (5.51) 115 (4.53)
Recommended Gaskets Between Flowtubes And 150 (6.0) 140.7 (5.54) 190 (7.48) 167 (6.57)
Users Flanges: 200 (8.0) 188.9 (7.44) 240 (9.45) 218 (8.58)
Gaskets Type
Use compressed non-asbestos fiber gaskets,
PTFE-sheathed non-asbestos gaskets or gaskets
which have equivalent elasticity.
For optional codes GA, GC, and GD, use rubber gas-
kets or others which have equivalent elasticity.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 7

Size of Inner Diameter of Grounding Ring,


Enclosure: IP66/IP67
Outer Diameter for Effective Sealing and Process Temperature:
Recommended Inner Diameter of Gasket: Maximum Surface Maximum Process Minimum Process
Temperature Temperature Temperature
T90C (+194F) +70C (+158F) 30C (22F)
T110C (+230F) +85C (+185F) 30C (22F)

AXR T130C (+266F) +130C (+266F) 30C (22F)


B
D *1 C A
Flowtube Ambient Temp.: 30C to +55C
Lining (22F to +131F)
Note: Grounding resistance of 100 or less is necessary.
When the optional code A is selected, grounding resist-
ance of 10 or less shall be required.
Grounding Ring
Flat Gasket
FM
PTFE-sheathed Non-asbestos Gasket
Applicable Standard:
FM3600, FM3610, FM3615,
*1: Do not have this length be smaller than the
inner diameter of grounding ring (A).
FM3810, ANSI/NEMA250
F06.ai
Type of Protection:
Electrode Construction: Explosionproof for Class I, Division 1, Groups A, B,
Internal insertion type C&D
Dust-ignitionproof for Class II/III, Division 1, Groups
E, F & G
n HAZARDOUS AREA CLASSIFICATION With intrinsically safe electrodes for Class I, Division
1, Groups A, B, C & D
ATEX: SEAL ALL CONDUITS WITHIN 18 INCHES
Applicable Standard: WHEN INSTALLED IN DIV. 2, SEALS NOT RE-
EN 60079-0, EN 60079-1, QUIRED
EN 60079-7, EN 60079-11, Specification of Protection:
EN 60079-31 Electrode Circuit Um: 250 V
Certificate: DEKRA 11ATEX0144 Power Supply/Current Output: 
Type of Gas Atmosphere Protection 42 Vdc max. / 4 to 20 mA
Type of Protection: Digital Output: ON; 2 Vdc, 120 mA max.
Group: II OFF; 30 Vdc max., 4 mA
Category: 2G Excitation Circuit: 29 V max.
Ex d e ia IIC T6...T4 Gb Enclosure: NEMA Type 4X
Specification of Protection: Process Temperature:
Electrode Circuit: Um=250 V Temperature Maximum Process Minimum Process
Power Supply/Current Output: Code Temperature Temperature
42 Vdc max., 4 to 20 mA, Um=250 V T6 +70C (+158F) 40C (40F)
Digital Output: ON; 2 Vdc, 120 mA max.
OFF; 30 Vdc max., 4 mA, Um=250 V T5 +85C (+185F) 40C (40F)
Excitation Circuit: 29 V max. T4 +130C (+266F) 40C (40F)
Enclosure: IP66/IP67
Process Temperature: Ambient Temp.:40C to +55C
(40F to +131F)
Temperature Maximum Process Minimum Process Note: Installation shall be in accordance with the manu-
Class Temperature Temperature facturers instructions, National Electric Code,
ANSI/NFPA-70, and Local Electric Code.
T6 +70C (+158F) 30C (22F)
T5 +85C (+185F) 30C (22F) CSA
T4 +130C (+266F) 30C (22F) Certificate No.: 2136807
Ambient Temp.: 30C to +55C For Division system of area classification
(22F to +131F) Applicable Standard:
C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5,
Type of Dust Atmosphere Protection C22.2 No.25, C22.2 No.30, C22.2 No.94,
Type of Protection: C22.2 No.157, C22.2 No.61010-1
Group: II Type of Protection:
Category: 2D Class I, Groups A, B, C and D;
Ex tb IIIC T90C, T110C, T130C Db Class II, Groups E, F and G; Class III
Specification of Protection: With Intrinsically Safe Electrodes for Class I,
Electrode Circuit: Um=250 V Groups A, B, C and D
Power Supply/Current Output: Specification of Protection :
42 Vdc max., 4 to 20 mA, Um=250 V Electrode Circuit Um: 250 V
Digital Output: ON; 2 Vdc, 120 mA max. Power Supply/Current Output: 42Vdc max./
OFF; 30 Vdc max., 4 mA, Um=250 V 4 to 20mA
Excitation Circuit: 29 V max.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 8
Digital Output: Process Sealing Certification:
On: 2Vdc, 120mA max. Dual Seal certified by CSA to the requirements of
Off: 30Vdc max., 4mA ANSI/ISA 12.27.01.
Excitation Circuit: 29V max. No additional sealing required.
Enclosure: Type 4X Primary seal failure annunciation;
Process Temperature: Deterioration of the flowrate output at nonzero flow
Temperature Maximum Process Minimum Process
point.
Code Temperature Temperature Unstable flowrate output at zero flow point.

T6 +70C (+158F) 40C (40F) IECEx:


T5 +85C (+185F) 40C (40F) Applicable Standard:
IEC60079-0, IEC60079-1,
T4 +130C (+266F) 40C (40F)
IEC60079-7, IEC60079-11,
Ambient Temperature: 40 to +55C (40F to IEC60079-31
+131F) Certificate: IECEx DEK 11.0053
For Zone system of area classification Type of Gas Atmosphere Protection
Applicable Standard: Type of Protection:
C22.2 No.60079-0, E60079-1, E60079-7, Ex d e ia IIC T6...T4 Gb
E60079-11, E61241-1-1, C22.2 No.61010-1 Specification of Protection:
Type of Gas Atmosphere Protection Electrode Circuit: Um=250 V
Type of Protection: Power Supply/Current Output:
Ex d e [ia] IIC T6T4 42 Vdc max., 4 to 20 mA, Um=250 V
with Intrinsically Safe Electrodes for Zone 0, Digital Output: ON; 2 Vdc, 120 mA max.
Ex ia IIC T6T4 OFF; 30 Vdc max., 4 mA, Um=250 V
Specification of Protection: Excitation Circuit: 29 V max.
Electrode Circuit Um: 250 V Enclosure: IP66/IP67
Power Supply/Current Output: 42Vdc max./ Process Temperature:
4 to 20mA Temperature Maximum Process Minimum Process
Digital Output: Class Temperature Temperature
On: 2Vdc, 120mA max.
T6 +70C (+158F) 30C (22F)
Off: 30Vdc max., 4mA
Excitation Circuit: 29V max. T5 +85C (+185F) 30C (22F)
Enclosure: IP66/IP67 T4 +130C (+266F) 30C (22F)
Process Temperature:
Ambient Temp.: 30C to +55C
Temperature Maximum Process Minimum Process (22F to +131F)
Code Temperature Temperature
Type of Dust Atmosphere Protection
T6 +70C (+158F) 40C (40F) Type of Protection:
T5 +85C (+185F) 40C (40F) Ex tb IIIC T90C, T110C, T130C Db
Specification of Protection:
T4 +130C (+266F) 40C (40F) Electrode Circuit: Um=250 V
Ambient Temperature: 40 to +55C (40F to Power Supply/Current Output:
+131F) 42 Vdc max., 4 to 20 mA, Um=250 V
Type of Dust Atmosphere Protection Digital Output: ON; 2 Vdc, 120 mA max.
Type of Protection: OFF; 30 Vdc max., 4 mA, Um=250 V
DIP A21 TA 90C, 110C, 130C Excitation Circuit: 29 V max.
Specification of Protection: Enclosure: IP66/IP67
Electrode Circuit Um: 250 V Process Temperature:
Power Supply/Current Output: 42Vdc max./ Maximum Surface Maximum Process Minimum Process
4 to 20mA Temperature Temperature Temperature
Digital Output: T90C (+194F) +70C (+158F) 30C (22F)
On: 2Vdc, 120mA max.
Off: 30Vdc max., 4mA T110C (+230F) +85C (+185F) 30C (22F)
Excitation Circuit: 29V max. T130C (+266F) +130C (+266F) 30C (22F)
Enclosure: IP66/IP67 Ambient Temp.: 30C to +55C
Process Temperature: (22F to +131F)
Maximum Surface Maximum Process Minimum Process Note: Grounding resistance of 100 or less is necessary.
Temperature TA Temperature Temperature When the optional code A is selected, grounding resistance
of 10 or less shall be required.
90C +70C (+158F) 40C (40F)
110C +85C (+185F) 40C (40F)
130C +130C (+266F) 40C (40F)
Ambient Temperature: 40 to +55C (40F to
+131F)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 9
TIIS n STANDARD PERFORMANCE
Certificate: Accuracy:
Size: mm(inch) Wafer Type -A** Flange Type -B** General-Purpose Use; Vs: Span setting value (m/s)
25 (1.0) TC19746 TC19746 Size in mm (in.) Span in m/s (ft/s) Accuracy
40 (1.5) TC19747 TC19747 0.25 cm/s
(at indications less than
50 (2.0) TC19748 TC19748 50% of span)
0.3 Vs < 1
65 (2.5) TC19749 TC19749 (1 Vs < 3.3) (0.4+0.1/Vs)% of rate
80 (3.0) TC19750 TC19750 (at indications 50% or
more of span)
100 (4.0) TC19751 TC19751
0.2% of span
150 (6.0) TC19753 TC19754 (at indications less than
200 (8.0) TC19756 TC19757 25 to 100 1 Vs < 2 35% of span)
(1 to 4) (3.3 Vs < 6.7) 0.5% of rate
Construction: Ex d e [ia] IIC T4 (at indications 35% or
more of span)
Converter: Flameproof enclosure and
intrinsically safety (ia) 0.16% of span
(at indications less than
Flowtube: Increased safety and 30% of span)
2 Vs 10
intrinsically safety (ia) (6.7 Vs 33) 0.5% of rate
Electrode: Intrinsically safety (ia) (at indications 30% or
Gas Group And Temperature Class: IIC T4 more of span)
l Non-intrinsically safety circuit 0.30 cm/s
Supply Voltage: 14.7 to 42 V dc (at indications less than
Output Signal: 4 to 20 mA dc 0.3 Vs < 1 50% of span)
Digital output: O
 N; 2 V dc, 120 mA, (1 Vs < 3.3) (0.3+0.2/Vs)% of rate
OFF; 30 V dc, 4 mA (at indications 50% or
Allowable Voltage (Um): 250 V ac 50/60Hz, more of span)
250 V dc 0.3% of span
Excitation Circuit: 29 V (at indications less than
150 to 200 1 Vs < 2 35% of span)
l Intrinsically safety circuit
Maximum Voltage (Uo): 14 V (6 to 8) (3.3 Vs < 6.7) 0.5% of rate
Maximum Current (Io): 17 mA (at indications 35% or
Maximum Electrical Power (Po): 0.12 W more of span)
l Fluid Temperature: 20 to 130C 0.16% of span
(at indications less than
l Ambient Temperature: 20 to 55C 30% of span)
2 Vs 10
l Grounding: (6.7 Vs 33) 0.5% of rate
Grounding resistance of 10 or less is necessary (at indications 30% or
for class A grounding terminal. more of span)
Grounding resistance of 100 or less is necessary
for Functional grounding terminal.
When the optional code A is selected, grounding
resistance of 10 or less shall be required.
l Flameproof packing adapter:
The specifying optional code G11 is necessary.
In case of two flameproof packing adapters, specify
optional code G32 with G11.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 10
Explosion proof Type; Vs: Span setting value (m/s) Accuracy for Multi-drop of HART
(generally accepted values)
Size in mm (in.) Span in m/s (ft/s) Accuracy
Vs: Span setting value (m/s)
0.30 cm/s Size in mm (in.) Span in m/s (ft/s) Accuracy
(at indications less than
0.3 Vs < 1 50% of span) 0.3 Vs < 1 (0.4+0.3/Vs)% of span
(1 Vs < 3.3) (1 Vs < 3.3)
(0.3+0.2/Vs)% of rate
(at indications 50% or 1 Vs < 2 0.5% of span
more of span) (3.3 Vs < 6.7)
0.3% of span 25 to 200 0.25% of span
(at indications less than (1 to 8) (at indications less
25 to 100 1 Vs < 2 35% of span) 2 Vs 10 than 50% of span)
(1 to 4) (3.3 Vs < 6.7) 0.5% of rate
(6.7 Vs 33) 0.5% of rate
(at indications 35% or (at indications 50% or
more of span) more of span)
0.16% of span
(at indications less than Repeatability (Reference):
2 Vs 10 30% of span) 0.2% of rate
(6.7 Vs 33) (When the flow velocity is 1.5 m/s toward 2 m/s of
0.5% of rate
(at indications 30% or setting span)
more of span)
0.50 cm/s Insulation Resistance:
(at indications less than Inspection location Terminal Test voltage Standard
0.3 Vs < 1 50% of span)
Power Supply/Digital
(1 Vs < 3.3) (0.5/Vs)% of rate SUPPLY/DO 100 M
Output - Functional 500 V DC
(at indications 50% or or more
Grounding
more of span)
0.45% of span When the optional code A is selected (with the lightning protec-
(at indications less than tor), values are as follows.
30% of span) Power Supply/Digital
SUPPLY/DO 20 M
0.25% of span Output - Functional 100 V DC
or more
150 to 200 1 Vs < 2 (at indications from 30% Grounding
(6 to 8) (3.3 Vs < 6.7) or more to less than 45% Note: Conduct the test according to the instruction manual.
of span)
0.5% of rate Dielectric Strength:
(at indications 45% or
more of span) Test Test
Inspection location Terminal Standard
voltage time
0.24% of span
(at indications less than Power Supply/Digital
SUPPLY/DO 500 V 1 25 mA
35% of span) Output - Functional
2 Vs 10 AC min. or less
Grounding
(6.7 Vs 33) 0.5% of rate
(at indications 35% or When the optional code A is selected (with the lightning protec-
more of span) tor), values are as follows.
The accuracy of a product before shipment is defined Power Supply/Digital
SUPPLY/DO 100 V 1 6 mA
as totalized value at the result of calibration test in our Output - Functional
AC min. or less
water actual flow test facility. Grounding
Calibrated conditions in our water actual test facility are Note: Conduct the test according to the instruction manual.
as follows:
Fluid temperature: 20 10C CE Marking:
Ambient temperature: 20 5C CE marking is affixed on the name plate except for
Length of straight runs: 10 D or more on the up- models with any of the following specifications.
stream side; 5 D or more on Optional Code: FF1, CF1, SF2, JF3
the downstream side
Reference conditions: Similar to BS EN29104 Safety Requirement Standards:
(1993); ISO 9104 (1991) CAN/CSA C22.2 No.61010-1-04
Altitude of installation site: Max. 2000 m above sea
level
Installation category: I
Overvoltage category (Installation category)
describes a number which defines a transient
overvoltage condition. It implies the regulation for
impulse withstand voltage. I applies to electrical
equipment which is supplied from the circuit when
appropriate transient overvoltage control means
(interfaces) are provided.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 11
Pollution degree: 2 n NORMAL OPERATING CONDITIONS
Pollution degree describes the degree to which Ambient Temperature:
a solid, liquid, or gas which deteriorates dielectric
strength or surface resistivity is adhering. 2 applies General-purpose USE:
to normal indoor atmosphere. Normally, only non- 40 to +55C (40 to +131F)
conductive pollution occurs. Occasionally, however, Explosion proof type:
temporary conductivity caused by condensation must In the case of explosion proof type, read descrip-
be expected. tion of Enclosure or Ambient Temperature in
Indoor/Outdoor use HAZARDOUS AREA CLASSIFICATION
EMC Conformity Standards: *1: Minimum temperature should also be limited according
EN61326-1 Class A, Table 2 (For use in industrial to minimum fluid temperature of flow tubes specification.
Read description of Fluid Temperature and Pressure.
locations) *2: Indicator operating range: 20 to +55C (4 to +131F)
EN61326-2-3
Ambient Humidity: 0 to 100%
Pressure Equipment Directive: Lengthy continuous operation at 95% or more is not
Module: H recommended.
Type of Equipment: Piping
Fluid Conductivity:
Type of Fluid: Liquid and Gas Size 25 to 200 mm (1 to 8 in.): 10 S/cm or larger
Group of Fluid: 1 and 2 (*4) Note: Fluids with large flow noise (pure water, fluids with
General-purpose Use/Explosion Proof Type; low conductivity and low viscosity such as alcohol)
cause the output fluctuation and therefor it is impossi-
DN PS PS DN ble to measure accurately.
CATEGORY
MODEL (mm) (MPa) (MPa
(*2) (*4) Output Fluctuation:
(*1) (*1) mm)
The output fluctuates depending on the fluid condi-
AXR025G Sound tions and damping settings.
Engineering The following table shows the output fluctuation as
25 4 100
Practice a rough guideline at flow velocity near 100% of flow
AXR025C (SEP) (*3)
span (damping: 5 s)
AXR040G Size 25 to 100 mm (1 to 4 in.)
40 4 160 II
AXR040C Fluid Fluctuation (% of rate) as a rough guideline
AXR050G Conductivity Flow Span Flow Span
50 4 200 II [S/cm] 2.0 m/s 4.0 m/s
AXR050C
AXR065G 10 3.0% or less 7.0% or less
65 2 130 II 50 1.0% or less 1.0% or less
AXR065C
AXR080G 100 0.5% or less 0.5% or less
80 2 160 II
AXR080C 500 0.5% or less 0.5% or less
AXR100G Size 150 to 200 mm (6 to 8 in.)
100 2 200 II
AXR100C Fluctuation (% of rate) as a rough guideline
Fluid
AXR150G Conductivity Flow Span Flow Span
150 2 300 II [S/cm]
AXR150C 2.0 m/s 4.0 m/s
AXR200G 10 5.0% or less Non-recommendation
200 2 400 III
AXR200C 50 2.0% or less 3.0% or less
*1: PS: Maximum allowable pressure for Flowtube 100 1.0% or less 1.0% or less
DN: Nominal size
*2: For details, refer to the following. 500 0.6% or less 1.0% or less
Table 6 covered by ANNEX II of Directive 97/23/EC
(until July 18th, 2016) Measurable Flow Rate Range:
Table 6 covered by ANNEX II of Directive 2014/68/EU SI Units (Size: mm, Flow rate: m3/h)
(from July 19th, 2016) Size 0 to Min. Span Flow 0 to Max. Span Flow
*3: Article 3, paragraph 3 of Directive 97/23/EC (mm) Rate (0.3 m/s) Rate (10 m/s)
(until July 18th, 2016)
Article 4, paragraph 3 of Directive 2014/68/EU 25 0 to 0.5302 m3/h 0 to 17.671 m3/h
(from July 19th, 2016) 40 0 to 1.3572 0 to 45.23
*4: Models classified in CATEGORY II shall not be used for unsta-
50 0 to 2.1206 0 to 70.68
ble gases of Group 1.
65 0 to 3.584 0 to 119.45
SIL Certification:
AXR series are certified by TV in compliance with 80 0 to 5.429 0 to 180.95
the following standards; 100 0 to 8.483 0 to 282.74
IEC 61508: 2000; Part1 to Part7
150 0 to 19.090 0 to 636.1
Functional Safety of Electrical/electronic/programma-
ble electronic safety-related systems; SIL 2 capabil- 200 0 to 33.930 0 to 1,130.9
ity for single flowmeter use, SIL 3 capability for dual
flowmeter use.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 12
English Units (Size: in., Flow rate: GPM) *1: Do not install anything in the flowmeter that may in-
terfere with the magnetic field, electromagnetic force,
Size 0 to Min. Span Flow 0 to Max. Span Flow
or flow velocity distribution.
(in.) Rate (1 ft/s) Rate (33 ft/s)
*2: A straight run may not be required on the down-
1.0 0 to 2.335 GPM 0 to 77.80 GPM stream side of the flowmeter. However, if a down-
stream valve or other fitting causes irregularity or
1.5 0 to 5.253 0 to 175.0
deviation in flows, provide a straight run of 2D to 3D
2.0 0 to 9.337 0 to 311.2 on the downstream side.
2.5 0 to 14.59 0 to 486.2 *3: The valves shall be mounted on the downstream side
so that deviated flows do not occur in the flowtube
3.0 0 to 21.01 0 to 700.2 and to avoid startup from an empty condition.
4.0 0 to 37.35 0 to 1244
Maintaining Stable Fluid Conductivity
6.0 0 to 84.03 0 to 2800
Do not install the flowmeter at a place where fluid
8.0 0 to 149.4 0 to 4979
conductivity tends to become uneven. If chemicals
are fed on the upstream side of a magnetic flowme-
Fluid Temperature and Pressure: ter, they may affect the flow-rates indications. To
The following figure shows maximum allowable fluid avoid this situation, it is recommended that the chem-
pressure for the flowtube. Further fluid pressure ical feed ports be located on the downstream side
should also be limited according to flange rating. of the flowmeter. If it is unavoidable that chemicals
25 to 50 mm (1.0 to 2.0 in.) must be fed on the upstream side, provide a sufficient
Pressure (flange type, wafer type) length of straight run (approximately 50D or more) to
MPa(psi) 65 to 200 mm (2.5 to 8.0 in.) ensure the proper mixture of fluids.
(flange type, wafer type)
4 (580)
*1 Mounting Position
Pipes must be fully filled with liquids.
2 (290) If the pipe is empty, the output fluctuates or the Pro-
cess Alarm (Signal Overflow) occurs. The pipe must
1 (145)
be fully filled with liquid.
Piping shall be designed so as to maintain the flow-
0.1 (-14.5) tube filled with fluids.
40 10 0 40 100 130
(-40) (14) (32) (104) (212) (266) Vertical mounting is effective in such cases as when
Temperature C (F) fluids tend to separate or solid matter may be pre-
F07.ai
cipitated. When employing vertical mounting, direct
*1: For wafer types of 40 to 200 mm (1.5 to 8.0 in.), and for the fluids from the bottom to the top to ensure that
carbon steel flange types (process connection code: the pipes remain fully filled.
C**) of 150 to 200 mm (6.0 to 8.0 in.), the minimum fluid
temperature is 10C (+14F). Correct Incorrect
*2: For fluid temperature of the explosion proof type, read Correct h
Incorrect
h>0
descriptions of HAZARDOUS AREA CLASSIFICA-
TION. h
h>0
Vibration Conditions: F09.ai
9.8 m/s2 or less (frequency of 500 Hz or less)
Note: Level of vibration is in conformity with IEC 60068-2-6 Mounting Positions
(SAMA 31.1-1980).
Avoid locations with much vibration where the pipe Avoiding air bubbles.
vibration frequency is 500 Hz or more. Such a condi- If air bubbles enter a measurement pipe, the flow
tion may cause damage to the instrument. rate indication may be affected and measurement
errors may occur.
n CAUTIONS FOR INSTALLATION If the fluid contains air bubbles, arrange piping to
prevent the bubbles from accumulating in a flow-
Mounting of Flowmeters and Required Length tube.
of Straight Runs Some operations of the valve may cause low pres-
Based on JIS B 7554 and our piping condition test sure and create air bubbles in the pipes, so mount
data, we recommend the piping conditions as shown the flowtube on the upstream side of the valve to
in the following figures. avoid possible low pressure and air bubbles.
When installing two or more magnetic flowmeters on a
single pipe, provide a run of at least 10D between them. Correct Incorrect
Correct
D: Flowtube Size
Gate valve Reducer Expander Incorrect
fully open pipe pipe
Valve
F10.ai

5 D or more 2 D or more 0 is allowable 0 is allowable 10 D or more 2 D or more Avoiding Air Bubbles


90-degree bent
Tee Various valves

5 D or more 0 is allowable 5 D or more 0 is allowable 10 D or more 2 D or more


F08.ai

Required length of straight runs

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 13
Mounting Orientation n ACCESSORIES
If electrodes are perpendicular to the ground, air Centering device (wafer type only): 1 pc.
bubbles near the top or precipitates at the bottom Plug: 1 pc.
may cause measurement errors.
Ensure that the converter of an integral flowmeter
is mounted above the piping to prevent water from n TERMINAL CONFIGURATION AND
entering them. TERMINAL WIRING
Correct
General-purpose Use/Explosion Proof Type except
Incorrect Incorrect TIIS:
Terminal configuration Terminal wiring
Air bubbles
Terminal
No. Symbols Description

Water can seep
Functional grounding
Electrode Electrode Precipitates into the converter.
Power supply and
SUPPLY
+
SUPPLY
current output
+ Digital output
DO

(One output can be
F11.ai DO selected from pulse,
alarm or status outputs.)
Mounting Orientation

Location
The flowmeter should be installed away from electri- F12.ai

cal motors, transformers, inverters, and other power


sources in order to avoid interference with measure- TIIS Explosion Proof Type:
ment. Terminal configuration Terminal wiring
Install the flowmeter in a location where it is not
Terminal
exposed to direct sunlight. No. Symbols Description
Functional grounding
Grounding
SUPPLY
Class A grounding
For accurate measurement of flow rate, a reference
Power supply and
electric potential needs to be kept in the magnetic DO


SUPPLY current output
flowmeter. Therefore, the magnetic flowmeter should
Digital output
be grounded in accordance with certain specifica-
DO (One output can be
selected from pulse,
tions (grounding resistance of 100 or less, or 10
alarm or status outputs.)
or less depending on the selected explosion proof
type and option). Grounding is mandatory especially
for insulated piping such as PVC-sheathed pipes. F12_02.ai

If not, the magnetic flowmeter measures the flow


incorrectly because the reference electrical potential Recommended Power and Output Cable:
is floating. Moreover, grounding is also mandatory Use polyvinyl chloride insulated and sheathed port-
in the simultaneous outputs of current and pulse. If able power cables (JIS C3312) or equivalents.
not, the flowmeter causes a large measurement error Outer Diameter:
because the outputs interfere with each other. With no gland option;
6.5 to 12 mm (0.26 to 0.47 in.)
Applications With gland options EG and EU;
10.5 or 11.5 mm (0.41 or 0.45 in.)
For a fluid containing high concentration slurries or With gland options EP;
hard solids (such as earth and sand, metal powder, 6 to 12 mm (0.24 to 0.47 in.)
and fiber), contact of the solids on the electrode Nominal Cross Section:
surface will make the output fluctuate. Therefore, Single wire: 0.5 to 2.5 mm2
two-wire magnetic flowmeters are not suitable for Stranded wire: 0.5 to 1.5 mm2
measuring such fluids. It is recommended to use
the AXF four-wire magnetic flowmeter.
In the vicinity of an electrolysis bath, strong stray
current may flow in the fluid. It is recommended to
use the AXF four-wire magnetic flowmeter in such
an application.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 14
n WIRING EXAMPLE (General-purpose Use/Explosion Proof Type except TIIS)
Current Output, Pulse Output, Status Output and Alarm Output
(General-purpose Use/Explosion Proof Type except TIIS)
Connection Description
Current Output AXR Terminal R3[]:Load Resistance
In this case, Distributor, etc.
Communication is Cable Resistance:R1[] *9 +
+
possible Cable Resistance:R2[] *9 R3 E1
SUPPLY
(up to a distance of 2
km when a CEV cable
is used.) +
DO 0.0236 (R1 + R2 + R3) + 14.7 E1 [V] 42*10
In the case of R3 = 250 []
0.0236 (R1 + R2) + 20.6 E1 [V] 42*10

Pulse Output AXR Terminal


In this case, 0.0236(R1+R2)+14.7E2[V]42*10
No communication is Cable Resistance:R1[] *9
+
possible when a four- SUPPLY Cable Resistance:R2[] *9 E2
wire cable is used.
R *7 *1
+
DO E3:30 V DC max

+ *6
Electric
counter

*1: This supply voltage requires a power source


with a maximum output current of no less than E3/R.
Pulse Output 0.0236(R1+R2)+14.7 E4[V]30
In this case,
AXR Terminal
No communication is *7 *2
possible when a three- Cable Resistance:R1[] *9 R E4
wire cable is used. +
SUPPLY Cable Resistance:R2[] *9

+ *6
+
DO Electric
counter

*2: This supply voltage requires a power source


with a maximum output current of no less than (E4/R+0.0236).
Status Output AXR Terminal
Alarm Output 0.0236R1+R2+14.7E2[V]42*10
Cable Resistance:R1[] *9
In this case, +
No communication is SUPPLY Cable Resistance:R2[] *9 E2
possible when a four-
wire cable is used. +
DO

External Power Supply Magnetic
30 V DC,120 mA max valve

Relay
AC Power Supply
Status Output AXR Terminal 0.0236R1+R2+14.7E2[V]42*10
Alarm Output
In this case, Cable Resistance:R1[] *9 E2
No communication is +
possible when a three- SUPPLY Cable Resistance:R2[] *9

wire cable is used.
+
DO

External Power Supply
Magnetic
30 V DC,120 mA max valve
Relay
AC Power Supply

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 15
Simultaneous Current-Pulse Output (General-purpose Use/Explosion Proof Type except TIIS)
Connection Description
Simultaneous Current- When simultaneous output of current and pulse output are used, no communication is possible in some
Pulse Output cases. Read the following example 1 to 3.
Example 1
In this case, 0.0236 x (R1 + R2+ R3) + 14.7 E1 [V] 42*10
Communication is In the case of R3=250[]
0.0236 x (R1 + R2) + 20.6 E1 [V] 42*10
possible (up to a AXR Terminal
Shielded Cable
distance of 2 km when Distributor, etc.
a CEV cable is used) Cable Resistance:R1[] *9 +
+ R3[]:Load Resistance
and when a two-wire SUPPLY Cable Resistance:R2[] *9 R3 E1
shielded cable is used.
+ *3
DO *7 R E3:30 V DC max

Shielded Cable
+ *6
*8 For the shielded cables in this example, Electric
use two-wire shielded cables
separately for SUPPLY and DO. counter
No communication is possible
when a shielded cable is not used.
However, simultaneous current-pulse output is possible.
*3: This supply voltage requires a power source
with a maximum output current of no less than E3/R.
Example 2
In this case, 0.0236 x (R1 + R2+ R3) + 14.7 E1 [V] 42*10
Communication is In the case of R3=250[]
0.0236 x (R1 + R2) + 20.6 E1 [V] 42*10
possible (up to a AXR Terminal Shielded Cable
distance of 2 km when Distributor, etc.
Cable Resistance:R1[] *9 +
a CEV cable is used) + R3[]:Load Resistance
Cable Resistance:R2[] *9 R3 E1
and when a one-wire SUPPLY
shielded cable is used.
+ *4
DO *7 R E3:30 V DC max
Shielded Cable
For the shielded cables in this example,
use two-wire shielded cables + *6
*8 Electric
separately for SUPPLY and DO. counter

*4: This supply voltage requires a power source


with a maximum output current of no less than E3/R.

Example 3
+
In this case, Recorder
No communication is or other
instrument
possible when a three-
wire cable is used. 250
AXR Terminal *5
Cable Resistance:R1[] *9 R *7 E5
+
SUPPLY Cable Resistance:R2[] *9 0.0236R1+R2+20.6E5[V]30

+
DO + *6
Electric
counter
*8
*5: This supply voltage requires a power source
with a maximum output current of no less than (E5/R+0.0236).

The range of load resis- The range of load resistance R for the pulse output must basically be 1 k and 2 W. The load resistance
tance R for the pulse should be selected by calculation as shown below when proper transmission is impossible due to the
output length of cable or frequency of pulse output.

E (V) E: Supply voltage (V)


0.1
R (k) (1) f: Frequency of pulse output (kHz)
120 C (F) f (kHz)
R: Value of load resistance (k)
E2(V) C: Cable capacitance (F)
P (mW) = (2) P: Electrical power of the load resistance (mW)
R (k) Note: C 0.1 (F/km) for CEV cable
Note: The communication is possible though it might not meet a part of the HART communication specification depending on use conditions.
When using current and pulse output simultareously, the HART communication may be influenced by noise comparing analog output
only.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 16
The Wiring Examples of Digital External Indicator Using Current Output
(General-purpose Use/Explosion Proof Type except TIIS)
Connection Description
Current Output Digital External Indicator

Example 1 77.7%
Connection to digital
external indicator - +
V2 V2: Voltage between terminals of External Indicator
AXR Terminal Relaying
terminal Distributor, etc.
+
+ E1 R3[]:
SUPPLY Cable Resistance:R2[] *9 Cable Resistance:R1[] *9 R3
- Load Resistance
- Cable Resistance:R4[] *9
+
DO Transmission of AXR 0.0236 (R1 + R2 + R3 + R4) + V2 + 14.7 E1 [V] 42*10
- output might fail when In the case of R3 = 250 []
the external indicator 0.0236 (R1 + R2 + R4) + V2 + 20.6 E1 [V] 42*10
breakdown occurs.

Example 2 Analog External Indicator


Connection to analog
external indicator
Internal resistance 10 or less

- +
AXR Terminal Relaying
terminal Distributor, etc.
+
+ E1 R3[]:
SUPPLY Cable Resistance:R2[] *9 Cable Resistance:R1[] *9 R3
- Load Resistance
-
Cable Resistance:R4[] *9
+
DO 0.0236 (R1 + R2 + R3 + R4 + 10) + 14.7 E1 [V] 42*10
Transmission of AXR
- output might fail when In the case of R3 = 250 []
the external indicator 0.0236 (R1 + R2 + R4 + 10 ) + 20.6 E1 [V] 42*10
breakdown occurs.

*6: To avoid the influence of external noise, use an electric counter which fits to the pulse frequency.
*7: Resistor is not necessary in the case of an electric counter which can receive contact pulse signal directly.
*8: Ground the AXR to avoid the current output error in simultaneous current-pulse output.
*9: Calculate the cable resistance by using the following as a rough guideline: 10.9 per 1 km for the cable with the cross section of
2 mm2, 19.5 per 1 km for the cable with the cross section of 1.25 mm2.
*10: The maximum voltage is 32 V DC in the case of Lightning Protector specification (optional code A).

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 17
n WIRING EXAMPLE (TIIS Explosion Proof Type)
Current Output, Pulse Output, Status Output and Alarm Output (TIIS Explosion Proof Type)
Connection Description
Current Output Hazardous area Non-hazardous area
In this case, AXR Terminal
Communication is JIS Class A
Distributor, etc.
possible Cable Resistance:R1[] *9 +
(up to a distance of 2 +
SUPPLY Cable Resistance:R2[] *9 R3 E1
km when a CEV cable
is used.) + Grounding resistance
DO R3[]:Load Resistance
of 100 or less (When
the optional code A is 0.0236 (R1 + R2 + R3) + 14.7 E1 [V] 42*10
selected: grounding In the case of R3 = 250 []
resistance of 10 ) 0.0236 (R1 + R2) + 20.6 E1 [V] 42*10
Pulse Output Hazardous area Non-hazardous area
In this case,
No communication is AXR Terminal 0.0236(R1+R2)+14.7E2[V]42*10
possible when a five-
JIS Class A
wire cable is used. Cable Resistance:R1[] *9
+ E2
SUPPLY Cable Resistance:R2[] *9

R *7 *1
+
DO E3:30 V DC max

+ *6
Electric
Grounding resistance counter
of 100 or less (When
the optional code A is *1: This supply voltage requires a power
selected: grounding source with a maximum output current
resistance of 10 ) of no less than E3/R.
Pulse Output Hazardous area Non-hazardous area
In this case,
No communication is 0.0236(R1+R2)+14.7 E4[V]30
possible when a four- AXR Terminal
JIS Class A *7 *2
wire cable is used. R E4
Cable Resistance:R1[] *9
+
SUPPLY Cable Resistance:R2[] *9

+ *6
+
DO Electric
Grounding resistance counter
of 100 or less (When
the optional code A is *2: This supply voltage requires a power
selected: grounding source with a maximum output current
resistance of 10 ) of no less than (E4/R+0.0236).
Status Output Hazardous area Non-hazardous area
Alarm Output AXR Terminal
In this case, 0.0236R1+R2+14.7E2[V]42*10
No communication is JIS Class A
possible when a five- + E2
SUPPLY Cable Resistance:R1[] *9
wire cable is used.
Cable Resistance:R2[] *9
+
DO

Grounding resistance External
Magnetic
of 100 or less (When Power Supply valve
the optional code A is 30 V DC,
selected: grounding Relay
120 mA max
resistance of 10 ) AC Power Supply

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 18

Connection Description
Status Output Hazardous area Non-hazardous area
Alarm Output
In this case, 0.0236R1+R2+14.7E2[V]42*10
No communication is AXR Terminal
JIS Class A
possible when a four-
wire cable is used. Cable Resistance:R1[] *9 E2
+
SUPPLY Cable Resistance:R2[] *9

+
DO

Grounding resistance External Magnetic
of 100 or less (When Power Supply valve
the optional code A is 30 V DC, Relay
selected: grounding 120 mA max
resistance of 10 ) AC Power Supply

Simultaneous Current-Pulse Output (TIIS Explosion Proof Type)


Connection Description
Simultaneous Current- When simultaneous output of current and pulse output are used, no communication is possible in some
Pulse Output cases. Read the following example 1 to 3.
Example 1
In this case, Hazardous area Non-hazardous area
Communication is
0.0236 x (R1 + R2+ R3) + 14.7 E1 [V] 42*10
possible (up to a In the case of R3=250[]
distance of 2 km when 0.0236 x (R1 + R2) + 20.6 E1 [V] 42*10
a CEV cable is used) AXR Terminal Shielded Cable JIS Class A R3[]:Load Resistance
and when a two-wire
Distributor, etc.
or three-wire shielded Cable Resistance:R1[] *9 +
cable is used. +
SUPPLY Cable Resistance:R2[] *9 R3 E1

+ *3
DO *7 R E3:30 V DC max

Shielded Cable + *6
*8
For the shielded cables in this example, Electric
use two-wire shielded cables counter
separately for SUPPLY and DO.
Grounding resistance of 100 or less No communication is possible
(When the optional code A is selected: when a shielded cable is not used.
grounding resistance of 10 ) However, simultaneous current-pulse output is possible.
*3: This supply voltage requires a power source with a maximum output current of no less than E3/R.

Example 2
In this case, Hazardous area Non-hazardous area
Communication is pos-
0.0236 x (R1 + R2+ R3) + 14.7 E1 [V] 42*10
sible (up to a distance In the case of R3=250[]
of 2 km when a CEV 0.0236 x (R1 + R2) + 20.6 E1 [V] 42*10
cable is used) and Shielded Cable
AXR Terminal
when a one-wire or Cable Resistance:R1[] *9 JIS Class A R3[]:Load Resistance
two-wire shielded cable Distributor, etc.
is used. Cable Resistance:R2[] *9 +
+
SUPPLY R3 E1

+ *4
DO *7 R E3:30 V DC max
Shielded Cable
For the shielded cables in this example, + *6
*8 Electric
use two-wire shielded cables counter
separately for SUPPLY and DO.
Grounding resistance of 100 or less
(When the optional code A is selected:
grounding resistance of 10 )
*4: This supply voltage requires a power source with a maximum output current of no less than E3/R.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 19

Connection Description
Example 3
In this case, Hazardous area Non-hazardous area 0.0236R1+R2+20.6E5[V]30
No communication is +
Recorder
possible when a four- or other
wire cable is used. instrument
AXR Terminal 250
JIS Class A *5
Cable Resistance:R1[] *9 R *7 E5
+
SUPPLY Cable Resistance:R2[] *9

+
DO + *6
Electric
Grounding resistance counter
*8
of 100 or less (When
the optional code A is *5: This supply voltage requires a
selected: grounding power source with a maximum
resistance of 10 ) output current of no less than (E5/R+0.0236).

The range of load resis- The range of load resistance R for the pulse output must basically be 1 k and 2 W. The load resistance
tance R for the pulse should be selected by calculation as shown below when proper transmission is impossible due to the
output length of cable or frequency of pulse output.
E (V) E: Supply voltage (V)
0.1
R (k) (1) f: Frequency of pulse output (kHz)
120 C (F) f (kHz) R: Value of load resistance (k)
2 C: Cable capacitance (F)
E (V)
P (mW) = (2) P: Electrical power of the load resistance (mW)
R (k) Note: C 0.1 (F/km) for CEV cable
Note: The communication is possible though it might not meet a part of the HART communication specification depending on use conditions.
When using current and pulse output simultareously, the HART communication may be influenced by noise comparing analog output
only.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 20
The Wiring Examples of Digital External Indicator Using Current Output
(TIIS Explosion Proof Type)
Connection Description
Current Output
Hazardous area Non-hazardous area Digital External Indicator Transmission of AXR
output might fail when
Example 1
77.7% the external indicator
Connection to digital
breakdown occurs.
external indicator
- V2 +
V2: Voltage between terminals of External Indicator
AXR Terminal Relaying
terminal
JIS Class A Distributor, etc.
+ +
SUPPLY Cable Resistance:R2[] *9 Cable Resistance:R1[] *9 R3 E1
- -
Cable Resistance:R4[] *9
+
DO R3[]:Load Resistance
-
Grounding resistance 0.0236 (R1 + R2 + R3 + R4) + V2 + 14.7 E1 [V] 42*10
of 100 or less In the case of R3 = 250 []
(When the optional 0.0236 (R1 + R2 + R4) + V2 + 20.6 E1 [V] 42*10
code A is selected:
grounding resistance
of 10 )

Example 2
Connection to analog Hazardous area Non-hazardous area Analog External Indicator
external indicator
Internal resistance 10 or less
Transmission of AXR
- + output might fail when
the external indicator
AXR Terminal Relaying
terminal breakdown occurs.
JIS Class A Distributor, etc.
+
+ Cable Resistance:R2[] *9 Cable Resistance:R1[] *9 E1
SUPPLY - R3
-
Cable Resistance:R4[] *9
+
DO R3[]:Load Resistance
- Grounding resistance
of 100 or less 0.0236 (R1 + R2 + R3 + R4 + 10) + 14.7 E1 [V] 42*10
(When the optional In the case of R3 = 250 []
code A is selected: 0.0236 (R1 + R2 + R4 + 10 ) + 20.6 E1 [V] 42*10
grounding resistance
of 10 )

*6: To avoid the influence of external noise, use an electric counter which fits to the pulse frequency.
*7: Resistor is not necessary in the case of an electric counter which can receive contact pulse signal directly.
*8: Ground the AXR to avoid the current output error in simultaneous current-pulse output.
*9: Calculate the cable resistance by using the following as a rough guideline: 10.9 per 1 km for the cable with the cross section of
2 mm2, 19.5 per 1 km for the cable with the cross section of 1.25 mm2.
*10: The maximum voltage is 32 V DC in the case of Lightning Protector specification (optional code A).

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 21
n MODEL AND SUFFIX CODE
Wafer Type

Model Suffix Code Description Applicable Model


AXR025 ---------------------------------------- Size 25 mm (1 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR040 ---------------------------------------- Size 40 mm (1.5 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR050 ---------------------------------------- Size 50 mm (2 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR065 ---------------------------------------- Size 65 mm (2.5 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR080 ---------------------------------------- Size 80 mm (3 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR100 ---------------------------------------- Size 100 mm (4 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR150 ---------------------------------------- Size 150 mm (6 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
AXR200 ---------------------------------------- Size 200 mm (8 in.) Two-wire Magnetic Flowmeter Integral Flowmeter
Use G ---------------------------------------- General-Purpose Use
C ---------------------------------------- Explosion proof Type (*1)
Output Signal -D ----------------------------------- Integral Flowmeter with 4 to 20 mA DC Output and digital
and communication (BRAIN protocol)
Communication -E ----------------------------------- Integral Flowmeter with 4 to 20 mA DC Output and digital
communication (HART protocol) (*12)
-J ----------------------------------- Integral Flowmeter with 4 to 20 mA DC Output with digital
communication (HART 5/HART 7 protocol) (*13)
Power Supply 1 --------------------------------- Integral Flowmeter Operating voltage range 14.7 to 42 V DC
Two-wire system
Lining (*2) A ------------------------------ Fluorocarbon PFA
Electrode Material (*2) L --------------------------- JIS SUS316L (AISI 316L SS/EN 1.4404 Equivalent)
P --------------------------- Platinum-iridium
H --------------------------- Hastelloy C276 Equivalent
T --------------------------- Tantalum
Electrode Structure 1 ------------------------ Non-replaceable
Grounding Ring and N -------------------- None (*3)
Grounding Electrode S -------------------- JIS SUS316 (AISI 316 SS/EN 1.4401 Equivalent)
Material (*2) L -------------------- JIS SUS316L or ASTM 316L (AISI 316L SS/EN 1.4404 Equivalent)
P -------------------- Platinum-iridium
H -------------------- Hastelloy C276 Equivalent
T -------------------- Tantalum
Process Connection -AA1 ------------- ANSI Class 150 Wafer
(*4) (*5) -AA2 ------------- ANSI Class 300 Wafer
-AD1 ------------- DIN PN 10 Wafer (*6) Size 200 mm (8.0 in)
-AD2 ------------- DIN PN 16 Wafer (*6) Size 65 mm (2.5 in.) to
200 mm (8.0 in.)
-AD4 ------------- DIN PN 40 Wafer (*6) Size 25 mm (1.0 in.) to
50 mm (2.0 in.)
-AJ1 ------------- JIS 10K Wafer
-AJ2 ------------- JIS 20K Wafer
-AG1 ------------- JIS F12 (JIS75M) Wafer Size 80 mm (3.0 in.) to
200 mm (8.0 in.)
Lay Length 1 --------------- Lay length code 1 (*7) Size 80 mm (3.0 in.) to
200 mm (8.0 in.)
2 --------------- Lay length code 2 (*8)
Electrical Connection (*9) -0 ----------- JIS G1/2 female
-2 ----------- ANSI 1/2 NPT female
-4 ----------- ISO M20 1.5 female
Indicator (*10)(*11) 1 --------- Integral Flowmeter with indicator (Horizontal)
2 --------- Integral Flowmeter with indicator (Vertical)
N -------- Integral Flowmeter without indicator
Calibration B ----- Always B
Options / Optional code (Read the Table of Optional Specifications)

*1: For explosion proof types, specify types of explosion proof certification using the optional codes.
For the TIIS flameproof type, select optional code G11. Available only for JIS G1/2 female electrical connections.
Available only for wiring of using a flameproof packing adapter approved by Yokogawa.
The flameproof metal conduit wiring for TIIS flameproof type is not permitted.
*2: Users must consider the characteristics of selected wetted parts material and influence of process fluids.
The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contami-
nate the users process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite,
and high-temperature steam (150C [302F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*3: Available only for metal piping.
*4: Mating dimensions are based on standards as follow:
ANSI: ASME B 16.5, DIN: DIN 2501, JIS: JIS B 2220 and JIS G 3443-2

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 22
*5: Allowable fluid pressure should also be limited according to fluid temperature and pressure.
*6: Even when DIN PN10, 16, or 40 is required for a model of size 25 to 50 mm (1.0 to 2.0 in.), select PN40 (Process connection code:
AD4) because there is no difference in the dimensions of the mating faces.
Even when DIN PN10 or 16 is required for a model of size 65 to 150 mm (2.5 to 6.0 in.), select PN16 (Process connection code: AD2)
because there is no difference in the dimensions of the mating faces.
*7: The dimensions of lay length code 1 are the same as those of the PFA lining standard lay length (lay length code 1) in the AXF series.
For details, read EXTERNAL DIMENSIONS.
*8: Excluding the size of 65 mm, dimensions of lay length code 2 are the same as those of PFA lining replacement models (lay length code
2) in AXF series. Lay lengths for special gaskets (optional codes GA, GC, GD) are different. For details, read EXTERNAL DIMEN-
SIONS.
*9: For an explosion proof type except for TIIS, select ANSI 1/2 NPT female or ISO M20 1.5 female.
For the TIIS flameproof type, select JIS G1/2 female and optional code G11.
*10: Select from among the figures at the right.

1 2 N

F23.ai

*11: In the case of the TIIS flameproof type, select with indicator (code 1 or 2).
*12: Output signal code -E: HART 5.(Output signal code -J is recommended for HART communication.)
*13: Output signal code -J: HART 5 or HART 7 selectable. Specify HART 5 or HART 7 when ordering.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 23
Flange Type

Model Suffix Code Description Applicable Model


AXR025 ----------------------------------- Size 25 mm (1 in.)Two-wire Magnetic Flowmeter Integral Flowmeter
AXR040 ----------------------------------- Two-wire Magnetic Flowmeter
Size 40 mm (1.5 in.) Integral Flowmeter
AXR050 ----------------------------------- Size 50 mm (2 in.)Two-wire Magnetic Flowmeter Integral Flowmeter
AXR065 ----------------------------------- Two-wire Magnetic Flowmeter
Size 65 mm (2.5 in.) Integral Flowmeter
AXR080 ----------------------------------- Size 80 mm (3 in.)Two-wire Magnetic Flowmeter Integral Flowmeter
AXR100 ----------------------------------- Two-wire Magnetic Flowmeter
Size 100 mm (4 in.) Integral Flowmeter
AXR150 ----------------------------------- Two-wire Magnetic Flowmeter
Size 150 mm (6 in.) Integral Flowmeter
AXR200 ----------------------------------- Two-wire Magnetic Flowmeter
Size 200 mm (8 in.) Integral Flowmeter
Use G ----------------------------------- General-Purpose Use
C ----------------------------------- Explosion proof Type (*1)
Output Signal -D -------------------------------- Integral Flowmeter with 4 to 20 mA DC Output and digital
and communication (BRAIN protocol)
Communication -E -------------------------------- Integral Flowmeter with 4 to 20 mA DC Output and digital
communication (HART protocol) (*11)
-J -------------------------------- Integral Flowmeter with 4 to 20 mA DC Output with digital
communication (HART 5/HART 7 protocol) (*12)
Power Supply 1 ------------------------------ Integral Flowmeter Operating voltage range 14.7 to 42 V DC
Two-wire system
Lining (*2) A --------------------------- Fluorocarbon PFA
Electrode L ------------------------ JIS SUS316L (AISI 316L SS/EN 1.4404 Equivalent)
Material (*2) P ------------------------ Platinum-iridium
H ------------------------ Hastelloy C276 Equivalent
T ------------------------ Tantalum
Electrode Structure 1 --------------------- Non-replaceable
Grounding Ring and N ------------------ None (*3)
Grounding Electrode S ------------------ JIS SUS316 (AISI 316 SS/EN 1.4401 Equivalent)
Material (*2) L ------------------ JIS SUS316L or ASTM 316L (AISI 316L SS/EN 1.4404 Equivalent)
P ------------------ Platinum-iridium
H ------------------ Hastelloy C276 Equivalent
T ------------------ Tantalum
Process Connection -BA1 ----------- ANSI Class 150 Flange JIS SUS304 or SUSF304
(*4) (*5) -BA2 ----------- ANSI Class 300 Flange JIS SUS304 or SUSF304
-BD1 ----------- DIN PN 10 Flange(JIS SUS304 or SUSF304) (*6) Size 200 mm (8.0 in.)
-BD2 ----------- DIN PN 16 Flange JIS SUS304 or SUSF304 (*6) Size 65 mm (2.5 in.) to
200 mm (8.0 in.)
-BD4 ----------- DIN PN 40 Flange JIS SUS304 or SUSF304 (*6) Size 25 mm (1.0 in.) to
50 mm (2.0 in.)
-BJ1 ----------- JIS 10K Flange JIS SUS304 or SUSF304
-BJ2 ----------- JIS 20K Flange JIS SUS304 or SUSF304
-BG1 ----------- JIS F12 (JIS75M) Flange JIS SUS304 or SUSF304 Size 80 mm (3.0 in.) to
200 mm (8.0 in.)
-CA1 ----------- ANSI Class 150 Flange (Carbon Steel) Size 150 mm (6.0 in.) to 200
mm (8.0 in.), Not available
for TIIS flameproof type.
-CA2 ----------- ANSI Class 300 Flange (Carbon Steel) Size 150 mm (6.0 in.) to 200
mm (8.0 in.), Not available
for TIIS flameproof type.
-CD1 ----------- DIN PN 10 Flange (Carbon Steel) (*6) Size 200 mm (8.0 in.), Not
available for TIIS flameproof
type.
-CD2 ----------- DIN PN 16 Flange (Carbon Steel) (*6) Size 150 mm (6.0 in.) to 200
mm (8.0 in.), Not available
for TIIS flameproof type.
-CJ1 ----------- JIS 10K Flange (Carbon Steel) Size 150 mm (6.0 in.) to 200
mm (8.0 in.), Not available
for TIIS flameproof type.
-CJ2 ----------- JIS 20K Flange (Carbon Steel) Size 150 mm (6.0 in.) to 200
mm (8.0 in.), Not available
for TIIS flameproof type.
-CG1 ---------- JIS F12 (JIS75M) Flange (Carbon Steel) Size 150 mm (6.0 in.) to 200
mm (8.0 in.), Not available
for TIIS flameproof type.
Lay Length 1 -------------Lay length code 1 (*7)
Electrical Connection (*8) -0 --------- JIS G1/2 female
-2 --------- ANSI 1/2 NPT female
-4 --------- ISO M20 1.5 female
Indicator (*9)(*10) 1 ------- Integral Flowmeter with indicator (Horizontal)
2 ------- Integral Flowmeter with indicator (Vertical)
N ------- Integral Flowmeter without indicator
Calibration B ---- Always B
Options / Optional code (Read the Table of Optional Specifications)

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 24
*1: For explosion proof types, specify types of explosion proof certification using the optional codes.
For the TIIS flameproof type, select optional code G11. Available only for JIS G1/2 female electrical connections.
Available only for wiring of using a flameproof packing adapter approved by Yokogawa.
The flameproof metal conduit wiring for TIIS flameproof type is not permitted.
*2: Users must consider the characteristics of selected wetted parts material and influence of process fluids.
The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage
to plant facilities. It is also possible that the instrument itself can be damaged and that fragments from the instrument can contami-
nate the users process fluids. Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen
sulfide, sodium hypochlorite, and high-temperature steam (150C [302F] or above). Contact Yokogawa for detailed information of
the wetted parts material.
*3: Available only for metal piping.
*4: Mating dimensions are based on standards as follow:
ANSI:ASME B 16.5, DIN: DIN 2501, JIS:JIS B 2220 and JIS G 3443-2
*5: Allowable fluid pressure should also be limited according to fluid temperature and pressure.
*6: Even when DIN PN10, 16, or 40 is required for a model of size 25 to 50 mm (1.0 to 2.0 in.), select PN40 (Process connection codes:
BD4) because there is no difference in the dimensions of the mating faces.
Even when DIN PN10 or 16 is required for a model of size 65 to 150 mm (2.5 to 6.0 in.), select PN16 (Process connection codes: BD2)
because there is no difference in the dimensions of the mating faces.
*7: The dimensions of lay length code 1 are the same as those of the PFA lining standard lay length (lay length code 1) in the AXF series.
For details, read EXTERNAL DIMENSIONS.
*8: For an explosion proof type except for TIIS, select ANSI 1/2 NPT female or ISO M20 1.5 female.
For the TIIS flameproof type, select JIS G1/2 female and optional code G11.
*9: Select from among the figures at the right.

1 2 N

F23.ai

*10: In the case of the TIIS flameproof type, select with indicator (code 1 or 2).
*11: Output signal code -E: HART 5.(Output signal code -J is recommended for HART communication.)
*12: Output signal code -J: HART 5 or HART 7 selectable. Specify HART 5 or HART 7 when ordering.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 25
n OPTIONAL SPECIFICATIONS
Available : Not available

Applicable
Model
Explosion
General
proof
Item Specifications Code

AXR***G

AXR***C
A lightning protector is built into the power supply and digital output terminals.
Lightning
Protector
Supply voltage: 14.7 to 32 V DC A
Allowable current: Max 600 A (8/20 s)
The current output is set to 3.2 mA (-5%) or less during System Alarms (hardware
failure), Process Alarms and Setting Alarms.
Down-scale of Standard products are delivered with a setting of 21.6 mA (110%) or more during
output status at System Alarms, Process Alarms and Setting Alarms. C1
alarms (Burnout) Note: In the case of style:S1 with optional code C1, the current output is set up to 3.2
mA or less during System Alarms, and 3.8 mA during Process Alarms and Setting
Alarms.
The flow rate span, transmission pulse weight, and totalizer display pulse weight can
be set in terms of mass unit. Specify the density of the process fluid when ordering
in addition to the mass flow rate span, transmission pulse weight (for mass unit), and
totalizer display pulse weight (for mass unit).
1. Density
a. Available density Numerics:
Specify the numeric within the value of 500 to 2000 kg/m3, 4.2 to 16.7 lb/gal,
or 31.2 to 124.8 lb/cf. And it can be up to five digits, to a maximum of 32000
ignoring the decimal point. A fraction is limited to the fourth decimal place.
b. Available density units: kg/m3, lb/gal, lb/cf
Example: A water density is about 1000kg/m3. In this case specify 1000kg/m3.
However a density is changed by temperature.
Specify the actual density.
Mass Unit (The 1000kg/m3 is equivalent to 8.345lb/gal and 62.43lb/cf.)
Setting MU
2. The mass flow rate span, transmission pulse weight, and totalizer display pulse
weight
a. Available density Numerics:
Specify the numeric within the value of 0.0001 to 32000. And it can be up to
five digits, to a maximum of 32000 ignoring the decimal point. A fraction is
limited to the fourth decimal place.
b. Mass Units Available mass units: t, kg, g, klb, lb
Available time units: /d, /h, /min, /s

Note1: In the case of specifying the mass flow span, calculate the volumetric flow span
by the setting density, and specify the available value in the mass flow span.
Note2: In the case of transmission pulse weight and totalizer display pulse weight,
specify the mass unit which was specified as the flow unit.
Waterproof Waterproof glands are attached to the electrical connections.
Glands Available only for JIS G1/2 female electric connections. EG

Waterproof
Waterproof glands with union joints are attached to the electrical connections. Avail-
Glands with
able only for JIS G1/2 female electric connections. EU
Union Joints
Plastic glands are attached to the electrical connections.
Plastic Glands
Available only for JIS G1/2 female electric connections. EP

Mirror finishing on the PFA lining inside of the tube to the smoothness lining.
The Ra is average of measured values on several points.
Mirror Finished
PFA Lining
Size 150 to 200 mm (6 to 8 in): Ra 0.05 to 0.15 m PM
Mirror finished PFA lining is standard for size 25 to 100 mm (1 to 4 in.) and optional
for size 150 to 200 mm (6 to 8 in.) specified by optional code PM.
A pendant tag plate of JIS SUS304 (AISI 304 SS/EN 1.4301 equivalent) is provided.
Stainless Steel Choose this option when a pendant tag plate is required in addition to the standard
Tag Plate nameplate with the tag number inscribed on it. SCT
Dimension (Height Width): Approx. 12.5 (4.92) 40 (15.7) mm (inch)
+90 degrees rotated converter to change the direction of the electrical connection. RA
Direction change
of the electrical +180 degrees rotated converter to change the direction of the electrical connection. RB
connection (*1)
90 degrees rotated converter to change the direction of the electrical connection. RC

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 26

Applicable
Model
Explosion
General
proof
Item Specifications Code

AXR***G

AXR***C
Bolts and nuts: Carbon steel;
Gaskets: Chloroprene rubber (*3) BCC

Bolts, nuts, and gaskets Bolts and nuts: Carbon steel;


Gaskets: PTFE-sheathed non-asbestos (*4) BCF
are provided for wafer
Bolts, Nuts, and connections. Available Bolts: JIS SUS304 (AISI 304 SS stainless steel equivalent);
Gaskets (*2) only for ANSI 150, Nuts: JIS SUS403 (AISI 403 SS stainless steel equivalent); BSC
JIS10K, or, JIS20K Gaskets: Chloroprene rubber (*3)
wafer connections.
Bolts: JIS SUS304 (AISI 304 SS stainless steel equivalent);
Nuts: JIS SUS403 (AISI 403 SS stainless steel equivalent); BSF
Gaskets: PTFE-sheathed non-asbestos (*4)
Viton gaskets for use with PVC piping.
Allowable temperature and pressure are equivalent to Valqua #4010, special fluor- GA
orubber not mixed.
Acid-resistant Viton gaskets for use with PVC piping.
Special Gaskets
(*5)
Allowable temperature and pressure are equivalent to Valqua #4010, special fluor- GC
orubber mixed (mixing #D2470).
Alkali-resistant Viton gaskets for use with PVC piping.
Allowable temperature and pressure are equivalent to Valqua #4010, special fluor- GD
orubber mixed (mixing #RCD970).
Electrodes, linings, and grounding rings are assembled and packed with polyethyl-
Oil-prohibited
Use
ene after being cleaned with water and acetone and dried with air. K1
The label OIL FREE is affixed.
Oil-prohibited Electrodes, linings, and grounding rings are assembled and packed with polyethyl-
Use with ene including desiccants after being cleaned with water and acetone and dried with
Dehydrating air. K5
Treatment The label OIL & WATER FREE is affixed.
Epoxy Resin Epoxy resin coating which has alkali-resistance instead of standard polyurethane
Coating resin coating. The color is same as standard type. X1

Three-layer coating (polyurethane coating on two-layer epoxy resin coating) in the


High Anti-corro-
sion Coating
same range as that for the standard coating. The color is same as standard type. X2
Salt/alkali/acid/weather-resistance.
Material Reproduced material certificates for pipe, electrodes, grounding rings/grounding
Certificate electrodes, flanges or mini flanges. M01

The test verifies the absence of leaks by applying the following water pressures
(which are determined under process connection conditions) to linings for ten min-
utes. Test results are described in a test certificate (QIC).
Process Connection: Water Pressure:
Hydrostatic Test
ANSI Class 150, DIN PN10, JIS 10K 1.5 MPa T01
ANSI Class 300, DIN PN16, JIS 20K 3.0 MPa
DIN PN40 6.0 MPa
JIS F12 1.25 MPa
Level 2: The Declaration and the Calibration Equipment List are issued. L2
Calibration Cer- Level 3: The Declaration and the Primary Standard List are issued. L3
tificate
Level 4: The Declaration and the Yokogawa Measuring Instruments Control System
are issued. L4

With a vent hole provided for permeable fluids (such as nitric acid, hydrofluoric acid,
Vent Hole or sodium hydroxide at high temperature). H
Available only for a flange type tube.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 27

Applicable
Model
Explosion
General
proof
Item Specifications Code

AXR***G

AXR***C
A flow test near 0, 25, 50, 75, and 100% of the user-specified span is performed
instead of the standard flow test and a test certificate (QIC) is submitted. Specify the
span flow rate and unit when placing an order.
Specify the span (100% flow span) whose corresponding flow velocity lies between
1.0 to 10 m/s and that is less than the maximum line capacity. Selectable range of
flow rate span is showing below.
Five-point
Size: mm (in.) Selectable range of flow rate span: m3/h
Calibration in
User-specified
(Flow rate span velocity: m/s) SC
25 (1) 1.77 (1.0) to 11 (6.22)
Span (*8)
40 (1.5) 4.53 (1.0) to 28 (6.30)
50 (2) 7.07 (1.0) to 56 (7.92)
65 (2.5) 12.0 (1.0) to 80 (6.70)
80 (3) 18.1 (1.0) to 126 (6.96)
100 (4) 28.3 (1.0) to 190 (6.72)
150 (6) 63.6 (1.0) to 380 (5.97)
200 (8) 113 (1.0) to 670 (5.92)
Bar-magnet for
operation of
magnet switches
Bar-magnet for operation of magnet switches, with a case. BM
(*6)
ATEX ATEX Explosion proof
Certification Read HAZARDOUS AREA CLASSIFICATION
KF2

FM Explosion proof
FM Approval
Read HAZARDOUS AREA CLASSIFICATION
FF1

CSA CSA Explosion proof


Certification Read HAZARDOUS AREA CLASSIFICATION
CF1

IECEx IECEx Explosion proof


Certification Read HAZARDOUS AREA CLASSIFICATION
SF2

TIIS flameproof
TIIS Certification Read HAZARDOUS AREA CLASSIFICATION JF3
(Need to select optional code G11.)

Flameproof One flameproof packing adapter and one blind plug. G11
packing adapter
for TIIS Flame-
proof Type (*7) One flameproof packing adapter addition G32

*1:
+90-degree +180-degree 90-degree
rotation rotation rotation
Standard
Optional Code Optional Code Optional Code
RA RB RC
Electrical Connection
Connection

Indicator

Indicator
Electrical

*2: When specifying the optional code BCC or BSC, it is advisable to specify the optional code GA, GC, or GD at the same time to prevent
potential leakage caused by the difference in elasticity between the flowtube and chloroprene gaskets.
*3: Allowable temperature and pressure with the optional code BCC or BSC (only for Gaskets: Chloroprene rubber) are equivalent to
Valqua #2010.
*4: Allowable temperature and pressure with the optional code BCF or BSF (only for Gaskets: PTFE-sheathed non-asbestos) are equiva-
lent to Valqua #7030 (S).
*5: Read description of Gasket in the Wetted Part Material.
Special gaskets are inserted between the flowtube and the grounding ring or grounding electrode.
*6: Keep the bar-magnet in the case because of the powerful magnetic force.
*7: For the TIIS flameproof type, select optional code G11. In case of two flameproof packing adapters, select optional code G32 with G11.
Available only for JIS G1/2 female electric connection.
*8: Standard flow test condition is follows;
- General-purpose use (25 to 200 mm)/ Exprosion proof type (25 to 100 mm): span; 2 m/s, test point; 0, 30, 100%
- Exprosion proof type (150, 200 mm): span; 2 m/s, test point; 0, 35, 100%

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 28
n EXTERNAL DIMENSIONS
Lay Length Code 1, AXR080-AXR100, Wafer Type
164 (6.46)*1 Unit: mm (approx. inch)
28 154(6.06)
(1.10) 33 70(2.76) 33 *1
90(3.54)
AXR080 G (1.30) 18.5(0.73) (1.30)
1 A 1 A 1
AXR100 C Ground Terminal

128(5.04)
(M4)

(2.87) (1.93)
49
73
Hi
D
Size code 080 100 )
(d
80 100
Size (3) (4)

H1
Lining code A A
Face-to- *2 120 150
face length L (4.72) (5.91)
Outside 129 155 W
D
dia. (5.08) (6.10) L*2
Inter diameter of 77 102
Grounding ring d (3.03) (4.02) *1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
129 155 *2: Depending on the selection of grounding ring code and optional code, add the following
Width W (5.08) (6.10) value to L (face-to-face length).
157 183
Height H1
(6.18) (7.20) Grounding Ring Code S, L, H P, T N
Max. 319 345 None +0 +26 (1.02) -2 (0.08)
Height Hi (12.54) (13.56) Optional
5.8 8.1 Code GA, GC, GD
Weight kg (lb) +8 (0.31) +30 (1.18)
(12.8) (17.9) (Special Gaskets) F28.ai

Lay Length Code 1, AXR150-AXR200, Wafer Type


Unit: mm (approx. inch)
164 (6.46) *1
28 154 (6.06)
(1.10) 33 70(2.76) 33*1
(1.93)

90 (3.54)
49

(1.30) 18.5(0.73) (1.30)

Ground Terminal
128 (5.04)

(M4)

AXR150 G
1 A 1 A 1
(2.87)

AXR200 C
73
D

)
(d
Hi

Size code 150 200


H1

150 200
Size (6) (8)
Lining code A A
Face-to- *2 200 250
face length L (7.87) (9.84)
Outside 202 252 L *2
D W
dia. (7.95) (9.92)
Inter diameter of 146.1 193.6
Grounding ring d (5.75) (7.62) *1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
220 272 *2: Depending on the selection of grounding ring code and optional code, add the following
Width W (8.66) (10.71) value to L (face-to-face length).
243 293
Height H1
(9.57) (11.54) Grounding Ring Code S, L, H P, T N
Max. 405 455 None +0 +32 (1.26) -2 (0.08)
Height Hi (15.93) (17.89) Optional
15.9 23.5 Code GA, GC, GD
Weight kg (lb) +10 (0.39) +38 (1.5)
(35.1) (51.8) (Special Gaskets) F28_02.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 29
Lay Length Code 2, AXR025, Wafer Type
Unit: mm (approx. inch)
164 (6.46)*1

28
G (1.10)
AXR025 1 A 1 A 2 33 70(2.76) 33*1
154 (6.06)
C 90(3.54)
(1.30) 18.5(0.73) (1.30)

Ground Terminal

128 (5.04)
(M4)

(2.87) (1.93)
49
Size code 025

Hi

73
Size 25 (1) D

H1
Lining code A
Face-to- *2 93 (d
)
face length L (3.66)
Outside D 67.5
dia. (2.66) W L*2
Inter diameter of 28
Grounding ring d (1.10) *1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
74.5 *2: Depending on the selection of grounding ring code and optional code, add the following
Width W
(2.93) value to L (face-to-face length).
92
Height H1 Grounding Ring Code S, L, H P, T N
(3.62)
Max. 253.5 None +0 +22 (0.87) -2 (0.08)
Height Hi (9.98) Optional
3.6 Code GA, GC, GD
Weight kg (lb) +8 (0.31) +26 (1.02)
(7.8) (Special Gaskets)
F29.ai

Lay Length Code 2, AXR040-AXR065, Wafer Type


Unit: mm (approx. inch)
164 (6.46)*1

28 154 (6.06)
(1.10)
33 70(2.76) 33*1 90(3.54)
AXR040 (1.30) 18.5(0.73) (1.30)
G Ground
AXR050 1 A 1 A 2 Terminal
C
128 (5.04)

AXR065 (M4)
(2.87) (1.93)
73 49
Hi

Size code 040 050 065 D


(d)
H1

40 50 65
Size (1.5) (2) (2.5)
Lining code A A A
W L*2
Face-to- *2 106 120 120
face length L (4.17) (4.72) (4.72)
Outside D 86 99 117
dia. (3.39) (3.90) (4.61)
*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in
Inter diameter of 41 53 66
the figure.
Grounding ring d (1.61) (2.09) (2.60)
*2: Depending on the selection of grounding ring code and optional code, add the
86 99 117
Width W (3.90) (4.61) following value to L (face-to-face length).
(3.39)
111 129 147
Height H1
(4.37) (5.08) (5.79) Grounding Ring Code S, L, H P, T N
Max. 273 291 309
Hi None +0 +22 (0.87) -2 (0.08)
Height (10.73) (11.44) (12.17) Optional
4.1 4.8 5.4 Code GA, GC, GD
Weight kg (lb) +8 (0.31) +26 (1.02)
(9.1) (10.7) (11.9) (Special Gaskets)
F30.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 30
Lay Length Code 2, AXR080-AXR100, Wafer Type
Unit: mm (approx. inch)

164 (6.46)*1

28 154 (6.06)
(1.10) 33 70(2.76) 33*1
AXR080 G 90(3.54)
1 A 1 A 2 (1.30) 18.5(0.73) (1.30)
AXR100 C
Ground Terminal

128 (5.04)
(M4)

(2.87) (1.93)
49
73
Size code

Hi
080 100

D
)
80 100 (d
Size (3) (4)

H1
Lining code A A
Face-to- *2 160 180
face length L (6.30) (7.09)
Outside D 129 155
dia. (5.08) (6.10)
Inter diameter of 77 102 W
L*2
Grounding ring d (3.03) (4.02)
129 155 *1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
Width W *2: Depending on the selection of grounding ring code and optional code, add the following
(5.08) (6.10)
value to L (face-to-face length).
H1 157 183
Height Grounding Ring Code S, L, H P, T N
(6.18) (7.02)
Max. 319 345 None +0 +22 (0.87) -2 (0.08)
Height Hi (12.54) (13.56) Optional
6.5 8.9 Code GA, GC, GD
Weight kg (lb) +8 (0.31) +26 (1.02)
(14.4) (19.6) (Special Gaskets) F31.ai

Lay Length Code 2, AXR150-AXR200, Wafer Type


Unit: mm (approx. inch)
164 (6.46)*1
28
154 (6.06)
49 (1.93)

(1.10) 33 70(2.76) 33*1


(1.30) 18.5 (0.73) (1.30) 90 (3.54)

Ground Terminal
128 (5.04)

(M4)

AXR150G
1 A 1 A 2
73 (2.87)

AXR200C
D

)
Hi

Size code 150 200 (d


150 200
Size (6) (8)
H1

Lining code A A
Face-to- *2 230 300
face length L (9.06) (11.81)
Outside D 202 252
dia. (7.95) (9.92) W L*2
Inter diameter of 140.7 188.9
Grounding ring d (5.54) (7.44)
220 272 *1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
Width W *2: Depending on the selection of grounding ring code and optional code, add the following
(8.66) (10.71)
value to L (face-to-face length).
H1 243 293
Height Grounding Ring Code S, L, H P, T N
(9.57) (11.54)
Max. 405 455 None +0 +28 (1.1) -6 (0.24)
Height Hi (15.93) (17.89) Optional
19.3 28.2 Code GA, GC, GD
Weight kg (lb) +2 (0.08) +30 (1.18)
(42.5) (62.2) (Special Gaskets) F31_02.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 31
Lay Length Code 1, AXR025, JIS/ANSI/DIN Flange Type
164 (6.46)*1 Unit: mm (approx. inch)

28
(1.10)
33 70(2.76) 33*1 154 (6.06)
(1.30) 18.5(0.73) (1.30) 90(3.54)
Ground
Terminal

128 (5.04)
(M4)

(2.87) (1.93)
49
B J 1
t*2

73
B J 2

Hi
N-h
G
AXR025 1 A 1 B A 1 1
(d)

(H2)
C
B A 2

H1
D
B D 4 C

L*2

Process Connection BJ1 (JIS10K) BJ2 (JIS20K) BA1 (ANSI Class 150) BA2 (ANSI Class 300) BD4 (DIN PN40)
Size code 025 025 025 025 025
Size 25 (1) 25 (1) 25 (1) 25 (1) 25 (1)

Lining code A A A A A
Face-to-face length L -3 *
0 2
200 (7.87) 200 (7.87) 200 (7.87) 200 (7.87) 200 (7.87)
Outside dia. D 125 (4.92) 125 (4.92) 108.0 (4.25) 124.0 (4.88) 115 (4.53)

Thickness t* 2 18 (0.71) 20 (0.79) 18.2 (0.72) 21.5 (0.85) 22 (0.87)


Inter diameter of d
Grounding ring 28 (1.10) 28 (1.10) 28 (1.10) 28 (1.10) 28 (1.10)

Pitch circle dia. C 90 (3.54) 90 (3.54) 79.2 (3.12) 88.9 (3.50) 85 (3.35)

Bolt hole interval 45 45 45 45 45

Hole dia. h 19 (0.75) 19 (0.75) 15.7 (0.62) 19.1 (0.75) 14 (0.55)

Number of holes N 4 4 4 4 4

Height H1 120 (4.74) 120 (4.74) 112 (4.40) 120 (4.74) 115 (4.54)

Height H2 58 (2.28) 58 (2.28) 58 (2.28) 58 (2.28) 58 (2.28)

Max. Height Hi 282 (11.09) 282 (11.09) 273 (10.76) 281 (11.07) 277 (10.90)

Weight kg (lb) 6.1 (13.4) 6.5 (14.3) 5.6 (12.3) 6.7 (14.7) 6.4 (14.1)

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
*2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length) and t
(thickness of flange).
L t L t L t
Grounding Ring Code S, L, H P, T N
None +0 +0 +26 (1.02) +13 (0.51) -2 (0.08) -1 (0.04)
Optional
Code GA, GC, GD
(Special Gaskets) +8 (0.31) +4 (0.16) +30 (1.18) +15 (0.59)
F32.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 32
Lay Length Code 1, AXR040-AXR065, JIS/ANSI/DIN Flange Type
164 (6.46)*1 Unit: mm (approx. inch)

28
(1.10)
33 70(2.76) 33*1 154 (6.06)
(1.30) (1.30)
18.5(0.73) 90(3.54)

Ground Terminal

128 (5.04)
(M4)

(1.93)
49
B J 1
B J 2

(2.87)
AXR040 t*2

73
G B A 1
AXR050 1 A 1 1 N-h

Hi
C B A 2
AXR065
(d)

(H2)
B D 2
B D 4

H1
D
C

L*2

Process Connection BJ1 (JIS10K) BJ2 (JIS20K) BA1 (ANSI Class 150) BA2 (ANSI Class 300) BD4 (DIN PN40) BD2 (DIN PN16)
Size code 040 050 065 040 050 065 040 050 065 040 050 065 040 050 065
Size 40 50 65 40 50 65 40 50 65 40 50 65 40 50 65
(1.5) (2) (2.5) (1.5) (2) (2.5) (1.5) (2) (2.5) (1.5) (2) (2.5) (1.5) (2) (2.5)
Lining code A A A A A A A A A A A A A A A
Face-to-face length L -3 *
0 2 200 200 200 200 200 200 200 200 200 200 200 200 200 200 200
(7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87) (7.87)
Outside dia. D 140 155 175 140 155 175 127.0 152.4 177.8 155.4 165.1 190.5 150 165 185
(5.51) (6.10) (6.89) (5.51) (6.10) (6.89) (5.00) (6.00) (7.00) (6.12) (6.50) (7.50) (5.91) (6.50) (7.28)
Thickness 20 20 22 22 22 24 21.5 23.1 26.4 24.6 26.4 29.4 22 24 22
t *2 (0.79) (0.79) (0.87) (0.87) (0.87) (0.94) (0.85) (0.91) (1.04) (0.97) (1.04) (1.16) (0.87) (0.94) (0.87)
Inter diameter of d 41 53 66 41 53 66 41 53 66 41 53 66 41 53 66
Grounding ring (1.61) (2.09) (2.60) (1.61) (2.09) (2.60) (1.61) (2.09) (2.60) (1.61) (2.09) (2.60) (1.61) (2.09) (2.60)
Pitch circle dia. C 105 120 140 105 120 140 98.6 120.7 139.7 114.3 127.0 149.4 110 125 145
(4.13) (4.72) (5.51) (4.13) (4.72) (5.51) (3.88) (4.75) (5.50) (4.50) (5.00) (5.88) (4.33) (4.92) (5.71)
Bolt hole interval 45 45 45 45 22.5 22.5 45 45 45 45 22.5 22.5 45 45 45
Hole dia. h 19 19 19 19 19 19 15.7 19.1 19.1 22.4 19.1 22.4 18 18 18
(0.75) (0.75) (0.75) (0.75) (0.75) (0.75) (0.62) (0.75) (0.75) (0.88) (0.75) (0.88) (0.71) (0.71) (0.71)
Number of holes N 4 4 4 4 8 8 4 4 4 4 8 8 4 4 4
Height H1 138 157 176 138 157 176 131 155 177 146 162 184 143 162 181
(5.43) (6.16) (6.93) (5.43) (6.16) (6.93) (5.17) (6.11) (6.97) (5.73) (6.36) (7.24) (5.63) (6.36) (7.13)
Height H2 68 79 89 68 79 89 68 79 89 68 79 89 68 79 89
(2.67) (3.11) (3.50) (2.67) (3.11) (3.50) (2.67) (3.11) (3.50) (2.67) (3.11) (3.50) (2.67) (3.11) (3.50)
Max. Height Hi 299 318 338 299 318 338 293 317 339 307 323 346 304 323 343
(11.79) (12.52) (13.31) (11.79) (12.52) (13.31) (11.53) (12.47) (13.35) (12.09) (12.72) (13.62) (11.98) (12.72) (13.50)
Weight kg (lb) 7.5 8.7 11.0 8.0 8.9 11.3 7.2 9.3 12.8 9.6 10.9 14.6 8.7 10.6 11.8
(16.5) (19.2) (24.2) (17.6) (19.6) (24.9) (15.8) (20.5) (28.2) (21.1) (24.0) (32.2) (19.1) (23.4) (26.0)

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
*2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length) and t (thickness of
flange).
L t L t L t
Grounding Ring Code S, L, H P, T N
None +0 +0 +26 (1.02) +13 (0.51) -2 (0.08) -1 (0.04)
Optional
Code GA, GC, GD
(Special Gaskets) +8 (0.31) +4 (0.16) +30 (1.18) +15 (0.59) F33.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 33
Lay Length Code 1, AXR080-AXR100, JIS/ANSI/DIN Flange Type
164 (6.46)*1
Unit: mm (approx. inch)
28
(1.10) 154 (6.06)
33 70(2.76) 33*1
(1.30) 18.5(0.73) (1.30) 90(3.54)
Ground
Terminal

128 (5.04)
(M4)

(2.87) (1.93)
B J 1

49
B J 2
t*2

73
AXR080 G B G 1
1 A 1 1 N-h
AXR100 C B A 1 )
(d

Hi
B A 2

(H2)
B D 2

H1
D


L*2

Process Connection BJ1 (JIS10K) BJ2 (JIS20K) BG1 (JIS F12) BA1 (ANSI Class 150) BA2 (ANSI Class 300) BD2(DIN PN16)
Size code 080 100 080 100 080 100 080 100 080 100 080 100
Size 80 100 80 100 80 100 80 100 80 100 80 100
(3) (4) (3) (4) (3) (4) (3) (4) (3) (4) (3) (4)
Lining code A A A A A A A A A A A A
200 250 200 250 200 250 200 250 200 250 200 250
Face-to-face length L -3 *
0 2
(7.87) (9.84) (7.87) (9.84) (7.87) (9.84) (7.87) (9.84) (7.87) (9.84) (7.87) (9.84)
185 210 200 225 211 238 190.5 228.6 209.6 254.0 200 220
Outside dia. D (7.28) (8.27) (7.87) (8.86) (8.31) (9.37) (7.50) (9.00) (8.25) (10.00) (7.87) (8.66)
22 22 26 28 22 22 27.9 27.9 32.4 35.8 24 24
Thickness t *2 (0.87) (0.87) (1.02) (1.10) (0.87) (0.87) (1.10) (1.10) (1.28) (1.41) (0.94) (0.94)
Inter diameter of d 77 102 77 102 77 102 77 102 77 102 77 102
Grounding ring (3.03) (4.02) (3.03) (4.02) (3.03) (4.02) (3.03) (4.02) (3.03) (4.02) (3.03) (4.02)
150 175 160 185 168 195 152.4 190.5 168.1 200.2 160 180
Pitch circle dia. C (5.91) (6.89) (6.30) (7.28) (6.61) (7.68) (6.00) (7.50) (6.62) (7.88) (6.30) (7.09)
Bolt hole interval 22.5 22.5 22.5 22.5 45 45 45 22.5 22.5 22.5 22.5 22.5
19 19 23 23 19 19 19.1 19.1 22.4 22.4 18 18
Hole dia. h (0.75) (0.75) (0.91) (0.91) (0.75) (0.75) (0.75) (0.75) (0.88) (0.88) (0.71) (0.71)
Number of holes N 8 8 8 8 4 4 4 8 8 8 8 8
187 211 195 218 200 225 190 220 200 233 195 216
Height H1 (7.36) (8.30) (7.68) (8.59) (7.87) (8.85) (7.48) (8.66) (7.87) (9.16) (7.68) (8.49)
95 106 95 106 95 106 95 106 95 106 95 106
Height H2 (3.74) (4.16) (3.74) (4.16) (3.74) (4.16) (3.74) (4.16) (3.74) (4.16) (3.74) (4.16)
349 372 357 380 362 386 352 382 362 394 357 377
Max. Height Hi (13.74) (14.65) (14.06) (14.95) (14.25) (15.21) (13.86) (15.02) (14.25) (15.52) (14.06) (14.85)
11.3 15.2 14.1 19.7 13.9 18.3 14.6 20.5 18.3 29.6 13.6 17.3
Weight kg (lb) (24.9) (33.5) (31.0) (43.4) (30.6) (40.3) (32.2) (45.2) (40.3) (65.2) (29.9) (38.1)

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
*2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length)
and t (thickness of flange).
L t L t L t
Grounding Ring Code S, L, H P, T N
None +0 +0 +26 (1.02) +13 (0.51) -2 (0.08) -1 (0.04)
Optional
Code GA, GC, GD
(Special Gaskets) +8 (0.31) +4 (0.16) +30 (1.18) +15 (0.59)

F34.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 34
Lay Length Code 1, AXR150-AXR200, JIS/ANSI/DIN Flange Type
Unit: mm (approx. inch)
164 (6.46)*1
28 154 (6.06)
(1.10)
33 70(2.76) 33*1
(1.30) 18.5(0.73) (1.30) 90 (3.54)
Ground
Terminal

128 (5.04)
(M4)

(2.87) (1.93)
49
t*2
B A

73
B D N-h

B J d

Hi

(H2)
AXR150G B G 1
1 A 1 1
AXR200C C A

H1
C D
C
C J
C G 1
D


L*2

Process Connection BJ1/CJ1 (JIS 10K) BJ2/CJ2 (JIS 20K) BG1/CG1 (JIS F12) BA1/CA1 (ANSI Class 150) BA2/CA2 (ANSI Class 300) BD1/CD1 (DIN PN10) BD2/CD2(DIN PN16)
Size code 150 200 150 200 150 200 150 200 150 200 200 150 200
Size 150 200 150 200 150 200 150 200 150 200 200 150 200
(6) (8) (6) (8) (6) (8) (6) (8) (6) (8) (8) (6) (8)
Lining code A A A A A A A A A A A A A
300 350 300 350 300 350 300 350 350 350 300 350
Face-to-face length L -3 * 300
0 2
(11.81) (13.78) (11.81) (13.78) (11.81) (13.78) (11.81) (13.78) (11.81) (13.78) (13.78) (11.81) (13.78)
280 330 305 350 290 342 279.4 342.9 317.5 381.0 340 285 340
Outside dia. D (11.02) (12.99) (12.01) (13.78) (11.42) (13.46) (11.00) (13.50) (15.00) (13.39) (11.22) (13.39)
(12.50)
27 27 33 35 27 29 30.4 33.4 41.5 46.1 29 27 29
Thickness t *2 (1.06) (1.06) (1.30) (1.38) (1.06) (1.14) (1.20) (1.31) (1.81) (1.14) (1.06) (1.14)
(1.63)
Inter diameter of d 146.1 193.6 146.1 193.6 146.1 193.6 146.1 193.6 146.1 193.6 193.6 146.1 193.6
Grounding ring (5.75) (7.62) (5.75) (7.62) (5.75) (7.62) (5.75) (7.62) (5.75) (7.62) (7.62) (5.75) (7.62)
240 290 260 305 247 299 241.3 298.5 269.7 330.2 295 240 295
Pitch circle dia. C (9.45) (11.42) (10.24) (12.01) (9.72) (11.77) (9.50) (11.75) (13.00) (11.61) (9.45) (11.61)
(10.62)
Bolt hole interval 22.5 15 15 15 30 22.5 22.5 22.5 15 15 22.5 22.5 15
23 23 25 25 19 19 22.4 22.4 22.4 25.4 22 22 22
Hole dia. h (0.91) (0.91) (0.98) (0.98) (0.75) (0.75) (0.88) (0.88) (1.00) (0.87) (0.87) (0.87)
(0.88)
Number of holes N 8 12 12 12 6 8 8 8 12 12 8 8 12
281 331 294 341 286 337 281 337 300 357 336 284 336
Height H1 (11.06) (13.03) (11.56) (13.43) (11.26) (13.27) (11.05) (13.29) (14.04) (13.23) (11.16) (13.23)
(11.80)
141 166 141 166 141 166 141 166 141 166 166 141 166
Height H2 (5.55) (6.54) (5.55) (6.54) (5.55) (6.54) (5.55) (6.54) (6.54) (6.54) (5.55) (6.54)
(5.55)
443 493 456 503 448 499 443 499 462 519 498 446 498
Max. Height Hi (17.42) (19.39) (17.95) (19.80) (17.64) (19.65) (17.43) (19.66) (20.41) (19.61) (17.54) (19.61)
(18.18)
29.2 38.7 38.5 53.3 31.3 44.6 32.3 50.6 53.9 80.2 43.9 30.1 43.3
Weight kg (lb) (64.4) (85.3) (84.9) (117.5) (69.0) (98.3) (71.2) (71.2) (176.8) (96.8) (66.4) (95.5)
(118.8)

*1: When indicator code N is selected, subtract 5 mm (0.2 inch) from the value in the figure.
*2: Depending on the selection of grounding ring code and optional code, add the following value to L (face-to-face length)
and t (thickness of flange).
L t L t L t
Grounding Ring Code S, L, H P, T N
None +0 +0 +32 (1.26) +16 (0.63) -2 (0.08) -1 (0.04)
Optional
Code GA, GC, GD
(Special Gaskets) +10 (0.39) +5 (0.20) +38 (1.5) +19 (0.75)
F34_02.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 35
Flameproof Packing Adapter for TIIS Flameproof Type (Optional code G11 or G32)
T1 Unit: mm (approx. inch)
Adapter body (M. Screw)
O-Ring
Packing case
16.5 (0.65)
Hexagon socket set screw
Packing (*)
18
Hexagon socket set screw
(0.71)
O-Ring
F L O-Ring C
G Washer
Union nut
*Packing Packing gland
(Choose from the table below Clamp ring
depend on cable outside diameter) D
Clamp nut
T2 O-Ring
B. coupling
Cable (users scope)
F35.ai
Nominal diameter Dimension Packing diameter Weight
Identification
Cable outer diameter kg Parts No.
T1 T2 C D L F G mark
(lb)
8.0 to 10.0
10.0(0.39) 16 8-10
35 39 94.5 (0.31 to 0.39) 20.0 0.26
G 1/2 G 1/2 G9601AM*
(1.38) (1.54) (3.72) 10.0 to 12.0 (0.79) (0.57)
12.0(0.47) 16 10-12
(0.39 to 0.47)
*: G 11: 1 unit
G 11 with G 32: 2 units

Unless otherwise specified, difference in the dimensions are the following table.

General tolerance in the dimensional outline drawing.


Unit : mm (approx.inch)
Category of basic dimension Category of basic dimension
Tolerance Tolerance
Above Equal or below Above Equal or below
3 (0.12) 0.7 (0.03) 500 (19.69) 630 (24.80) 5.5 (0.22)
3 (0.12) 6 (0.24) 0.9 (0.04) 630 (24.80) 800 (31.50) 6.25 (0.25)
6 (0.24) 10 (0.39) 1.1 (0.04) 800 (31.50) 1000 (39.37) 7.0 (0.28)
10 (0.39) 18 (0.71) 1.35 (0.05) 1000 (39.37) 1250 (49.21) 8.25 (0.32)
18 (0.71) 30 (1.18) 1.65 (0.06) 1250 (49.21) 1600 (62.99) 9.75 (0.38)
30 (1.18) 50 (1.97) 1.95 (0.08) 1600 (62.99) 2000 (78.74) 11.5 (0.45)
50 (1.97) 80 (3.15) 2.3 (0.09) 2000 (78.74) 2500 (98.43) 14.0 (0.55)
80 (3.15) 120 (4.72) 2.7 (0.11) 2500 (98.43) 3150 (124.02) 16.5 (0.65)
120 (4.72) 180 (7.09) 3.15 (0.12)
180 (7.09) 250 (9.84) 3.6 (0.14)
250 (9.84) 315 (12.40) 4.05 (0.16)
315 (12.40) 400 (15.75) 4.45 (0.18)
400 (15.75) 500 (19.69) 4.85 (0.19)

Remarks: The numeric is based on criteria of tolerance class IT18 in JIS B 0401.

n SIZING DATA (Measurable flow velocity is from 0 m/s.)


Flow velocity
SI Units Size: mm *Measurable flow velocity is from 0 m/s.
m/s
0

0
0
25

80
40
50
65

10

15
20

10.0
5.0

1.0

0.5
0.3
0.01 0.1 1 10 100 1,000
Flow rate (m3/h)

Flow velocity English Units Size: inch * Measurable flow velocity is from 0 ft/s.
ft/s
1.5

2.5

33
2

6
1

10
5.0

2.0
1.0
0.1 1.0 10 100 1,000 10,000
Flow rate (GPM) F36.ai

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00
<<Contents>> <<Index>> 36

ORDERING INFORMATION

Note 1: When ordering, the span flow rate, unit, out- If a span flow rate and its unit are not specified, the
put pulse weight, and totalizer display pulse relevant product is delivered with the setting at 1
weight can be specified. These parameters m/s (3.3 ft/s).
will then be set before shipment. A Tokuchu 5. Transmission pulse weight
request is necessary except when these
parameters are specified within the range. If specified, a span flow rate must be set first, and
then volume per pulse must be set.
Note 2: Some options, if ordered, require the
relevant specifications to be input when It can be specified numerically within the value
ordering. from 0.0001 to 32000, and its unit must be speci-
fied in the same unit as the span flow rate.
1. Model, specification and optional codes
(Example: When m3 is selected as Span Flow
2. Tag number Rate, specify 10 m3/p as pulse weight unit.)
Each tag number can be specified in up to 16 char- Unless specified, the relevant product is delivered
acters in a combination of letters (capital or small with the setting at 0 pulse/second.
letters), numbers, - and ..
6. Totalizer display pulse weight
If specified, the tag number is inscribed on the
products name plate and tag plate (if optional code If specified, a span flow rate must be set first, and
SCT is selected). then volume per totalization pulse count must be
set.
Tag number is set into a converters memory. For
HART5 protocol, up to 8 characters is set into Tag. It can be specified numerically within the value
For HART7 protocol, up to 8 characters is set into from 0.0001 to 32000, and its unit must be speci-
Tag and up to 16 characters is set into Long Tag. fied in the same unit as the span flow rate.
If a tag number is not specified, the tag number is (Example: when m3 is selected as Span Flow
set as a blank. Rate, specify 10 m3/p as pulse weight unit.)
3. Software tag Unless specified, the relevant product is delivered
with the setting at 0 pulse/second.
If the user wishes to change only the tag number
to be set into converters memory, specify the 7. Fluid name
software tag. Each software tag can be specified 8. HART protocol revision
in a combination of letters (capital or small letters), When specifying Output signal -J, it is manda-
numbers, - and .. tory to specify HART protocol revision HART5 or
For BRAIN protocol, up to 16 characters is set into HART7
Tag No.
For HART5 protocol, up to 8 characters is set into
Tag. RELATED INSTRUMENTS
For HART7 protocol, Up to 8 characters is set into Calibrator for Magnetic Flowmeter (AM012):
Tag and up to 32 characters is set into Long tag.
GS 1E6K2-E
4. Span flow rates and units
BT200 Brain Terminal: GS 01C00A11-00EN
Span flow rate can be specified numerically within
FieldMate: GS 01R01A01-01E
the value of 0.0001 to 32000. It can be up to five
digits, to a maximum of 32000 ignoring the decimal
point, and a fraction is limited to the fourth decimal Reference
place.
Specify the unit which is specified for the flow unit ADMAG and AXR are registered trademarks of Yokogawa
in the Span Setting Function. Electric Corporation.
The span flow rates are set to the first range in the Company names and product names used in this material
forward direction. are registered trademarks or trademarks of their respective
A span flow rate and its unit must be specified owners.
when the Mass Unit Setting (optional code MU)
or Five-point Calibration in User-specified Span
(optional code SC) is specified.

All Rights Reserved. Copyright 2009, Yokogawa Electric Corporation GS 01E30D01-01EN June 10, 2016-00