Вы находитесь на странице: 1из 251

NBCC (INDIA) LIMITED

Project: Residential cum Training Complex for Special Protection


Group at Sector-21, Dwarka, New Delhi

BILL OF QUANTITIES
(BOQ)
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

GRAND SUMMARY OF COST (Figures in Rs.)

COST OF WORK
Sl. No. DESCRIPTION OF HEAD OF WORK SCHEDULED ITEMS BASED
NON SCHEDULED ITEMS
ON DSR 2014
1 CIVIL WORKS 2,469,754,708.60 549,043,978.75
2 INTERNAL PLUMBING WORKS 116,819,397.00 69,579,040.39
3 EXTERNAL PLUMBING WORKS 39,073,401.63 15,369,975.90
4 INTERNAL ELECTRICAL WORKS 116,093,519.00 77,744,449.00
5 EXTERNAL ELECTRICAL WORKS 10,110,738.00 252,091,956.00
6 FIRE FIGHTING WORKS 75,165,845.00
7 HVAC WORKS 515,252.00 65,656,915.00
8 ELEVATOR WORKS 118,065,033.00
9 CCTV WORKS 17,928,882.00
10 ACOUSTICAL WORKS 15,824,182.00
11 SITE DEVELOPMENT WORKS 82,223,821.70 22,441,907.09
TOTAL 2,834,590,837.93 1,278,912,164.13
GRAND TOTAL 4,113,503,002.06

GS 1
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF CIVIL WORKS (figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 Earth Work 150,373,833.70 -
2 Concrete Work 36,123,366.75 12,160,500.00
3 RCC Work 1,389,858,025.25 11,146,900.00
4 Brick Work 173,288,056.75 -
5 Stone Work 2,163,344.50 -
6 Marble Work 27,533,063.00 1,220,736.00
7 Wood Work 104,923,830.95 421,367,240.40
8 Steel Work 141,064,591.60 313,975.00
9 Flooring Work 168,451,178.75 5,404,665.00
10 Roofing Work 19,996,910.65 19,236,413.35
11 Water Proofing Work 29,017,493.50 13,447,895.00
12 Finishing Work 113,679,299.50 58,114,090.00
13 Aluminium Works 109,721,087.45 4,238,460.00
14 Miscellaneous Work 3,560,626.25 2,393,104.00
TOTAL OF CIVIL WORKS CARRIED OVER TO GRAND
SUMMARY OF COSTS 2,469,754,708.60 549,043,978.75

BOQ - (CIVIL) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - CIVIL WORKS
CHAPTER - 1 : EARTH WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.6 1.1 Earthwork in excavation by mechanical means (hydraulic
excavator)/manual means over areas (exceeding 30cm in depth, 1.5m in
width as well as 10sqm on plan) including disposal of excavated earth
lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly
dressed :
2.6.1 1.1.1 All kinds of soil cum 266915 155.60 41,531,974.00
2.8 1.2 Earth work in excavation by mechanical means (hydraulic
excavator)/manual means in foundation trenches or drains (not exceeding
1.5m in width or 10sqm on plan) including dressing of sides and ramming
of bottoms lift upto 1.5m, including getting out the excavated soil and
disposal of surplus excavated soil as directed, within a lead of 50 m:

2.8.1 1.2.1 All Kinds of soil cum 870 157.50 137,025.00


2.26 1.3 Extra for every additional lift of 1.5 m or part thereof in excavation /
banking excavated or stacked materials .
2.26.1 1.3.1 All Kinds of soil cum 645175 46.25 29,839,343.75
2.25 1.4 Filling available excavated earth (excluding rock) in trenches, plinth, sides
of foundations etc. in layers not exceeding 20 cm in depth: consolidating
each deposited layer by ramming and watering, lead up to 50 m and lift
upto 1.5 m. cum 72950 112.40 8,199,580.00
1.1 1.5 Carriage of material by mechanical transport including loading, unloading
and stacking upto10 Km
1.1.2 1.5.1 Earth
1.1.2.3 1.5.1.1 Up - to 5 Km cum 249635 153.07 38,211,629.45
1.1.2.8 1.5.1.2 Beyond 5 km upto 10 km cum 131875 210.77 27,795,293.75
2.34 1.6 Supplying chemical emulsion in sealed containers including delivery as
specified.
2.34.1 1.6.1 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% litre 4215 185.95 783,779.25

BOQ - (CIVIL) 2
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.35 1.7 Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL
anti-termite treatment (excluding the cost of chemical emulsion):
2.35.2 1.7.1 Along the external wall below concrete or masonry apron using chemical
emulsion @ 2.25 litres per linear meter including drilling and plugging
holes etc.:
2.35.2.1 1.7.1.1 With Chlorpyriphos/ Linadane E.C. 20% with 1% concentration. Meter 1720 22.70 39,044.00
2.35.3 1.8 Treatment of soil under existing floors using chemical emulsion @ one
litre per hole, 300mm apart including drilling 12mm diameter holes and
plugging with cement mortar 1:2 (1 cement:2 coarse sand) to match the
existing floor.:
2.35.3.1 1.8.1 With Chlorpyriphos/ Linadane E.C. 20% with 1% concentration. SqM 7230 118.90 859,647.00
2.27 1.9 Supplying and filling in plinth with Jamuna sand under floors, including
watering, ramming, consolidating and dressing complete. cum 3270 910.25 2,976,517.50
TOTAL OF EARTH WORK CARRIED OVER TO SUMMARY OF CIVIL
WORKS 150,373,833.70 -

BOQ - (CIVIL) 3
CHAPTER - 2 : CONCRETE WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
4.1 2.1 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - All work upto plinth level.

4.1.4 2.1.1 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm


nominal size) cum 125 5,335.25 666,906.25
4.1.6 2.1.2 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 40mm
nominal size) cum 135 4,672.50 630,787.50
4.1.8 2.1.3 1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm
nominal size) cum 5020 4,301.15 21,591,773.00
4.1.11 2.1.4 1:5:10 (1 cement : 5 fine sand : 10 graded stone aggregate 40 mm
nominal size) cum 3310 3,721.65 12,318,661.50
NS 2.2 Providing and laying in position cement concrete 1:5.10 with Jhama brick
aggregate in sunken portion of WC as per the direction of Engineer-in-
charge cum 3350 3,630.00 12,160,500.00
4.10 2.3 Providing and laying damp - proof course 40 mm thick with cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5
mm nominal size) sqm 1020 257.80 262,956.00
4.12 2.4 Extra for providing and mixing water proofing material in cement concrete per
work in doses by weight of cement. As par manufacturer's specification. 50kg.
cement 270 48.15 13,000.50
4.13 2.5 Applying a coat of residual petroleum bitumen of grade of VG-10 of
approved quality using 1.7 kg per square metre on damp proof course
after cleaning the surface with brushes and finally with a piece of cloth
lightly soaked in kerosene oil sqm 1000 132.00 132,000.00
4.14 2.6 Extra for concrete work in superstructure above floor V level for each four
floors or part thereof. cum 885 573.20 507,282.00
TOTAL OF CONCRETE WORK CARRIED OVER TO SUMMARY OF
CIVIL WORKS 36,123,366.75 12,160,500.00

BOQ - (CIVIL) 4
CHAPTER - 3 : R.C.C WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.9 3.1 Centring and shuttering including strutting, propping etc. and removal of
form for:
5.9.1 3.1.1 Foundations, footings, bases of columns etc. for mass concrete. sqm 9425 196.45 1,851,541.25
5.9.2 3.1.2 Walls (any thickness) including attached pilasters, butteresses, plinth
and string courses etc. sqm 29970 360.80 10,813,176.00
5.9.3 3.1.3 Suspended floors, roofs,landings, balconies and access platform. sqm 117300 401.65 47,113,545.00
5.9.4 3.1.4 Shelves (Cast in situ) sqm 3040 401.65 1,221,016.00
5.9.5 3.1.5 Lintels, beams, plinth beams, girders, bressumers and cantilevers. sqm 180245 332.15 59,868,376.75
5.9.6 3.1.6 Columns, Pillars, Piers, Abutments, Posts and Struts sqm 84715 453.35 38,405,545.25
5.9.7 3.1.7 Stairs, (excluding landings) except spiral-staircases. sqm 5870 395.65 2,322,465.50
5.9.14 3.1.8 Extra for shuttering in circular work (20% of respective centering and
shuttering items)
a) Column sqm 6500 90.67 589,355.00
b) Beam sqm 4605 66.43 305,910.15
c) Slab sqm 2720 80.33 218,497.60
5.9.15 3.1.9 Small lintels not exceeding 1.5m clear span, moulding as in cornices,
window sills, string courses, bands, copings, bed plates, anchor blocks
and the like sqm 5020 196.45 986,179.00
5.9.16 3.1.10 Edges of slab and breaks in floors and walls.
5.9.16.1 3.1.10.1 Under 20 cm wide metre 6740 116.40 784,536.00
5.9.19 3.1.11 Weather shade, Chajjas, corbels etc., including edges sqm 1075 492.35 529,276.25
5.11 3.2 Extra for additional height in centering, shuttering where ever required
with adequate bracing, propping etc., including cost of de-shuttering and
decentering at all levels, over a height of 3.5 m, for every additional
height of 1 metre or part thereof (Plan area to be measured).

5.11.1 3.2.1 Suspended floors, roofs, landing, beams and balconies (Plan area to be
measured) sqm 34090 159.05 5,422,014.50
5.22 3.3 Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete upto plinth level.

5.22.6 3.3.1 Thermo-Mechanically Treated bars Kg 4778905 68.10 325,443,430.50

BOQ - (CIVIL) 5
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.22A 3.4 Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete above plinth level.

5.22A.6 3.4.1 Thermo-Mechanically Treated bars Kg 4931595 68.10 335,841,619.50


5.23 3.5 Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick
cement mortar 1:3 (1 Cement : 3 fine sand). sqm 4945 134.70 666,091.50
5.30 3.6 Add for plaster drip course/ groove in plastered surface or moulding to
R.C.C. projections. mtr 41275 30.75 1,269,206.25
5.33 3.7 Providing and laying in position machine batched and machine mixed
design mix M-25 grade cement concrete for reinforced cement concrete
work,using cement content as par approved design mix, including
pumping of concrete to site of laying but excluding the cost of centring,
shuttering, finishing and reinforcement. including admixtures in
recommended proportions. as per IS 9103 to accelerate, retard setting of
concrete improve workability without impairing strength and durability as
per direction of Engineer-in-Charge.
(Note:-cement concrete considered in this item is @ 330 kg/cum.
Excess/less cement used as per design mix. is payable/recoverable
separately)

5.33.1 3.7.1 All works upto plinth level. cum 42050 6,296.15 264,753,107.50
5.33.2 3.7.2 All works above plinth level upto floor V level. cum 35280 7,014.55 247,473,324.00
5.38 3.8 Extra for R.C.C./ B.M.C/ R.M.C. work above floor V level for each four
floors or part thereof. cum 11985 174.20 2,087,787.00
5.35 3.9 Add for using extra cement in the items of design mix over and above the
specified cement content therein quintal 45185 742.75 33,561,158.75
NS 3.10 Providing & fixing Polyethylene joint filler board in expansion joints
150mm wide in columns of approximate size of 350 to 650mm and in
beams of aaproximate depth of 500 to 650 mm manufactured by M/s
Supreme Industries Limited or equivalent over a layer of neoprene based
adhesive at apporox. 500gms per sq. Mtr (Density not less 30kg/cum)
and finishing the same with EPDM membrane and epoxy as per
manufacturer's manual and instruction sqm 3950 2,822.00 11,146,900.00
5.29 3.11 Providing and fixing sheet covering over expansion joints with iron
screws as per design.
5.29.2 3.11.1 Aluminium fluted strips 3.15 mm thick

BOQ - (CIVIL) 6
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.29.2.1 3.11.1.1 150 mm wide meter 2245 330.05 740,962.25
5.1 3.12 Providing and laying in position specified grade of reinforced cement
concrete excluding the cost of centering, shuttering, finishing and
reinforcement - All work upto plinth level.
5.1.3 3.12.1 1:2:4 ( 1Cement : 2 coarse sand :4 graded stone aggregate 20 mm
nominal size) cum 1065 5,725.90 6,098,083.50
22.4 3.13 Providing and Placing in position suitable PVC water stops conforming to
IS:12200 for construction/ expansion joints between two RCC members
and fixed to the reinforcement with binding wire before pouring concrete
etc. complete.
22.4.2 3.13.1 Dumb bell with central bulb (180mm wide, 8mm thick) metre 3235 461.15 1,491,820.25
TOTAL OF R.C.C WORKS CARRIED OVER TO SUMMARY OF CIVIL
WORKS 1,389,858,025.25 11,146,900.00

BOQ - (CIVIL) 7
CHAPTER - 4 : BRICK WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
6.1 4.1 Brick work with common burnt clay F.P.S.(non modular) bricks of class
designation 7.5 in foundation and plinth in :
6.1.2 4.1.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 2945 4,677.25 13,774,501.25
6.4 4.2 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level in all
shapes and sizes in :
6.4.2 4.2.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 1010 5,426.15 5,480,411.50
6.5 4.3 Extra for brick work / AAC block masonry / Tile brick masonry in
superstructure above floor V level, for each four floors or part thereof by
mechanical means.
cum 8990 289.05 2,598,559.50
6.38 4.4 Providing and laying autoclaved aerated cement blocks masonry with 100
mm thick AAC blocks in super structure above plinth level up to floor V
level in cement mortar 1:4 (1 cement : 4 coarse sand ). The rate includes
providing and placing in position 2 Nos 6 mm dia M.S. bars at every third
course of masonry work. cum 23710 6,386.95 151,434,584.50
TOTAL OF BRICK WORK CARRIED OVER TO SUMMARY OF CIVIL
WORKS 173,288,056.75 -

BOQ - (CIVIL) 8
CHAPTER - 5 : STONE WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
7.23 5.1 Stone work (machine cut edges) for wall lining etc. (veneer work) upto 10
metre height, backing filled with a grout of average 12 mm thick cement
mortar 1:3 (1 cement : 3 coarse sand) including pointing in white cement
mortar 1:2 (1 white cement : 2 stone dust) with an admixtureof pigment
matching the stone shade : (To be secured to the backingand the sides by
means of cramps and pins which shall be paid forseparately) :

7.23.1 5.1.1 Red sand stone - exposed face fine dressed with rough backing.
7.23.1.5 5.1.1.1 30 mm thick sqm 305 2,172.00 662,460.00
7.23.3 5.1.2 White sand stone - exposed face fine dressed with rough backing.
7.23.3.5 5.1.2.1 30 mm thick sqm 675 2,195.20 1,481,760.00
7.32 5.2 Stone work, plain in copings, cornices, string courses and plinth courses,
upto 75 mm thick in Cement mortar 1:6 (1 cement : 6 coarse sand),
including pointing with white cement mortar 1:2 (1 white cement : 2 stone
dust) with an admixture of pigment matching the stone shade.

7.32.1 5.2.1 Red sand stone cum 0.5 38,249.00 19,124.50


TOTAL OF STONE WORKS CARRIED OVER TO SUMMARY OF CIVIL
WORKS 2,163,344.50 -

BOQ - (CIVIL) 9
CHAPTER - 6 : MARBLE WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
8.1 6.1 Marble work gang saw cut (polished and machine cut) of thickness 18 mm
for wall lining (veneer work), backing filled with a grout of average 12 mm
thick in cement mortar 1:3 (1 cement : 3 coarse sand), including pointing
with white cement mortar 1:2 (1 white cement : 2 marble dust) with an
admixture of pigment to match the marble shade (To be secured to the
backing by means of cramps, which shall be paid for separately).

8.1.1 6.1.1 Raj Nagar Plain white marble/ Udaipur green marble/ Zebra black marble.

8.1.1.2 6.1.1.1 Area of slab over 0.05 sqm sqm 1550 2,914.25 4,517,087.50
8.2 6.2 Providing and fixing 18 m thick gang saw cut, mirror polished,
premoulded and prepolished, machine cut for kitchen platforms, vanity
counters, window sills, facias and similar locations of required size,
approved shade,colour and texture laid over 20 mm thick base cement
mortar 1:4 ( 1 cement : 4 coarse sand) joints treated with white cement,
mixed with matching pigment, epoxy touch ups, including rubbing, curing
moulding and polishing to edges to give high gloss finish etc. complete at
all levels.
8.2.1 6.2.1 Raj Nagar Plain white marble/ Udaipur green marble/ Zebra
black marble
8.2.1.2 6.2.1.1 Area of slab over 0.50 sqm sqm 680 2,463.55 1,675,214.00
8.2.2 6.2.2 Granite of any colour and shade
8.2.2.2 6.2.2.1 Area of slab over 0.50 sqm. sqm 3570 3,907.40 13,949,418.00
8.3 6.3 Providing edge moulding to 18 mm thick marble stone counters, Vanities
etc. including machine polishing to edge to give high gloss finish etc.
complete as per design approved by Engineer - in- Charge
8.3.2 6.3.1 Granite work metre 3905 230.55 900,297.75
8.4 6.4 Extra for fixing marble/granite stone, over and above corresponding basic
item, in facia and drops of width upto 150 mm with epoxy resin based
adhesive, including cleaning etc. complete. metre 3905 247.40 966,097.00
8.5 6.5 Extra for providing opening of required size & shape for wash basin/
kitchen sink in kitchen platform, vanity counter and similar location in
marble/granite/stone work, including necessary holes for pillar taps etc.
including moduling, rubbing and polishing of cut edges etc. complete.
each 295 386.60 114,047.00

BOQ - (CIVIL) 10
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
8.7 6.6 Providing and fixing cramps of required size & shape in RCC/ CC / Brick
masonry backing with cement mortar 1:2 ( 1 cement :2 coarse sand),
including drilling necessary hole in stones and embedding the cramp in
the hole (fastener to be paid separately).
8.7.2 6.6.1 Stainless steel cramps kg 6425 574.65 3,692,126.25
8.10 6.7 Providing and fixing stone slab with table rubbed, edges rounded and
polished, of size 75x50 cm deep and 1.8 cm thick, fixed in urinal partitions
by cutting a chase of appropriate width with chase cutter and embedding
the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1
cement : 2 coarse sand : 4 graded stone aggregate 6 mm nominal size)
as per direction of Engineer-in-charge and finished smooth.

8.10.2 6.7.1 Granite Stone of approved shade sqm 10 3,263.50 32,635.00


8.11 6.8 Providing and fixing machine cut, mirror / eggshell polished , Marble stone
work for wall lining (veneer work) including dado, skirting, risers of steps
etc., in required design and pattern wherever required, stones of different
finished surface texture, on 12 mm (average) thick cement mortar 1:3 (1
cement : 3 oarse sand) laid and jointed with white cement slurry @ 3.3
kg/sqm including pointing with white cement slurry admixed with pigment
of matching shade, including rubbing, curing, polishing etc. all complete as
per Architectural drawings, and as directed by the Engineer-in-Charge.
a. 18 mm thick Italian Marble stone slab,Perlato, Rosso verona, Fire Red
or Dark Emperadore etc.
sqm 35 7,022.60 245,791.00
8.12 6.9 Providing and laying flamed finish Granite stone flooring in required
design and patterns, in linear as well as curvilinear portions of the building
all complete as per the architectural drawings with 18 mm thick stone slab
over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4
coarse sand) laid and jointed with cement slurry and pointing with white
cement slurry admixed with pigment of matching shade including rubbing,
curing and polishing etc. all complete as specified and as directed by the
Engineerin-Charge :

a. 6.9.1 Flamed finish granite stone slab Jet Black, Cherry Red, Elite Brown, Cat
Eye or equivalent. sqm 400 3,244.35 1,297,740.00

BOQ - (CIVIL) 11
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 6.10 Providing and fixing 18mm thick gang saw cut mirror polished
(premoulded and prepolished) machine cut Granite stone of required
size of approved shade,colour and texture for wall lining over 12mm thick
bed of cement mortar1:3 (1cement :3 coarse sand)and cement slurry
@3.3 kg/sqm mixed with matching pigment, epoxy touch ups, including
rubbing, curing moulding and polishing to the edge to give high gloss
finish etc. complete at all levels.
Granite of any colour and shade
6.10.1 Area of Slab upto 0.5 sqm sqm 352 3,468.00 1,220,736.00
8.6 6.11 Mirror polishing on marble work/Granite work/stone work where ever
required to give high gloss finish complete. sqm 670 212.85 142,609.50
TOTAL OF MARBLE WORK CARRIED OVER TO SUMMARY OF CIVIL
WORKS 27,533,063.00 1,220,736.00

BOQ - (CIVIL) 12
CHAPTER - 7 : WOOD WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
9.5 7.1 Providing and fixing panelled or panelled and glazed shutters for doors,
windows and clerestory windows, including ISI marked M.S. pressed butt
hinges bright finished of required size with necessary screws, excluding
panelling which will be paid for separately, all complete as per direction of
Engineer-in-charge
9.5.1 7.1.1 Second class teak wood
9.5.1.1 7.1.1.1 35 mm thick shutters sqm 3205 2,689.05 8,618,405.25
9.7 7.2 Providing and fixing panelling or panelling and glazing in panelled or
panelled and glazed shutters for doors, windows and clerestory windows
(Area of opening for panel inserts excluding portion inside grooves or
rebates to be measured). Panelling for panelled or panelled and glazed
shutters 25 mm to 40 mm thick :
9.7.8 7.2.1 Fly proof stainless steel grade 304 wire gauge with 0.5 mm dia. wire and
1.4 mm wide aperture with matching wood beading sqm 1945 1,602.40 3,116,668.00
9.21 7.3 Providing and fixing ISI marked flush door shutters conforming to IS:2202
(Part I) non-decorative type, core of block board construction with frame of
1st class hard wood and well matched commercial 3 ply veneering with
vertical grains or cross bands and face veneers on both faces of shutters :

9.21.1 7.3.1 35 mm thick including ISI marked Stainless Steel butt hinges with
necessary screws. sqm 5250 1,909.55 10,025,137.50
9.24 7.4 Extra for providing vision panel not exceeding 0.1 sqm in all type of flush
doors (cost of glass excluded) (overall area of door shutter to be
measured):
9.24.1 7.4.1 Rectangular or square sqm 130 139.40 18,122.00
9.26 7.5 Extra for cutting rebate in flush door shutters (Total area of the shutter to
be measured). sqm 9110 104.55 952,450.50
9.43 7.6 Providing and fixing 18 mm thick, 150 mm wide pelmet of coir veneer
board ISI marked IS : 14842, including top cover of 6 mm coir
veneerboard, nickle plated M.S. Pipe 20 mm dia. (heavy type) curtain rod
with nickel plated brackets, including fixing with 25x3 mm M.S. Flat 10 cm
long fixed to pelmet with hollock wood cleats of size 100 mm x 40 mm x 40
mm on both inner side of pelmet and rawl plugs 75 mm long etc. all
complete. metre 4940 478.25 2,362,555.00
9.48 7.7 Providing and fixing M.S. grills of required pattern in frames of windows
etc. with M.S. flats, square or round bars etc. including priming coat with
approved steel primer all complete.

BOQ - (CIVIL) 13
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
9.48.2 7.7.1 Fixed to openings /wooden frames with rawl plugs screws etc. kg 90965 116.90 10,633,808.50
9.62 7.8 Providing and fixing ISI marked oxidised M.S sliding door bolts with nuts
and screws etc. complete:
9.62.1 7.8.1 300 x16 mm each 961 173.20 166,445.20
9.63 7.9 Providing and fixing ISI marked oxidized M.S. tower bolt black finish,
(Barrel type) with necessary screws etc. complete.
9.63.1 7.9.1 250 x 10 mm each 1732 66.95 115,957.40
9.63.2 7.9.2 200x10 mm each 481 58.65 28,210.65
9.66 7.10 Providing and fixing ISI marked oxidised M.S. handles conforming to IS:
4992 with necessary screws etc. complete :
9.66.1 7.10.1 125 mm each 1854 28.90 53,580.60
9.66.2 7.10.2 100 mm each 100 26.40 2,640.00
9.76 7.11 Providing and fixing bright finished brass 100 mm mortice latch and lock
with 6 levers and a pair of lever handles of approved quality with
necessary screws etc. complete . Each 302 546.40 165,012.80
9.95 7.12 Providing and fixing ISI marked aluminium butt hinges anodised (anodic
coating not less than grade AC 10 as per IS : 1868) transparent or dyed to
required colour or shade with necessary screws etc. complete:

9.95.4 7.12.1 100 X 63 X 4 mm each 31635 91.90 2,907,256.50


9.96 7.13 Providing and fixing aluminium sliding door bolts ISI marked anodised (
anodic coating not less than grade AC 10 as per IS:1868) transparent or
dyed to required colour or shade with nuts and screws etc. complete.

9.96.2 7.13.1 250 x 16 mm each 3372 189.00 637,308.00


9.97 7.14 Providing and fixing aluminium tower bolts, ISI marked, anodised (anodic
coating not less than grade AC 10 as per IS : 1868 ) transparent or dyed to
required colour or shade, with necessary screws etc. complete :

9.97.3 7.14.1 200 x 10 mm each 11388 79.25 902,499.00


9.97.4 7.14.2 150 x 10 mm each 12497 65.35 816,678.95
9.97.5 7.14.3 100 x 10 mm each 10703 52.35 560,302.05
9.84 7.15 Providing and fixing aluminium extruded section body tubular type
universal hydraulic door close each 10433 1,043.60 10,887,878.80
9.90 7.16 Providing and fixing special quality chromium plated brass cupboard locks
with six levers of approved quality including necessary screws etc.
complete.
9.90.2 7.16.1 Size 50 mm each 6227 186.35 1,160,401.45

BOQ - (CIVIL) 14
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
9.91 7.17 Providing and fixing chromium plated brass 50 mm cupboard or wardrobe
knobs with nuts complete.
each 10191 65.70 669,548.70
9.92 7.18 Providing and fixing chromium plated brass handles with necessary
screws etc. complete:
9.92.1 7.18.1 125 mm each 17225 240.55 4,143,473.75
9.92.3 7.18.2 75mm each 7344 182.10 1,337,342.40
9.100 7.19 Providing and fixing aluminium handles ISI marked , anodised (anodic
coating not less than grade AC 10 as per IS:1868) transparent or dyed to
required colour or shade with necessary screws etc. complete.

9.100.1 7.19.1 125 mm each 10888 69.80 759,982.40


9.100.3 7.19.2 75 mm each 9205 46.95 432,174.75
9.101 7.20 Providing and fixing aluminium hanging floor door stopper ISI marked
anodised (anodic coating not less than grade AC 10 as per IS:1868)
transparent or dyed to required colour and shade with necessary screws
etc. complete.
9.101.1 7.20.1 Single rubber stopper each 7521 37.50 282,037.50
NS 7.21 Providing and fixing fly proof stainless steel grade 304 wire gauge, to
windows and clerestory windows using wire gauge with average width of
aperture 1.4 mm in both directions with wire of dia. 0.50 mm all complete
with aluminium beading sqm 4220 1,360.47 5,741,183.40
9.115 7.22 Providing and fixing powder coated telescopic drawer channels 300 mm
long with necessary screws etc. complete as per directions of
Engineerincharge. one set 6350 198.95 1,263,332.50
9.116 7.23 Providing and fixing sliding arrangement in racks/ cupboards/cabinets
shutter by with stainless steel rollers to run inside C or E aluminium
channel section (The payment of C or E channel shall be made
separately) each 11358 12.60 143,110.80
9.117 7.24 Providing and fixing factory made uPVC door frame made of uPVC
extruded sections having an overall dimension as below (tolerance
1mm), with wall thickness 2.0 mm ( 0.2 mm), corners of the door frame
to be Jointed with galvanized brackets and stainless steel screws, joints
mitred and Plastic welded. The hinge side vertical of the frames reinforced
by galvanized M.S. tube of size 19 X 19 mm and 1mm ( 0.1 mm) wall
thickness and 3 nos. stainless steel hinges fixed to the frame complete as
per manufacturers specification and direction of Engineerin-in-charge

9.117.2 7.24.1 Extruded section profile size 42x50 mm metre 28555 202.15 5,772,393.25

BOQ - (CIVIL) 15
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
9.118 7.25 Providing and fixing to existing door frames.
9.118.1 7.25.1 24 mm thick factory made PVC door shutters made of styles and rails of a
uPVC hollow section of size 59x24 mm and wall thickness 2 mm ( 0.2
mm) with inbuilt edging on both sides. The styles and rails mitred and joint
at the corners by means of M.S. galvanised/plastic brackets of size
75x220 mm having wall thickness 1.0 mm and stainless steel screws. The
styles of the shutter reinforced by inserting galvanised M.S. tube of size
20x20 mm and 1 mm ( 0.1 mm) wall thickness. The
lock rail made up of 'H' section, a uPVC hollow section of size 100x24 mm
and 2 mm ( 0.2 mm) wall thickness, fixed to the shutter styles by means
of lastic/galvanised M.S. 'U' cleats. The shutter frame filled with a uPVC
multi-chambered single panel of size not less than 620 mm, having over all
thickness of 20 mm and 1 mm ( 0.1 mm) wall thickness. The panels filled
vertically and tie bar at two places by inserting horizontally 6 mm
galvanised M.S. rod and fastened with nuts and washers, complete as per
manufacturer's specification and direction of Engineer-in-charge. (For
W.C. and bathroom door shutter).
sqm 9820 2718.60 26,696,652.00
9.127 7.26 Providing & Fixing decorative high pressure laminated sheet of plain /
wood grain in gloss / matt / suede finish with high density protective
surface layer and reverse side of adhesive bonding quality conforming to
IS : 2046 Type S, including cost of adhesive of aproved quality
9.127.2 7.26.1 1.0 mm thick. sqm 7295 676.40 4,934,338.00
9.131 7.27 Providing and fixing factory made shutters of Pre-laminated particle board
flat pressed three layer or graded wood particle board with one side
decorative finish and other side balancing lamination conforming to IS:
12823 Grade l Type ll, of approved design, and edges sealed with water
resistant paint and lipped with aluminium U type edge beading allround
the shutter, including fixing with angle cleat, grip strip, cadmium plated
steel screws, including fixing of aluminium hinges 100x63x4 mm
etc.complete as per architectural drawing and direction of Engineer-in-
Charge (Cost of U beading and hinges will be paid for separately).
sqm 65 1,310.30 85,169.50
9.132 7.28 Providing and fixing aluminum U beading of required size to Pre-
laminated/ flush door shutter, including fixing etc. complete as per direction
of Engineer-in-charge. kg 185 442.35 81,834.75

BOQ - (CIVIL) 16
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 7.29 Providing and fixing wardrobe 600 deep with 18 mm thick commercial ply
BWR grade for sides, top , bottom, shelves 18 mm thick commercial
board BWR for shutters finished with lamination and 6 mm thick ply BWR
grade for back ,100mm x 20mm thick skirting. All un exposed surface shall
be finished with synthetic enamel paint. All exposed edges of ply and
board to be finished with 6mm thick T.W. lipping. Necessary hardware and
fittings as shown in drawing / approved by the architect / client. Surface
area to be measured. sqm 36780 9,787.00 359,965,860.00
NS 7.30 Providing and fixing overhead storage unit in kitchen 300 deep with 18 mm
thick commercial ply BWR grade for sides, top and bottom, 19 mm thick
commercial board BWR for shutters and 6 mm thick ply BWR grade for
back , All exposed edges of ply and board to be finished with 2 mm thick
PVC edge binding. All exposed surfaces of cupboard to be finished with 1
mm thick laminate of approved colour and shade, all unexposed surfaces
to be finished with balancing laminate of approved colour with necessary
hardware and fittings as shown in drawing / approved by the architect /
client. Surface area to be measured.

7.30.1 300 MM DEEP sqm 3380 6,805.00 23,000,900.00


NS 7.31 Providing and fixing wardrobe 600 deep with 18 mm thick commercial ply
BWR grade for sides, top , 18 mm thick commercial ply for shelves, 2 no
drawers on telescopic channels,19 mm thick commercial board BWR for
shutters and 6 mm thick ply BWR grade for back ,100mm x 20mm thick
skirting, All exposed edges of ply and board to be finished with 6mm thick
T.W. lipping. All exposed and unexposed surfaces of cupboard to be
finished with 4 mm thick teak with melamine polish including cost of
drawers with necessary hardware and fittings as shown in drawing /
approved by the architect / client. Surface area to be measured.
sqm 1920 9,000.00 17,280,000.00

BOQ - (CIVIL) 17
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 7.32 Supply and fixing of Wooden door frame of section 145 mm x 70 mm with
heat activated intumescent fire seal strip of section 10 mm x 4 mm
(Astroflame / Abesco and one coat of anti-termite fire retardant Primer
and 55 mm thick asbestos free composite fire / smoke check wooden
shutters of 120 min. Fire Rating confirming to BS;476 Part 22 & IS : 3614
Part II comprising of two 9 mm thick Starpan Calcium Silicate boards, a
100% without Asbestos, Brucite and Meerschaum, having density not
3 *
more than 1150Kg/M and thermal conductivity 0.14 W/m K sandwiching
31mm thick fire resistance insulation filler faced with 3 mm thick
commercial ply facing on both side with heat activated intumescent fire
seal strip of size 10 mm x 4 mm (Astroflame / Abesco mounted in the
grooves of hardwood lipping on all sides except bottom. The intumescent
sealant shall be used to fill the gaps between board and internal wooden
lipping. sqm 1025 11,729.00 12,022,225.00
NS 7.33 Providing & fixing toilet cubicles similar to MODLE TYPE : Greenlam
Sturdo Vibrance- Serene with the following specifications each 30 33,432.00 1,002,960.00
Thickness of Compact Laminate : 12mm
Accessories Details : Standard Nylon polymide and anodised
aluminium top rail and u channel
a) Adjustable foot.
b) U -Channel
c) Gravity hinges (Right /Left)
d) Coat Hook
e) Door Knob
f) Lockset with indicator.
g) Aluminium Anodised Top Rail
h) Screws & Wall Plugs
NS 7.34 Providing & fixing urinal partition MODEL -A - PRIVY DIVIDER
PANELS of Greenlam or equivalent with the following specifications
each 8 4,752.00 38,016.00
Made of 12 mm thick compact laminate.
Total height 1195 mm , depth 550 mm, gap from ground 500 to 600 mm
Hardware : - Stainless steel l clamp shall be used to attach the divider to
the wall,Stainless steel L clamp hardware fittings along with SU 304
screws shall be used to fix the Urinal Partitions on the wall.
NS 7.35 Providing & fixing toilet cubicles similar to MODLE TYPE : Greenlam
Sturdo Kiddie World with the following specifications
Color of HPL Boards : As per Greenlam Sturdo Range

BOQ - (CIVIL) 18
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Thickness of Compact Laminate : 12mm
Size of Partitions : Partition height 1500 mm and door ht. 1250 mm
Accessories Details : Standard Stainless Steel (Grade - 304)
a) Stainless Steel Shoe Box Up
b) U -Channel
c) Stainless Steel Gravity hinges (Right /Left)
d) Coat Hook with door Stopper
e) Door Knob
f) Lockset with indicator.
g) Screws & Wall Plugs
Overall height : 1500 mm(Including 100mm Ground Clearence) nos. 32 30,336.00 970,752.00
9.139 7.36 Providing and fixing panic bar / latch (Double point) fitted with a single
body, Trim Latch & Lock on back side of the Panic Latch of reputed brand
and manufacture to be approved by the Engineer- in- charge, all
complete. nos. 575 6,133.30 3,526,647.50
NS 7.37 Providing and fixing outside Access Device for Panic Bar each 264 5,096.00 1,345,344.00
21.18 7.38 Providing and fixing 12 mm thick frameless toughened glass door shutter
of approved brand and manufacture, including providing and fixing top &
bottom pivot & spring type fixing arrangement and making necessary holes
etc. for fixing required door fittings, all complete as per direction of
Engineer-in-charge (Door handle, lock and stopper etc.to be paid
separately). sqm 140 4,746.25 664,475.00
TOTAL OF WOOD WORK CARRIED OVER TO SUMMARY OF CIVIL
WORKS 104,923,830.95 421,367,240.40

BOQ - (CIVIL) 19
CHAPTER - 8 : STEEL WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
10.2 8.1 Structural steel work riveted, bolted or welded in built up sections, trusses
and framed work, including cutting, hoisting, fixing in position and applying
a priming coat of approved steel primer all complete. kg 35985 73.95 2,661,090.75
10.5 8.2 Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6mm
angle iron and 3mm M.S. gusset plates at the junctions and corners, all
necessary fittings complete, including applying a priming coat of approved
steel primer.
10.5.1 8.2.1 Using M.S. angles 40x40x6 mm for diagonal braces. sqm 125 3,073.85 384,231.25
10.6 8.3 Supplying and fixing rolling shutters of approved make, made of required
size M.S. laths, interlocked together through their entire length and jointed
together at the end by end locks, mounted on specially designed pipeshaft
with brackets, side guides and arrangements for inside and outsidelocking
with push and pull operation complete, including the cost ofproviding and
fixing necessary 27.5 cm long wire springs manufacturedfrom high tensile
steel wire of adequate strength conforming to IS: 4454 -part 1 and M.S.
top cover of required thickness for rolling shutter

10.6.3 8.3.1 80x0.90 mm M.S. laths with 0.90 mm thick top cover sqm 180 1,797.50 323,550.00
10.7 8.4 Providing and fixing ball bearing for rolling shutters. each 27 438.95 11,851.65
10.11 8.5 Providing and fixing factory made ISI marked steel glazed doors, windows
and ventilators, side /top /centre hung, with beading and all members such
as F7D,F4B, K11 B and K12 B etc. complete of standard rolled steel
sections, joints mitred and flash butt welded and sash bars tenoned and
riveted, including providing and fixing of hinges, pivots, including priming
coat of approved steel primer, but excluding the cost of other fittings,
complete all as per approved design, (sectional weight of only steel
members shall be measured for payment).

10.11.1 8.5.1 Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block
15x10x10 cm of C.C. 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) kg 230 114.15 26,254.50

BOQ - (CIVIL) 20
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
10.13 8.6 Providing and fixing T-iron frames for doors, windows and ventilators of
mild steel Tee-sections, joints mitred and welded, including fixing of
necessary butt hinges and screws and applying priming coat of approved
steel primer.
10.13.1 8.6.1 Fixing with 15x3 mm lugs 10 cm long embedded in cement concrete block
15x10x10 cm of C.C. 1:3:6( 1 Cement : 3 coarse sand : 6 graded stone
aggregate : 20mm nominal size) kg 895 83.70 74,911.50
10.18 8.7 Providing and fixing circular / hexagonal cast iron or M.S. sheet box for
ceiling fan clamp, of internal dia 140 mm, 73 mm height, top lid of 1.5 mm
thick M.S. sheet with its top surface hacked for proper binding, top lid shall
be screwed into the cast iron/M.S. sheet box by means of 3.3 mm dia
round headed screws, one lock at the corners. Clamp shall be made of 12
mm dia M.S. bar bent to shape as per standard drawing .
each 3286 142.95 469,733.70
10.25 8.8 Steel work welded in built up sections/ framed work, including cutting,
hoisting, fixing in position and applying a priming coat of approved steel
primer using structural steel etc.as required
10.25.2 8.8.1 In gratings, frames, guard bar, ladders, railings, brackets, gates & similar
works kg 1298530 90.10 116,997,553.00
10.26 8.9 Providing and fixing hand rail of approved size by welding etc. to steel
ladder railing, balcony railing, staircase railing and similar works,
including applying priming coat of approved steel primer.
10.26.1 8.9.1 M. S. tube kg 87680 104.70 9,180,096.00
10.27 8.10 Providing and fixing carbon steel galvanised ( minimum coating 5 micron)
dash fastener of 10 mm dia double threaded 6.8 grade (yield strength 480
N/mm2), counter sunk head, comprising of 10 m dia polyamide PA 6
grade sleeve, including drilling of hole in frame , concrete/ masonry, etc.
as per direction of Engineer-in-charge.
10.27.3 8.10.1 10 x 120 mm each 74815 86.75 6,490,201.25

BOQ - (CIVIL) 21
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
10.28 8.11 Providing and fixing stainless steel ( Grade 304) railing made of Hollow
tubes, channels, plates etc., including welding, grinding, buffing, polishing
and making curvature (wherever required) and fitting the same with
necessary stainless steel nuts and bolts complete, i/c fixing the railing with
necessary accessories & stainless steel dash fasteners , stainless steel
bolts etc., of required size, on the top of the floor or the side of waist slab
with suitable arrangement as per approval of Engineer-in-charge, (for
payment purpose only weight of stainless steel members shall be
considered excluding fixing accessories such as nuts, bolts, fasteners
etc.). kg 7155 619.40 4,431,807.00
10.19 8.12 Providing and fixing mild steel round holding down bolts with nuts and
washer plates complete. kg 180 73.95 13,311.00
NS 8.13 Providing and fixing stainless steel ( Grade 304)Hollow tubes, channels,
plates etc., including welding, grinding, buffing, polishing and making
curvature (wherever required) and fitting the same with necessary
stainless steel nuts and bolts complete with necessary accessories &
stainless steel dash fasteners , stainless steel bolts etc., of required size
with suitable arrangement as per approval of Engineer-in-charge by
specialist agency for Glass canopy kg 475 661.00 313,975.00
TOTAL OF STEEL WORK CARRIED OVER TO SUMMARY OF CIVIL
WORKS 141,064,591.60 313,975.00

BOQ - (CIVIL) 22
CHAPTER - 9 : FLOORING
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
11.16 9.1 Precast terrazo tiles 22 mm thick with graded marble chips of size upto 12
mm, laid in floors, and landings, jointed with neat cement slurry mixed with
pigment to match the shade of the tiles, including rubbing and polishing
complete, on 20 mm thick bed of cement mortar 1:4 (1 cement:4 coarse
sand) :
11.16.1 9.1.1 Light shade pigment using white cement sqm 27560 1,029.05 28,360,618.00
11.18 9.2 Precast terrazo tiles 22 mm thick with graded marble chips of sizes upto
12 mm, in skirting and risers of steps not exceeding 30 cm in height, on 12
mm thick cement plaster 1:3 (1 cement : 3 coarse sand), jointed with neat
cement slurry mixed with pigment to match the shade of the tiles, including
rubbing and polishing complete with tiles of :

11.18.1 9.2.1 Light shade pigment using white cement sqm 2885 1,316.15 3,797,092.75
11.26 9.3 Kota stone slab flooring over 20 mm (average) thick base laid over and
jointed with grey cement slurry mixed with pigment to match the shade of
the slab, including rubbing and polishing complete with base of cement
mortar 1:4 (1 cement : 4 coarse sand):

11.26.1 9.3.1 25 mm thick sqm 24270 1,141.40 27,701,778.00


11.27 9.4 Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars
laid on 12 mm (average) thick cement mortar 1:3 (1 cement : 3 coarse
sand) and jointed with grey cement slurry mixed with pigment to match the
shade of the slabs, including rubbing and polishing complete.
sqm 5505 1,191.25 6,557,831.25
11.29 9.5 40 mm thick fine dressed stone flooring over 20 mm (average) thick base
of cement mortar 1:5 (1 cement : 5 coarse sand), including pointing with
cement mortar 1:2 (1 cement : 2 stone dust) with an admixture of pigment
to match the shade of stone.
11.29.1 9.5.1 Red sand stone sqm 1510 686.45 1,036,539.50
11.29.2 9.5.2 White sand stone sqm 180 712.00 128,160.00
11.31 9.6 Extra for pre finished nosing in treads of steps of Kota stone/ sand stone
slab. metre 11285 75.80 855,403.00

BOQ - (CIVIL) 23
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
11.36 9.7 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS:
15622 (thickness to be specified by the manufacturer), of approved make,
in all colours, shades except burgundy, bottle green, black of any size as
approved by Engineer-in-Charge, in skirting, risers of steps and dados,
over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand)
and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in
white cement mixed with pigment of matching shade complete.
sqm 43705 836.65 36,565,788.25
11.37 9.8 Providing and laying Ceramic glazed floor tiles of size 300x300 mm
(thickness to be specified by the manufacturer) of 1st quality conforming
to IS : 15622 of approved make in colours such as White, Ivory, Grey,
Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 (1 Cement : 4
Coarse sand) including pointing the joints with white cement and matching
pigment etc. complete. sqm 20580 785.40 16,163,532.00
11.41 9.9 Providing and laying vitrified floor tiles in different sizes (thickness to be
specified by the manufacturer) with water absorption less than 0.08% and
conforming to IS:15622 ,of approved make,in all colours and shades, laid
on 20mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand) including
grouting the joints with white cement and matching pigments etc.
complete.

11.41.2 9.9.1 Size of Tile 600x 600 mm sqm 10735 1,405.95 15,092,873.25
11.46 9.10 Providing and laying Vitrified tiles in different sizes (thickness to be
specified by manufacturer), with water absorption less than 0.08 % and
conforming to I.S. 15622, of approved make, in all colours & shade, in
skirting, riser of steps, over 12 mm thick bed of cement mortar 1:3 (1
cement: 3 coarse sand), including grouting the joint with white cement &
matching pigments etc. complete.
11.46.2 9.10.1 Size of Tile 600x600 mm sqm 905 1,415.40 1,280,937.00
16.68 9.11 Providing and laying 60mm thick factory made cement concrete
interlocking paver block of M -30 grade made by block making machine
with strong vibratory compaction, of approved size, design & shape, laid in
required colour and pattern over and including 50mm thick compacted
bed of coarse sand, filling the joints with fine sand etc. all complete as per
the direction of Engineer-in-charge. sqm 2405 602.20 1,448,291.00

BOQ - (CIVIL) 24
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
16.89 9.12 Providing and laying matt finished vitrified tile of size 300x300x9.8mm
having with water absorption less than 0.5% and conforming to IS: 15622
of approved make in all colours and shades in for outdoor floors such as
footpath, court yard, multi modals location etc., laid on 20mm thick base of
cement mortar 1:4 (1cement : 4 coarse sand) in all shapes & patterns
including grouting the joints with white cement mixed with matching
pigments etc. complete as per direction of Engineer-in-Charge.
sqm 450 986.35 443,857.50
NS 9.13 Providing & fixing of a flexible, homogeneous, non-directional Vinyl floor
covering with a delicate design incorporated throughout the entire 2.00
mm thickness of the product. Having standard BS EN ISO 10874:2012
and BS EN 649:2011 ( Group T) and Slip resistance R10. Its Total Weight
is 2800g/m2 in Sheet of size 15mtrs x 2mtrs, having Surface treated with
the new RQ Protect patented process that completely replaces the
application of wax or polish during the lifetime of the product. Anti-fungal
and anti-bacterial flooring which complies with the EN 649 (34 / 43) and
having abrasion resistance Group T wear rating. It is suitable for heavy
traffic areas. Its Residual Indentation is ~0.03 (< 0.10)mm as per standar
EN 433. Dimensional Stability as per EN 434 is < 0.40% and flexibility as
per EN435 is < 20mm. Passed with Continuous Castor Chair Test. Sound
Insulation as per EN ISO 717-2 is 4dB and Reaction to Fire as per EN
13501-1:2007+A1:2009 is Bfl-S1 Class.
sqm 840 2,609.00 2,191,560.00
11.3 9.14 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate) finished with a floating coat of neat cement, including
cement slurry, but excluding the cost of nosing of steps etc. complete.

11.3.1 9.14.1 40 mm thick with 20 mm nominal size stone aggregate sqm 13495 353.35 4,768,458.25
11.6 9.15.1 Cement plaster skirting (upto 30 cm height) with cement mortar 1:3 (1
cement : 3 coarse sand) finished with a floating coat of neat cement.

11.6.1 9.15.1 18 mm thick sqm 245 377.25 92,426.25

BOQ - (CIVIL) 25
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
11.5 9.16 62 mm thick cement concrete flooring with concrete hardener topping,
under layer 50 mm thick cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 20mm nominal size) and top layer 12mm
thick cement hardener consisting of mix 1:2 (1 cement hardener mix : 2
graded stone aggregate, 6mm nominal size) by volume, hardening
compound mixed @ 2 litre per 50 kg of cement or as per manufactures
specifications. This includes cost of cement slurry, but excluding the cost
of nosing of steps etc. complete.
sqm 36655 588.90 21,586,129.50
11.53 9.17 Providing and fixing Glass mossaic tiles at finished plain wall surface of
size 20 mm x 20 mm x 4 mm in all colour, design , fixing in customize
design as per direction of Engineer-in- Charge. The glass mosaic tiles to
be fixed on the wall surface with the help of approved adhesive applied at
the rate of 2.5 kg per sqm and grouting of the same. The rate is inclusive
of all operation, material and required pattern approved by Engineer-in-
Charge:
sqm 995 1,752.60 1,743,837.00
NS 9.18 8mm thick click type HDF laminated board flooring of approved make over
2 mm thick approved cell foam, including 0.5 mm polythene sheet over
cement concrete screed smooth finish as specified (base cement
concrete screeding measured and paid separately). sqm 2145 1,455.00 3,120,975.00
NS 9.19 Providing and fixing 100 mm high 12 mm thick TW skirting with
necessary screws and malamine polish all complete. metre 370 249.00 92,130.00
16.90 9.20 Providing and laying tactile tile (for vision impaired persons as per
standards) of size 300x300x9.8mm having with water absorption less than
0.5% and conforming to IS: 15622 of approved make in all colours and
shades in for outdoor floors such as footpath, court yard, multi modals
location etc., laid on 20mm thick base of cement mortar 1:4 (1cement : 4
coarse sand) in all shapes & patterns including grouting the joints with
white cement mixed with matching pigments etc. complete as per direction
of Engineer-in-Charge. sqm 575 1,439.35 827,626.25
TOTAL OF FLOORING WORK CARRIED OVER TO SUMMARY OF
CIVIL WORKS 168,451,178.75 5,404,665.00

BOQ - (CIVIL) 26
CHAPTER - 10 : ROOFING
8 -
DSR RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
12.21 10.1 Providing gola 75 x 75 mm in cement concrete 1:2:4 (1 cemment : 2
course sand : 4 stone aggregate 10 mm & down gauge) including finishing
with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design.

12.21.1 10.1.1 In 75 x 75 mm deep chase metre 5440 143.10 778,464.00


12.22 10.2 Making khurras 45x45 cm with average minimum thickness of 5 cm
cement concrete 1:2:4 (1 cement :2 coarse sand : 4 graded stone
aggregate of 20 mm nominal size) over P.V.C. sheet 1mx1mx400 micron,
finished with 12mm cement plaster 1:3 (1 cement :3 coarse sand) and a
coat of neat cement, rounding the edges and making and finishing the
outlet complete each 416 186.65 77,646.40
NS 10.3 Supplying and stacking of good earth at site including royalty and carriage
up to 1 km (earth measured in stacks will be reduced by 20% for
payment). cum 7400 320.68 2,373,061.60
NS 10.4 Filling available earth cum 7255 112.40 815,462.00
22.21 10.5 Extra for covering top of membrane with Geotextile, 120 gsm non woven,
100% polyester of thickness 1 to 1.25 mm bonded to the membrane with
intermittent touch by heating the membrane by Butane Torch as per
manufactures recommendation. sqm 14250 74.85 1,066,612.50
NS 10.6 Supplying, filling, spreading & leveling gravels of size range 5 mm to 10
mm, in required thickness, for all leads & lifts, all complete as per direction
of Engineer-incharge. cum 715 910.65 651,114.75
13.6 10.7 20 mm cement plaster of mix :
13.6.1 10.7.1 1:4 (1 cement : 4 coarse sand) sqm 14250 242.05 3,449,212.50
13.21 10.8 Extra for providing and mixing water proofing material in cement plaster per bag
work in proportion recommended by the manufacturers. of 50kg
cement
used in
the mix 1825 50.65 92,436.25
NS 10.9 Waterproofing treatment to construction joints as per following steps :
Chasing open the construction joints to form U shape groove and
thereafter cleaning the surface to the requirements, and doing treatment in
the chased portion at the vendor specified coverage rate and method to
seal the construction joints. Work shall be guranteed for ten(10) years
from the date of completion against any leakage metre 805 264.00 212,520.00

BOQ - (CIVIL) 27
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 10.10 Cementitious based dry Krystol T1 crystalline powder capable of creating
crystals to seal the pores, intecises, microcracks in the concrete. This
Krystol T1 system become integral part of concrete and is not affected by
surface wear and abrasion. This will be applied on wet saturated new
concrete surfaces. . It will be able to withstand high hydrostatic pressure,
stop moisture coming up through concrete to debond any overlay system.
It will eliminate the need for surface applied membranes etc. It does not
contain stearates, sodium or silicate and is not hydrophobic type. It will be
able to grow crystals year after year should seal microcracks (not live /
moving crack) that may occur from subsequent damage to structure.
Apply slurry to the concrete surface with a brush in a circular, scrubbing
motion so as to achieve maximum adhesion and penetration. Apply the
slurry to the entire concrete slab @ 1kg per sqm.

sqm 14250 397.00 5,657,250.00


NS 10.11 Providing and applying Roof Guard ( a TPE) waterproofing with a
elongation of 440% to be applied in 3 coats including Primer coat ,
Applying 1st coat of primer by mixing 25% water and 75% roofguardi by
volume and allowing to dry. Applying of second coat of acrylic coating by
mixing 5% water and 95% roof gard i by volume.Applying third coat of
Acrylic coating by mixing 5% water and 95% roofgardi. Total consumption
of 3 coats to be 0.75 kg/sq.m The coating once dried coating will have
over 440% elongation. sqm 14250 487.50 6,946,875.00

BOQ - (CIVIL) 28
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
12.45 10.12 Providing and fixing false ceiling at all height including providing and fixing
of frame work made of special sections, power pressed from M.S. sheets
and galvanized with zinc coating of 120 gms/sqm (both side inclusive) as
per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm
thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one
flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long
with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of
25x10x0.50 mm of required length with nuts & bolts of required size and
other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9
mm running at the spacing of 1200 mm centre to centre, to which the
ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges
of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall
be fixed in a direction perpendicular to G.I. intermediate channel with
connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at
every junction, including fixing perimeter channels 0.5 mm thick 27 mm
high having flanges of 20 mm and 30 mm long, the perimeter of ceiling
fixed to wall/partition with the help of rawl plugs at 450 mm centre, with
25mm long dry wall screws @ 230 mm interval, including fixing of gypsum
board to ceiling section and perimeter channel with the help of dry wall
screws of size 3.5 x 25 mm at 230 mm c/c, including jointing and finishing
to a flush finish of tapered and square edges of the board with
recommended jointing compound, jointing tapes, finishing with jointing
compound in 3 layers covering upto 150 mm on both sides of joint and two
coats of primer suitable for board, all as per manufacturer's specification
and also including the cost of making openings for light fittings, grills,
diffusers, cutouts made with frame of perimeter channels suitably fixed, all
complete as per drawings, specification and direction of the Engineer-in-
Charge but excluding the cost of painting with:

12.45.1 10.12.1 12.5mm thick tapered edge gypsum plain board conforming to IS : 2095 -
Part 1. sqm 1355 907.10 1,229,120.50

BOQ - (CIVIL) 29
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
12.53 10.13 Providing and Fixing 15 mm thick densified tegular edged eco friendly light
weight calcium silicate false ceiling tiles of approved texture
spintone/cosmos / Hexa or equivalent of size 595 x 595 mm in true
horizontal level, suspended on inter locking metal grid of hot dipped
galvanised steel sections (galvanising @ 120 grams per sqm including
both side) consisting of main 'T' runner suitably spaced at joints to get
required length and of size 24x38 mm made from 0.33 mm thick
(minimum) sheet, spaced 1200 mm centre to centre, and cross "T" of size
24x28 mm made out of 0.33 mm (Minimum) sheet, 1200 mm long spaced
between main'T' at 600 mm centre to centre to form a grid of 1200x600
mm and secondary cross 'T' of length 600 mm and size 24 x28 mm made
of 0.33 mm thick (Minimum) sheet to be inter locked at middle of the
1200x 600 mm panel to from grid of size 600x600 mm, resting on
periphery walls /partitions on a Perimeter wall angle pre-coated steel of
size(24x24X3000 mm made of 0.40 mm thick (minimum) sheet with the
help of rawl plugs at 450 mm centre to centre with 25 mmlong dry wall
screws @ 230 mm and laying 15 mm thick densified edges calicum
silicate ceiling tiles of approved texture (Spintone / Cosmos/hexa) in the
grid, including, cutting/ making opening for services like diffusers, grills,
light fittings, fixtures, smoke detectors etc., wherever required. Main 'T'
runners to be suspended from ceiling using G.I. slotted cleats of size
25x35x1.6 mm fixed to ceiling with 12.5 mm dia and 50 mm long dash
fasteners, 4 mm G.I. adjustable rods with galvanised steel level clips of
size 85 x 30 x 0.8 mm, spaced at 1200 mm centre to centre along main 'T'
, bottom exposed with 24 mm of all T-sections shall be pre-painted with
polyster baked paint, for all heights, as per specifications, drawings and as
directed by engineer-in-charge.

10.13.1 Note :- Only calcium silicate false ceiling area will be measured from wall
to wall. No deduction shall be made for exposed frames/opening (cut outs)
having area less than 0.30 sqm.The calcium silicate ceiling tile shall have
NRC value of 0.50 (Minimum), light reflection > 85%, non - combustible as
per B.S. 476 part IV, 100% humidity resistance and also having thermal
conductivity <0.043 w/m 0 KC. sqm 5310 1,649.15 8,756,986.50

BOQ - (CIVIL) 30
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
12.56 10.14 Providing and laying roof insulation with 40 mm thick impervious sprayed,
closed cell free Rigid Polyurethane foam over deck insulation conforming
to IS - 12432 Pt. III (density of foam being 40-45 kg/ cum), over a coat of
polyurethane primer applied @ 6-8 sqm per litre, laying 400 G polythene
sheet over PUF spray and providing a wearing course of 40 mm thick
cement screed 1: 2 : 4 (1 cement : 2 coarse sand : 4 stone aggregate 20
mm nominal size) in chequered rough finish, in panels of 2.5 m x 2.5 m
and embedding with 24 G wire netting and sealing the joints with
polymerized mastic, all complete as per direction of Engineer-in-Charge.
sqm 940 1,167.20 1,097,168.00
12.63 10.15 Providing and applying two coats of High Albedo paint having minimum
Solar Reflective Index (SRI) 108 (with solar reflectance & thermal
emittance tested as per ASTM) C 1549 and ASTM C 1371 respectively),
VOC less than 10 cc/gm. The coating thickness and the methodology of
application shall strctly as per manufacturers specifications and as
approved by engineer In charge. Surface preparation includes cleaning
with metal wire brush to remove all dust, fungus etc., washing with water
all complete. The contractor shall give guarantee for the perfomance of
SRI and also the durabitity of coating, all complete as per direction of
Engineer-in-incharge. sqm 13390 257.60 3,449,264.00
NS 10.16 Providing and fixing U baffle metal ceiling with 50mm X 100mm baffle
panel @ 100mm c/c with GI suspension system by specialist agency
sqm 310 8,323.00 2,580,130.00
TOTAL OF ROOFING WORK CARRIED OVER TO SUMMARY OF CIVIL
WORKS 19,996,910.65 19,236,413.35

BOQ - (CIVIL) 31
CHAPTER - 11 : WATER PROOFING
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
22.3 11.1 Providing and laying water proofing treatment to vertical and horizontal
surfaces of depressed portions of W.C., kitchen and the like consisting of:
(i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water
proofing compound conforming to IS 2645 in recommended proportions
including rounding off junction of vertical and horizontal surface.
(ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand)
mixed with water proofing compound in recommended proportion
including rounding off junction of vertical and horizontal surface.
(iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg.
per sqm of area.
(iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC
sheet should be 100 mm wide and pasted to each other with bitumen @
1.7 kg/sqm).

sqm 17360 522.90 9,077,544.00


22.6 11.2 Providing and laying water proofing treatment on roofs of slabs by
applying cement slurry mixed with water proofing cement compound
consisting of applying: a) after surface preparation, first layer of slurry of
cement @ 0.488 kg/sqm mixed with water proofing cement compound @
0.253 kg/sqm. b) laying second layer of Fibre glass cloth when the first
layer is still green. Overlaps of joints of fibre cloth should not be less than
10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement @
1.289 kg/sqm mixed with water proofing cement compound @ 0.670
kg/sqm and coarse sand @ 1.289 kg/sqm. This will be allowed to air cure
for 4 hours followed by water curing for 48 hours. The entire treatment will
be taken upto 30 cm on parapet wall and tucked into groove in parapet all
around. d) fourth and final layer of brick tiling with cement mortar (which
will be paid for separately. For the purpose of measurement the entire
treated surface will be measured.
sqm 16210 390.35 6,327,573.50

BOQ - (CIVIL) 32
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
12.19 11.3 Providing and laying brick tiles over mumty roofs, grouted with cement
mortar 1:3 (1 cement : 3 fine sand) mixed with 2% of integral water
proofing compound by weight of cement, over 12 mm layer of cement
mortar 1:3 (1 cement : 3 fine sand) and finished neat :
12.19.1 11.3.1 With common burnt clay F.P.S. (non modular) brick tiles of class
designation 10 sqm 16210 420.50 6,816,305.00
22.14 11.4 Grading roof for water proofing treatment with
22.14.1 11.4.1 Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) cum 1220 5,570.55 6,796,071.00
NS 11.5 Raft / Footing
Mixing integral Crystalline dry powder to be added in designed concrete
mix @ 0.8% by wt of cement / cum .in entire thickness of raft and footing.
The admixture will not contain, stearates, sodium or silicate. It will not
hydrophobic or surface densifier, will be able to withstand high hydrostatic
pressure and does not require any protection coating. It will become a
real integral part of concrete. kg 29665 319.00 9,463,135.00
NS 11.6 Retaining Wall
Cementitious based crystalline powder capable of creating crystals to
seal the pores, intecises, microcracks in the concrete. This system
become integral part of concrete and is not affected by surface wear and
abrasion. This will be applied on wet saturated new concrete surfaces.
This should be non toxic and suitable for application in drinking water
tanks. It will be able to withstand high hydrostatic pressure, stop moisture
coming up through concrete to debond any overlay system. It will
eliminate the need for surface applied membranes etc. It does not contain
stearates, sodium or silicate and is not hydrophobic type. It will be able to
grow crystals year after year should seal microcracks (not live / moving
crack) that may occur from subsequent damage to structure. Apply slurry
to the concrete surface with a brush in a circular, scrubbing motion so as
to achieve maximum adhesion and penetration. Apply the slurry to the
entire concrete slab @ 1kg per sqm.
Sqm 9200 404.00 3,716,800.00

BOQ - (CIVIL) 33
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 11.7 Construction Joint
Waterproofing treatment to construction joints as per following steps :
Chasing open the construction joints to form U shape groove and
thereafter cleaning the surface to the requirements, and doing treatment in
the chased portion at the vendor specified coverage rate and method to
seal the construction joints. Work shall be guranteed for ten(10) years
from the date of completion against any leakage metre 1015 264.00 267,960.00
TOTAL OF WATER PROOFING WORK CARRIED OVER TO SUMMARY
OF CIVIL WORKS 29,017,493.50 13,447,895.00

BOQ - (CIVIL) 34
CHAPTER - 12 : FINISHING
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
13.1 12.1 12 mm cement plaster of mix:
13.1.2 12.1.1 1:6 (1 cement : 6 fine sand) sqm 14520 149.45 2,170,014.00
13.2 12.2 15 mm cement plaster on the rough side of single or half brick wall of mix :

13.2.2 12.2.1 1:6 (1 cement : 6 fine sand) sqm 22195 172.80 3,835,296.00
13.4 12.3 12 mm cement plaster of mix:
13.4.1 12.3.1 1:4 (1 cement : 4 coarse sand) sqm 241025 172.30 41,528,607.50
13.16 12.4 6 mm cement plaster of mix
13.16.1 12.4.1 1:3 (1 cement : 3 fine sand) sqm 86260 134.70 11,619,222.00
13.18 12.5 Neat cement punning. sqm 20 41.40 828.00
13.3 12.6 20 mm cement plaster of mix
13.3.1 12.6.1 1:4 (1 cement : 4 fine sand) sqm 37965 228.10 8,659,816.50
13.21 12.7 Extra for providing and mixing water proofing material in cement plaster per bag
work in proportion recommended by the manufacturers. of 50kg.
Cement
used in
the mix

4860 50.65 246,159.00


13.26 12.8 Providing and applying white cement based putty of average thickness 1
mm, of approved brand and manufacturer, over the plastered wall surface
to prepare the surface even and smooth complete.
sqm 122435 110.95 13,584,163.25
13.22 12.9 Extra for plastering exterior walls of height more than 10 m from ground
level for every additional height of 3 m or part thereof. sqm 20380 37.95 773,421.00
13.24 12.10 Extra for plastering done on moulding, cornices or architraves including
neat finish to line and level :
13.24.1 12.10.1 In one coat sqm 115 273.25 31,423.75
13.37 12.11 White washing with lime to give an even shade:
13.37.1 12.11.1 New work (three or more coats) sqm 97290 16.20 1,576,098.00

BOQ - (CIVIL) 35
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
13.62 12.12 Painting with synthetic enamel paint of approved brand and manufacture
of required colour to give an even shade :
13.62.1 12.12.1 Two or more coats on new work over an under coat of suitable shade with
ordinary paint of approved brand and manufacture sqm 70 106.25 7,437.50
13.83 12.13 Wall painting with premium acrylic emulsion paint of interior grade, having
VOC (Volatile Organic Compound ) content less than 50 grams/ litre of
approved brand and manufacture, including applying additional coats
wherever required to achieve even shade and colour.
13.83.2 12.13.1 Two coats sqm 315735 75.35 23,790,632.25
13.84 12.14 Painting with synthetic enamel paint, having VOC (Volatile Organic
Compound) content less than 150 grams/ litre, of approved brand and
manufacture, including applying additional coats wherever required to
achieve even shade and colour.
13.84.2 12.14.1 Two coats sqm 32020 71.60 2,292,632.00
13.47 12.15 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone
additives of required shade
13.47.1 12.15.1 New work (Two or more coats applied @ 1.43 ltr/10 sqm. over and
including priming coat of exterior primer applied @ 2.20 kg/10 sqm). sqm 37065 94.95 3,519,321.75
NS 12.16 Supply & fixing GRC tile of Stone & Wood Veneer of approved make as
per manufacturers specification sqm 14335 4,054.00 58,114,090.00
13.68 12.17 French spirit polishing :
13.68.1 12.17.1 Two or more coats on new works including a coat of wood filler sqm 100 193.95 19,395.00
13.29 12.18 18 mm thick plain cement mortar band in cement mortar 1:4 (1 cement : 4
fine sand):
13.29.3 12.18.1 Raised Band cm per
metre 5120 4.85 24,832.00
TOTAL OF FINISHING WORK CARRIED OVER TO SUMMARY OF
CIVIL WORKS 113,679,299.50 58,114,090.00

BOQ - (CIVIL) 36
CHAPTER - 13 : ALUMINIUM WORK
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
21.1 13.1 Providing and fixing aluminium work for doors, windows, ventilators, and
partitions with extruded built up standard tubular sections / appropriate Z
sections and other sections of approved make conforming to IS:733 and
IS: 1285, fixing with dash fasteners of required dia and size, including
necessary filling up the gaps at junctions i.e. at top, bottom and sides with
required EPDM rubber / neoprene gasket etc. Aluminium sections shall be
smooth, rust free, straight, mitred and jointed mechanically wherever
required including cleat angle, Aluminium snap beading for
glazing/paneling, C.P brass/stainless steel screws all complete as per
architectural drawings and the direction of Engineer in charge (Glazing,
Paneling and dash fasteners to be paid for separately).

21.1.1 13.1.1 For fixed Portion


21.1.1.1 13.1.1.1 Anodised aluminium (anodised transparent or dyed to required shade
according to IS: 1868, Minimum anodic coating of grade AC 15) kg 124630 348.50 43,433,555.00
21.1.2 13.2 For shutters of doors, windows & ventilators including providing and fixing
hinges / pivots and making provision for fixing of fittings wherever required
including the cost of EPDM rubber / Neoprene gasket required (Fittings
shall be paid for separately.)
21.1.2.1 13.2.1 Anodised aluminium (anodised transparent or dyed to required shade
according to IS: 1868, Minimum anodic coating of grade AC 15) kg 70395 405.90 28,573,330.50
21.3 13.3 Providing and fixing glazing in aluminium door, window, ventilator shutters
and partition etc. with EPDM rubber / neoprene gasket etc.complete as
per the architectural drawings and the direction of engineer in charge
(cost of aluminium snap beading shall be paid in basic item).

21.3.1 13.3.1 With float glass panes of 4.0 mm thickness . sqm 100 828.75 82,875.00
21.3.2 13.3.2 With float glass panes of 5.50 mm thickness sqm 12805 1,054.20 13,499,031.00

BOQ - (CIVIL) 37
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
21.4 13.4 Providing and fixing double action hydraulic floor spring of approved brand
and manufacture conforming to IS : 6315, having brand logo embossed
on the body / plate with double spring mechanism and door weight upto
125 kg, for doors, including cost of cutting floors, embedding in floors as
required and making good the same matching to the existing floor
finishing and cover plates with brass pivot and single piece M.S. sheet
outer box with slide plate etc. complete as per the direction of Engineer-in-
charge.
21.4.1 13.4.1 With stainless steel cover plate minimum 1.25 mm thickness each 28 2,039.00 57,092.00
21.11 13.5 Providing and fixing Stainless steel (SS 304 grade) adjustable friction
windows stays of approved quality with necessary stainless steel screws
etc.to the side hung windows as per direction of Engineer-in-charge
complete
21.11.1 13.5.1 205 x 19 mm. each 18492 228.75 4,230,045.00
21.8 13.6 Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone
work by providing weather silicon sealant over backer rod of approved
quality as per architectural drawings and direction of Engineer-in-charge
complete.
21.8.1 13.6.1 Upto 5mm depth and 5 mm width metre 58665 88.75 5,206,518.75
21.14 13.7 Providing and fixing anodised aluminium (anodised transparent or dyed to
required shade according to IS:1868. Minimum anodic coating of grade
AC 15) sub frame work for windows and ventilators with extruded built up
standard tubular sections of approved make conforming to IS:733 and
IS:1285 fixed with dash fastener of required dia and size (dash fastener to
be paid for saparately). kg 45390 312.20 14,170,758.00
21.16 13.8 Providing and fixing aluminium round shape handle of outer dia 100 mm
with SS screws etc .complete as per direction of Engineer-in-Charge.

21.16.1 13.8.1 Anodized (AC 15 ) aluminium each 44 65.60 2,886.40

BOQ - (CIVIL) 38
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
21.17 13.9 Providing and fixing anodised aluminium grill (anodised transparent or
dyed to required shade according to IS: 1868 with minimum anodic
coating of grade AC 15) of approved design/pattern, with approved
standard section and fixed to the existing window frame with C.P.brass/
stainless steel screws @ 200 mm centre to centre, including cutting the
grill to proper opening size for fixing and operation of handles and fixing
approved anodised aluminium standard section around the opening, all
complete as per requirement and direction of Engineer-in-charge. (Only
weight of grill to be measured for payment).
kg 1130 403.35 455,785.50
21.13 13.10 Providing and fixing 100 mm brass locks (best make of approved quality)
for aluminium doors including necessary cutting and making good etc.
complete. each 22 418.65 9,210.30
NS 13.11 Providing & fixing STRUCTURAL CURTAIN GLAZING system with double
glazed hermetically sealed glazing with 6 mm thick clear float glass both
side, having 12 mm air gap, including providing EPDM gasket, perforated
aluminium spacers, desiccants, sealant (Both primary andsecondary
sealant) etc. as per specifications, drawings with and including
aluminium splice section, glazing tape, back up foam, expansion anchor
bolts, nuts, aluminium pelmet, aluminium stool, structural silicon sealant,
silicon weather seal, EPDM gasket, smoke seal, glazed openable
door/window units without any frame visible from the outside to match the
structural glazing with necessary hardware of approved make, spandrel
area with single glazing with similar glass with and including internal
ployester coating and 5 mm thick black faced thermal insulation mineral
wool, 12 mm thick approved fire rated calcium silicate board fixed to soffit
of beams etc. all complete as specified.
sqm 470 9,018.00 4,238,460.00
TOTAL OF ALUMINIUM WORK CARRIED OVER TO SUMMARY OF
CIVIL WORKS 109,721,087.45 4,238,460.00

BOQ - (CIVIL) 39
CHAPTER - 14 : MISCELLANEOUS WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
4.17 14.1 Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement :
3 coarse sand: 6 graded stone aggregate 20 mm nominal size) over 75
mm thick bed of dry brick ballast 40 mm nominal size well rammed and
consolidated and grouted with fine sand, including finishing the top
smooth. sqm 3195 419.30 1,339,663.50
6.44 14.2 Brick edging 7 cm wide 11.4 cm deep to plinth protection with common
burnt clay FPS (non modular) bricks of class designation 7.5 including
grouting with cement mortar 1:4(1 cement: 4 fine sand).
metre 4255 38.15 162,328.25
NS 14.3 Providing and fixing fire hose cabinet door 1200x1500 mm with 40x75x14
gauge pressed steel door frame with 25x5x100 mm M.S. holdfast fixed in
concrete block in masonry, including shutters of 40x75x14 gauge pressed
steel stiles including 4 mm thick clear glass fixed with 12x12 mm M.S.
beading, fixing 75x40 mm brass hinges, Welding a 40x6mm M.S. flat on
the right shutter, including 2 coats of approved steel primer and synthetic
enamel paint of approved quality and shade, complete as per drawing.
each 276 5,144.00 1,419,744.00
5.18 14.4 Providing precast cement concrete Jali 1:2:4 (1 cement : 2 coarse sand: 4
graded stone aggregate 6 mm nominal size), reinforced with 1.6 mm dia
mild steel wire, including centering and shuttering, roughening cleaning,
fixing and finishing in cement mortar 1:3 (1 cement: 3 fine sand) etc.
complete, excluding plastering of the jambs, sills and soffits.

5.18.2 14.4.1 40 mm thick sqm 1440 638.90 920,016.00


NS 14.5 Providing and fixing multiwall 6mm multicel with X-structurer clear / bronze
/ Mettalic silver Polycarbonate sheet , aluminium/ SS cleats, aluminium
sheet edge, U Channe, Aluminium top and bottom profiles for turning
joints and SDS Screws for fixing of Polycarbonate Panel & sealed with
silicon sealant (Winsil - 20 of GE / Dow corning) for water proffing at the
required joints. Rectification of all damages caused to the building while
fixing the canopy shall be rectified to the satisfaction of the Engineer - in -
charge. sqm 170 4,580.00 778,600.00
NS 14.6 Providing and fixing 12 mm thick clear toughend glass in glass canopy
complete as per the architectural drawings and the direction of engineer
in charge sqm 40 4,869.00 194,760.00

BOQ - (CIVIL) 40
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
16.69 14.7 Providing and laying at or near ground level factory made kerb stone of M-
25 grade cement concrete in position to the required line, level and
curvature, jointed with cement mortar 1:3 (1 cement: 3 coarse sand),
including making joints with or without grooves (thickness of joints except
at sharp curve shall not to more than 5mm), including making drainage
opening wherever required complete etc. as per direction of Engineer-in-
charge (length of finished kerb edging shall be measured for payment).
(Precast C.C. kerb stone shall be approved by Engineer-in-charge).
cum 215 5,295.90 1,138,618.50
TOTAL OF MISCELLANEOUS WORK CARRIED OVER TO SUMMARY
OF CIVIL WORKS 3,560,626.25 2,393,104.00

BOQ - (CIVIL) 41
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
SUMMARY OF INTERNAL PLUMBING WORKS (figures in Rs.)
Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 Soil Waste & Vent Pipes & Fittings Works 55,149,602.70

Internal Water Supply & Internal Water Supply & Solar Water Heating
2 20,534,178.45 27,275,667.09
System

3 Sanitary Fixtures 33,510,738.75 42,303,373.30


4 Rain Water Pipes & Fittings 5,022,423.85
5 Sewerage System 918,350.60
6 Storm Water Drainage System 1,684,102.65
TOTAL OF INTERNAL PLUMBING WORKS CARRIED
OVER TO GRAND SUMMARY OF COSTS 116,819,397.00 69,579,040.39

BOQ - PL(INT) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - INTERNAL PLUMBING WORKS
CHAPTER - 1 : SOIL WASTE & VENT PIPES AND FITTINGS WORKS
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
17.35 1.1 Providing and fixing soil waste and vent pipes
17.35.1.2 (a) 100mm diameter centrifugally cast (spun) iron S&S pipe as per IS:3989.
Metre 23200 917.75 21,291,800.00
17.35.2.2 (b) 75mm diameter centrifugally cast (spun) iron S&S pipe as per IS:3989.
Metre 6095 791.30 4,822,973.50
17.37/12.3 1.2 Providing and fixing M.S. holder-bat clamps of approved design to sand
8 cast iron centrifugally cast (spun) iron S&S pipes embedded in and
including cement concrete blocks 10x 10 x 10 cm of 1:2:4 mix (1 cement :
2 coarse sand : 4 graded stone aggregate 20mm nominal size) including
cost of cutting holes and making good the walls, etc.

17.37.1 (a) For 100mm diametre Each 8900 152.90 1,360,810.00


17.37.1 (b) For 75mm diametre Each 2865 150.60 431,469.00
17.38 1.3 Providing and fixing bend of required degree with access door, insertion
rubber washer 3 mm thick, bolts and nuts complete.
17.38.1.2 (a) 100mm centrifugally cast (spun) iron S&S as per IS:3989. Each 89 385.70 34,327.30
17.39 1.4 Providing and fixing plain bend of required degree:
17.39.1.2 (a) 100mm centrifugally cast (spun) iron S&S as per IS:3989. Each 2577 335.75 865,227.75
17.39.2.2 (b) 75mm centrifugally cast (spun) iron S&S as per IS:3989. Each 2 248.80 497.60
17.40 1.5 Providing and fixing heel rest bend.
17.40.1.2 (a) 100mm centrifugally cast (spun) iron S&S as per IS:3989. Each 577 371.75 214,499.75
17.43 1.6 Providing and fixing single equal plain junction of required degree with
access door, insertion rubber washer 3mm thick, bolts and nuts complete

17.43.1.2 (a) 100 x 100 x 100mm centrifugally cast (spun) iron S&S Each 4451 623.80 2,776,533.80
17.44 1.7 Providing and fixing single equal plain junction of required degree :
17.44.1.2 (a) 100x100x100 mm Sand cast iron S&S as per IS - 3989 Each 355 576.20 204,551.00
17.44.2.2 (b) 75x75x75 mm Sand cast iron S&S as per IS - 3989 Each 1594 405.60 646,526.40
17.48 1.8 Providing and fixing single unequal plain junction of required degree
17.48.1.2 (a) 100x100x75 mm Sand cast iron S&S as per IS - 3989 Each 1650 690.00 1,138,500.00

BOQ - PL(INT) 15
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
17.55 1.9 Providing and fixing door pieces insertion rubber washer 3mm thick,
bolts and nuts complete
17.55.1.2 (a) 100mm centrifugally cast iron S&S as per IS: 3989. Each 577 513.45 296,260.65
17.56 1.10 Providing and fixing terminal guard
17.56.1.2 (a) 100mm centrifugally cast (spun) iron S&S as per IS: 3989. Each 577 434.50 250,706.50
17.56.2.2 (b) 75mm centrifugally cast (spun) iron S&S as per IS: 3989. Each 188 370.75 69,701.00
12.39/17.5 1.11 Providing lead caulked joints to sand cast iron/centrifugally cast (spun)
8 iron pipes and fittings of diameter
17.58.1 (a) 100mm Each 41305 243.75 10,068,093.75
17.58.2 (b) 75mm Each 9875 205.30 2,027,337.50
17.59 1.12 Providing and fixing M.S. stays and clamps for sand cast
iron/centrifugally cast (spun) iron pipe of diameter:
17.59.1 (a) 100mm Each 577 68.60 39,582.20
17.59.1 (b) 75mm Each 188 57.15 10,744.20
17.60 1.13 Providing and fixing cast iron trap of self cleansing design with sand cast
iron screwed down or hinged grating with or without vent, arm complete,
including cost of cutting and making good the walls and floors

17.60.1.1 (a) 100mm inlet and 100mm outlet centrifugally cast (spun) iron S&S as per
IS: 3989. Each 2778 982.55 2,729,523.90
17.65 1.14 Painting sand cast iron/centrifugally cast (spun) iron soil, waste vent
pipes and fittings with paint of any colour such as chocolate, grey or buff,
etc., over a coat of primer (of approved quality) for new work.
17.65.1 (a) 100mm diametre pipe Metre 16405 38.65 634,053.25
17.65.2 (b) 75mm diametre pipe Metre 6080 29.50 179,360.00
4.1 1.15 Providing and laying in position cement concrete of specified grade
excluding the cost of centring and shuttering - All work up to plinth level.

4.1.3 (a) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm


nominal size) cum 303 5,466.30 1,656,288.90
18.10 1.16 Providing and fixing G.I. pipes complete with G.I. fittings and clamps
including cutting and making good the walls etc., (Internal work) :
18.10.4 (a) 32mm nominal bore Metre 2915 343.20 1,000,428.00
18.10.6 (b) 50mm nominal bore Metre 2665 527.20 1,404,988.00
18.12.8 (c) 80mm diameter pipe Metre 1410 637.05 898,240.50

BOQ - PL(INT) 16
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
18.40 1.17 Painting G.I. pipes and fittings with two coats of anti-corrosive bitumastic
paint of approved quality.
18.40.4 (a) 32mm diameter pipe Metre 2915 10.40 30,316.00
18.40.6 (b) 50mm diameter pipe Metre 2665 14.15 37,709.75
18.40.8 (c) 80mm diameter pipe Metre 1410 20.25 28,552.50
TOTAL OF SOIL WASTE & VENT PIPES AND FITTINGS CARRIED
OVER TO SUMMARY OF INTERNAL PLUMBING WORKS
55,149,602.70 -

BOQ - PL(INT) 17
CHAPTER - 2 : INTERNAL WATER SUPPLY & SOLAR WATER HEATING SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
INTERNAL WATER SUPPLY
18.7 2.1 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply, including all CPVC plain &
brass threaded fittings, including fixing the pipe with clamps at 1.00 m
spacing. This includes jointing of pipes & fittings with one step CPVC
solvent cement and testing of joints complete as per direction of Engineer
in Charge.
Internal work - Exposed on Wall
18.7.2 (a) 20 mm nominal outer dia Pipes Metre 2935 190.55 559,264.25
18.7.3 (b) 25 mm nominal outer dia Pipes Metre 5465 231.30 1,264,054.50
18.7.4 (c) 32 mm nominal outer dia Pipes Metre 5255 296.70 1,559,158.50
18.7.5 (d) 40 mm nominal outer dia Pipes Metre 4830 407.90 1,970,157.00
18.7.6 (e) 50 mm nominal outer dia Pipes Metre 5110 581.55 2,971,720.50
18.8 2.2 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply, including all CPVC plain &
brass threaded fittings, i/c fixing the pipe with clamps at 1.00 m spacing.
This includes jointing of pipes & fittings with one step CPVC solvent
cement and the cost of cutting chases and making good the same
including testing of joints complete as per direction of Engineer in Charge.

Concealed work, including cutting chases and making good the


walls etc.
18.8.2 (a) 20 mm nominal outer dia Pipes Metre 30905 296.40 9,160,242.00
18.8.3 (b) 25 mm nominal outer dia Pipes Metre 6980 351.30 2,452,074.00
18.8.4 (c) 32 mm nominal outer dia Pipes Metre 85 422.40 35,904.00
18.9 2.3 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply including all CPVC plain &
brass threaded fittings This includes jointing of pipes & fittings with one
step CPVC solvent cement ,trenching ,refilling & testing of joints complete
as per direction of Engineer in Charge.
External Work
18.9.2 (a) 20mm nominal outer dia pipes Metre 15 163.30 2,449.50
18.9.3 (b) 25mm nominal outer dia pipes Metre 35 209.50 7,332.50
18.9.4 (c) 32mm nominal outer dia pipes Metre 25 262.35 6,558.75
18.9.5 (d) 40mm nominal outer dia pipes Metre 60 350.50 21,030.00

BOQ - PL (INT) 18
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
18.9.6 (e) 50mm nominal outer dia pipes Metre 60 524.10 31,446.00
18.18 2.4 Providing and fixing ball (brass) valve of approved quality. High or low
pressure, with plastic floats complete:
18.18.2 (a) 20 mm nominal bore Each 3 409.90 1,229.70
18.18.3 (b) 25 mm nominal bore Each 8 449.95 3,599.60
18.32 2.5 Constructing masonry Chamber 30x30x50 cm inside, in brick work in
cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I.
surface box 100x100 x75 mm (inside) with hinged cover fixed in cement
concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size), i/c necessary excavation, foundation
concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate
40mm nominal size ) and inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat
cement complete as per standard design :

18.32.1 a) With common burnt clay F.P.S (non modular) bricks of class designation
7.5 Each 15 1,157.75 17,366.25
18.33 2.6 Constructing masonry Chamber 60x60x75 cm inside, in brick work in
cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I.
surface box 100mm top diameter, 160 mm bottom diameter and 180 mm
deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2
coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c
necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand
: 10 graded stone aggregate 40 mm nominal size) and inside plastering
with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished
with a floating coat of neat cement complete as per standard design :

18.33.1 a) With common burnt clay F.P.S (non modular) bricks of class designation
7.5 Each 24 6,754.30 162,103.20
19.19 2.7 Providing and fixing in position pre-cast R.C.C. manhole cover and frame
of required shape and approved quality 19.19.1 L D- 2.5
19.19.3 H D - 20
19.19.3.1 a) Circular shape 560 mm internal diameter (For over head tanks) Each 104 1,511.55 157,201.20
18.48 2.8 Providing and placing on terrace (at all floor levels) polyethylene water
storage tank, ISI : 12701 marked, with cover and suitable locking
arrangement and making necessary holes for inlet, outlet and overflow
pipes but without fittings and the base support for tank. per litre 2000 7.25 14,500.00

BOQ - PL (INT) 19
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
ELECT. 2.9 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber
DSR 2014 Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation
/ 16.7.1 as specified

16.7.1.5 a) 80 mm dia Each 19 3,638.00 69,122.00


16.7.1.4 b) 100 mm dia Each 13 5,205.00 67,665.00
NS 2.10 Complete Item Rate for Providing and fixing 600mm long puddle flanges
fabricated out of 6mm thick M.S. plates along with flanges of suitable size
properly fixed in walls and top slabs of underground and overhead tanks.
The rate includes all taxes, handling, rehandling, lead lift, loading,
unloading T&P, Labour Charges etc.
a) 25mm dia Each 72 248.70 17,906.05
b) 32mm dia Each 36 293.53 10,567.09
c) 40mm dia Each 36 349.63 12,586.69
d) 50mm dia Each 72 434.31 31,269.96
e) 65mm dia Each 72 576.96 41,540.81
f) 100mm dia Each 72 1,305.08 93,965.49
NS 2.11 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply including all CPVC plain &
brass threaded fittings including fixing the pipe with clamps at 1.00 m
spacing. This includes jointing of pipes & fittings with one step CPVC
solvent cement and testing of joints complete as per direction of Engineer
in Charge.
Exposed on Wall
(a) 65mm nominal outer dia pipes (SCH-40 ASTM F-441) Metre 1255 1,535.00 1,926,425.00
(b) 80mm nominal outer dia pipes (SCH-40 ASTM F-441) Metre 995 1,940.00 1,930,300.00
(c) 100mm nominal outer dia pipes (SCH-40 ASTM F-441) Metre 965 2,685.00 2,591,025.00

BOQ - PL (INT) 20
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 2.12 Providing and fixing lever operated gun metal ball valve with SS ball.
(a) 20mm nominal bore Each 3943 591.00 2,330,313.00
(b) 25mm nominal bore Each 1231 865.00 1,064,815.00
(c) 32mm nominal bore Each 220 1,409.00 309,980.00
(d) 40mm nominal bore Each 241 1,960.00 472,360.00
(e) 50mm nominal bore Each 74 2,840.00 210,160.00
(f) 65mm nominal bore Each 71 5,908.00 419,468.00
NS 2.13 Providing and fixing ball valves with plastic float for inlet for water
storage tanks.
(a) 32mm dia Each 5 3,248.00 16,240.00
(b) 40mm dia Each 12 7,878.00 94,536.00
(c) 50mm dia Each 12 4,334.00 52,008.00
NS 2.14 Providing and fixing class-O Kaiflex ST insulation 6mm thick to hot
water pipe and fittings and valves as per manufacturer's
recommendations complete to satisfaction of Engineer in charge.
(a) 20mm nominal bore Metre 23480 169.00 3,968,120.00
(b) 25mm nominal bore Metre 350 194.00 67,900.00
NS 2.15 Providing and fixing Insulation to CPVC Pipes and valves with 50mm
thick resin bonded preformed mineral wool pipe sections of density not
less than 144 kg/cum. as per IS:9842 and applying 26g Aluminium sheet
as cladding, properly rolled and grooved with joints sealed with a strap of
roofing felt (type-III Grade-I conforming to IS:1322) complete with self
tapping screws centre to centre distance of 150mm to close cladding
joints. The pipes shall be painted with zinc chromate primer before
applying insulation (Lloyd Insulation Make).

(a) 20mm dia Metre 1745 311.00 542,695.00


(b) 25mm dia Metre 1850 353.00 653,050.00
(c) 32mm dia Metre 2030 393.00 797,790.00
(d) 40mm dia Metre 1150 430.00 494,500.00
(e) 50mm dia Metre 2130 499.00 1,062,870.00
NS 2.16 Providing and fixing 100mm dia G.I. vent pipe on Under ground and over
0
head tank inlcuding cost of 2 Nos. 90 bend and painting with enamel
paint complete with in all respect. Each 100 4,805.00 480,500.00

BOQ - PL (INT) 21
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
SOLAR WATER HEATING SYSTEM
NS 2.17 Providing and fixing solar water heating system with direct heating
complete with solar panels, insulated MS storage vessel with cemamic
lining inside & interconnecting pipes and valves complete in all respect as
per manufacturer specifications. Tank shall be supplied without electrical
boosters. (TATA BP / Solarhart Make).
(The Vendor shall include in this rate cost of all interconnecting pipes and
valves & insulations connecting the panels).
(a) Capacity 300 LPD (comprising 3 nos. collector panels and 300 ltres MS
storage vessel) Each 16 83,806.00 1,340,896.00
(b) Capacity 200 LPD (comprising 2 nos. collector panels and 200 ltres MS
storage vessel) Each 95 65,704.00 6,241,880.00
TOTAL OF INTERNAL WATER SUPPLY & SOLAR WATER HEATING
SYSTEM CARRIED OVER TO SUMMARY OF INTERNAL PLUMBING
WORKS 20,534,178.45 27,275,667.09

BOQ - PL (INT) 22
CHAPTER - 3 : SANITARY FIXTURES
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
17.1 3.1 Providing and fixing water closet squatting pan (Indian type W.C pan)
with 100 mm sand cats iron P or S trap, 10 litre low level white P.V.C
flushing cistern with manually controlled device (handle lever) confirming
to IS : 7231, with all fittings and fixtures complete including cutting and
making good the walls and floors where required.

17.1.1 (a) White Vitreous china Orissa Pattern W.C pan of size 580x440mm with
integral type foot rests. Each 798 3,392.80 2,707,454.40
17.78 3.2 Providing and fixing white vitreous china extended wall mounting water
closet of size 780x370x690 mm of approved shape including providing &
fixing white vitreous china cistern with dual flush fitting, of flushing
capacity 3 litre/6 litre (adjustable to 4 litre/8 litres), including seat cover,
and cistern fittings, nuts, bolts and gasket etc complete.
Each 1077 10,100.90 10,878,669.30
17.80 3.3 Providing and fixing white vitreous china battery based infrared sensor
operated urinal of approx. size 610 x 390 x 370 mm having pre & post
flushing with water (250 ml & 500 ml consumption), having water inlet
from back side, including fixing to wall with suitable brackets all as per
manufacturers specification and direction of Engineer-in-charge. Each 43 16,724.95 719,172.85
17.7 3.4 Providing and fixing wash basins with C.P. brass pillar tap, 32mm C.P.
brass waste of standard pattern, including painting of fittings and brackets,
cutting and making good the walls and floors where required.
17.7.1 (a) White Vitreous china Wash basin of size 630 x 450mm with a pair of
15mm C.P brass pillar taps. Each 1882 2,331.15 4,387,224.30
17.10 3.5 Providing and fixing stainless steel A ISI : 304 (18/8) kitchen sink as per
IS : 13983 with CI brackets and stainless steel plug 40mm including
painting of fittings and brackets, cutting and making good the walls where
required.
17.10.1 Kitchen sink with drain board
17.10.1.1 (a) 510 x 1040mm bowl depth 250mm Each 877 7,052.15 6,184,735.55
17.22 3.6 Providing and fixing G.I. inlet connection for flush pipe connecting with
W.C. pan. Each 1889 103.20 194,944.80

BOQ - PL (INT) 23
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
17.28 3.7 Providing and fixing P.V.C. waste pipe for sink or wash basin including
P.V.C. waste fittings complete.
17.28.2 Flexible pipe
17.28.2.1 a) 32 mm dia (for wash basin) Each 1890 74.45 140,710.50
17.28.2.2 b) 40 mm dia (for sink and urinal) Each 877 76.75 67,309.75
17.31 3.8 Providing and fixing 600x450 mm bevelled edge mirror of superior glass
(of approved quality) complete with 6 mm thick hard board ground fixed to
wooden cleats with C.P. brass screws and washers complete. Each 1887 793.95 1,498,183.65
17.34 3.9 Providing and fixing toilet paper holder.
17.34.2 (a) Vitreous China Each 643 334.55 215,115.65
17.73 3.10 Providing and fixing PTMT towel rail complete with brackets fixed to
wooden cleats with CP brass screws with concealed fittings arrangement
of approved quality and colour.
17.73.2 a) 600 mm long towel rail with total length of 645 mm, width 78 mm and
effective height of 88 mm, weighing not less than 190 gms Each 806 541.50 436,449.00
18.22 3.11 Providing and fixing CP Brass shower rose with 15 or 20 mm inlet.
18.22.1 a) 100 mm diametre Each 668 72.05 48,129.40
18.52 3.12 Providing and fixing CP Brass stop cock (concealed of standard design
and of approved make confirming to IS : 8931
18.52.1 a) 15 mm nominal bore Each 668 619.75 413,993.00
18.53 3.13 Providing and fixing C.P brass angle valve for basin mixer and geyser
points of approved quality confirming to IS:8931
18.53.1 (a) 15 mm nominal bore Each 10638 507.70 5,400,912.60
18.65 3.14 Providing and fixing PTMT soap Dish Holder having length of 138mm,
breadth 102mm, height of 75mm with concealed fitting arrangements,
weighing not less than 106 gms. Each 1320 164.95 217,734.00
NS 3.15 Providing and fixing vitreous China Sanitary fixturs and CP fitting and
other accessaries for Handicapped toilet Hindware Cat no. 70002
(Matrix Set-1). Each Matrix Set shall comprised (Wash Basin 65 x 35 with
one pair mounting brackets, EWC & Cistern complete with fittings & seat
cover, one no hinged rail 76 cm and five nos of grab rails 60 cm).
complete all respect. Each 14 72,326.00 1,012,564.00
NS 3.16 Providing and fixing C.P. brass 2 Way Bib Cock with Wall Flange ( Jaquar
Cat NO. FLR-5041N or approved equivalent) including cutting and
making good the walls wherever required. (For WC)
(a) 15mm dia Each 1889 1,748.00 3,301,972.00

BOQ - PL (INT) 24
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 3.17 Providing and fixing C.P. brass Bib Cock (Straight Line Model) With Wall
Flange (Jaquar Cat NO. FLR-5047N or approved equivalent) including
cutting and making good the walls wherever required. (For Shower &
Wash basin hot & cold water)
(a) 15mm dia Each 4104 1,243.00 5,101,272.00
NS 3.18 Providing and fixing C.P. Central Hole Basin Mixer without Popup Waste
System with 450mm Long Braided Hoses(Jaquar Cat No. CON-167KNB
or approved equivalent. (for wash basin) Each 478 2,906.00 1,389,068.00
NS 3.19 Providing and fixing CP brass sink mixer, mixing fittings (JAQUAR Cat.
No. CON-CHR-309KN or approved equivalent. Each 237 3,018.00 715,266.00
NS 3.20 Providing and fixing C.P. brass Bottle trap (Jaquar Cat. No. ALD-769B
or approved equivalent including cutting and making good the walls
wherever required. Each 582 1,541.00 897,324.30
NS 3.21 Providing & fixing CP concealed stop cock Jaquar Cat No. CON-089KN
or approved equivalent Each 529 1,077.00 569,733.00
NS 3.22 Providing & fixing CP brass shower rose with shower arm Jaguar Cat
No. OHS-1789 & 483 or approved equivalent. Each 473 3,419.00 1,617,187.00
NS 3.23 Providing & fixing CP wall mixer non telephonic type Jaguar Cat No.
CON-CHR-219KN or approved equivalent Each 473 3,234.00 1,529,682.00
NS 3.24 Providing and fixing S.S. hinged grating, 6mm thick with frame (JAYNA
TOPAZ Cat. No. TR 102 including setting in floor with cement mortar 1:3.
Each 6704 245.00 1,642,480.00
NS 3.25 Providing and fixing C.P. brass twin robe hooks, JAQUAR Cat. No. 1161
or equivalent make . Each 1461 583.00 851,763.00
NS 3.26 Providing and fixing C.P. brass soap dish (Jaquar Cat. No. CAN-1131N)
including cutting and making good the walls wherever required complete
to the satisfaction of Engineer in charge. Each 487 605.00 294,635.00
NS 3.27 Providing and fixing, Glass Bottle Liquid Soap Dispenser with push lever
assembly complete with soap refill - (JAQUAR Cat No. ACN-1135N)
Make or approved equivalent. Each 56 1,213.00 67,928.00
NS 3.28 Providing and fixing automatic high pressure electric water heaters
VENUS-Magma-Vertical 25GV2 with glass lining thermostats with each
element and high temperature cut off, necessary insulation, safety valve,
etc. all complete.
a) 15 litres Each 874 8,874.00 7,755,876.00
b) 25 litres Each 1116 10,218.00 11,403,288.00

BOQ - PL (INT) 25
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 3.29 Providing and Fixing Health Faucet JAQUAR Cat. No. 573 (ALLIED
SERIES) or equivalent make with flexible pipe and wall hook with each
European W.C. Pan. Each 1091 1,863.00 2,032,533.00
NS 3.30 Providing and fixing white vitreous china Janitor Sink HSI Cat. NO.
50001 of 53x43x18 with CI brackets, 40mm CP brass waste with CP brass
union, complete including cutting and making good the walls wherever
required. Each 16 6,072.00 97,152.00
NS 3.31 Providing and fixing white glazed vitreous china Division Plates for
urinals (H.S.I. Cat no. 61001 approved equivalent) of size 680x 300 mm.
Each 43 2,219.00 95,417.00
NS 3.32 Providing and fixing C.P. brass towel ring JAQUAR Cat No. ACN-1121N
(CONTINENTAL SERIES) or approved equivalent complete with C.P.
brass brackets fixed to rawl plug of approved design with C.P. brass
screws. Each 674 1,042.00 702,308.00
NS 3.33 Providing and fixing C.P. brass towel rail 600mm Long JAQUAR Cat. No.
1111NM or approved equivalent. Each 417 1,381.00 575,877.00
NS 3.34 Providing and fixing stainless steel Toilet Paper Holder JAQUAR Cat.
No. ACN-1151N or equivalent make fixed in position by means of C.P.
screws and rawl plugs embedded in the walls complete including cutting
and making good the walls wherever required. Each 448 1,451.00 650,048.00
TOTAL OF SANITARY FIXTURES AND FITTINGS CARRIED OVER TO
SUMMARY OF INTERNAL PLUMBING WORKS 33,510,738.75 42,303,373.30

BOQ - PL (INT) 26
CHAPTER - 4 : RAIN WATER PIPES AND FITTINGS
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
12.41 4.1 Providing and fixing on wall face unplasticised rigid pvc rain water pipes
conforming to IS 13592 type a including jointing with seal ring conforming
to IS 5382 leaving 10mm gap for thermal expansion (i) single socketed
pipes
12.41.1 a) 75mm diameter Metre 9003 145.70 1,311,737.10
12.41.2 b) 110mm diameter Metre 7190 231.65 1,665,563.50
12.42 4.2 Providing and fixing on wall face unplasticised PVC moulded fittings/
accessories for unplasticised rigid PVC rain water pipes conforming to IS
13592 type A including jointing with seal ring conforming to IS 5382 leving
10mm gap for thermal expansion
12.42.1 4.2.1 Coupler
12.42.1.1 a) 75mm Each 17 108.65 1,847.05
12.42.1.2 b) 110mm Each 217 138.30 30,011.10
12.42.4 4.2.2 Single tee without door
12.42.4.1 a) 75x75x75 mm Each 1926 195.30 376,147.80
12.42.4.2 b) 110x110x110 mm Each 217 248.55 53,935.35
12.42.5 4.2.3 Bend 87.5o
12.42.5.1 a) 75mm bend Each 32 113.25 3,624.00
12.42.5.2 b) 110mm bend Each 217 161.55 35,056.35
12.42.6 4.2.4 Shoe (plain)
12.42.6.1 a) 75mm shoe Each 32 167.85 5,371.20
12.42.6.2 b) 110mm shoe Each 217 295.10 64,036.70
12.43 4.3 Providing and fixing unplasticised PVC pipe clips of approved design to
unplasticised PVC rain water pipes by means of 50x50x50mm hard wood
plugs screws with MS screws of required length including cutting brick
work and fixing in cement mortar 1:4( 1cement 4 coarse sand ) and
making good the wall etc. complete
12.43.1 a) 75mm Each 2564 172.80 443,059.20
12.43.2 b) 110mm Each 1938 189.05 366,378.90
12.44 4.4 Providing and fixing to the inlet mouth of rain water pipe cast iron grating
15cm dia meter and weighing not less than 440 grams Each 236 41.10 9,699.60

BOQ - PL (INT) 27
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
4.1 4.5 Providing and laying in position cement concrete of specified grade
excluding the cost of centring and shuttering - All work up to plinth level.

4.1.3 (a) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm


nominal size) cum 120 5466.30 655,956.00
TOTAL OF RAIN WATER PIPES AND FITTINGS CARRIED OVER TO
-
SUMMARY OF INTERNAL PLUMBING WORKS 5,022,423.85

BOQ - PL (INT) 28
CHAPTER - 5 : SEWERAGE SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
19.1 5.1 Providing, laying and jointing glazed stoneware pipes class SP-1 with
stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine
sand) including testing of joints etc. complete:
19.1.1 (a) 100 mm diameter Metre 385 206.55 79,521.75
19.2 5.2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand :
10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes
including bed concrete as per standard design:
19.2.1 a) 100mm dia SW pipe Metre 385 592.60 228,151.00
19.4 5.3 Providing and fixing square-mouth S.W. gully trap class SP-1 complete
with C.I. grating brick masonry chamber with water tight C.I. cover with
frame of 300 x300 mm size (inside) the weight of cover to be not less than
4.50 kg and frame to be not less than 2.70 kg as per standard design :

19.4.2 150 x 100mm size P-type


19.4.2.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 301 1594.35 479,899.35
2.10 5.4 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m including getting out the excavated soil, and then returning the
soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed, within a lead of 50 m :

2.10.1 All kind of soils


2.10.1.2 a) Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.
Metre 385 208.30 80,195.50

BOQ - PL (INT) 29
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
Based on 5.5 Constructing of masonry Grease Trap with brick masonry in cement
DSR No. mortar 1:5 (1 cement: 5 fine sand) RCC top slab with 1:2:4 mix (1 cement:
(4.1.8), 2 coarse sand: 4 graded stone aggregate 20 mm nominal size),
(6.36.1), foundation concrete 1:4:8 mix (1 cement: 4 coarse sand: 8 graded stone
(13.9.1), aggregate 40 mm nominal size) including RCC Baffle walls, excavation
(5.3) & and refilling inside plastering 12 mm thick with cement mortar 1:3 (1
(5.9.3) cement: 3 coarse sand) finished with a floating coat of neat cement and
making channels in cement concrete 1:2:4 (1 cement: 2 coarse sand: 4
graded stone aggregate 20 mm nominal size) complete with Two nos. CI
light duty Manholes covers of size 600x600x600mm at top slab.

a) Size 1.5mx0.75mx0.75m deep 3 16861.00 50,583.00


TOTAL OF SEWERAGE SYSTEM CARRIED OVER TO SUMMARY OF
INTERNAL PLUMBING WORKS 918,350.60 -

BOQ - PL (INT) 30
CHAPTER - 6 : STORM WATER DRAINAGE SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
19.6 6.1 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc. complete :

19.6.2 a) 150mm dia RCC pipe Metre 360 348.30 125,388.00


19.2 6.2 Providing and laying cement concrete 1:5:10 (1 cement: 5 fine sand: 10
graded stone aggregate 40mm nominal size) all-round S.W. pipes
including bed concrete as per standard design.
19.2.2 a) 150mm dia RCC pipe Metre 360 724.70 260,892.00
19.27 6.3 Constructing brick masonry road gully chamber 50x45x60cm with bricks
in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450mm
precast RCC horizontal grating with frame complete as per standard
design.
19.27.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 308 3957.50 1,218,910.00
19.31 6.4 Extra for depth beyond 45 cm of brick masonry chamber :
19.31.1 a) For 455x610 mm size
19.31.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 1 3924.65 3,924.65
2.10 6.5 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m including getting out the excavated soil, and then returning the
soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed, within a lead of 50 m :

2.10.1 a) All kind of soils


2.10.1.2 Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.
Metre 360 208.30 74,988.00
TOTAL OF STORM WATER DRAINAGE SYSTEM CARRIED OVER TO
-
SUMMARY OF INTERNAL PLUMBING WORKS 1,684,102.65

BOQ - PL (INT) 31
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF EXTERNAL PLUMBING WORKS (figures in Rs.)


Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 DRAINAGE PIPES & FITTINGS 4,225,167.26 3,625,057.00
2 SEWERAGE SYSTEM 6,816,767.75 316,549.79
3 STORM WATER DRAINAGE SYSTEM 11,199,103.48 2,933,170.46
4 EXTERNAL DRAIN 1,828,315.70
5 EXTERNAL WATER SUPPLY SYSTEM 6,728,512.60 1,483,002.00
6 RAIN WATER HARVESTING 7,457,997.65
7 MISCELLANEOUS WORKS 74,784.00 204,503.65
8 TUBEWELL & TUBEWELL PUMPS 275,668.20 287,700.00
9 PUMPING SYSTEM 3,915,854.00
10 WATER TREATMENT SYSTEM 1,321,314.00

SUCTION AND DELIVERY PIPES AND VALVES FOR WATER


11 467,085.00 1,282,825.00
SUPPLY PUMPS
TOTAL OF EXTERNAL PLUMBING WORKS CARRIED
OVER TO GRAND SUMMARY OF COSTS 39,073,401.63 15,369,975.90

BOQ - PL(EXT) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - EXTERNAL PLUMBING WORKS
CHAPTER - 1 : DRAINAGE PIPES & FITTINGS
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.1 Providing and fixing SWR uPVC pipes (Type-B) confirming to IS 13592 :
1992 including all fittings e.g. plain or door bends, junctions, cowls,
offsets, access pieces etc. jointing with rubber rings and solvent cement
including cutting holes in walls, floors excavation, refilling and disposal of
surplus earth wherever required and making good. (For Basement 1 & 2)

a) 110 mm dia Metre 435 780.00 339,300.00


b) 160 mm dia Metre 35 1,104.00 38,640.00
NS 1.2 Providing and laying uPVC pipes confirming to IS 4985: 2000) pressure
2
10 kg/cm including all fittings e.g. plain or door bends, junctions, cowls,
offsets, access pieces etc. jointing with rubber rings and solvent cement
including cutting and making good the walls, floors, RCC work, etc.,
cutting chases and filling the same with cement concrete 1:3:6 (1 cement :
3 coarse sand : 6 graded stone aggregate 20mm nominal size) or cement
mortar 1:4 (1 cement : 4 coarse sand) as required.

a) 160 mm dia Metre 570 1,389.00 791,730.00


b) 110 mm dia Metre 1235 670.00 827,450.00
c) 75 mm dia Metre 310 355.00 110,050.00
NS 1.3 Providing and fixing CP Brass floor cleanout plug as per drawing
complete with G.I. Socket jointed to drainage pipe outlet with lead caulked
joint.
a) 100 mm dia Each 132 1,481.00 195,492.00
NS 1.4 Providing and fixing S.S. hinged grating, 6mm thick with frame (JAYNA
TOPAZ Cat. No. TR 102 including setting in floor with cement mortar 1:3.
(For Basement 1 & 2) Each 71 245.00 17,395.00
4.1 1.5 Providing and laying in position cement concrete of specified grade
excluding the cost of centring and shuttering - All work up to plinth level.
(For Basement 1 & 2)
4.1.3 (a) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size) cum 4 5,466.30 22,849.13

BOQ - PL (EXT) 1
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
17.35 1.6 Providing and fixing soil waste and vent pipes
17.35.1.2 (a) 100mm diameter centrifugally cast (spun) iron S&S pipe as per IS:3989.
Metre 1350 917.75 1,238,962.50
17.37/12.3 1.7 Providing and fixing M.S. holder-bat clamps of approved design to sand
8 cast iron centrifugally cast (spun) iron S&S pipes embedded in and
including cement concrete blocks 10x 10 x 10 cm of 1:2:4 mix (1 cement :
2 coarse sand : 4 graded stone aggregate 20mm nominal size) including
cost of cutting holes and making good the walls, etc.

17.37.1 (a) For 100mm diametre Each 743 152.90 113,604.70


17.39 1.8 Providing and fixing plain bend of required degree:
17.39.1.2 (a) 100mm centrifugally cast (spun) iron S&S as per IS:3989. Each 286 335.75 96,024.50
17.42 1.9 Providing and fixing double equal plain junction of required degree.
17.42.1.2 (a) 100x100x100x100 mm Sand cast iron S&S as per IS - 3989 Each 26 748.10 19,450.60
17.44 1.10 Providing and fixing single equal plain junction of required degree :
17.44.1.2 (a) 100x100x100 mm Sand cast iron S&S as per IS - 3989 Each 146 576.20 84,125.20
12.39/17.5 1.11 Providing lead caulked joints to sand cast iron/centrifugally cast (spun)
8 iron pipes and fittings of diameter
17.58.1 (a) 100mm Each 2321 243.75 565,743.75
17.65 1.12 100mm
17.65.1 (a) 100mm diametre pipe Metre 1350 38.65 52,177.50
18.66 1.13 Providing and laying S&S CI standard specials such as tees bends
collars tapers and caps etc suitable for flanged jointing as per IS : 1538.

18.66.1 (a) Upto 300mm dia quintal 93 6,596.55 610,180.88


18.72 1.14 Providing & fixing S&S Centrifugally Cast (Spun) / Ductile Iron Pipes
conforming to IS : 8329 :
18.72.15 (a) 100 mm Ductile iron Class K-9 pipes Metre 1190 1,130.55 1,345,354.50

BOQ - PL (EXT) 2
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
18.70 1.15 Providing push-on-joints to Centrifugally (Spun) Cast Iron Pipes or
Ductile Iron Pipes including testing of joints and the cost of rubber gasket
:
18.70.1 (a) 100 mm dia pipes joint 1240 61.85 76,694.00
NS 1.16 Making connection of 100mm CI pipes with DI double flanged water
supply main header (IS:8329, Class-K9) at basement ceiling/ground by
provision of CI flange piece & CI reducer in workmanship like manner
including testing of joints complete in all respects as per drawings. Each 290 4,500.00 1,305,000.00
TOTAL OF DRAINAGE PIPES & FITTINGS (BASEMENT 1 & 2)
CARRIED OVER TO SUMMARY OF EXTERNAL PLUMBING WORKS
4,225,167.26 3,625,057.00

BOQ - PL (EXT) 3
CHAPTER - 2 : SEWERAGE SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.1 2.1 Providing, laying and jointing glazed stoneware pipes class SP-1 with
stiff mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine
sand) including testing of joints etc. complete:
19.1.1 a) 100 mm diameter Metre 15 206.55 3,098.25
19.1.2 b) 150 mm diameter Metre 1060 314.35 333,211.00
19.2 2.2 Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand :
10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes
including bed concrete as per standard design:
19.2.1 a) 100mm dia SW pipe Metre 15 592.60 8,889.00
19.2.2 b) 150mm dia SW pipe Metre 1060 724.70 768,182.00
19.6 2.3 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc. complete :
19.6.2 a) 150mm dia RCC pipe Metre 25 348.30 8,707.50
19.6.3 b) 250mm dia RCC pipe Metre 1155 468.60 541,233.00
19.6.4 c) 300mm dia RCC pipe Metre 225 506.35 113,928.75
19.2 2.4 Providing and laying cement concrete 1:5:10 (1 cement: 5 fine sand: 10
graded stone aggregate 40mm nominal size) all-round RCC pipes
including bed concrete as per standard design.
19.2.2 a) 150mm dia RCC pipe Metre 25 724.70 18,117.50
19.2.4 b) 250mm dia RCC pipe Metre 1155 977.00 1,128,435.00
NS c) 300mm dia RCC pipe Metre 225 1,406.89 316,549.79

BOQ PL (EXT) 4
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.30 2.5 Constructing brick masonry chamber for underground C.I. inspection
chamber and bends with bricks in cement mortar 1:4 (1 cement : 4 coarse
sand) C.I. cover with frame (light duty) 455x610 mm internal dimensions,
total weight of cover with frame to be not less than 38 kg (weight of cover
23 kg and weight of frame 15 kg), R.C.C. top slab with 1:2:4 mix (1
cement: 2 coarse sand : 4 graded stone aggregate 20 mm nominal size),
foundation concrete 1:5:10 (1 cement : 5 fine sand : 10 graded stone
aggregate 40 mm nominal size), inside plastering 12 mm thick with
cement mortar 1:3 (1 cement : 3 coarse sand), finished smooth with a
floating coat of neat cement on walls and bed concrete etc. complete as
per standard design:
19.30.1 Inside dimensions 455x610 mm and 45 cm deep for single pipe line :
19.30.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 2 4,692.05 9,384.10
19.31 2.6 Extra for depth beyond 45 cm of brick masonry chamber :
19.31.1 For 455x610 mm size
19.31.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 25 3,924.65 98,116.25
19.7 2.7 Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4
coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse
sand : 4 graded stone aggregate 20 mm nominal size), foundation
concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate
40mm nominal size), inside plastering 12mm thick with cement mortar 1:3
(1 cement : 3 coarse sand) finished with floating coat of neat cement and
making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4
graded stone aggregate 20mm nominal size) finished with a floating coat
of neat cement complete as per standard design :

19.7.1 Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light
duty) 455x610 mm internal dimensions, total weight of cover and frame to
be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg):

19.7.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 119 8,507.00 1,012,333.00

BOQ PL (EXT) 5
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.8 2.8 Extra for depth for manholes:
19.8.1 Size 90 x 80 cm
19.8.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 18 5,638.20 101,487.60
19.9 2.9 Constructing brick masonry circular type manhole 0.91 m internal dia at
bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse
sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1
cement : 3 coarse sand) finished with a floating coat of neat cement,
foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone
aggregate 40 mm nominal size), and making necessary channel in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) finished with a floating coat of neat
cement, all complete as per standard design :
19.9.1 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade
designation) 560 mm internal diameter conforming to I.S. 12592, total
weight of cover and frame to be not less than 182 kg., fixed in cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20
mm nominal size) including centering, shuttering all complete.
19.9.1.1 a) (Excavation,
With commonfoot rests
burnt and
clay 12mm(non
F.P.S. thickmodular)
cement plaster at class
bricks of the external
designation
7.5 Each 20 8,738.55 174,771.00
19.10 2.10 Extra depth for circular type manhole 0.91m internal dia (at bottom)
19.10.1 a) beyond 0.91 mburnt
With common to 1.67 m F.P.S. (non modular) bricks of class designation
clay
7.5 Metre 12 4,842.40 58,108.80
19.11 2.11 Constructing brick masonry circular manhole 1.22m internal dia at bottom
and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand)
inside cement plaster 12mm thick with cement mortar 1:3 (1 cement :3
coarse sand) finished with a floating coat of neat cement foundation
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate
40mm nominal size) and making necessary channel in cement concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size) finished with a floating coat of neat cement, all complete as
per standard design :

BOQ PL (EXT) 6
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.11.1 1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade
designation) 560mm internal diameter conforming to I.S. 12592, total
weight of cover and frame to be not less than 182kg. fixed in cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate
20mm nominal size) including centering, shuttering all complete.
(Excavation, foot rests and 12 mm thick cement plaster at the external
surface shall be paid for separately) :
19.11.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 14 16,467.90 230,550.60
19.12 2.12 Extra depth for circular type manhole 1.22m internal dia (at bottom)
beyond 1.68 m to 2.29 m :
19.12.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 7 6,270.70 43,894.90
19.13 2.13 Constructing brick masonry circular manhole 1.52 m internal dia at
bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse
sand) inside cement plaster 12mm thick with cement mortar 1:3 (1 cement
: 3 coarse sand) finished with a floating coat of neat cement, foundation
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate
40mm nominal size) and making necessary channel in cement concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size) finished with a floating coat of neat cement, all complete as
per standard design :
19.13.1 2.30m deep with SFRC Cover and frame (heavy duty HD-20 grade
designation) 560mm internal diameter conforming to I.S. 12592, total
weight of cover and frame to be not less than 182 kg. fixed in cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate
20mm nominal size) including centering, shuttering all complete.
(Excavation, foot rests and 12 mm thick cement plaster at the external
surface shall be paid for separately) :
19.13.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 21 34,976.25 734,501.25
19.14 2.14 Extra depth for circular type manhole 1.52 m internal dia (at bottom)
beyond 2.30 m :
19.14.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 31 14,842.95 460,131.45

BOQ PL (EXT) 7
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.16 2.15 Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS :
1786 having minimum cross section as 23 mmx25mm and over all
minimum length 263 mm and width as 165mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by
ribbing or chequering besides necessary and adequate anchoring
projections on tail length on 138 mm as per standard drawing and suitable
to with stand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification mark to
be visible even after fixing, including fixing in manholes with 30x20x15 cm
cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Each 497 311.60 154,865.20
2.6 2.16 Earth work in excavation by mechanical means (hydraullic excavator) /
manual means over areas (exceeding 30cm in depth. 1.5m in width as
well as 10 sqm on plan) including disposal of excavated earth lead upto
50m and lift upto 1.5m, disposal earth to be levelled and neatly dressed.

2.6.1 a) All kinds of soil Cum 788 155.60 122,612.80


2.25 2.17 Filling available excavated earth (excluding rock) in treanches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead up to
50m and lift upt 1.5m. Cum 117 112.40 13,150.80
2.10 2.18 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m including getting out the excavated soil, and then returning the
soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed, within a lead of 50 m :

2.10.1 All kind of soils


2.10.1.2 a) Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.
Metre 2455 208.30 511,376.50

BOQ PL (EXT) 8
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Based on 2.19 Providing and fixing MS grating consisting of MS frame made of angle
DSR No. size 25mm x 25mm x 4mm thick to be fixed on brick / concrete with 2 nos
10.2, 4.1.3 hold fasts of size 100mm x 25mm x 4mm thick to be embeded with
& 13.61 cement concrete block of size 150mm x 100mm x 100mm of mix 1:2:4 ( 1
cement : 2 coarse sand : 4 graded stone aggregate 20mm nominal size)
on each face of wall. The removable cover shall be made out of MS
angle size 25mm x 25mm x 4mm thick having vertically welded transverse
members made out of MS flats of size 25mm x 5mm thick at a spacing of
25mm centre to centre including painting with two coats of synthetic
enamel paint over a coat of primer complete as per direction of engineer -
in - charge. ( Only weight of Angle, Flats & hold fast will be measured for
payment & nothing extra will be paid.) (For Basement 1 & 2)

a) Size 600mm x 350 mm Kg 2083 80.50 167,681.50


TOTAL OF SEWERAGE SYSTEM CARRIED OVER TO SUMMARY OF
EXTERNAL PLUMBING WORKS 6,816,767.75 316,549.79

BOQ PL (EXT) 9
CHAPTER - 3 : STORM WATER DRAINAGE SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.6 3.1 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes
with collars jointed with stiff mixture of cement mortar in the proportion of
1:2 (1 cement : 2 fine sand) including testing of joints etc. complete :

19.6.2 a) 150mm dia RCC pipe Metre 3555 348.30 1,238,206.50


19.6.3 b) 250mm dia RCC pipe Metre 785 468.60 367,851.00
19.6.4 c) 300mm dia RCC pipe Metre 425 506.35 215,198.75
19.6.5 d) 450mm dia RCC pipe Metre 520 705.90 367,068.00
19.6.6 e) 500mm dia RCC pipe Metre 135 934.10 126,103.50
19.6.7 f) 600mm dia RCC pipe Metre 20 1,379.45 27,589.00
19.2 3.2 Providing and laying cement concrete 1:5:10 (1 cement: 5 fine sand: 10
graded stone aggregate 40mm nominal size) all-round S.W. pipes
including bed concrete as per standard design.
19.2.2 a) 150mm dia RCC pipe Metre 3555 724.70 2,576,308.50
19.2.4 b) 250mm dia RCC pipe Metre 785 977.00 766,945.00
NS c) 300mm dia RCC pipe Metre 425 1,406.89 597,927.38
NS d) 450mm dia RCC pipe Metre 520 3,164.45 1,645,515.58
NS e) 500mm dia RCC pipe Metre 135 3,908.80 527,687.47
NS f) 600mm dia RCC pipe Metre 20 8,102.00 162,040.02
19.27 3.3 Constructing brick masonry road gully chamber 50x45x60cm with bricks
in cement mortar 1:4 (1 cement : 4 coarse sand) including 500x450mm
precast RCC horizontal grating with frame complete as per standard
design.
19.27.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 335 3,957.50 1,325,762.50
19.31 3.4 Extra for depth beyond 45 cm of brick masonry chamber :
19.31.1 a) For 455x610 mm size
19.31.1.1 With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 34 3,924.65 131,475.78

BOQ - PL (EXT) 10
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.9 3.5 Constructing brick masonry circular type manhole 0.91 m internal dia at
bottom and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse
sand), in side cement plaster 12 mm thick with cement mortar 1:3 (1
cement : 3 coarse sand) finished with a floating coat of neat cement,
foundation concrete 1:3:6 mix (1 cement : 3 coarse sand : 6 graded stone
aggregate 40 mm nominal size), and making necessary channel in
cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size) finished with a floating coat of neat
cement, all complete as per standard design :
19.9.1 0.91 m deep with S.F.R.C. cover and frame (heavy duty, HD-20 grade
designation) 560 mm internal diameter conforming to I.S. 12592, total
weight of cover and frame to be not less than 182 kg., fixed in cement
concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size) including centering, shuttering all complete. (Excavation,
foot rests and
12mm thick cement plaster at the external surface shall be paid for
separately):
19.9.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 31 8,738.55 270,895.05
19.10 3.6 Extra depth for circular type manhole 0.91m internal dia (at bottom)
beyond 0.91 m to 1.67 m
19.10.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 7 4,842.40 31,475.60
19.11 3.7 Constructing brick masonry circular manhole 1.22m internal dia at bottom
and 0.56m dia at top in cement mortar 1:4 (1 cement :4 coarse sand)
inside cement plaster 12mm thick with cement mortar 1:3 (1 cement :3
coarse sand) finished with a floating coat of neat cement foundation
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate
40mm nominal size) and making necessary channel in cement concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size) finished with a floating coat of neat cement, all complete as
per standard design :

BOQ - PL (EXT) 11
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.11.1 1.68 m deep with SFRC Cover and frame (heavy duty HD-20 grade
designation) 560mm internal diameter conforming to I.S. 12592, total
weight of cover and frame to be not less than 182kg. fixed in cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate
20mm nominal size) including centering, shuttering all complete.
(Excavation, foot rests and 12 mm thick cement plaster at the external
surface shall be paid for separately) :
19.11.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 16 16,467.90 263,486.40
19.12 3.8 Extra depth for circular type manhole 1.22m internal dia (at bottom)
beyond 1.68 m to 2.29 m :
19.12.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 15 6,270.70 94,060.50
19.13 3.9 Constructing brick masonry circular manhole 1.52 m internal dia at
bottom and 0.56 m dia at top in cement mortar 1:4 (1 cement : 4 coarse
sand) inside cement plaster 12mm thick with cement mortar 1:3 (1 cement
: 3 coarse sand) finished with a floating coat of neat cement, foundation
concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate
40mm nominal size) and making necessary channel in cement concrete
1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size) finished with a floating coat of neat cement, all complete as
per standard design :
19.13.1 2.30m deep with SFRC Cover and frame (heavy duty HD-20 grade
designation) 560mm internal diameter conforming to I.S. 12592, total
weight of cover and frame to be not less than 182 kg. fixed in cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate
20mm nominal size) including centering, shuttering all complete.
(Excavation, foot rests and 12 mm thick cement plaster at the external
surface shall be paid for separately) :
19.13.1.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Each 33 34,976.25 1,154,216.25
19.14 3.10 Extra depth for circular type manhole 1.52 m internal dia (at bottom)
beyond 2.30 m :
19.14.1 a) With common burnt clay F.P.S. (non modular) bricks of class designation
7.5 Metre 49 14,842.95 727,304.55

BOQ - PL (EXT) 12
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
19.16 3.11 Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS :
1786 having minimum cross section as 23 mmx25mm and over all
minimum length 263 mm and width as 165mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by
ribbing or chequering besides necessary and adequate anchoring
projections on tail length on 138 mm as per standard drawing and suitable
to with stand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification mark to
be visible even after fixing, including fixing in manholes with 30x20x15 cm
cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Each 542 311.60 168,887.20
2.6 3.12 Earth work in excavation by mechanical means (hydraullic excavator) /
manual means over areas (exceeding 30cm in depth. 1.5m in width as
well as 10 sqm on plan) including disposal of excavated earth lead upto
50m and lift upto 1.5m, disposal earth to be levelled and neatly dressed.

2.6.1 a) All kinds of soil Cum 828 155.60 128,836.80


2.25 3.13 Filling available excavated earth (excluding rock) in treanches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead up to
50m and lift upt 1.5m. Cum 119 112.40 13,375.60
2.10 3.14 Excavating trenches of required width for pipes, cables, etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5 m including getting out the excavated soil, and then returning the
soil as required, in layers not exceeding 20 cm in depth, including
consolidating each deposited layer by ramming, watering, etc. and
disposing of surplus excavated soil as directed, within a lead of 50 m :

2.10.1 All kind of soils


2.10.1.2 a) Pipes, cables etc. exceeding 80 mm dia. but not exceeding 300 mm dia.
Metre 4750 208.30 989,425.00
2.10.1.3 b) Pipes, cables etc. exceeding 300 mm dia. but not exceeding 600 mm dia.
Metre 660 325.20 214,632.00
TOTAL OF STORM WATER DRAINAGE SYSTEM CARRIED OVER TO
SUMMARY OF EXTERNAL PLUMBING WORKS 11,199,103.48 2,933,170.46

BOQ - PL (EXT) 13
CHAPTER - 4 : EXTERNAL DRAIN
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.6 4.1 Earth work In excavation by mechanical means (Hydraulic
excavator)/manual means over areas (exceeding 30cm in depth. 1.5m in
width as well as 10 Sqm on plan) including disposal of excavated earth,
lead up to 50m and lift up to 1.5m, disposed earth to be levelled and
neatly dressed.
2.6.1 a) All kinds of soil Cum 336 155.60 52,281.60
2.25 4.2 Filling available excavated earth (excluding rock) in treanches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth,
consolidating each deposited layer by ramming and watering, lead up to
50m and lift upt 1.5m. Cum 37 112.40 4,158.80
4.1 4.3 Providing and laying position cement concrete of specified grade
excluding the cost of centering and shuttering-All work up to plinth level:

4.1.8 a) 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40mm


nominal size). Cum. 94 4,301.15 404,308.10
11.3 4.4 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate) finished with a floating coat of neat cement including
cement slurry, but excluding the cost of nosing of steps, etc., complete.

11.3.1 a) 40mm thick with 20mm nominal size stone aggregate Sqm. 233 353.35 82,330.55
4.4 4.5 Providing and laying cement concrete in kerbs, steps and the like at or
near ground level excluding the cost of centering shuttering and finishing.

4.4.1 a) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm


nominal size). Cum. 35 5,466.30 191,320.50
6.1 4.6 Brick work with common burnt clay F.B.S (non modular) bricks of class
designation 75 in foundation and plinth in:
6.1.1 a) Cement mortar 1:4 (1 cement : 4 fine sand). Cum. 68 4,918.65 334,468.20

BOQ - PL (EXT) 14
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
13.4 4.7 Cement plaster (in coarse sand) 12mm cement plaster of mix:
13.4.1 a) 1:4 (1 cement : 4 coarse sand) Sqm. 490 172.30 84,427.00
5.1 4.8 Providing and laying in position specified grade of reinforced cement
concrete, excluding the cost of centering, shuttering, finishing and
reinforcement-All work upt to plinth level.
a) 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
5.1.3
nominal size) Cum. 33 5,725.90 188,954.70
5.22 4.9 Reinforcement for RCC work including straightening, cutting, bending,
placing in position and binding all complete.
5.22.6 a) Thermo-Mechanically Treated bars Kg. 6200 68.10 422,220.00
5.9 Centring and shuttering including strutting, propping etc. and removal of
4.10
form for :
5.9.1 a) Foundations, footings, bases of columns etc. for mass concrete. Sq.m 325 196.45 63,846.25
TOTAL OF EXTERNAL DRAIN CARRIED OVER TO SUMMARY OF
-
EXTERNAL PLUMBING WORKS 1,828,315.70

BOQ - PL (EXT) 15
CHAPTER - 5 : EXTERNAL WATER SUPPLY SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
18.9 5.1 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having
thermal stability for hot & cold water supply including all CPVC plain &
brass threaded fittings This includes jointing of pipes & fittings with one
step CPVC solvent cement ,trenching ,refilling & testing of joints complete
as per direction of Engineer in Charge.
External Work
18.9.3 a) 25mm nominal outer dia pipes Metre 260 209.50 54,470.00
18.9.4 b) 32mm nominal outer dia pipes Metre 170 262.35 44,599.50
18.9.5 c) 40mm nominal outer dia pipes Metre 450 350.50 157,725.00
18.9.6 d) 50mm nominal outer dia pipes Metre 865 524.10 453,346.50
18.9.7 e) 62.5mm nominal outer dia pipes Metre 65 1,462.35 95,052.75
18.9.8 f) 75 mm nominal inner dia Pipes Metre 10 2,051.25 20,512.50
18.32 5.2 Constructing masonry Chamber 30x30x50 cm inside, in brick work in
cement mortar 1:4 (1 cement :4 coarse sand) for stop cock, with C. I.
surface box 100x100 x75 mm (inside) with hinged cover fixed in cement
concrete slab 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone
aggregate 20 mm nominal size), i/c necessary excavation, foundation
concrete 1:5:10 ( 1 cement : 5 fine sand : 10 graded stone aggregate
40mm nominal size ) and inside plastering with cement mortar 1:3 (1
cement : 3 coarse sand) 12mm thick, finished with a floating coat of neat
cement complete as per standard design :

18.32.1 a) With common burnt clay F.P.S (non modular) bricks of class designation
7.5 Each 72 1,157.75 83,358.00

BOQ - PL (EXT) 16
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
18.33 5.3 Constructing masonry Chamber 60x60x75 cm inside, in brick work in
cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I.
surface box 100mm top diameter, 160 mm bottom diameter and 180 mm
deep ( inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2
coarse sand : 4 graded stone aggregate 20mm nominal size ) , i/c
necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand
: 10 graded stone aggregate 40 mm nominal size) and inside plastering
18.33.1 a) with
With cement
common mortar
burnt1:3 (1 F.P.S
clay cement : 3 coarse
(non sand)
modular) 12 of
bricks mmclass
thick,designation
finished
7.5 Each 29 6,754.30 195,874.70
18.34 5.4 Constructing masonry Chamber 90x90x100 cm inside, in brick work in
cement mortar 1:4 (1 cement : 4 coarse sand) for sluice valve, with C.I.
surface box 100 mm top diameter, 160 mm bottom diameter and 180 mm
deep (inside) with chained lid and RCC top slab 1:2:4 mix (1 cement : 2
coarse sand : 4 graded stone aggregate 20 mm nominal size ), i/c
necessary excavation, foundation concrete 1:5:10 (1 cement : 5 fine sand
: 10 graded stone aggregate 40 mm nominal size ) and inside plastering
with cement mortar 1:3 (1 cement : 3 coarse sand) 12 mm thick, finished
with a floating coat of neat cement complete as per standard design :

18.34.1 a) With common burnt clay F.P.S (non modular) bricks of class designation
7.5 Each 22 11,672.35 256,791.70
18.59 5.5 Providing and fixing C.I. double acting air valve of approved quality with
bolts, nuts, rubber, insertions etc. complete (The tail pieces, tapers etc if
required will be paid separately).
18.59.1 (a) 50mm dia Each 22 4,778.30 105,122.60
18.66 5.6 Providing and laying S&S CI standard specials such as tees bends
collars tapers and caps etc suitable for flanged jointing as per IS : 1538.

18.66.1 (a) Upto 300mm dia quintal 23 6,596.55 151,720.65


18.72 5.7 Providing & fixing S&S Centrifugally Cast (Spun) / Ductile Iron Pipes
conforming to IS : 8329 :
18.72.15 (a) 100 mm Ductile iron Class K-9 pipes Metre 525 1,130.55 593,538.75
18.72.16 (b) 150 mm Ductile iron Class K-9 pipes Metre 2950 1,434.40 4,231,480.00

BOQ - PL (EXT) 17
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
18.70 5.8 Providing push-on-joints to Centrifugally (Spun) Cast Iron Pipes or
Ductile Iron Pipes including testing of joints and the cost of rubber gasket
:
18.70.1 (a) 100 mm dia pipes joint 280 61.85 17,318.00
18.70.2 (b) 150 mm dia pipes joint 685 96.15 65,862.75
5.9 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber
16.7.1
Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation
ELECT.
as specified
DSR 2014
16.7.1.5 (a) 80 mm dia Each 11 3,638.00 40,018.00
16.7.1.4 (b) 100 mm dia Each 6 5,205.00 31,230.00
16.7.1.2 c) 150 mm dia Each 16 6,499.00 103,984.00
19.19 5.10 Providing and fixing in position pre-cast R.C.C. manhole cover and frame
of required shape and approved quality 19.19.1 L D- 2.5
19.19.4 EHD - 35
19.19.4.1 (a) Circular shape 560 mm internal dia (For under ground tank) Each 16 1,656.70 26,507.20
5.11 Providing and fixing lever operated gun metal ball valve with SS ball.
NS a) 25mm nominal bore Each 48 865.00 41,520.00
NS b) 32mm nominal bore Each 7 1,409.00 9,863.00
NS c) 40mm nominal bore Each 17 1,960.00 33,320.00
NS d) 50mm nominal bore Each 15 2,840.00 42,600.00
NS e) 65mm nominal bore Each 3 5,908.00 17,724.00

BOQ - PL (EXT) 18
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.12 Providing, Laying, Jointing and Testing of HDPE Pipes complete with
fittings & saddles where required. (The cost shall including provision
of markers plates at a regular distance of 30m centre to centre).

The work shall be done as per specifications and in general shall include:

a) Providing HDPE pipes (of PE 80 grade as per IS 4984-1995 ). The


pipes shall have a working pressure of PN 10.
b) Providing fabricated and moulded fittings of same or higher grade and
upto 63 mm OD shall be rated PN 16 and 75 mm OD and above shall be
rated for PN 10.
Providing, laying and fixing HDPE compression type fittings (as required,
adaptor fittings, saddles, etc. including jointing, testing etc. all complete.
The compression fittings upto 63 mm OD shall be rated PN 16 and 75 mm
OD and above shall be rated for PN 10.
c) Excavation of trenches and refilling including thrust blocks
d) Laying in position in excavated trenches.
e) Jointing by heat fusion technique.
f) Encasing the laid pipe with river sand of grading zone V or coarser, 150
mm all around.
NS a) 75mm OD- 6.0 kg/cm Metre 1480 704.00 1,041,920.00
NS b) 63mm OD- 6.0 kg/cm Metre 35 463.00 16,205.00
NS c) 50mm OD- 6.0 kg/cm Metre 140 299.00 41,860.00
NS d) 40mm OD- 6.0 kg/cm Metre 315 196.00 61,740.00
NS d) 32mm OD- 10.0 kg/cm Metre 160 190.00 30,400.00
NS d) 25mm OD- 10.0 kg/cm Metre 50 117.00 5,850.00
NS 5.13
Making connection of 40mm & 50mm CPVC pipes with DI double flanged
water supply main header (IS:8329, Class-K9) at basement ceiling/ground
by provision of CPVC flange piece & CPVC reducer in workmanship like
manner including testing of joints complete in all respects as per drawings. Each 40 3,500.00 140,000.00
TOTAL OF EXTERNAL WATER SUPPLY SYSTEM CARRIED OVER TO
SUMMARY OF EXTERNAL PLUMBING WORKS 6,728,512.60 1,483,002.00

BOQ - PL (EXT) 19
CHAPTER - 6 : RAIN WATER HARVESTING
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
6.1 EARTH WORK
2.6 6.1.1 Earth work in excavation by mechanical means (Hydraulic excavator) /
manual means over areas (exceeding 30cm in depth, 1.5m in width as
well as 10 sq.m on plan) including disposal of excavated earth, lead upto
50m and lift up to 1.5m, disposed earth to be levelled and neatly dressed.

2.6.1 a) All kinds of soil Cum 520 155.60 80,912.00


2.10 6.1.2 Excavating trenches of required width for pipes, cables etc including
excavation for sockets, and dressing of sides, ramming of bottoms, depth
upto 1.5m including getting out the excavated soil, and then returning the
soil as required in layers not exceeding 20 cm in depth including
consolidating each deposited layer by ramming, watering etc. and
disposing of surplus excavated soil as directed, within a lead of 50m.

2.10.1.2 a) Pipes, cables etc, exceeding 80mm dia but not exceeding 300mm dia
Metre 75 208.30 15,622.50
2.10.1.3 b) Pipes, cables etc, exceeding 300mm dia but not exceeding 600mm dia
Metre 75 325.20 24,390.00
2.26 6.1.3 Extra for every additional lift of 1.5 m or part thereof in excavation /
banking excavated or stacked materials.
2.26.1 a) All kinds of soil Cum 520 46.25 24,050.00
2.27 6.1.4 Supplying and filling in plinth with jamuna sand under floors including,
watering, ramming consolidating and dressing complete. Cum 25 910.25 22,756.25
TOTAL OF EARTH WORKS 167,730.75 -
6.2 CONCRETE & RCC WORK
4.1 6.2.1 Providing & laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - All work up to plinth level.

4.1.6 a) 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 40 mm


nominal size). Cum 22 4,672.50 102,795.00

BOQ - PL (EXT) 20
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.3 6.2.2 Reinforced cement concrete work in beams, suspended floors, roofs
0
having slop upto 15 landings, balconies, shelves, chajjas, lintels, bands,
plain window sills, staircases and spiral staire cases upto floor five level
excluding the cost of centring, shuttering, finishing and reinforcement with
1:2 :4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size). Cum 137 6,778.20 928,613.40
5.22 6.2.3 Steel reinforcement for RCC work including straightening, cutting,
bending, placing in position and binding all complete upto plinth level.
5.22.6 a) Thermo-Mechanically Treated bars kg 15070 68.10 1,026,267.00
5.9 6.2.4 Centring and shuttering including strutting, propping etc. and removal of
form for:
5.9.2 a) Walls (any thickness) including attached pilasters, butteresses, plinth and
string courses etc. Sqm 2000 360.80 721,600.00
5.9.3 b) Suspended floors, roofs, landings, balconies and access platform. Sqm 200 401.65 80,330.00
TOTAL OF CONCRETE & RCC WORK 2,859,605.40 -
6.3 BRICK WORKS
6.1 6.3.1 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundation and plinth in:
6.1.2 a) Cement mortar 1:6 (1 cement : 6 coarse sand) Cum 235 4,677.25 1,099,153.75
TOTAL OF BRICK WORKS 1,099,153.75 -
6.4 FINISHING (PLASTER WORK)
13.9 6.4.1 Cement plaster 1:3 (1 cement: 3 coarse sand) finished with a floating coat
of neat cement.
13.9.1 a) 12 mm cement plaster Sqm 1115 226.10 252,101.50
TOTAL OF PLASTER WORKS 252,101.50 -

BOQ - PL (EXT) 21
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
6.5 MISCELLANEOUS WORKS FOR RAIN WATER HARVESTING
19.16 6.5.1 Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS :
1786 having minimum cross section as 23 mmx25mm and over all
minimum length 263 mm and width as 165mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by
ribbing or chequering besides necessary and adequate anchoring
projections on tail length on 138 mm as per standard drawing and suitable
to with stand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification mark to
be visible even after fixing, including fixing in manholes with 30x20x15 cm
cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Each 270 311.60 84,132.00
19.19 6.5.2 Providing and fixing in position pre-cast R.C.C. manhole cover and frame
of required shape and approved quality.
19.19.3 H D -20
19.19.3.1 a) Circular shape 560 mm internal diameter Each 20 1,511.55 30,231.00
19.6 6.5.3 Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1
cement : 2 fine sand) including testing of joints etc. complete :

19.6.4 (a) 300mm dia RCC pipe Metre 150 506.35 75,952.50
19.3 6.5.4 Providing and laying cement concrete 1:5:10 (1 cement : 5 fine sand: 10
graded stone aggregate 40mm nominal size) upto haunches for S.W.
pipes including bed concrete as per standard design.
19.3.5 (a) 300mm dia RCC pipe Metre 150 720.70 108,105.00
24.5 6.5.5 Supplying, filling, spreading & leveling stone boulders of size range 5 cm
to 20 cm, in recharge pit, in the required thickness, for all leads & lifts, all
complete as per direction of Engineer-in-charge. Cum 25 504.15 12,603.75
24.6 6.5.6 Supplying, filling, spreading & leveling gravels of size range 5 mm to 10
mm, in the recharge pit, over the existing layer of boulders, in required
thickness, for all leads & lifts, all complete as per direction of Engineer- in-
charge. Cum 1470 910.65 1,338,655.50

BOQ - PL (EXT) 22
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
24.1 6.5.7 Boring/drilling bore well of required dia for casing/ strainer pipe, by
suitable method prescribed in IS:2800 (part I), including collecting
samples from different strata, preparing and submitting strata chart/bore
log, including hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per direction of Engineer-
in-charge, upto 90 metre depth below ground level.

24.1.1 a) All types of soil


24.1.1.1 300 mm dia Metre 800 407.10 325,680.00
24.10 6.5.8 Supplying, assembling, lowering and fixing in vertical position in bore well,
ERW (Electric Resistance Welded) FE 410 mild steel screwed and
socketed/ plain ended casing pipes of required dia, conforming to IS:
4270, of reputed & approved make, including painted with outside surface
with two coats of anticorrosive paint of approved brand and manufacture,
including required hire & labour charges, fittings & accessories, all
complete, for all depths, as per direction of Engineer-in-charge.

24.10.2 a) 150 mm nominal size dia having minimum wall thickness 5.00 mm Metre 400 1,335.40 534,160.00
24.11 6.5.9 Supplying, assembling, lowering and fixing in vertical position in bore well,
ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of
size 1.6/3.2mm) mild steel threaded and socketed / plain level ended pipe
(type A) of required dia, conforming to IS: 8110, of reputed and approved
make, having wall thickness not less than 5.40 mm, including painted with
outside surface with two coats of anticorrosive bitumestic paint of
approved brand and manufacture, including hire & labour charges, fittings
& accessories, all complete, for all depths, as per direction of Engineer-in-
charge.
24.11.2 a) 150 mm nominal size dia . Metre 400 1,418.65 567,460.00
24.15 6.5.10 Providing and fixing bail plug/Bottom plug of required dia to the bottom of
pipe assembly of tubewell as per IS:2800 (Part-I).
24.15.2 a) 150 mm dia Each 10 242.65 2,426.50
TOTAL OF MISCELLANEOUS WORKS FOR RAIN WATER
HARVESTING 3,079,406.25 -
TOTAL OF RWH CHAMBER (10 NOS.) CARRIED OVER TO SUMMARY
OF EXTERNAL PLUMBING WORKS 7,457,997.65 -

BOQ - PL (EXT) 23
CHAPTER - 7 : MISCELLANEOUS WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 7.1 Providing and fixing 600mm long puddle flanges fabricated out of 6mm
thick M.S. plates along with flanges of suitable size properly fixed in walls
and top slabs of underground tanks.
a) 25mm dia Each 20 248.70 4,973.90
b) 32mm dia Each 12 293.53 3,522.36
c) 40mm dia Each 12 349.63 4,195.56
d) 50mm dia Each 20 434.31 8,686.10
e) 65mm dia Each 10 576.96 5,769.56
f) 80mm dia Each 22 710.87 15,639.22
g) 100mm dia Each 20 1,305.08 26,101.53
h) 150mm dia Each 8 3,114.33 24,914.66
i) 200mm dia Each 8 4,227.59 33,820.76
NS 7.2 Providing and fixing 100mm dia G.I. vent pipe on Under ground and over
0
head tank inlcuding cost of 2 Nos. 90 bend and painting with enamel
paint complete with in all respect.
a) 100 mm dia Each 16 4,805.00 76,880.00
19.16 7.3 Providing orange colour safety foot rest of minimum 6 mm thick plastic
encapsulated as per IS : 10910 on 12mm dia steel bar conforming to IS :
1786 having minimum cross section as 23 mmx25mm and over all
minimum length 263 mm and width as 165mm with minimum 112 mm
space between protruded legs having 2 mm tread on top surface by
ribbing or chequering besides necessary and adequate anchoring
projections on tail length on 138 mm as per standard drawing and suitable
to with stand the bend test and chemical resistance test as per
specifications and having manufacture's permanent identification mark to
be visible even after fixing, including fixing in manholes with 30x20x15 cm
cement concrete block 1:3:6 (1 cement : 3 coarse sand : 6 graded stone
aggregate 20 mm nominal size) complete as per design.
Each 240 311.60 74,784.00
TOTAL OF MISCELLANEOUS WORKS CARRID OVER TO SUMMARY
OF EXTERNAL PLUMBING WORKS 74,784.00 204,503.65

BOQ - PL (EXT) 24
CHAPTER - 8 : TUBEWELL & TUBEWELL PUMPS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Note: The quantities may varies as per site conditions.
NS 8.1 Geo Hydrological Survey of site using resistivity method to assess the
ground water potentials and select the best possible location for tubewell
for 3500 GPH yield. Job 2 25,000.00 50,000.00
24.1 8.2 Boring/drilling bore well of required dia for casing/ strainer pipe, by
suitable method prescribed in IS:2800 (part I), including collecting
samples from different strata, preparing and submitting strata chart/bore
log, including hire & running charges of all equipments, tools, plants &
machineries required for the job, all complete as per direction of Engineer-
in-charge, upto 90 metre depth below ground level.
24.1.1 a) All types of soil
24.1.1.1 300 mm dia mtr. 120 445.25 53,430.00
24.10 8.3 Supplying, assembling, lowering and fixing in vertical position in bore well,
ERW (Electric Resistance Welded) FE 410 mild steel screwed and
socketed/ plain ended casing pipes of required dia, conforming to IS:
4270, of reputed & approved make, including painted with outside surface
with two coats of anticorrosive paint of approved brand and manufacture,
including required hire & labour charges, fittings & accessories, all
complete, for all depths, as per direction of Engineer-in-charge.

24.10.2 a) 150 mm nominal size dia having minimum wall thickness 5.00 mm mtr. 60 1,335.40 80,124.00
24.11 8.4 Supplying, assembling, lowering and fixing in vertical position in bore well,
ERW (Electric Resistance Welded) FE 410 plain slotted (having slot of
size 1.6/3.2mm) mild steel threaded and socketed / plain level ended pipe
(type A) of required dia, conforming to IS: 8110, of reputed and approved
make, having wall thickness not less than 5.40 mm, including painted with
outside surface with two coats of anticorrosive bitumestic paint of
approved brand and manufacture, including hire & labour charges, fittings
& accessories, all complete, for all depths, as per direction of Engineer-in-
charge.
24.11.2 a) 150 mm nominal size dia . mtr. 60 1,418.65 85,119.00
24.14 8.5 Providing and fixing M.S. clamp of required dia to the top of Casing/
housing pipe of tubewell as per IS: 2800 (part I), including necessary bolts
& nuts of required size complete.
24.14.2 a) 150 mm clamp. Each 2 1,170.95 2,341.90

BOQ - PL (EXT) 25
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
24.12 8.6 Development of tube well in accordance with IS: 2800 (part I) and IS
11189, to establish maximum rate of usable water yield without sand
content (beyond permissible limit), with required capacity air compressor,
running the compressor for required time till well is fully developed,
measuring yield of well by "V" notch method or any other approved
method, measuring static level & draw down etc. by step draw down
method, collecting water samples & getting tested in approved laboratory,
i/c disinfection of tubewel, all complete, including hire & labour charges of
air compressor, tools & accessories etc., all as per requirement and
direction of Engineer-in-charge.
Hrs. 80 677.10 54,168.00
NS 8.7 Providing and fixing single / multistage submersible tubewell pump
suitable for 150mm bore with stainless steel casing, NORYL impeller,
stainless steel shaft and built in non return valve coupled with submersible
squirrel cage motors suitable for 145V 10% volts. 3 phase, 50 cycles AC
supply.
a) Capacity 200 lpm
Providing,
Fixing
Excavating
Constructing
Providing
Supplying
Head of and
50m and
vitreous
installing
&laying
toand
trenches
and
grease
masonry
brick
fixing
fixing
60mfixing
fixing
and
masonry
fixing
china
and
in
PVC
trap
Sand
of
M.S.
position
chamber
joining
required
in
commissioning
80half
waste
Structural
Cast
mineral
position
xmanhole
open
40
the
stall
in30
Iron
Iron
width
pipework
xmedium
position
surface
x46
lipped
30
work
Rain
wool
Soil,
vent
with
cm
for
20x No. 2 30,000.00 60,000.00
NS 8.8 50mm dia GI column pipe of heavy class duly flanged. mtr. 150 350.00 52,500.00
NS 8.9 Providing and fixing gunmetal pressure gauge (100mm dia) of rating (0-10
2
kg/cm ) with gunmetal isolating cock and connecting pipe. No. 2 2,500.00 5,000.00
NS 8.10 Providing and fixing 50mm cable clips with nuts & bolts. Nos. 48 50.00 2,400.00
NS 8.11 Providing and fixing 50mm dia supporting clamps with nuts and bolts. Pair 2 400.00 800.00
NS 8.12 Providing and fixing 3C - 6 sq.m submersible cable. mtr. 200 175.00 35,000.00
NS 8.13 Providing and fixing Butterfly valve of cast body with stainless steel disc
and stainless steel stem, teflon bushing and niterite o'rings.
a) 80mm dia No. 2 5,000.00 10,000.00
NS 8.14 Providing and fixing steel wire rope 6mm dia complete with wire rope
clamps for safety of pump set. mtr. 150 50.00 7,500.00
NS 8.15 Supplying & laying 1.1KV grade aluminium conductor PVC insulated and
PVC sheathed armoured cables including 8 SWG GI earth wire on
surface/cable trays as required.
a) 3 Core - 6sq.mm mtr. 20 225.00 4,500.00

BOQ - PL (EXT) 26
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 8.16 Providing and fixing dust and vermin proof motor control panel fabricated
from 14 SWG MS sheet with stove enamelled paint and comprising of: (for
Tubewell pumps)
a) One feeder of 63 ampere 4 Pole ELCB.
b) One fully automatic star delta starter with push buttons and indicating
lights.
c) One panel type volt meter 96mm square with Rotary selection switch for
reading voltage between phase and neutral or incoming feeder.
d) Three Neon Phase indicating lights on the incoming Main.
e) One Ampere meter 96mm square panel type of appropriate range.
f) Etched plastic identification plates for all switch gears.
g) Space for liquid level controller.
h) All internal wiring should be colour coded from incoming main to
switchgear, starters, meters, indicating lights. No. 2 30,000.00 60,000.00
24.15 8.17 Supplying of 150mm dia tail plug with all required specials complete as
per directions of Engineer -in-Charge.
24.15.2 a) 150 mm clamp. No. 2 242.65 485.30
TOTAL OF TUBEWELL & TUBEWELL PUMPS (2 NOS.) CARRIED
OVER TO SUMMARY OF EXTERNAL PLUMBING WORKS 275,668.20 287,700.00

BOQ - PL (EXT) 27
CHAPTER - 9 : PUMPING SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
9.1 Providing, fixing, testing and commissioning of Vertical in line type pump
set with SS casing, SS impeller and SS shaft suitable for operation on
400/440 volts, 3 phase 2900 RPM, TEFC electric motor mounted on a
common channel base plate with coupling guard, 150mm dia pressure
gauge, GM isolation cock and cement concrete foundation with plaster
complete as required.
NS a) Filter Feed pumps (Domestic)
Pump capacity - 400 lpm
Head - 30 m
RPM - 2900 Each 3 136,399.00 409,197.00
NS b) Domestic water transfer pumps
Pump capacity - 800lpm
Head - 60 m
RPM - 2900 Each 2 258,440.00 516,880.00
NS c) Filter Feed pumps (Flushing)
Pump capacity - 400 lpm
Head - 30 m
RPM - 2900 Each 2 136,399.00 272,798.00
NS d) Flushing water transfer pumps
Pump capacity - 800lpm
Head - 60 m
RPM - 2900 Each 2 258,440.00 516,880.00
NS 9.2 Providing, fixing and commissioning non clog type mono block
submersible drainage pumps suitable for handling solids of 12 mm size
with totally water and dust proof motor as specified
a) Capacity 500 lpm & Head 10 m (in pump room sump 2 nos.) Each 4 79,362.00 317,448.00
b) Capacity 300 lpm & Head 10 m (in basement sump 11 nos.) Each 22 36,658.00 806,476.00

BOQ - PL (EXT) 28
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 9.3 Providing and fixing Transistorised liquid level controllers with low
voltage Relays and Seamless Steel probes and PVC shroud, including
necessary wiring and conduiting from probes to display panel/motor
control panels and to provide Audible Alarm for low level for each
underground tank. (The cost of all required cabling from probes to Motor
control panels to be including in the rate).
a) For Domestic Filter feed
To start domestic filter feed pumps at low water level in domestic treated
under ground tank and stop at high water level in domestic treated treated
tank and stop at low water level in domestic water tank & flushing water
filter feed tank. Set 2 10,338.00 20,676.00
NS 9.4 Supply, installation, testing and commissioning of dust, damp and vermin
proof, free floor standing factory built sheet steel enclosed nondrawout
modular panel for water supply pumps, fabricated out of suitable sized
square tubular section and covered with 2.0mm thick CRCA sheet,
hinged doors of 2mm thick CRCA sheet, duly painted complete with earth
bus, necessary metering protections & indications and mounted with the
following including all inter connection etc. (Including earthing). (Inside
Domestic water tank pump room)

i) Incoming
ii) One No. 200 amps TP incoming MCCB complete with the following:
iii) 1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and fuses.
(1 set).
iv) 1 No. 0-200 amps 96x96sq.mm ammeter with 60/5 amps ratio CT's and
selector switch.
v) Over voltage and under voltage tripping machanism for persistent voltage
fluctations of more than 10% of the rated voltage for more than 5
minutes. (1set)
b) Phase indicating lamps with toggle switches.
c) Indication lamps for ON/OFF/TRIP status of motors.
i) Aluminium bus bar of 150 amps for three phase and neutral.
ii) Outgoing Feeders/Starters.
iii) 16 amps TPN MCB with DOL starter with built-in SPP each suitable 4 HP
Filter Feed pumps (3 Nos).
iii) 63 amps TPN MCB with STAR DELTA starter with built-in SPP each
suitable 15 HP Domestic water transfer pumps (3 Nos).

BOQ - PL (EXT) 29
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
iv) 32 amps TPN MCB with built-in SPP each suitable for 7.5 HP drainage
pumps panel in pumproom(1 Set).
16 amps TPN MCB with built-in SPP each suitable for 5 HP tubewell
pumps panel (2 Sets).
Rotary manual/auto/off switch. (4 Nos.)
a) Spares
b) 63 amps TPN MCB 10 KA - 2 Nos.
c) 32 amps TPN MCB 10 KA - 2 Nos.
d) Note :
e) All switch gear/panels shall be suitable for 10 KA rating.
f) All outgoing will have 96 sq. mm size ammeter and CT.
g) All starter will have spare 10 amps 230 V coil auxiliary contractor for
building Automation system.
h) All starter units for pumps to be provided with 3 level liquid level
contractor.
i) Lamps.
j) All pumps to be provided with duty selector switch.
All pumps to be provided with sequence timer 220/440 V AC/DC and
alternate working of pumps between 6 to 8 hours or alternate use of
pumps after one service in sequence.
All pumps to be provided with over load relay.
All starter to be provided with single phase preventor.
Necessary cable alleys for space switches, level controller internal wiring
and copper earthing of all equipment shall also be included. All switch
gears/control gears shall be motor duty rating. Each 1 289,766.00 289,766.00
9.5 Supply, installation, testing and commissioning of dust, damp and vermin
proof, free floor standing factory built sheet steel enclosed nondrawout
modular panel for water supply pumps, fabricated out of suitable sized
square tubular section and covered with 2.0mm thick CRCA sheet,
hinged doors of 2mm thick CRCA sheet, duly painted complete with earth
bus, necessary metering protections & indications and mounted with the
following including all inter connection etc. (Including earthing). (Inside
Flushimg water tank pump room)

BOQ - PL (EXT) 30
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS a)
i) Incoming
ii) One No. 100 amps TP incoming MCCB complete with the following:
iii) 1 No. 0-500 volts 96x96 sq. mm ammeter with selector switch and fuses.
(1 set).
iv) 1 No. 0-200 amps 96x96sq.mm ammeter with 60/5 amps ratio CT's and
selector switch.
v) Over voltage and under voltage tripping machanism for persistent voltage
fluctations of more than 10% of the rated voltage for more than 5
minutes. (1set)
b) Phase indicating lamps with toggle switches.
c) Indication lamps for ON/OFF/TRIP status of motors.
i) Aluminium bus bar of 100 amps for three phase and neutral.
ii) Outgoing Feeders/Starters.
iii) 16 amps TPN MCB with DOL starter with built-in SPP each suitable 4 HP
Filter Feed pumps (2 Nos).
iii) 63 amps TPN MCB with STAR DELTA starter with built-in SPP each
suitable 15 HP Domestic water transfer pumps (2 Nos).
iv) 32 amps TPN MCB with built-in SPP each suitable for 7.5 HP drainage
pumps panel in pumproom(1 Set).
Rotary manual/auto/off switch. (4 Nos.)
a) Spares
b) 63 amps TPN MCB 10 KA - 2 Nos.
c) 32 amps TPN MCB 10 KA - 2 Nos.
d) Note :
e) All switch gear/panels shall be suitable for 10 KA rating.
f) All outgoing will have 96 sq. mm size ammeter and CT.
g) All starter will have spare 10 amps 230 V coil auxiliary contractor for
building Automation system.
h) All starter units for pumps to be provided with 3 level liquid level
contractor.
i) Lamps.
j) All pumps to be provided with duty selector switch.
All pumps to be provided with sequence timer 220/440 V AC/DC and
alternate working of pumps between 6 to 8 hours or alternate use of
pumps after one service in sequence.
All pumps to be provided with over load relay.

BOQ - PL (EXT) 31
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
All starter to be provided with single phase preventor.
Necessary cable alleys for space switches, level controller internal wiring
and copper earthing of all equipment shall also be included. All switch
gears/control gears shall be motor duty rating. Each 1 289,766.00 289,766.00
NS 9.6 Providing and fixing wall mounted dust and vermin proof motor control
panel fabricated from 14 SWG MS sheet with stove enamelled paint and
comprising of the following: (For drainage pumps in pump room )
a) 32 amps incoming MCB (1 No.)
b) Fully tapped Copper bus bas of suitable capacity. (1 set)
c) Panel type volt meter 96mm square with Rotary selection switch for
reading voltage between phase and neutral or incoming feeder. (1 set)

d) Phase indicating lights with toggle switches and shall be protected by 2


amps MCB's. (2 sets)
e) Ampere meter 96mm square panel type of appropriate range. (1 set)
f) 32 amps outgoing MCB (2 Nos.)
g) Fully automatic DOL starters with push buttons indicating lights and
overload relay each for drainage pump. (2 Nos.)
h) Single phasing preventors. (2 Nos.)
i) Rotary manual/auto/off switch. (2 Nos.)
j) Space of one liquid level controller Set 13 35,519.00 461,747.00
NS 9.7 Supplying and laying the PVC insulated & sheathed FRLS Armoured
cables of 1.1 K.V. Aluminium Conductor on prelaid cabel trays including
supplying and making and termination with brass compression glands:
(cabel trays shall be installed by electrical cotrator).

a) 3 Core x 4 sq.mm Metre 30 204.00 6,120.00


b) 3 Core x 10 sq.mm Metre 30 270.00 8,100.00
TOTAL OF WATER SUPPLY PUMPS CARRIED OVER TO SUMMARY
OF EXTERNAL PLUMBING WORKS - 3,915,854.00

BOQ - PL (EXT) 32
CHAPTER - 10 : WATER TREATMENT SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 10.1 Providing and fixing skid mounted vertical MSRL Dual Media pressure
filter fabricated from IS 226/2062 plate 5mm thick for shell and 6mm thick
M.S. plate for dished ends complete with initial charge of filter media, face
piping and valves accessories, painting, testing and commissioning
complete.(2 nos. for domestic water supply & 1 no. for flushing water
supply system)
a) For Domestic water supply system
Capacity 24000 lph.
Working pressure 2.5 kg./cm2
Design pressure 4 kg./cm2 Each 3 373,302.00 1,119,906.00
NS 10.2 Providing and fixing bulk water meter with direct reading dial in KL, all
internal parts and strainer in gun metal/brass.
a) 100 mm dia Each 3 17,316.00 51,948.00
NS 10.3 Providing and fixing direct reading rate of flow Rota Meter
a) For 100 mm dia Each 3 15,677.00 47,031.00
NS 10.4 Providing and fixing gun metal dial type pressure gauge (100mm dia) of
rating 0-10 kg./cm2 with gun metal isolating cock pig and connecting pipe.
Each 6 1,278.00 7,668.00
NS 10.5 Supply, assembly, erection, testing and commissioning of chlorinator with
metering pump suitable for operation on 220 5% single phase, 50 Hz AC
supply, compete in all respects.
a) Suitable for flow rate 0 -6 lph Each 3 31,587.00 94,761.00
TOTAL OF WATER TREATMENT SYSTEM CARRIED OVER TO
SUMMARY OF EXTERNAL PLUMBING WORKS - 1,321,314.00

BOQ - PL (EXT) 33
CHAPTER - 11 :SUCTION AND DELIVERY PIPES AND VALVES FOR WATER SUPPLY PUMPS
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL.
DESCRIPTION OF ITEM UNIT QTY
NS NO. DSR NS DSR ITEMS NS ITEMS
NS 11.1 Providing and fixing G.I. suction & delivery headers/pipes for water supply
pumps (IS:1239 heavy class) with G.I. Fittings (bends, tees, reducers,
plugs, union, flange & blank flanges etc) and clamps and jointing with
teflon tape or hold tite including chase cutting and making good the walls,
floors etc. wherever required.
a) 80 mm nominal bore (For Sump pump) Meter 690 998.00 688,620.00
b) 100 mm nominal bore Meter 50 1,417.00 70,850.00
c) 150 mm nominal bore Meter 40 2,081.00 83,240.00
d) 200 mm nominal bore Meter 20 2,373.00 47,460.00
NS 11.2 Painting for G.I. Pipes with two or more coats of synthetic enamel paint of
approved quality and shade over a coat of approved primer coat as
directed including surface preparation (Shade as per pipe colour code)

a) 80 mm nominal bore (For Sump pump) Meter 690 50.00 34,500.00


b) 100 mm nominal bore Meter 50 60.00 3,000.00
c) 150 mm nominal bore Meter 40 70.00 2,800.00
d) 200 mm nominal bore Meter 20 80.00 1,600.00
NS 11.3 Providing and fixing reinforced Neoprene flexible pipe connectors with all
accessories on all pumps delivery.
2
Suitable for 20 Kg/cm
a) 150mm Each 5 18,900.00 94,500.00
b) 200mm Each 5 25,500.00 127,500.00
16.7.1 11.4 BUTTERFLY VALVE (MANUAL) with C I body SS Disc, Nitrile Rubber
ELECT. Seal & O- Ring PN 16 pressure rating for chilled water/hot eater circulation
DSR 2014 as specified

16.7.1.5 a) 80 mm dia Each 26 3,638.00 94,588.00


16.7.1.4 b) 100 mm dia Each 3 5,205.00 15,615.00
16.7.1.2 c) 150 mm nominal bore Each 10 6,499.00 64,990.00
16.7.1.1 d) 200 mm nominal bore Each 3 10,982.00 32,946.00

BOQ - PL (EXT) 34
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL.
DESCRIPTION OF ITEM UNIT QTY
NS NO. DSR NS DSR ITEMS NS ITEMS
16.7.3 11.5 NON - RETURN VALVE with duel plate of C I body SS plates vulcanized
ELECT. NBR seal flanged end & PN 16 pressure rating for chilled / hot water
DSR 2014 circulation including insulation as specified.

16.7.3.1 a) 200 mm dia Each 1 9,530.00 9,530.00


16.7.3.2 b) 150 mm dia Each 5 6,345.00 31,725.00
16.7.3.4 c) 100 mm dia Each 7 3,776.00 26,432.00
16.7.3.5 d) 80 mm dia Each 13 2,728.00 35,464.00
NS 11.6 Providing and fixing suction strainer with M.S. flanged connection
1000mm long, fabricated from 16 gauge Brass sheet with 3mm slots.
a) 150mm nominal bore Each 5 15,085.00 75,425.00
b) 200mm nominal bore Each 5 10,666.00 53,330.00
16.7.4 11.7 Y - STRAINER of Ductile CI Body flanged ends with stainless steel
ELECT. strainer for chilled / hot water circulation including insulation as specified.
DSR 2014

16.7.4.1 a) 200mm nominal bore Each 5 20,741.00 103,705.00


16.7.4.2 b) 150mm nominal bore Each 5 10,418.00 52,090.00
TOTAL OF SUCTION AND DELIVERY PIPES AND VALVES CARRIED
OVER TO SUMMARY OF EXTERNAL PLUMBING WORKS
467,085.00 1,282,825.00

BOQ - PL (EXT) 35
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF INTERNAL ELECTRICAL WORKS - ( figures in Rs.)

Sl. No. Description of Items Schedule Items Non Schedule items


1 Point Wiring 76,428,651.00
2 Telephone, TV & Data 5,578,215.00 9,955,658.00
3 Cable & End Termination 659,584.00 3,808,020.00
4 Main Distribution Board 16,697,267.00 27,304,634.00
5 Fittings & Accessories 2,876,594.00 36,676,137.00
6 Earthing 13,853,208.00
TOTAL OF INTERNAL ELECTRICAL WORKS CARRIED OVER
TO GRAND SUMMARY OF COSTS 116,093,519.00 77,744,449.00

BOQ - EL(INT) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP(SPG) AT DWARKA
BILL OF QUANTITY - INTERNAL ELECTRICAL WORKS
CHAPTER - 1 : POINT WIRING
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DRS NS DSR ITEMS NS ITEMS
NS
1.3 1.1 Wiring for light point/fan point/exhaust fan point/call bell point with 1.5
Sq.mm FRLS PVC insulated, copper conductor, single core cable in
surface/recessed steel conduit, with modular switch, modular plate,
suitable GI box and earthing the point with 1.5 Sq.mm FRLS PVC
insulated copper conductor single core cable etc. as required.
1.3.1 1.1.1 Group-A Point 18831 677.00 12,748,587.00
1.3.2 1.1.2 Group-B Point 3360 811.00 2,724,960.00
1.3.3 1.1.3 Group-C Point 3386 1,003.00 3,396,158.00
1.4 1.2 Wiring for twin control light point with 1.5 Sq.mm FRLS PVC insulated,
copper conductor, single core cable in surface/recessed steel conduit, 2
way modular switch, modular plate, suitable GI box and earthing the point
with 1.5 Sq.mm FRLS PVC insulated copper conductor single core cable
etc. as required. Point 1158 1,069.00 1,237,902.00
1.5 1.3 Wiring for light/power plug with 2x4 sq.mm FRLS PVC insulated, copper
conductor, single core cable in surface/recessed steel conduit alongwith
1 No. 4 Sq.mm FRLS PVC insulated copper conductor single core cable
for loop earthing as required. Mtr 47060 233.00 10,964,980.00
1.6 1.4 Wiring for light/power plug with 4x4 sq.mm FRLS PVC insulated, copper
conductor, single core cable in surface/recessed steel conduit alongwith
2 No. 4 Sq.mm FRLS PVC insulated copper conductor single core cable
for loop earthing as required. Mtr 23190 359.00 8,325,210.00
1.7 1.5 Wiring for circuit/ submain wiring alongwith earth wire with the following
sizes of FRLS PVC insulated copper conductor, single core cable in
surface/ recessed steel conduit as required
1.7.1 1.5.1 2 x 1.5 Sqmm + 1 x 1.5 Sq.mm earth wire Mtr 49910 106.00 5,290,460.00
1.7.4 1.5.2 2 x 6 Sqmm + 1 x 6 Sq.mm earth wire Mtr 2980 221.00 658,580.00
1.7.5 1.5.3 2 x 10 Sqmm + 1 x 10 Sq.mm earth wire Mtr 3300 327.00 1,079,100.00
1.7.9 1.5.4 4 x 6 Sqmm + 2 x 6 Sq.mm earth wire Mtr 1630 389.00 634,070.00
1.7.10 1.5.5 4 x 10 Sqmm + 2 x 10 Sq.mm earth wire Mtr 28160 597.00 16,811,520.00
1.7.11 1.5.6 4 x 16 Sqmm + 2 x 16 Sq.mm earth wire Mtr 7435 883.00 6,565,105.00

BOQ - EL(INT) 2
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DRS NS DSR ITEMS NS ITEMS
NS
1.31 1.6 Supplying & fixing suitable size GI box with modular plate and cover in
front on surface or in recess, including providing & fixing 3 pin 5/6 Amps
modular socket outlet and 5/6 Amp. modular switch, connections etc. as
required. (For light plugs to be used in non residential buildings).
Each 10308 303.00 3,123,324.00
1.32 1.7 Supplying & fixing suitable size GI box of with modular plate and cover in
front on surface or in recess including providing & fixing 6 pin 5/6 & 15/16
Amp. modular socket outlet and 15/16 Amps modular switch,
connections etc. as required. Each 4758 395.00 1,879,410.00
1.25 1.8 Supplying & fixing stepped type electronic fan regulator on the existing
modular plate switch box including connections but excluding modular
plate etc. as required. Each 3283 284.00 932,372.00
1.38 1.9 Supplying and fixing call bell/buzzer suitable for single phase, 230 volts,
complete as required. Each 933 61.00 56,913.00
TOTAL OF POINT WIRING WORK CARRIED OVER TO SUMMARY OF
ELECTRICAL WORKS 76,428,651.00 -

BOQ - EL(INT) 3
CHAPTER - 2 : TELEPHONE , TV & DATA
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
1.24 2.1 Supplying & fixing following modular switch/socket on the existing
modular plate & switch box including connections but excluding
modular plate etc. as required.
1.24.3 2.1.1 15/16 amp switch Each 37 111.00 4,107.00
1.24.4 2.1.2 3 pin 5/6 amp socket outlet Each 111 79.00 8,769.00
1.24.6 2.1.3 Telephone socket outlet Each 1926 95.00 182,970.00
1.24.7 2.1.4 TV Antenna socket outlet Each 1045 94.00 98,230.00
1.20 2.2 Supplying and fixing of following sizes of steel conduit along with
accessoris in surface/recess including painting in case of surface
conduit or cutting the wall and making good the same in case of
recessed conduit as required.
1.20.2 2.2.1 25mm (for Telephone & Data) Mtr 14130 142.00 2,006,460.00
1.20.3 2.2.2 32mm (for Telephone & Data) Mtr 7015 193.00 1,353,895.00
1.18 2.30 Supplying and drawing following pair, 0.5 Sq.mm dia FRLS PVC
insulated annealed copper conductor, unarmoured telephone cable in
the existing surface/recessed steel/PVC conduit as required.
1.18.2 2.3.1 2- Pair Mtr 46280 18.00 833,040.00
NS 2.3.2 10-Pair Telephone Cable. Mtr 4670 75.00 350,250.00
NS 2.3.3 20-Pair Telephone Cable. Mtr 100 144.00 14,400.00
NS 2.4 Supplying, laying and fixing PVC insulated and PVC sheathed 0.5 mm
dia copper conductor armoured telephone cable of following sizes in
existing pipes/on wall/shafts and making connections from Tele[phone
main junction box and telephone sub-junction box with all accessories
as required
2.4.1 10-Pair Telephone Cable. Mtr 750 144.00 108,000.00
2.4.2 20-Pair Telephone Cable. Mtr 1500 247.00 370,500.00
2.4.3 50-Pair Telephone Cable. Mtr 2370 524.00 1,241,880.00
2.4.4 100-Pair Telephone Cable. Mtr 8150 921.00 7,506,150.00

BOQ - EL(INT) 4
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 2.5 Providing and fixing in position 2mm thick M.S. Telephone junction box
of size suitable for fixing of following Krone Tag Block with key lock
arrangement. Also provide clamps for fixing tag blocks.
2.5.1 10 pair Telephone Tag Block Box Each 183 607.00 111,081.00
2.5.2 20 pair Telephone Tag Block Box Each 7 971.00 6,797.00
2.5.3 50 pair Telephone Tag Block Box Each 7 2,186.00 15,302.00
2.5.4 100 pair Telephone Tag Block Box Each 11 3,643.00 40,073.00
2.5.5 150 pair Telephone Tag Block Box Each 2 5,120.00 10,240.00
2.5.6 300 pair Telephone Tag Block Box Each 2 9,107.00 18,214.00
2.5.7 400 pair Telephone Tag Block Box Each 1 12,143.00 12,143.00
2.5.8 600 pair Telephone Tag Block Box Each 2 18,215.00 36,430.00
NS 2.6 Supply , Installtion , Testing and comissioning of CAT 6 UTP cable
23AWG solid copper conductors Approved Make :
Molex/Panduit/Siemon Mtr 1200 34.00 40,800.00
NS 2.7 Supply , Installtion , Testing and comissioning of CAT6 information
outlet (I/O) Approved Make : Molex/Panduit/Siemon Each 37 342.00 12,654.00
NS 2.8 Supply installation testing and commissioning of 6U wall mounted
cabinets equipped with one lockable door made of tinted glass, top &
bottom cable entry plates, ventilation grills at side, cable manager,
power supply strip, 230volts AC 90CFM fans, cantilever tray, earthing
strip & accessories complete as required. Each 4 15,186.00 60,744.00
1.27 2.9 Supplying & fixing following size/modules, GI box alongwith modular
base & cover plate for modular switches in recess etc. as required.
1.27.1 2.9.1 1 or 2 Module (75 mm x 75 mm) Each 2971 166.00 493,186.00
1.27.6 2.9.2 12 Module (200 mm x 150 mm) Each 37 334.00 12,358.00
1.19 2.10 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid
copper conductor PE insulated, shielded with fine tinned copper braid
and protected with PVC sheath in the existing surface/ recessed steel/
PVC conduit as required. Mtr 20900 28.00 585,200.00
TOTAL OF MAIN DISTRIBUTION BOARD WORK CARRIED OVER
TO SUMMARY OF ELECTRICAL WORKS 5,578,215.00 9,955,658.00

BOQ - EL(INT) 5
CHAPTER - 3 : CABLE & END TERMINATION
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 3.1 Supplying & fixing of the following XLPE 1100 Volts grade Al.
Conductor armoured cables complete as required.
3.1.1 3.5C X 35 sq mm Mtr 2530 429.00 1,085,370.00
3.1.2 4C X 6 sq mm Mtr 350 212.00 74,200.00
3.1.3 4C X 16 sq mm Mtr 3350 305.00 1,021,750.00
9.1 3.2 Supplying and making end termination with brass compression gland
and aluminium lugs for following size of PVC insulated and PVC
sheathed / XLPE aluminium conductor cable of 1.1 KV grade as
required.
9.1.21 3.2.1 3,1/2x35 sq.mm (32mm) Each 272 270.00 73,440.00
9.1.32 3.2.2 4x6 sq.mm (25mm) Each 38 193.00 7,334.00
9.1.33 3.2.3 4x16 sq.mm (28mm) Each 598 245.00 146,510.00
NS 3.4 Fabricating and installing following size of perforated M. S. cable trays
including horizontal and vertical bends, reducers, tees, cross members
and other accessories as required and duly suspended from the ceiling
with M. S. suspenders and including painting with powder coating etc
as required.
3.4.1 150 mm width X 50 mm depth X 1.6 mm thickness Mtr 770 656.00 505,120.00
3.4.2 200 mm width X 50 mm depth X 1.6 mm thickness Mtr 540 930.00 502,200.00
3.4.3 300 mm width X 50 mm depth X 1.6 mm thickness Mtr 540 1,147.00 619,380.00
14.14 3.5 Providing, laying and fixing following dia RCC pipe NP2 class (light
duty) in ground complete with RCC collars, jointing with cement mortar
1:2 (1 cement : 2 fine sand) including trenching (75 cm deep) and
refilling etc as required.
14.14.1 3.5.1 100 mm dia Mtr 200 337.00 67,400.00
14.14.2 3.5.2 150 mm dia Mtr 300 384.00 115,200.00
14.14.3 3.5.3 250 mm dia Mtr 300 455.00 136,500.00
14.14.4 3.5.4 300 mm dia Mtr 200 566.00 113,200.00
TOTAL OF CABLE & END TERMINATION WORK CARRIED OVER
TO SUMMARY OF ELECTRICAL WORKS 659,584.00 3,808,020.00

BOQ - EL(INT) 6
CHAPTER - 4 : MAIN & DISTRIBUTION BOARD
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.10 4.1 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C"
curve, miniature circuit breaker suitable for inductive load of following
poles in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
2.10.1 4.1.1 Single pole Each 18878 169.00 3,190,382.00
NS 4.1.2 40A SP MCB Each 18 413.00 7,434.00
2.10.2 4.1.3 Single pole and neutral Each 140 441.00 61,740.00
NS 4.1.4 40A SPN MCB Each 10 858.00 8,580.00
2.10.4 4.1.5 Tripple pole Each 121 696.00 84,216.00
NS 4.1.6 40A TP MCB Each 38 1,332.00 50,616.00
NS 4.1.7 63A TP MCB Each 9 1,401.00 12,609.00
2.10.5 4.1.8 Tripple pole and neutral Each 43 887.00 38,141.00
NS 4.1.9 40A TPN MCB Each 16 1,759.00 28,144.00
NS 4.1.10 63A TPN MCB Each 34 1,833.00 62,322.00
2.7 4.2 Supplying and fixing following way prewired SP&N MCB distribution
board of steel sheet for 240 volts on surface/ recess complete with
loose wire box, terminal connectors for all incoming and outgoing
circuits, duly prewired with suitable size FRLS PVC insulated copper
conductor up to terminal blocks, tinned copper bus bar, neutral link,
earth bar, din bar, detachable gland plate, interconnections, powder
painted including earthing etc. as required. (But without MCB/ RCCB/
Isolator)
2.7.4 4.2.1 2 + 4 way,/ 6 way Double door Each 84 2,508.00 210,672.00
2.7.5 4.2.2 2 + 8 way,/ 10 way Double door Each 68 2,995.00 203,660.00
2.7.6 4.2.3 2 + 12 way,/ 14 way Double door Each 14 3,613.00 50,582.00
2.14 4.3 Supplying and fixing following rating, double pole, (single phase and
neutral), 240 volts, residual current circuit breaker (RCCB), having a
sensitivity current upto 300 milliamperes in the existing MCB DB
complete with connections, testing and commissioning etc. as required.

2.14.1 4.3.1 25 amps Each 73 1,645.00 120,085.00


2.14.2 4.3.2 40 amps Each 52 1,714.00 89,128.00

BOQ - EL(INT) 7
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.8 4.4 Supplying and fixing following way prewired TP&N MCB distribution
board of steel sheet for 415 volts on surface/ recess complete with
loose wire box, terminal connectors for all incoming and outgoing
circuits, duly prewired with suitable size FRLS PVC insulated copper
conductor up to terminal blocks, tinned copper bus bar, neutral link,
earth bar, din bar, detachable gland plate, interconnections, powder
painted including earthing etc. as required.(But without MCB/ RCCB/
Isolator)
2.8.5 4.4.1 4 way (4 + 12), Double door Each 15 7,357.00 110,355.00
2.8.6 4.4.2 6 way (4 + 18), Double door Each 745 9,496.00 7,074,520.00
2.8.7 4.4.3 8 way (4 + 24), Double door Each 148 10,405.00 1,539,940.00
2.8.8 4.4.4 12 way (4 + 36), Double door Each 28 12,782.00 357,896.00
2.15 4.5 Supplying and fixing following rating, four pole, (three phase and
neutral), 415 volts, residual current circuit breaker (RCCB), having a
sensitivity current upto 300 milliamperes in the existing MCB DB
complete with connections, testing and commissioning etc. as required.

2.15.1 4.5.1 25 amps Each 2 2,088.00 4,176.00


2.15.2 4.5.2 40 amps Each 744 2,123.00 1,579,512.00
2.15.3 4.5.3 63 amps Each 189 2,294.00 433,566.00
2.9 4.6 Supplying and fixing following way prewired vertical type TP&N MCB
distribution board of steel sheet for 415 volts on surface/recess
complete with loose wire box of sheet steel, dust protected,duly powder
painted, inclusive of 200 amps tinned copper bus bar, common neutral
link, earth bar, din bar for mounting MCBs,terminal connectors for all
incoming and outgoing circuits, duly prewired with adequate size of
FRLS PVC insulated copper conductor upto the terminal connector/
neutral link, earthing etc as required (But without MCB/ RCCB/
Isolator). (Note : Prewired vertical type MCB TPDB is normally used
where 3 phase outlets are required.)
2.9.5 4.6.1 4 way Double door Each 1 7,901.00 7,901.00
2.9.6 4.6.2 6 way Double door Each 2 10,204.00 20,408.00

BOQ - EL(INT) 8
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.7 Supplying and fixing following ways surface/ recess mounting, vertical
type, 415 volts, TPN MCB distribution board of sheet steel, dust
protected, duly powder painted, inclusive of 200 amps tinned copper
bus bar, common neutral link, earth bar, din bar for mounting MCB's,
with provision of MCCB as incomer, interconnection between incomer
MCCB and bus bars (but without MCB's/ MCCB/RCCB) as required

4.7.1 6 way Double door Each 7 13,256.00 92,792.00


4.7.2 12 way Double door Each 14 19,510.00 273,140.00
2.2 4.8 Providing and fixing following rating and breaking capacity and pole
MCCB in existing cubicle panel board including drilling holes in cubicle
panel, making connections, etc. as required.
NS 4.8.1 63 Amp, 16 KA,TPMCCB Each 3 3,205.00 9,615.00
2.2.1 4.8.2 100 Amp, 16 KA,TPMCCB Each 18 3,205.00 57,690.00
2.16 4.9 Supplying and fixing DP sheet steel enclosure on surface/ recess along
with 25/32amps 240 volts C curve DP MCB complete with
connections, testing and commissioning etc. as required Each 104 617.00 64,168.00
2.18 4.10 Supplying and fixing 20 amps, 240 volts, SPN industrial type, socket
outlet, with 2 pole and earth, metal enclosed plug top alongwith 20
amps "C" curve, SP, MCB, in sheet steel enclosure, on surface or in
recess, with chained metal cover for the socket out let and complete
with connections, testing and commissioning etc. as required. Each 919 954.00 876,726.00
2.20 4.11 Supplying and fixing 30 amps, 415 volts, TPN industrial type, socket
outlet, with 4 pole and earth, metal enclosed plug top alongwith 30
amps "C" curve, TPMCB, in sheet steel enclosure, on surface or in
recess, with chained metal cover for the socket out let and complete
with connections, testing and commissioning etc. as required. Each 211 2,473.00 521,803.00

BOQ - EL(INT) 9
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.12 Supplying, installation , testing and comissioning of cubical type LT
panel suitable for 415Volts 3 phase 4wire 50 Hz AC supply system
having front surface area Sq.mtr (approx) fabricated in
compartmentalized design from CRCA sheet steel of 2 mm thick for
frame work and covers , 3 mmthick for gland plates including cleaning
and finishing complte with 7 tank process for power coating in
approved shade having --Amp capacity extensible type TPN aluminium
alloy bus bars of high conductivity DMC/SMC bus bars supports with
short circuit withstand capacity of 31 MVA for 1 second, bottom base
channel of MS section not less than 100mmx 50 mmx 5mm thick,
fabrication shall be done in transportable setctions, entire panel shall
have a common copper earthbar of size25 mm x 5 mm at the rear with
2 No earth stud solid connections from main bus bars to switchgears
with required size of aluminium bus bars and control wiring with 2.5 Sq.
mm PVCinsulated copper conductor S/C cable alleys cable gland and
plates in bottom half ,including providing following switchgars .

NOTE:- MCCB's wherever specified shall have rotary handle,


current limiting, load line reversability & horz. Cum vertical
mounting feature. Beyond 320A capacity MCCB's shall have
positive isolation, double break/contact repulsion and double
insulation features. MCCB's shall be used with terminal spreaders.

NS 4.12.1 Basement Light & Power


Incomer
1 No. 200A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 50 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-200Amp) with selector switch and 1 set of
3Nos.CT's of ratio 200/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .

BOQ - EL(INT) 10
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
BUS-BAR
TPN aluminium bus bars of minimum of 300Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

Outgoing
63A MCCB, TPN, 25Ka Thermal with o/l & s/c, RYB LED lamps with 2A
protection MCB----10 nos.
63A MCB TPN 10Ka ---------4 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 4 385,198.00 1,540,792.00
Type II Flats
NS 4.12.2 Light & Power Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 400A, 4 pole MCCB having braking capacity 70 KA with
Microprocessr based o/l, e/f & s/c & time delay protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-400Amp) with selector switch and 1 set of
3Nos.CT's of ratio 400/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 600Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

BOQ - EL(INT) 11
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
OUTGOING
160A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 18 224,835.00 4,047,030.00
NS 4.12.3 Meter Panel Power
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 125A, 4 pole MCCB having braking capacity 25 KA with thermal
based o/l, e/f & s/c protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-125Amp) with selector switch and 1 set of
3Nos.CT's of ratio 125/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
32A TPN MCB, 10KA 9Nos.
Space for 32A three phase Electronic Energy Meter as per requirement
of BSES with LCD display CL-1.0 9Nos.
The Meter boxes shall be suitable for accomodating 9 Nos.three phase
electronics energy meter in separate cubicle compartments of
minimum size as per BSES with space for necessary interconnection
and clearances. (requirement of space for energy meter shall be
confirmed from electricity authorities)

BOQ - EL(INT) 12
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
The Meter boxes shall have suitable size MS bracket/bakelite plate to
accommodate meters.Each meter box shall be individually sealable
and suitable arrangement for locking with proper hinges and shall have
a window fixed with Acrylic sheet on the front cover so that meter
reading can be taken comfortably.
Rate shall include all fixing acessories as required
Proper cable alley for accomodating incoming cables and outgoing
copper cables / wires.
Separate earthing terminals
The job includes complete internal wiring with 2x10 sq. mm. copper
wires with lugs and ferrule markings.
Meter board as described above shall conform to electricity board
norms and approved drawings
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 72 121,175.00 8,724,600.00
NS 4.12.4 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

BOQ - EL(INT) 13
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 6 286,053.00 1,716,318.00
Type III Flats
NS 4.12.5 Light & Power Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 400A, 4 pole MCCB having braking capacity 70 KA with
Microprocessr based o/l, e/f & s/c & time delay protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-400Amp) with selector switch and 1 set of
3Nos.CT's of ratio 400/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 500Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
200A MCCB, TPN, 50Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complete as
required Each 3 294,181.00 882,543.00

BOQ - EL(INT) 14
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.12.6 Meter Panel Light & Power
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 200A, 4 pole MCCB having braking capacity 50 KA with Thermal
based o/l, e/f & s/c protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-200Amp) with selector switch and 1 set of
3Nos.CT's of ratio 200/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 300Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A TPN Electronic Energy Meter as per requirement of BSES with
LCD display CL-1.0---------8 nos.
63A TPN MCB 10Ka ---------8 no.
The Meter boxes shall be suitable for accomodating 8 Nos.three phase
electronics energy meter in separate cubicle compartments of
minimum size as per BSES with space for necessary interconnection
and clearances. (requirement of space for energy meter shall be
confirmed from electricity authorities)
The Meter boxes shall have suitable size MS bracket/bakelite plate to
accommodate meters.Each meter box shall be individually sealable
and suitable arrangement for locking with proper hinges and shall have
a window fixed with Acrylic sheet on the front cover so that meter
reading can be taken comfortably.
Rate shall include all fixing acessories as required
Proper cable alley for accomodating incoming cables and outgoing
copper cables / wires.
Separate earthing terminals

BOQ - EL(INT) 15
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
The job includes complete internal wiring with 2x10 sq. mm. copper
wires with lugs and ferrule markings.
Meter board as described above shall conform to electricity board
norms and approved drawings
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 12 138,152.00 1,657,824.00
NS 4.12.7 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 2 286,053.00 572,106.00

BOQ - EL(INT) 16
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Type IV Flats
NS 4.12.8 Meter Panel Light & Power
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 250A, 4 pole MCCB having braking capacity 50 KA with thermal
based o/l, e/f & s/c protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-250Amp) with selector switch and 1 set of
3Nos.CT's of ratio 250/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 400Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A TPN Electronic Energy Meter as per requirement of BSES with
LCD display CL-1.0---------7 no.
63A TPN MCB 10Ka ---------7 no.
The Meter boxes shall be suitable for accomodating 7 Nos.three phase
electronics energy meter in separate cubicle compartments of
minimum size as per BSES with space for necessary interconnection
and clearances. (requirement of space for energy meter shall be
confirmed from electricity authorities)
The Meter boxes shall have suitable size MS bracket/bakelite plate to
accommodate meters.Each meter box shall be individually sealable
and suitable arrangement for locking with proper hinges and shall have
a window fixed with Acrylic sheet on the front cover so that meter
reading can be taken comfortably.
Rate shall include all fixing acessories as required
Proper cable alley for accomodating incoming cables and outgoing
copper cables / wires.

BOQ - EL(INT) 17
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Separate earthing terminals
The job includes complete internal wiring with 2x10 sq. mm. copper
wires with lugs and ferrule markings.
Meter board as described above shall conform to electricity board
norms and approved drawings
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 4 139,776.00 559,104.00
NS 4.12.9 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
32A MCB, TPN, 10Ka 4 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 311,698.00 311,698.00

BOQ - EL(INT) 18
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Type V Flats
NS 4.12.10 Meter Panel Light & Power
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 300A, 4 pole MCCB having braking capacity 70 KA with
Microprocessrl based o/l, e/f & s/c & time delay protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-300Amp) with selector switch and 1 set of
3Nos.CT's of ratio 300/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 500Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A TPN Electronic Energy Meter as per requirement of BSES with
LCD display CL-1.0 ---------7 no.
63A TPN MCB 10Ka ---------7 no.
The Meter boxes shall be suitable for accomodating 7 Nos.three phase
electronics energy meter in separate cubicle compartments of
minimum size as per BSES with space for necessary interconnection
and clearances. (requirement of space for energy meter shall be
confirmed from electricity authorities)
The Meter boxes shall have suitable size MS bracket/bakelite plate to
accommodate meters.Each meter box shall be individually sealable
and suitable arrangement for locking with proper hinges and shall have
a window fixed with Acrylic sheet on the front cover so that meter
reading can be taken comfortably.
Rate shall include all fixing acessories as required
Proper cable alley for accomodating incoming cables and outgoing
copper cables / wires.

BOQ - EL(INT) 19
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Separate earthing terminals
The job includes complete internal wiring with 2x10 sq. mm. copper
wires with lugs and ferrule markings.
Meter board as described above shall conform to electricity board
norms and approved drawings
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 4 167,406.00 669,624.00
NS 4.12.11 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
32A MCB, TPN, 10Ka 4 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 311,698.00 311,698.00

BOQ - EL(INT) 20
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.12.12 Hostal SO & SA
Light Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 150A, 4 pole MCCB having braking capacity 25 KA with thermal
based o/l, e/f & s/c protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-150Amp) with selector switch and 1 set of
3Nos.CT's of ratio 150/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 300Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
100A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
63A MCB TPN 10Ka ---------4 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 184,743.00 184,743.00
NS 4.12.13 Power Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 250A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 50 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set

BOQ - EL(INT) 21
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Digital type ammeter (0-250Amp) with selector switch and 1 set of
3Nos.CT's of ratio 250/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 400Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
150A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----1 no.
100A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----7 nos.
63A MCB TPN 10Ka ---------2 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 3 382,128.00 1,146,384.00
NS 4.12.14 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .

BOQ - EL(INT) 22
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 2 286,053.00 572,106.00
NS 4.12.15 Transit Hostal SO & SA
Light Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 100A, 4 pole MCCB having braking capacity 25 KA with thermal
based o/l, e/f & s/c protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-100Amp) with selector switch and 1 set of
3Nos.CT's of ratio 100/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

BOQ - EL(INT) 23
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----6 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 157,835.00 157,835.00
NS 4.12.16 Power Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 300A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 50 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-300Amp) with selector switch and 1 set of
3Nos.CT's of ratio 300/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 500Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
100A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----7 nos.
63A MCB TPN 10Ka ---------2 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 391,879.00 391,879.00

BOQ - EL(INT) 24
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.12.17 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 273,052.00 273,052.00
Transit Accomodation GO
NS 4.12.18 Power Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 100A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 25 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set

BOQ - EL(INT) 25
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Digital type ammeter (0-100Amp) with selector switch and 1 set of
3Nos.CT's of ratio 100/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
40A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----11 nos.
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----1 no.
63A MCB TPN 10Ka ---------2 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 398,741.00 398,741.00
NS 4.12.19 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .

BOQ - EL(INT) 26
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 273,052.00 273,052.00
Centre of Excellence
NS 4.12.20 Panel Light & Power
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 300Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

BOQ - EL(INT) 27
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----11 nos.
63A MCB TPN 10Ka --------- 4nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 402,353.00 402,353.00
NS 4.12.21 Panel Stage Light
200 Amp, 50 KA,TPN MCCB with enclosure having the following
accessories for Auditorium Internal & Stage Lighting
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-200Amp) with selector switch and 1 set of
3Nos.CT's of ratio 200/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required . Each 1 39,550.00 39,550.00
NS 4.12.22 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

BOQ - EL(INT) 28
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 273,052.00 273,052.00
Community Centre
NS 4.12.23 Light Panels
Same as item No.4.12 above, but having the following switchgears:
1 No. 125A, 4 pole MCCB having braking capacity 25 KA with thermal
based o/l, e/f & s/c protection.
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-125Amp) with selector switch and 1 set of
3Nos.CT's of ratio 125/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----4 nos.
63A MCB TPN 10Ka ---------8 nos.
40A MCB SPN 10Ka ---------12 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 205,330.00 205,330.00

BOQ - EL(INT) 29
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.12.24 Power Panels
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 250A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 50 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-250Amp) with selector switch and 1 set of
3Nos.CT's of ratio 250/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 400Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
125A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----1 no.
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
63A MCB TPN 10Ka ---------6 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 342,218.00 342,218.00
NS 4.12.25 Lift Panel
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 160A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 35 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set

BOQ - EL(INT) 30
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Digital type ammeter (0-160Amp) with selector switch and 1 set of
3Nos.CT's of ratio 160/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----5 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 273,052.00 273,052.00
OAT
NS 4.12.26 Light & Power
Same as item No.4.12 above, but having the following switchgears:
Incomer
1 No. 100A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 25 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-100Amp) with selector switch and 1 set of
3Nos.CT's of ratio 100/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required .

BOQ - EL(INT) 31
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
BUS-BAR
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at
required interval complete for cross section, side supports and their
spacing etc. for withstanding fault level of 31 MVA for 1 sec

OUTGOING
32A SPN MCB 10Ka ---------16 nos.
40A SPN Electronic Energy Meter ---------14 no.
63A MCCB, TPN, 25Ka Thermal with o/l & s/c along with RYB LED
lamps with 2A MCB----3 nos.
63A MCB TPN 10Ka ---------4 nos.
32A Metal clad TPN socket with rotary switch------2 nos.
16A Metal clad SPN socket with rotary switch------2 nos.
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Each 1 481,452.00 481,452.00
NS 4.12.27 Nursary School
1 No. 200A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 50 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-200Amp) with selector switch and 1 set of
3Nos.CT's of ratio 200/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required . Each 1 183,659.00 183,659.00

BOQ - EL(INT) 32
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 4.12.28 Reception
1 No. 100A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 25 KA fully interlocked with Microprocessor based
O/L, S/C and EF protection
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
Digital type ammeter (0-100Amp) with selector switch and 1 set of
3Nos.CT's of ratio 200/5A, Class-1 accuracy and 15 VA burden - 1 set

3Nos. Phase indicating LED lamps with 2 Amp backup MCB as


required . Each 1 167,587.00 167,587.00
TOTAL OF MAIN DISTRIBUTION BOARD WORK CARRIED OVER
TO SUMMARY OF ELECTRICAL WORKS 16,697,267.00 27,304,634.00

BOQ - EL(INT) 33
CHAPTER - 5 : FITTINGS AND ACCESSORIES
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 5.1 Supplying of light fittings complete with all accessories with choke,
starter, capacitor, igniter etc. of the following type as required.(All fixtures
to be complete with lamps)
1 Supply of surface mounted light fixture suitable for 2 Nos 28 Watt FTL
(TL5) lamp as per Philips Cat No TMS 122M 2X28w EBE complete with
suitable Electronic Ballast, Lamp etc. as required. Each 1914 1,778.00 3,403,092.00
2 Supply of surface mounted light fixture suitable for 1 No 28 Watt FTL
(TL5) lamp as per Philips Cat No TMS 122M 1X28w EBE complete with
suitable Electronic Ballast, Lamp etc. as required. Each 4437 1,234.00 5,475,258.00
3 Supply of circular surface mounted LED downlight fixture suitable for 6
Watt LED as per Virex Eta 6w (5700K) complete with all as required.
Each 3124 1,529.00 4,776,596.00
4 Supply of recessed mounted circular downlight fixture suitable for 2 No
18 Watt CFL lamp as per Philips Cat no FBH 145 2X18w complete with
suitable Electronic Ballast, Lamp etc. as required. Each 42 2,210.00 92,820.00
5 Supply of recessed mounted circular downlight fixture suitable for 2 No
26 Watt CFL lamp as per Philips Cat no FBH 225 2X26w complete with
suitable Electronic Ballast, Lamp etc. as required. Each 22 2,806.00 61,732.00
6 Supply of circular recessed mounted LED downlight fixture suitable for 6
Watt LED as per Virex Epsilon Slim 6w (5700K) complete with all as
required. Each 117 1,889.00 221,013.00
7 Supply of circular recessed mounted LED downlight fixture suitable for
12 Watt LED as per Virex Epsilon Slim 12w (5700K) complete with all as
required. Each 12 1,889.00 22,668.00
8 Supply of circular recessed mounted LED downlight fixture suitable for
18 Watt LED as per Virex Epsilon Slim 18w (5700K) complete with all as
required. Each 16 2,339.00 37,424.00
9 Supply of wall mirror light fixture suitable for 1 Nos 14 Watt TL5 lamp as
per Philips Cat no TCH 207/14 complete with suitable Electronic Ballast,
Lamp etc. as required. Each 1032 555.00 572,760.00
10 Supply of wall mounted bracket light fixture suitable for 1 No 60w GLS
lamp as per Decon Cat no 05AH-01 complete with suitable Electronic
Ballast, Lamp etc. as required. Each 7908 802.00 6,342,216.00

BOQ - EL(INT) 34
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
11 Supply of Bulk Head light fixture suitable for 1 Nos 9 Watt CFL lamp as
per Philips Cat no FXC101 1X9w complete with suitable Electronic
Ballast, Lamp etc. as required. Each 48 1,172.00 56,256.00
12
Supply of recessed mounted square light fixture suitable for 4 Nos 14
Watt TL5 lamp as per Philips Cat no TBS 570 EBP OD DF WH 4X14w
complete with suitable Electronic Ballast, Lamp etc. as required. Each 78 6,949.00 542,022.00
13 Supply of circular recessed mounted LED downlight fixture suitable for
24 Watt LED as per Virex Epsilon Slim 24w (5700K) complete with all as
required. Each 54 3,007.00 162,378.00
14 Supply of External Street light fixture suitable for 1 Nos 36 Watt CFL
lamp as per Philips Cat no FGS120 1XPL 36w HF complete with suitable
Electronic Ballast, Lamp etc. as required. Each 197 2,077.00 409,169.00
15 Supply, fixing, testing and comissioning of Aviation light fixture
suitablre for Red LED light fixture yellow painted & die cast alluminium
alloy housing red coloured polycarbonate dome with complete
accessories as required (Make Bajaj Cat No BGAV 302 LED) Each 46 10,640.00 489,440.00
1.41 5.2 Installation, testing and commissioning of pre-wired, fluorescent
fitting/compact fluorescent fitting of all types, complete with all
accessories and tube etc. directly on ceiling/wall including connection
with 1.5 Sqmm FRLS PVC insulated, copper conductor, single core
cable and earthing etc. as required. Each 19047 91.00 1,733,277.00
1.44 5.3 Installation, testing and commissioning of ceiling fan, including wiring the
down rods of standard lenght(upto 30 cm) with 1.5 Sqmm FRLS PVC
insulated, copper conductor, single core cable etc. as required. Each 3283 95.00 311,885.00
1.50 5.4 Installation of exhaust fan in the existing opening, including making good
the damage, connection, testing, commissioning etc. as required.

1.50.1 5.4.1 Upto 450 mm sweep Each 2828 204.00 576,912.00


1.51 5.5 Extra for fixing of louvers/shutters complete with frame for a exhaust fans
of all sizes. Each 2828 90.00 254,520.00
NS 5.6 Supplying of approved make ceiling fan of double ball bearing of the
following sizes with all accessories suitable for operation on 230V single
phase, 50 Hz, AC supply complete as required.
5.6.1 1200mm sweep Each 3283 1,746.00 5,732,118.00

BOQ - EL(INT) 35
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 5.7 Supplying of 230V (nominal voltage) exhaust fan with its all accessories
complete as required of following size:
5.7.1 300mm sweep1400 RPM (Heavy duty) Each 2714 2,831.00 7,683,334.00
5.7.2 380mm sweep1400 RPM (Heavy duty) Each 114 3,389.00 386,346.00
NS 5.8 Supplying installation testing and commisssioning of approved make
HIGH SPEED wall fan of the following sizes with in-built regulator and its
all accessories suitable for operation on 230V single phase, 50 Hz, AC
supply complete as required.
5.8.1 450mm sweep Each 65 3,223.00 209,495.00
TOTAL OF FITTING & ACCESSORIES CARRIED OVER TO
SUMMARY OF ELECTRICAL WORKS 2,876,594.00 36,676,137.00

BOQ - EL(INT) 36
CHAPTER - 6 : EARTHING & LIGHTNING PROTECTION
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.4 6.1 Earthing wih GI Earth plate 600mmx600mmx6mm thick including
accessories and providinng masanory encliosure with cover plate having
locking arrangement and watering pipe etc. with charcoal or coke and salt
complete as rerquired. Each 462 4,490.00 2,074,380.00
5.11 6.2 Providing and fixing 25mmx 5mm G. I. strip in 40mm dia G. I. pipe from
earth electrode including connection with G.I.nut bolt spring, washer
excavation and re-filling as required. as required. Merer 4620 421.00 1,945,020.00
5.15 6.3 Providing and fixing 25mm x 5mm G. I. strip on surface or in recess for
connections etc. as required. Merer 23100 142.00 3,280,200.00
5.16 6.4 Providing and fixing 6 SWG dia GI wire on surface or in recess for loop
earthing as required. Meter 11650 35.00 407,750.00
6.1 6.5 Providing and fixing of lightning conductor finial, made of 25 mm dia 300
mm long, copper tube, having single prong at top, with 85 mm dia 3 mm
thick copper base plate including holes etc. complete as required. Each 48 764.00 36,672.00
6.4 6.6 Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial
or any other metallic object) by riveting / nut bolting/ sweating and
soldering etc as required. Each 158 72.00 11,376.00
6.5 6.7 Providing and fixing copper tape 20 mm X 3 mm thick on parapet or
surface of wall for lightning conductor complete as required.(For horizontal
run) Metre 7620 376.00 2,865,120.00
6.6 6.8 Providing and fixing copper tape 20 mm X 3 mm thick on parapet or
surface of wall for lightning conductor complete as required.(For vertical
run) Metre 3520 406.00 1,429,120.00
6.11 6.9 Providing and fixing testing joint, made of 20 mm X 3 mm thick copper
strip, 125 mm long, with 4 nos. of tinned brass bolts, nuts, chuck nuts and
spring washers etc. complete as required. Each 158 195.00 30,810.00
6.13 6.10 Providing and laying copper tape 32 mm X 6 mm from earth electrode
directly in ground as required. Metre 1580 1,122.00 1,772,760.00
TOTAL OF EARTHING & LIGHTNING PROTECTION WORK CARRIED
OVER TO SUMMARY OF ELECTRICAL WORKS 13,853,208.00

BOQ - EL(INT) 37
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
SUMMARY OF EXTERNAL ELECTRICAL WORKS - ( figures in Rs.)
Sl. No. Description of Items Schedule Items Non Schedule items
1 Transformer & Safety Equipments 63,959,453.00
2 Main LT Panel & Misc. Panels 81,214,260.00
3 LT Cables and End Terminations 6,087,888.00 36,715,080.00
4 DG Set and Miscellaneous 56,234,816.00
5 Earthing 3,001,680.00
6 Pole Lights 1,021,170.00 13,968,347.00

TOTAL OF EXTERNAL ELECTRICAL WORKS CARRIED OVER TO


GRAND SUMMARY OF COSTS 10,110,738.00 252,091,956.00

BOQ - EL(EXT) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - EXTERNAL ELECTRICAL WORKS
CHAPTER-1 : TRANSFORMER AND SAFETY EQUIPMENT
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO.
NS DSR NS DSR ITEMS NS ITEMS
TRANSFORMER (Dry type)
NS 1.1 Supplying, installation , testing and comissioning of cast resin dry type
1250KVA rating 11/0.433 KV , 3phase , 50 Hz DYN11 Vector group ,
copper wound ,class F insulation associated with winding temperature
indicator /controller actuated by means of resistance temperature
detector embedded in LV winding , indoor type transformer with
approximately 5% impendence,tapping for offload operation on HV
sidein steps of 2.5,5,7.5 having cable endboxes on HV side suitable for
3x240 Sq.mm XLPE cable of 11 KV grade and - Amp bus truncking
arrangement on LV side with neutral brought out seperately including
supplying and laying of copper conductor multi core control cable from
transformer to HT breaker for safety triping suitably mounted on MS
channel including supplying and routing of suitable MS chanel with all
accessories and confirming to IS 11171 ;1985 and as per specifications
attached complete in all aspect as required at site.

Transformer shall be housed in welded steel and bolted cover


construction suitable for IP23 type with door interlocking and provided
with folloing fittings
a) Off load type tap changing link on tap switch.
b) RTD temperature comtroller
c)Lifting lugs
d) bi-directional rollers
e) Rating diagram and terminal marking plate
f) Additional neutral seperately brought out on a bushing for earthing.
g) Earthing terminals 2nos. For body earthing
h) Necessary hardwares, clampas, lugs etc. for termination on HV/MV
etc.
i) WTI Digital type
Note:- Maximum allowable losses of transformer shall not exceed the
value given in general specification for electrical works part-IV substatin
clause 3.2.17 Each 14 2,779,937.00 38,919,118.00

BOQ - EL(EXT) 2
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO.
NS DSR NS DSR ITEMS NS ITEMS
NS 1.2 Supplying, installation , testing and comissioning of cast resin dry type
750KVA rating 11/0.433 KV , 3phase , 50 Hz DYN11 Vector group ,
copper wound ,class F insulation associated with winding temperature
indicator /controller actuated by means of resistance temperature
detector embedded in LV winding , indoor type transformer with
approximately 5% impendence,tapping for offload operation on HV
sidein steps of 2.5,5,7.5 having cable endboxes onHV side suitable for
3x240 Sq.mm XLPE cable of 11 KV grade and - Amp bus truncking
arrangement on LV side with neutral brought out seperately including
supplying and laying of copper conductor multi core control cable from
transformer to HT breaker for safety triping suitably mounted on MS
channel including supplying and routing of suitable MS chanel with all
accessories and confirming to IS 11171 ;1985 and as per specifications
attached complete in all aspect as required at site.

Transformer shall be housed in welded steel and bolted cover


construction suitable for IP 23 type with door interlocking and provided
with following fittings
a) Off load type tap changing link on tap switch.
b) RTD temperature comtroller
c)Lifting lugs
d) bi-directional rollers
e) Rating diagram and terminal marking plate
f) Additional neutral seperately brought out on a bushing for earthing.
g) Earthing terminals 2nos. For body earthing
h) Necessary hardwares, clampas, lugs etc. for termination on HV/MV
etc.
i) WTI Digital type
Note:- Maximum allowable losses of transformer shall not exceed the
value given in general specification for electrical works part-IV substatin
clause 3.2.17 Each 1 1,650,181.00 1,650,181.00

BOQ - EL(EXT) 3
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO.
NS DSR NS DSR ITEMS NS ITEMS
NS 1.3 Supplying of the following size of control cable of XLPE as per IS- 7098,
Part-II
1.3.1 c) 7cx1.5 sq. mm copper control ar. Cable Mtr. 600 354.00 212,400.00
1.3.2 c) 5cx2.5 sq. mm copper control ar. Cable Mtr. 600 394.00 236,400.00
NS 1.4 Supplying, installation , testing and comissioning of 2000 Amps 4 pole
pre fabricated Sandwitched bus trunking suiatble for 415 Volts 3Phase
4wire 50 Hz AC supply system (between transformers LT side and
incomer of LT panel side ) of Aluminium bus bar complete with bends,
expansion joints, fire barriers, copper flexible end connectiions at both
ends, adopter boxes, phasecrossover, earthing with 2 runs of copper
earth of size 25 mm x 5 mm strips etc including necessary supports etc
asper specifications attached as required . Note: the bus trunking
shall be measured along the length of enclosure . The copper
strips which will go inside the LT panel and end termination boxes
of transformers shall not be taken into measurement of bus
trunking quantity . (for 14 nos. transformers)
Mtr. 600 35,739.00 21,443,400.00
NS 1.5 Supplying, installation , testing and comissioning of 1600 Amps 4 pole
pre fabricated Sandwitched bus trunking suiatble for 415 Volts 3Phase
4wire 50 Hz AC supply system (between transformers LT side and
incomer of LT panel side ) of Aluminium bus bar complete with bends,
expansion joints, fire barriers, copper flexible end connectiions at both
ends, adopter boxes, phasecrossover, earthing with 2 runs of copper
earth of size 25 mm x 5 mm strips etc including necessary supports etc
asper specifications attached as required . Note: the bus trunking
shall be measured along the length of enclosure . The copper
strips which will go inside the LT panel and end termination boxes
of transformers shall not be taken into measurement of bus
trunking quantity . (for 1 no. transformer)
Mtr. 30 30,358.00 910,740.00

BOQ - EL(EXT) 4
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO.
NS DSR NS DSR ITEMS NS ITEMS
Misc. safety equipment
NS 1.6 Providing and fixing danger plates of mild steel atleast 2 mm thick and
vitreous enameled white on both sides and with inscriptions in single
red colour on front side as required .
NS 1.7 High voltage - size 250 mm x 200mm Each 48 433.00 20,784.00
NS 1.8 Medium voltage - size 200mm x 150mm Each 48 433.00 20,784.00
NS 1.9 Providing and fixing carbon dioxide(CO2) type fire extinguishers
confirming to IS 2878- 1976 and cylinders fully charged of foloowing
capacity
1.9.1 4.5 Kg Each 12 3,875.00 46,500.00
NS 1.10 Supply and fixing of foam fire extinguishers , portable type 9 ltr capacity
hanged on wall with bracket complete as required . Each 12 3,038.00 36,456.00
NS 1.11 Supply and fixing safety instruction chart in word duly framed with 5mm
thick glass as required ( Approx front area 1.20 sq.mtr) Each 6 815.00 4,890.00
NS 1.12 Providing of set of 4 Nos .9.5 Ltr capacity GI bucket painted in post
office red colour with prior coat of red oxide paint and written with white
paint (fire) andmounted on MS angel iron frame with bracket of
appropriate size and capacity including fillings and extras . Each 12 2,090.00 25,080.00
NS 1.13 First aid box as approved by St.John ambulance4 brigade /Indian red
cross confirming to IS 2217 - 1963 Each 12 560.00 6,720.00
NS 1.14 Providing of rubber mat 1 mtr wide and 12mm thick to with stand 15 KV
di electric strength as per IS 5424 -1969 Mtr. 18 2,600.00 46,800.00
NS 1.15 Providing of rubber mat 1 mtr wide and 6 mm thick to with stand 3.3 KV
di electric strength as per IS 5424 -1969 Mtr. 240 1,580.00 379,200.00
TOTAL OF HT SWITCH GEAR AND SAFETY EQUIPMENT WORK
CARRIED OVER TO SUMMARY OF EXTERNAL ELECTRICAL
WORKS - 63,959,453.00

BOQ - EL(EXT) 5
CHAPTER-2 : MAIN LT PANEL & MISC. PANELS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Main LT PANEL-1 ( Located in ESS 2,3 & 5)
NS 2.1 Supplying, installation , testing and comissioning of cubical type LT panel
suitable for 415Volts 3 phase 4wire 50 Hz AC supply system having front
surface area Sq.mtr (approx) fabricated in compartmentalized design
from CRCA sheet steel of 2 mm thick for frame work and covers , 3
mmthick for gland plates including cleaning and finishing complte with 7
tank process for power coating in approved shade having --Amp capacity
extensible type TPN aluminium alloy bus bars of high conductivity
DMC/SMC bus bars supports with short circuit withstand capacity of 31
MVA for 1 second, bottom base channel of MS section not less than
100mmx 50 mmx 5mm thick, fabrication shall be done in transportable
setctions, entire panel shall have a common copper earthbar of size25
mm x 5 mm at the rear with 2 No earth stud solid connections from main
bus bars to switchgears with required size of aluminium bus bars and
control wiring with 2.5 Sq. mm PVCinsulated copper conductor S/C cable
alleys cable gland and plates in bottom half ,including providing following
switchgars .
A (I) Incoming
3 No. 2000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type voltmeter 0-500V with selector
switch & backup 2A MCB for each ACB
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 2000/5 class1 accuracy and 15VA burden
for each ACB

BOQ - EL(EXT) 6
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
B. (ii) Bus Coupler
2 No. 2000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 50Ka fitted with interlocked
door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact,
confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
Independent manual spring clsing mechanism - 1 No.
Breaker ON/OFF indication light with 2A MCB , test terminal block set,
MCB , circuits as per standatd practice , auxiallry contact for positive
interlockingof the breakers as required. --1set
C. (iii) Bus Bars
4 Pole aluminium bus bars of minimum of 2400Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
D. (iv) Interlocking
Electrical through advance contacts in ACB (Incomer and bus coupler)
and mechanical (casstle key) interlocking should be provided to ensure
that only one supply is available at a time on each section of bus to
eleminate any possibility of accidentally approaching two supplies at one
bus section.
E Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)

BOQ - EL(EXT) 7
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
i 3No. 1200-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 1200/5 class1 accuracy and 15VA burden
for each ACB
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
ii 11 No. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 630/5 class1 accuracy and 15VA burden 7
nos
provision of space for4 nos electronic energy meter complete with ct & pt
as per requirement of BSES
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip
Shunt trip coilindication light. with 2A MCB , test terminal block set, MCB ,
220 Volt AC

BOQ - EL(EXT) 8
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
iii 10Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
provision of space for 10 nos electronic energy meter complete with ct &
pt as per requirement of BSES
iv 1No.160A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
provision of space for 1no electronic energy meter complete with ct & pt
as per requirement of BSES
v 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
provision of space for 2 nos electronic energy meter complete with ct & pt
as per requirement of BSES
vi 3 sets of suitable size CT in Y Phase for capacitor panel
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 3 9,397,336.00 28,192,008.00
Main LT PANEL-1 ( Located in ESS 4)
NS 2.2 Same as item No.2.1 above, but having the following switchgears:
A (I) Incoming
3 No. 2000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type voltmeter 0-500V with selector
switch & backup 2A MCB for each ACB
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 2000/5 class1 accuracy and 15VA burden
for each ACB

BOQ - EL(EXT) 9
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
B. (ii) Bus Coupler
2 No. 2000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 50Ka fitted with interlocked
door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact,
confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
Independent manual spring clsing mechanism - 1 No.
Breaker ON/OFF indication light with 2A MCB , test terminal block set,
MCB , circuits as per standatd practice , auxiallry contact for positive
interlockingof the breakers as required. --1set
C. (iii) Bus Bars
4 Pole aluminium bus bars of minimum of 2400Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
D. (iv) Interlocking
Electrical through advance contacts in ACB (Incomer and bus coupler)
and mechanical (casstle key) interlocking should be provided to ensure
that only one supply is available at a time on each section of bus to
eleminate any possibility of accidentslly approachinbg two supplies at
one bus section.
E Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)

BOQ - EL(EXT) 10
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
i 3 No. 1200-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 1200/5 class1 accuracy and 15VA burden
for each ACB
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
ii 6 Nos. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 630/5 class1 accuracy and 15VA burden 3
nos
provision of space for 3 nos electronic energy meter complete with CT &
PT as per requirement of BSES

BOQ - EL(EXT) 11
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
iii 5 Nos. 300A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
provision of space for 5 nos electronic energy meter complete with ct & pt
as per requirement of BSES
iv 3Nos. 250A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
provision of space for3 no electronic energy meter complete with ct & pt
as per requirement of BSES
v 6Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
provision of space for 6 nos electronic energy meter complete with ct & pt
as per requirement of BSES
vi 2 No. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
provision of space for 2nos electronic energy meter complete with ct & pt
as per requirement of BSES
vii 3 sets of suitable size CT in Y Phase for capacitor panel
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 7,759,209.00 7,759,209.00
Main LT PANEL-1 ( Located in ESS 6)
NS 2.3 Same as item No.2.1 above, but having the following switchgears:
A (I) Incoming
2 No. 2000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.

BOQ - EL(EXT) 12
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type voltmeter 0-500V with selector
switch & backup 2A MCB for each ACB
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 2000/5 class1 accuracy and 15VA burden
for each ACB
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
B. (ii) Bus Coupler
1 No. 2000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 50Ka fitted with interlocked
door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact,
confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
Independent manual spring clsing mechanism - 1 No.
Breaker ON/OFF indication light with 2A MCB , test terminal block set,
MCB , circuits as per standatd practice , auxiallry contact for positive
interlockingof the breakers as required. --1set
C. (iii) Bus Bars
4 Pole aluminium bus bars of minimum of 2400Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
D. (iv) Interlocking
Electrical through advance contacts in ACB (Incomer and bus coupler)
and mechanical (casstle key) interlocking should be provided to ensure
that only one supply is available at a time on each section of bus to
eleminate any possibility of accidentslly approachinbg two supplies at
one bus section.

BOQ - EL(EXT) 13
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
E Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i 3 Nos. 1200-Amps. four pole electrically operaterd horizontal drawout
type air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 1200/5 class1 accuracy and 15VA burden
for each ACB
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
ii 7Nos. 300A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
CT's of ratio 300/5A , class 1 accuracy -- (1Set of 3nos.) 4 nos
Digital type ammeter 0-300A with selector switch 4 nos
provision of space for 3nos electronic energy meter complete with ct & pt
as per requirement of BSES
iii 5Nos. 250A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
CT's of ratio 250/5A , class 1 accuracy -- (1Set of 3nos.) 1 no
Digital type ammeter 0-250A with selector switch 1 no
provision of space for 4nos electronic energy meter complete with ct & pt
as per requirement of BSES

BOQ - EL(EXT) 14
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
iv 7 Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection
provision of space for 7nos electronic energy meter complete with ct & pt
as per requirement of BSES
v 1No. 160A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
provision of space for 1 no electronic energy meter complete with ct & pt
as per requirement of BSES
vi 2 No. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
provision of space for 1 no electronic energy meter complete with ct & pt
as per requirement of BSES
vii 2 sets of suitable size CT in Y Phase for capacitor panel
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 4,405,482.00 4,405,482.00
Main LT PANEL-1 ( Located in ESS 1)
NS 2.4 Same as item No.2.1 above, but having the following switchgears:
A (I) Incoming
1 No. 1600-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type voltmeter 0-500V with selector
switch & backup 2A MCB for each ACB
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 1600/5 class1 accuracy and 15VA burden
for each acb

BOQ - EL(EXT) 15
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
B. (iii) Bus Bars
4 Pole aluminium bus bars of minimum of 1600Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i. 2 No. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
provision of space for 1 no electronic energy meter complete with ct & pt
as per requirement of BSES
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
ii. 3 Nos. 250A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
provision of space for 3 nos electronic energy meter complete with ct & pt
as per requirement of BSES

BOQ - EL(EXT) 16
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
iii 1No. 160A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
provision of space for 1 no electronic energy meter complete with ct & pt
as per requirement of BSES
iv 2 Nos. 100A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
provision of space for 2 nos electronic energy meter complete with ct & pt
as per requirement of BSES
v 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
provision of space for 2 nos electronic energy meter complete with ct & pt
as per requirement of BSES
vi 1 sets of suitable size CT in Y Phase for capacitor panel
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 1,710,363.00 1,710,363.00
NS 2.5 CAPACITOR PANEL-500 KVAR
Same as item No.2.1 above, but having the following switchgears:
1 No. 1000-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
CT's of ratio 1000/5A , class 1 accuracy --1 set (1Set of 3nos.)
Digital type ammeter 0-1000A with selector switch -- 1Set
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .

BOQ - EL(EXT) 17
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Shunt trip coil 220 Volt AC .
Suitable size power factor meter with necessaary accessories as
required.
BUSBARS
4 Pole aluminium bus bars of minimum of 1200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
OUTGOINGS
9 No. 150A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
2 No. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
1 No. 32A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
9 Nos.50 KVAR contactors, with ON - OFF push buttons
2 Nos.20 KVAR contactors, with ON - OFF push buttons
1 Nos 10 KVAR contactors, with ON - OFF push buttons
4 No. 63A, TPN isolator 10 KA
Automatic power factor correction relay with all accessories for sensing
of power factor of the system and initiating corrrective action( for 'cutting
in' or 'cutting out' of required number of capacitor banks) including step
controller, reversing mechanism, time delay and No Volt relay etc.

One red 'ON' and Green 'OFF' indicating lamps for each bank of
capacitors
One auto/manual selector switch for automatic or manual operation
3 phase 433V power factor improvement capacitor banks of the following
capacities;
9 set of 50 KVAR
2 set of 20 KVAR
1 set of 10 KVAR
Panel as described as per above specifications grouted, installed &
tested complete as required. Set 14 1,213,800.00 16,993,200.00

BOQ - EL(EXT) 18
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
NS 2.6 CAPACITOR PANEL-300 KVAR
Same as item No.2.1 above, but having the following switchgears:
1 No. 800-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
CT's of ratio 800/5A , class 1 accuracy --1 set (1Set of 3nos.)
Digital type ammeter 0-800A with selector switch -- 1Set
Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
Suitable size power factor meter with necessaary accessories as
required.
BUSBARS
4 Pole aluminium bus bars of minimum of 800Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
OUTGOINGS
5 No. 150A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
2 No. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
1 No. 32A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection

BOQ - EL(EXT) 19
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
5 Nos.50 KVAR contactors, with ON - OFF push buttons
2 Nos.20 KVAR contactors, with ON - OFF push buttons
1 Nos 10 KVAR contactors, with ON - OFF push buttons
4 No. 63A, TPN isolator 10 KA
Automatic power factor correction relay with all accessories for sensing
of power factor of the system and initiating corrrective action( for 'cutting
in' or 'cutting out' of required number of capacitor banks) including step
controller, reversing mechanism, time delay and No Volt relay etc.

One red 'ON' and Green 'OFF' indicating lamps for each bank of
capacitors
One auto/manual selector switch for automatic or manual operation
3 phase 433V power factor improvement capacitor banks of the following
capacities;
5 set of 50 KVAR
2 set of 20 KVAR
1 set of 10 KVAR
Panel as described as per above spedifications grouted, installed &
tested complete as required. Set 1 930,398.00 930,398.00
NS 2.7 MAIN DG ESSENTIAL LOAD PANEL (located in ESS 2)
Same as item No.2.1 above, but having the following switchgears:
(I) Incoming
3 No. 1200-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1200/5 ratio class 1.0 metering
,15 VA Burden

BOQ - EL(EXT) 20
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
1 no automatic battery charger with DC volt meter and DC ammeter
BUS COUPLER
2 No. 1200-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 50Ka fitted with interlocked
door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact,
confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1200/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC

BOQ - EL(EXT) 21
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
(ii) Interlocking
The Bus section and Incoming ACB's shall be electrically interlocked with
PLC's to achieve the sequence of operation as per requirement in case
of manual override mode.
(iii) Bus Bars
4 Pole aluminium bus bars of minimum of 1200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
PLC AUTO LOAD MANAGEMENT
PLC controlled load management system with auto starting, auto load
sharing with load management far both DG Sets so as to make optimum
utilisation of DG sets.
Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i 5 Nos. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 800/5 class1 accuracy and 15VA burden

3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as coil
Shunt trip per 220
standatd practice
Volt AC . , auxiallry contact for positive

BOQ - EL(EXT) 22
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
ii 6 Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
CT's of ratio 200/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-200A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 2Nos. 160A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
CT's of ratio 160/5A , class 1 accuracy --(1Set of 3nos.)
Digital type ammeter 0-160A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 1 No. 100A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 100/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-100A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iv 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 60/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-60A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 5,373,260.00 5,373,260.00
NS 2.8 MAIN DG ESSENTIAL LOAD PANEL (located in ESS 4)
Same as item No.2.1 above, but having the following switchgears:
(I) Incoming
3 No. 1200-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB

BOQ - EL(EXT) 23
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1200/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
1 no automatic battery charger with DC volt meter and DC ammeter
BUS COUPLER
2 Nos. 1200-Amps. four pole electrically operaterd horizontal drawout
type air circuit breaker of fault breaking capacity 50Ka fitted with
interlocked door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact,
confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1200/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .

BOQ - EL(EXT) 24
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
(ii) Interlocking
The Bus section and Incoming ACB's shall be electrically interlocked with
PLC's to achieve the sequence of operation as per requirement in case
of manual override mode.
(iii) Bus Bars
4 Pole aluminium bus bars of minimum of 1200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
PLC AUTO LOAD MANAGEMENT
PLC controlled load management system with auto starting, auto load
sharing with load management far both DG Sets so as to make optimum
utilisation of DG sets.
Outgoings (MCCB's whereverspecified shall have rotary handle,
shall have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i 3 No. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 630/5 class1 accuracy and 15VA burden

3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .

BOQ - EL(EXT) 25
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Shunt trip coil 220 Volt AC .
ii 3 Nos. 300A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
CT's of ratio 300/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-300A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
ii 4 Nos. 250A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
CT's of ratio 250/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-250A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 7 Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
CT's of ratio 200/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-200A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iv 1 No. 160A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
CT's of ratio 160/5A , class 1 accuracy --(1Set of 3nos.)
Digital type ammeter 0-160A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
v 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 60/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-60A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 4,982,644.00 4,982,644.00

BOQ - EL(EXT) 26
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
NS 2.9 MAIN DG ESSENTIAL LOAD PANEL (located in ESS 3 & 5)
Same as item No.2.1 above, but having the following switchgears:
(I) Incoming
2 Nos. 1200-Amps. four pole electrically operaterd horizontal drawout
type air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1200/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
1 no automatic battery charger with DC volt meter and DC ammeter
BUS COUPLER
1 No. 1200-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 50Ka fitted with interlocked
door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact,
confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .

BOQ - EL(EXT) 27
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
3 nos cast resin current transformer of 1200/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
(ii) Interlocking
The Bus section and Incoming ACB's shall be electrically interlocked with
PLC's to achieve the sequence of operation as per requirement in case
of manual override mode.
(iii) Bus Bars
4 Pole aluminium bus bars of minimum of 1200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
PLC AUTO LOAD MANAGEMENT
PLC controlled load management system with auto starting, auto load
sharing with load management for all DG Sets so as to make optimum
utilisation of DG sets.
Outgoings (MCCB's whereverspecified shall have rotary handle,
shall have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i 3 Nos. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.

BOQ - EL(EXT) 28
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 630/5 class1 accuracy and 15VA burden
for each ACB
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
ii 5 Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
CT's of ratio 200/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-200A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 2 Nos. 160A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection.
CT's of ratio 160/5A , class 1 accuracy --(1Set of 3nos.)
Digital type ammeter 0-160A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iv 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 60/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-60A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 2 3,537,026.00 7,074,052.00

BOQ - EL(EXT) 29
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
NS 2.10 MAIN DG ESSENTIAL LOAD PANEL (located in ESS 6)
Same as item No.2.1 above, but having the following switchgears:
(I) Incoming
1 No. 1600-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1600/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
1 no automatic battery charger with DC volt meter and DC ammeter
(iii) Bus Bars
4 Pole aluminium bus bars of minimum of 1600Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
PLC AUTO LOAD MANAGEMENT
PLC controlled load management system with auto starting, auto load
sharing with load management far both DG Sets so as to make optimum
utilisation of DG sets.

BOQ - EL(EXT) 30
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Outgoings (MCCB's whereverspecified shall have rotary handle,
shall have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i 2 Nos. 300A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
CT's of ratio 300/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-300A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
1 No. 250A, TPN MCCB having braking capacity 80 KA with
ii Microprocessor based over load and short circuit protection,
CT's of ratio 250/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-250A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 6 Nos. 200A, TPN MCCB having braking capacity 50 KA with Thermal
Magnetic based protection
CT's of ratio 200/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-200A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 60/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-60A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 1,415,100.00 1,415,100.00

BOQ - EL(EXT) 31
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
NS 2.11 MAIN DG ESSENTIAL LOAD PANEL (located in ESS 1)
Same as item No.2.1 above, but having the following switchgears:
(I) Incoming
1 No. 1600-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
3 nos cast resin current transformer of 1600/5 ratio class 1.0 metering
,15 VA Burden
Energy Analyzer Digital meter 415 V AC CT ratio/5 auxiliary 230 V AC 96
sq.mm(A,U,HZ,KW,KWH)
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
6 NO + 6 NC Contacts
Shunt trip coil 24 V DC and under voltage coil 230 V AC
Under Voltage Relay - 415 V AC
1 no automatic battery charger with DC volt meter and DC ammeter
(iii) Bus Bars
4 Pole aluminium bus bars of minimum of 1600Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
PLC AUTO LOAD MANAGEMENT
PLC controlled load management system with auto starting, auto load
sharing with load management far both DG Sets so as to make optimum
utilisation of DG sets.

BOQ - EL(EXT) 32
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Outgoings (MCCB's whereverspecified shall have rotary handle,
shall have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
i 3 Nos. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 70Ka manually operated
fitted with interlocked door, automatic safety shutters, mechanical
ON/OFF and service/test/isolated position indicator and frame earthing
contact ,confiming to IS 13947-2 1993 as amended upto date complete
with following accessories for each ACB/MCCB
Mechnical and electrical interlocking with bus coupler
Independent manual spring clsing mechanism - 1 No.
Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
Digital type 96 mm sq. flush pattern type ammeter with selector switch &
one set of 3 nos. CT's of ratio 630/5 class1 accuracy and 15VA burden

3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
Shunt trip coil 220 Volt AC .
ii 3 Nos 250A, TPN MCCB having braking capacity 80 KA with
Microprocessor based over load and short circuit protection,
CT's of ratio 250/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-250A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
iii 3 Nos. 125A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 160/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-200A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .

BOQ - EL(EXT) 33
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
iii 2 Nos. 63A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection
CT's of ratio 60/5A , class 1 accuracy -- (1Set of 3nos.)
Digital type ammeter 0-60A with selector switch
3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB as required .
Panel as described as per specification dully grouted, installed making
foundation with cement mortar, bricks etc dully tested and complet as
required Set 1 2,378,544.00 2,378,544.00
TOTAL OF MAIN LT PANEL AND MISC. PANEL WORKS CARRIED
OVER TO SUMMARY OF EXTERNAL ELECTRICAL WORKS 81,214,260.00

BOQ - EL(EXT) 34
CHAPTER-3 : LT CABLES AND TERMINATIONS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
7.1 3.1 Laying of one No. PVC insulated and PVC sheathed/XLPE power cable of
1.1 KV grade of following size direct in ground including excavation sand
cushioning, protective covering and refilling the trench etc. as required.

7.1.1 3.1.1 Upto 35 sq. mm Metre 2160 195.00 421,200.00


7.1.2 3.1.2 Above 35 sq. mm and upto 95 sq. mm Metre 3600 202.00 727,200.00
7.1.3 3.1.3 Above 95 sq. mm and upto 185 sq. mm Metre 1000 210.00 210,000.00
7.1.4 3.1.4 Above 185 sq. mm and upto 400 sq. mm Metre 7500 233.00 1,747,500.00
7.2 3.2 Laying of one number additional PVC insulated and PVC sheathed / XLPE
power cable of 1.1 KV grade of following size direct in ground in the same
trench in one tier horizontal formation including excavation, sand
cushioning, protective covering and refilling the trench etc as required.

7.2.1 3.2.1 Upto 35 sq. mm Metre 720 133.00 95,760.00


7.2.2 3.2.2 Above 35 sq. mm and upto 95 sq. mm Metre 800 141.00 112,800.00
7.2.3 3.2.3 Above 95 sq. mm and upto 185 sq. mm Metre 590 149.00 87,910.00
7.2.4 3.2.4 Above 185 sq. mm and upto 400 sq. mm Metre 1700 171.00 290,700.00
7.5 3.3 Laying of one number PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size in the existing RCC/ HUME/
METAL pipe/Tray as required.
7.5.1 3.3.1 Upto 35 sq. mm Metre 360 16.00 5,760.00
7.5.2 3.3.2 Above 35 sq. mm and upto 95 sq. mm Metre 300 25.00 7,500.00
7.5.3 3.3.3 Above 95 sq. mm and upto 185 sq. mm Metre 220 33.00 7,260.00
7.5.4 3.3.4 Above 185 sq. mm and upto 400 sq. mm Metre 1250 58.00 72,500.00
7.6 3.4 Laying of one number PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size in the existing masonry open duct
as required.
7.6.1 3.4.1 Upto 35 sq. mm Metre 360 12.00 4,320.00
7.6.2 3.4.2 Above 35 sq. mm and upto 95 sq. mm Metre 100 20.00 2,000.00
7.6.3 3.4.3 Above 95 sq. mm and upto 185 sq. mm Metre 220 27.00 5,940.00
7.6.4 3.4.4 Above 185 sq. mm and upto 400 sq. mm Metre 1250 50.00 62,500.00

BOQ - EL(EXT) 35
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
9.1 3.5 Supplying and making end termination with brass compression gland and
aluminium lugs for following size of PVC insulated and PVC sheathed /
XLPE aluminium conductor cable of 1.1 KV grade as required.

9.1.19 3.5.1 3.5x300 sq. mm.(70mm) Set 300 1,064.00 319,200.00


9.1.18 3.5.2 3.5x240 sq. mm.(62mm) Set 100 953.00 95,300.00
9.1.15 3.5.3 3.5x150 sq. mm.(50mm) Set 20 564.00 11,280.00
9.1.14 3.5.4 3.5x120 sq. mm.(45mm) Set 20 473.00 9,460.00
9.1.12 3.5.5 3.5x70 sq. mm.(35mm) Set 60 349.00 20,940.00
9.1.10 3.5.6 3.5x35 sq. mm.(28mm) Set 30 264.00 7,920.00
9.1.33 3.5.7 4x16 sq. mm.(28mm) Set 50 245.00 12,250.00
NS 3.6 Supply of the following LT - XLPE 1100 Volts grade Al. Conductor
armoured cables. complete as required and as per tender specifications.

3.6.1 3,1/2 Cx300 sq.mm Mtr 7500 2,654.00 19,905,000.00


3.6.2 3.5x240 sq. mm. Mtr 4200 2,165.00 9,093,000.00
3.6.3 3.5x150 sq. mm. Mtr 910 1,380.00 1,255,800.00
3.6.4 3,1/2 Cx120 sq.mm Mtr 1120 1,164.00 1,303,680.00
3.6.5 3,1/2 Cx70 sq.mm Mtr 4800 749.00 3,595,200.00
3.6.6 3,1/2 Cx35 sq.mm Mtr 600 429.00 257,400.00
3.6.7 4x16sq.mm Mtr 3000 374.00 1,122,000.00
3.6.8 5 core 1.5 sq. mm copper control cable Mtr 600 305.00 183,000.00
4.1 3.7 Supplying and installing following size of perforated pre-painted M.S. cable
trays with perforation not more than 17.5%, in convenient sections, joined
with connectors, suspended from the ceiling with M.S. suspenders
including bolts & nuts, painting suspenders etc as required.
4.1.2 3.7.1 150 mm width X 50 mm depth X 1.6 mm thickness Mtr. 300 520.00 156,000.00
4.1.8 3.7.2 300 mm width X 62.5 mm depth X 2.0 mm thickness Mtr. 150 878.00 131,700.00
4.1.14 3.7.3 600 mm width X 75 mm depth X 2.0 mm thickness Mtr. 150 1,493.00 223,950.00
4.1.15 3.7.4 750 mm width X 75 mm depth X 2.0 mm thickness Mtr. 100 1,939.00 193,900.00
4.1.16 3.7.5 900 mm width X 75 mm depth X 2.0 mm thickness Mtr. 100 2,038.00 203,800.00

BOQ - EL(EXT) 36
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
4.2 3.8 Supplying and installing following size of perforated pre-painted M.S. cable
trays bends with perforation not more than 17.5%,, joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc as required.
4.2.2 3.8.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 30 964.00 28,920.00
4.2.8 3.8.2 300 mm width X 62.5 mm depth X 2.0 mm thickness Each 15 1,636.00 24,540.00
4.2.14 3.8.3 600 mm width X 75 mm depth X 2.0 mm thickness Each 15 2,869.00 43,035.00
4.2.15 3.8.4 750 mm width X 75 mm depth X 2.0 mm thickness Each 10 3,341.00 33,410.00
4.2.16 3.8.5 900 mm width X 75 mm depth X 2.0 mm thickness Each 10 3,936.00 39,360.00
4.3 3.9 Supplying and installing following size of perforated pre-painted M.S. cable
trays reducers with perforation not more than 1.75%, joined with
connectors, suspended from the ceiling with M.S. suspenders including
bolts & nuts, painting suspenders etc as required.
4.3.2 3.9.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 15 1,349.00 20,235.00
4.3.8 3.9.2 300 mm width X 62.5 mm depth X 2.0 mm thickness Each 8 2,345.00 17,587.50
4.3.14 3.9.3 600 mm width X 75 mm depth X 2.0 mm thickness Each 8 4,127.00 30,952.50
4.3.15 3.9.4 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 5 4,822.00 24,110.00
4.3.16 3.9.5 900 mm width X 62.5 mm depth X 2.0 mm thickness Each 5 5,704.00 28,520.00
4.4 3.10 Suppying and installing following size of perforated pre-painted M.S. cable
trays Tee's with perfortion not more than 17.5% joined with connectors,
suspended from the ceiling with M.S. suspenders including bolts & nuts,
painting suspenders etc as required.
4.4.2 3.10.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 15 1,714.00 25,710.00
4.4.8 3.10.2 300 mm width X 62.5 mm depth X 2.0 mm thickness Each 8 3,056.00 22,920.00
4.4.14 3.10.3 600 mm width X 75 mm depth X 2.0 mm thickness Each 8 5,388.00 40,410.00
4.4.15 3.10.4 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 5 6,303.00 31,515.00
4.4.16 3.10.5 900 mm width X 62.5 mm depth X 2.0 mm thickness Each 5 7,471.00 37,355.00

BOQ - EL(EXT) 37
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
4.5 3.11 Supplying and installing following size of perforated pre-painted M.S. cable
trays cross members with perforation not more than 17.5% joined with
connectors, suspended from the ceiling with M.S. suspenders including
bolts & nuts, painting suspenders etc as required.
4.5.2 1.11.1 150 mm width X 50 mm depth X 1.6 mm thickness Each 6 767.00 4,602.00
4.5.8 1.11.2 300 mm width X 62.5 mm depth X 2.0 mm thickness Each 3 1,283.00 3,849.00
4.5.14 1.11.3 600 mm width X 75 mm depth X 2.0 mm thickness Each 3 2,237.00 6,711.00
4.5.15 1.11.4 750 mm width X 62.5 mm depth X 2.0 mm thickness Each 2 2,597.00 5,194.00
4.5.16 1.11.5 900 mm width X 62.5 mm depth X 2.0 mm thickness Each 2 3,051.00 6,102.00
14.14 3.12 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in
ground complete with RCC collars, jointing with cement mortar 1:2 (1
cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as
required.
14.14.1 3.12.1 100 mm dia Mtr. 100 337.00 33,700.00
14.14.2 3.12.2 150 mm dia Mtr. 200 384.00 76,800.00
14.14.3 3.12.3 250 mm dia Mtr. 500 455.00 227,500.00
14.14.4 3.12.4 300 mm dia Mtr. 50 566.00 28,300.00
TOTAL OF LT CABLES AND TERMINATIONS WORK CARRIED OVER
TO SUMMARY OF EXTERNAL ELECTRICAL WORKS 6,087,888.00 36,715,080.00

BOQ - EL(EXT) 38
CHAPTER-4 : DG SET AND MISCELLANEOUS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
DG SET FOR SUB-STATION
NS 4.1 Providing installation testing and comissioning of silent type disel
generating set along with having prime power rating of 600 KVA ,
415Volts at 1500 RPM , 0.8 lagging power factor at 415 Volts suitable for
50 hz ,3 phase system and for 0.85 load factor conforming to General
specifications for electrical works Part-VII (DG Sets)and consisting of the
following
a Disel engine
Disel engine 4 stroke water cool ,electric start of suitable BHP at 1500
RPM suitable for above output of altenator at 40 degree C , 50 % RH and
at 1000 mtr MSL and confirming to BS 5514 , BS 649,IS 10000, capable of
taking 10% overloading for 1 hour after 12 hours of continous operation
.The engine will be fitted complete with all the required accessories .

b Engine mounted instrument panel fitted with and having digital display for
following
(i) Start stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication
(vi) RPM indication
(vii) Overspeed indication
(viii) Low lube oil trip indication
(ix) Engine hours indication
(x) Electronic governer of Class A1
c. Alternator
Synchronous alternator rated at 600 KVA , 415Volts at 1500 RPM , 3
Phase ,50 Hz ,AC supply with 0.8 legging power factor at 40 degree C
,50% RH and at 1000 mtr MSL . The alternator shall be having SPDP
enclosure,brushless , continous duty ,self excited and self regulated
through AVR confirming to IS 4722 /BS 2613 suitable for tropical
conditions and with class F/H insulation
(d) Base frame and foundation

BOQ - EL(EXT) 39
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Both the engine and alternator shall be mounted on suitable base frame
made of MS Chanel with necessary reinforcement which shall be installed
on suitable cement concrete foundation and vibration isolation
arrangement as per recommendation of manufacturer .
(e) Fuel Tank
Daily service fuel tank of 990 ltrs capacity fabricated out of 3 mm thick MS
sheet complete with all standard accessories and fuel piping between fuel
tank and disel engine with MS class C pipes of suitable dia complete with
valves ,level indications and accessories as required as per specific
specifications .
(f) Exhaust Systems
Dry exhaust many fold with hospital exhaust silencer
(g) Starting systerm 24 V DC starting system comprising of starter motor
/voltage regulator and arrangement for initial excitation compared with
suitable numbers of batteries (360 AH capacity led acid type ) as required
as per specifications .
(h) Accoustic and weather proof enclosure with arrangenment for fresh air
intake for cooling of the engine and alternator , extraction , discharging hot
air into the atmosphere as per specifications .
(i) Supply and fixing exhaust gas piping of suitable dia welded black MS ,B
class pipe confirming to IS 3589 cut to required lengths and installed with
necessary bends , supports and clamps , anti vibration mountings
,insulation of exhaust systems with mineral wool /rockwool, 50 mm thick
wire mesh and aluminium cladding etc as required as per specifications
Set 10 4,553,719.00 45,537,190.00
NS 4.2 Providing installation testing and comissioning of silent type disel
generating set along with having prime power rating of 750 KVA ,
415Volts at 1500 RPM , 0.8 lagging power factor at 415 Volts suitable for
50 hz ,3 phase system and for 0.85 load factor conforming to General
specifications for electrical works Part-VII (DG Sets)and consisting of the
following
a Disel engine

BOQ - EL(EXT) 40
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Disel engine 4 stroke water cool ,electric start of suitable BHP at 1500
RPM suitable for above output of altenator at 40 degree C , 50 % RH and
at 1000 mtr MSL and confirming to BS 5514 , BS 649,IS 10000, capable of
taking 10% overloading for 1 hour after 12 hours of continous operation
.The engine will be fitted complete with all the required accessories .

b Engine mounted instrument panel fitted with and having digital display for
following
(i) Start stop switch with key
(ii) Water temperature indication
(iii) Lubrication oil pressure indication
(iv) Lubrication oil temperature indication
(v) Battery charging indication
(vi) RPM indication
(vii) Overspeed indication
(viii) Low lube oil trip indication
(ix) Engine hours indication
(x) Electronic governer of Class A1
c. Alternator
Synchronous alternator rated at 750 KVA , 415Volts at 1500 RPM , 3
Phase ,50 Hz ,AC supply with 0.8 legging power factor at 40 degree C
,50% RH and at 1000 mtr MSL . The alternator shall be having SPDP
enclosure,brushless , continous duty ,self excited and self regulated
through AVR confirming to IS 4722 /BS 2613 suitable for tropical
conditions and with class F/H insulation
(d) Base frame and foundation
Both the engine andd alternator shall be mounted on suitable base frame
made of MS Chanel with necessary reinforcement which shall be installed
on suitable cement concrete foundation and vibration isolation
arrangement as per recommendation of manufacturer .
(e) Fuel Tank

BOQ - EL(EXT) 41
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
Daily service fuel tank of 990 ltrs capacity fabricated out of 3 mm thick MS
sheet complete with all standard accessories and fuel piping between fuel
tank and disel engine with MS class C pipes of suitable dia complete with
valves ,level indications and accessories as required as per specific
specifications .
(f) Exhaust Systems
Dry exhaust many fold with hospital exhaust silencer
(g) Starting systerm 24 V DC starting system comprising of starter motor
/voltage regulator and arrangement for initial excitation compaed with
suitable numbers of batteries (360 AH capacity led acid type ) as required
as per specifications .
(h) Accoustic and weather proof enclosure with arrangenment for fresh air
intake for cooling of the engine and alternator , extraction , discharging hot
air into the atmosphere as per specifications .
(i) Supply and fixing exhaust gas piping of suitable dia welded black MS ,B
class pipe confirming to IS 3589 cut to required lengths and installed with
necessary bends , supports and clamps , anti vibration mountings
,insulation of exhaust systems with mineral wool /rockwool, 50 mm thick
wire mesh and aluminium cladding etc as required as per specifications
Set 2 5,348,813.00 10,697,626.00
TOTAL OF DG SET AND MISCELLANEOUS WORK CARRIED OVER
TO SUMMARY OF ADDITIONAL ELECTRICAL WORKS 56,234,816.00

BOQ - EL(EXT) 42
CHAPTER-5 : EARTRHING
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT Qty
NO. DRS NS DSR ITEMS NS ITEMS
NS
5.2 5.1 Earthing with G. I. earth pipe 4.5 mtr. long, 40 mm dia including
accessories, and providing masonary enclosure with cover plate having
locking arrangement and watering pipe etc. with charcoal or coke and salt
as required. Set 10 3,926.00 39,260.00
5.4 5.2 Earthing wih GI Earth plate 600mmx600mmx6mm thick including
accessories and providinng masanory encliosure with cover plate having
locking arrangement and watering pipe etc. with charcoal or coke and salt
complete as rerquired. Set 90 4,490.00 404,100.00
5.6 5.3 Earthing wih Copper Earth plate 600mmx600mmx3mm thick including
accessories and providinng masanory encliosure with cover plate having
locking arrangement and watering pipe etc. (but without charcoal or coke
and salt) complete as rerquired. Each 60 9,292.00 557,520.00
5.10 5.4 Providing and fixing 25mmx 5mm copper strip in 40mm dia G. I. pipe from
earth electrode including connection with brass.nut bolt spring, washer
excavation and re-filling as required. as required. Mtr. 600 1,082.00 649,200.00
5.11 5.5 Providing and fixing 25mmx 5mm G. I. strip in 40mm dia G. I. pipe from
earth electrode, as required. Mtr. 900 421.00 378,900.00
5.12 5.6 Providing and laying earth connection from earth electrode with 6 SWG dia
G.I. Wire in 15 mm dia G.I. pipe from earth electrode including connection
with G.I. thimble excavation and re-filling as required. Mtr. 100 151.00 15,100.00
5.14 5.7 Providing and fixing 25mm x 5mm copper strip on surface or in recess for
connections etc. as required. Mtr. 600 856.00 513,600.00
5.15 5.8 Providing and fixing 25mm x 5mm G. I. strip on surface or in recess for
connections etc. as required. Mtr. 2500 142.00 355,000.00
5.18 5.9 Providing and fixing 6 SWG dia GI wire on surface or in recess for loop
earthing as required. Mtr. 2000 23.00 46,000.00
5.19 5.10 Providing and fixing 4 mm dia Copper wire on surface or in recess for loop
earthing as required. Mtr. 500 86.00 43,000.00
TOTAL OF EARTHING WORK CARRIED OVER TO SUMMARY OF
EXTERNAL ELECTRICAL WORKS 3,001,680.00

BOQ - EL(EXT) 43
CHAPTER - 6 : POLE LIGHTS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
NS 6.1 Fabrication, Supply, installation, testing and commissioning of street light
feeder pillar (IP-56) suitable for operation on 415V, 50 Hz, 3 phase, 4 wire,
AC system , fabricated with 14 SWG thick CRCA sheet with 200Amp TPN
aluminium bus bar, connections, inter-connections, internal wiring, gland
plates, bottom entry of incoming & outgoing cables as per site
requirement, powder coating, earthing etc. complete with foundation as
required and comprising the following switchgear components and
accessories:
2Nos 63A, TPN, MCCB, having breaking capacity 25KA with Thermal
Magnetic based protection as incomer.
3Nos. 32A TP Contactor (230V coil)
TPN aluminium bus bars of minimum of 200Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc. for
withstanding fault level of 31 MVA for 1 sec
1 No. selector switch to select auto/manual operation
1 No. L&T timer TSQ-ST (daily dial-1x24hr)
6 Nos 10A DP MCB
1 set of push buttons for manual ON/OFF
A set of copper busbars,all connections, wiring as required for automatic
ON - OFF operation. Set 6 123,343.00 740,058.00
NS 6.2 Supplying and fixing of brick light as per Bajaj Cat. No.- BEOPL 118 CFL
1x18W CFL with 18w CFL lamp or of similar specifications of other
approved makes Each 30 2,514.00 75,420.00

BOQ - EL(EXT) 44
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
NS 6.3 Supply and erection of 60mm dia GI pole 4.0 mtr. Overall length with
reducer at top complete with 250x250x10mm thick base plate in cement
con;crete 1:3:6 (1 cement, 3 coarse, 6graded stone aggregate 40mm.
Nominal size) including excavation and refilling including painting etc as
required. Supply and fixing dust and weather proof gasketted
200x150x100 mm nominal size 2 mm thick MS sheet steel cable looping
box on the existing GI pole with MS clamp made out of 25x3 mm thick GI
flat iron with suitable GI nuts and bolts complete with hinged cover and
locking screw and washers, earthing studs including supply and fixing of 1
no. 6A SP MCB, 8 Nos.terminal block( for loop-in loop-out) suitable for
upto 4x16 sq.mm PVC cable fixed on 6mm thick hylam sheet complete in
all respects including earthing etc. Each 8 6,606.00 52,848.00
NS 6.4 Supplying and fixing 4nos.20mm dia x700mm long GI foundation bolt (EN8
grade) with nuts , washer including 2nos. template of 3 mm thick size. 320
x 320 mm with 4nos 28 mm dia holes to match with PCD of pole base
plate as required . Each 8 1,699.00 13,592.00
NS 6.5 Fabrication, desigining , supplying and fixing of galvanised armed bracket
50mm dia 1000mm long single overhanged with tightening bolt etc asper
approved by by engineer incharge.(For sport area) Each 8 2,076.00 16,608.00
NS 6.6 Supplying, installation testing and commissiong of following capacity
outdoor luminaire with specified lamp, control gears such as balast
condensor and ignitor etc on the exisisting street light pole as required .
Flood light luminaire 400w integral with pressure die cast aluminium
housung IP65 similar to Philips Cat. No. MWF331 1XHPITP400A WITH
1XHPIT400W lamp for( flood light) Each 30 10,143.00 304,290.00
NS 6.7 Supply, fixing, testing and comissioning of single arm 4M Pole with
Homdec Pole including foundation bolt Cat No HL-2840 & pole Bracket cat
no HL-PBKT-103-1 including light fixture as per Homdec Cat No HL-2304
with 28W LED or similar specifications of other approved makes. Each 42 32,490.00 1,364,580.00
NS 6.8 Supply, fixing, testing and comissioning of double arm 4M Pole with
Homdec Pole includin foundation bolt Cat No HL-2840 & pole Bracket cat
no HL-PBKT-103-2 including light fixture as per Homdec Cat No HL-2304
with 2x28W LED or similar specifications of other approved makes.
Each 18 50,875.00 915,750.00

BOQ - EL(EXT) 45
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
NS 6.9 Supply, fixing, testing and comissioning of single arm 6M Pole with
Homdec Pole includin foundation bolt Cat No HL-2840 & pole Bracket cat
no HL-PBKT-103-1 including light fixture as per Homdec Cat No HL-2304
with 36W LED or similar specifications of other approved makes. Each 65 38,692.00 2,514,980.00
NS 6.10 Supply, fixing, testing and comissioning of double arm 6M Pole with
Homdec Pole includin foundation bolt Cat No HL-2840 & pole Bracket cat
no HL-PBKT-103-2 including light fixture as per Homdec Cat No HL-2304
with 2x36W LED or similar specifications of other approved makes.
Each 40 60,236.00 2,409,440.00
NS 6.11 Supply, fixing, testing and comissioning of single arm 9M Pole with
Homdec Pole includin foundation bolt Cat No HL-2840 & pole Bracket cat
no HL-PBKT-103-1 including light fixture as per Homdec Cat No HL-2304
with 100W LED or similar specifications of other approved makes. Each 23 65,752.00 1,512,296.00
NS 6.12 Supply erection testing and commissioning of stand alone Solar LED
street light with IP 65 LED fixture having a system wattage of 21 watt with
appprx. 1864 lumen system output , 100Wp high efficiency crystalline
solar panel certified IEC 61215 and 100Ah tubular lead acid maintenance
free battery. Each LED lumen efficiency shall be more than 120
lumens/watt. The solar charge controller shall be of microprocessor based
MPPT make with 96% efficiency & enclosed in IP65 box.The charge
controller shall provide all safety protections and temperature compansed
charging for of the battery. The battery shall be housed in a box made from
galvanised steel and powder coated . The solar sysem shall be mounted
on a 5mtr. above ground MS galvanised pole (total height 6.0 metre)
complete with cement concrete foundations.
Each 45 59,613.00 2,682,585.00
14.14 6.13 Providing, laying and fixing following dia RCC pipe NP2 class (light duty) in
ground complete with RCC collars, jointing with cement mortar 1:2 (1
cement : 2 fine sand) including trenching (75 cm deep) and refilling etc as
required.
14.14.1 6.13.1 100 mm dia Meter 300 337.00 101,100.00

BOQ - EL(EXT) 46
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO.
NS DSR NS DSR ITEMS NS ITEMS
9.1 6.14 Supplying and making end termination with brass compression gland and
aluminium lugs for following size of PVC insulated and PVC sheathed /
XLPE aluminium conductor cable of 1.1 KV grade as required.

9.1.33 6.14.1 4x16sq.mm (28mm) Each 12 245.00 2,940.00


9.1.7 6.14.2 3x10sq.mm (22mm) Each 360 161.00 57,960.00
NS 6.15 Supply of the following LT - XLPE 1100 Volts grade Al. Conductor
armoured cables. complete as required and as per tender specifications.

6.15.1 4x16sq.mm Mtr 300 305.00 91,500.00


6.15.2 3x10sq.mm Mtr 5400 236.00 1,274,400.00
7.3 6.16 Laying of one number PVC insulated and PVC sheathed / XLPE power
cable of 1.1 KV grade of following size direct in ground including
excavation and refilling the trench etc as required, but excluding sand
cushioning and protective covering.
7.3.1 6.16.1 Upto 35 sq. mm Meter 5700 87.00 495,900.00
5.2 6.17 Earthing with G.I. earth pipe 4.5 metre long 40 mm dia including
accessories, and providing masonry enclosure with cover plate having
locking arrangement and watering pipe etc. with charcoal/ coke and salt
as required. Set 45 3,926.00 176,670.00
5.11 6.18 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from
earth electrode including connection with G.I. nut, bolt, spring, washer
excavation and re-filling etc. as required. Meter 300 421.00 126,300.00
5.15 6.19 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for
connections etc. as required. Meter 400 142.00 56,800.00
5.16 6.20 Providing and fixing 6 SWG dia GI wire on surface or in recess for loop
earthing as required. Meter 100 35.00 3,500.00
TOTAL OF POLE LIGHT WORK CARRIED OVER TO SUMMARY OF
EXTERNAL ELECTRICAL WORKS 1,021,170.00 13,968,347.00

BOQ - EL(EXT) 47
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
SUMMARY OF FIRE PROTECTION WORKS (figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 PUMPS & ACCESSORIES 3,385,123.00
2 ELECTRICAL WORKS 2,834,641.00
3 PIPING & ACCESSORIES (HYDRANT SYSTEM) 37,891,142.00
4 FIRE EXTINGUISHERS 6,269,788.00
5 FIRE ALARM WORKS 24,785,151.00
TOTAL OF WORKS CARRIED OVER TO GRAND
SUMMARY OF COSTS 75,165,845.00

BOQ - (FF) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - FIRE FIGHTING WORKS
CHAPTER - 1 : PUMPS & ACCESSORIES
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 1.1 Supplying, installing, testing, & commissioning of electric driven Main Fire
pump set consisting of the following.
Horizontally mounted centrifugal end suction type pump complete for
delivery of 2280 ltrs./minute against a total head of 70 metres with bronze
impeller complete with Mechanical Seal.
Squirrel cage induction motor suitable for 415 V, 50Hz, AC supply of 60
HP rating for the above pump with synchronous speed of 2900 RPM
T.E.F.C type such as confirming to IP:55 and flexible coupling and
coupling guard with the pump. Motor shall accept +/- 10% variation in
voltage and +/- 3 % variation in frequency. Motor shall accept +/- 10%
variation in voltage and +/- 3 % variation in frequency.
Common bed plate of fabricated mild steel channel or cast iron type.
Suitable cement concrete pump foundation of 1:2:4 ratio ( 1 cement : 2
fine aggregate : 4 coarse aggregate ) with MS bolts, washers as required.
Set 2 368,367.00 736,734.00
NS 1.2 Supplying, installing, testing, & commissioning of Engine driven Standby
pump set consisting of the following.
Horizontally mounted centrifugal end suction type pump complete for
delivery of 2280 ltrs./minute against a total head of 70 metres with bronze
impeller complete with Mechanical Seal.
Heat Exchanger cooled Diesel Engine developing 75 BHP for the above
pump, flexible coupling and coupling guard with the Pump, common bed
plate
Rate for mounting
shall of the Engine
also include andPipe
Exhaust Pump,of RCC Foundation
required length and
and size to
discharge exhaust gases externally, with muffler, day
Common bed plate of fabricated mild steel channel or cast oil tank oftype.
iron 200 lts
Suitable cement concrete pump foundation of 1:2:4 ratio ( 1 cement : 2
fine aggregate : 4 coarse aggregate ) with MS bolts, washers as required.
Set 1 601,282.00 601,282.00

BOQ - (FF) 2
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 1.3 Supplying, Installation, Testing, & Commissioning of electric driven
Pressurisation Pump suitable for automatic operation consisting of the
following complete in all respects as required.
Horizontally mounted centrifugal end suction type pump complete for
delivery of 180 ltrs./minute against a total head of 70 metres with bronze
impeller complete with Mechanical Seal.
Suitable HP Squirrel cage induction motor, TEFC, synchronous speed
2900 RPM, suitable for operation on 415 V, 3 phase 50 Hz, AC with IP 55
protection for enclosure, horizontal foot mounted type with class F
insulation, conforming to IS:326.
Suitable reinforced cement concrete pump foundation duly plastered with
anti vibration pads. Set 1 114,279.00 114,279.00
NS 1.4 Supplying, Installation, Testing, & Commissioning of electric driven
Terrace Pump suitable for automatic operation & consisting of the
following complete in all respects as required.
Suitable HP Squirrel cage induction motor, TEFC, synchronous speed
2900 RPM, suitable for operation on 415 V, 3 phase 50 Hz, AC with IP 55
protection for enclosure, horizontal foot mounted type with class F
insulation, conforming to IS:326.
Suitable HP Squirrel cage induction motor, TEFC, synchronous speed
2900 RPM, suitable for operation on 415 V, 3 phase 50 Hz, AC with IP 55
protection for enclosure, horizontal foot mounted type with class F
insulation, conforming to IS:326.
Suitable reinforced cement concrete pump foundation duly plastered with
anti vibration pads. Set 20 81,812.00 1,636,240.00
NS 1.5 Supplying, testing, installation & commissioning of pressure switches for
Fire Pumps Set 24 4,462.00 107,088.00
NS 1.6 Supplying, testing, installation & commissioning of pressure guages with
mini ball valve and siphon tube. Set 50 3,790.00 189,500.00
TOTAL OF PUMPS & ACCESSORIES WORK CARRIED OVER TO
SUMMARY OF FIRE FIGHTING & FIRE DETECTION WORKS 3,385,123.00

BOQ - (FF) 3
CHAPTER - 2 : ELECTRICAL WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 2.1 Fabricating, supplying, erection, testing and commissioning of totally
enclosed cubicle type free standing, floor mounted, compartmentalised,
sectionalised, dust, damp and vermin proof, with suitable natural
ventilation arrangement, front and rear accessible, lockable power cum
control panel, fabricated from 1.6 / 2 mm thick MS sheet ( to give IP 54
protection ) spray painted with approved colour shade, heavy 4 strip
sleeved aluminium / aluminium alloy bus bar, bus bar supports,
interconnecting from busbars to outgoing switches / MCCBs including
earthing the board suitable to accomodate the following including
numbering etc., as required:
Cubical panel as described above with following:
Incoming section : 400 Amps MCCB, 3 pole with neutral link 25 KA, 415
V+ 1 No., Digital Voltmeter with phase selection push button = 1 No., 3
Phase indication lamps, instrument fuses and switches, 500 Amp Al. Bus
bar
Outgoing Section:
250 A TP MCCB with neutral link 25 KA 415 V = 1 Nos.
On / Off indicating Lamp = 1 set.
Suitable fully automatic star delta starter for motor complete with single
phase preventer relay = 1 no.
Ammeter with Phase selection = 1 No.
Carried Over
CT Ratio 250 : 5 = 3 nos
63 A TP MCCB with neutral link 10 KA 415 V = 2 Nos.
On / Off indicating Lamp = 2 sets.
Suitable fully automatic star delta starter for motor = 2 nos.
Digital Ammeter with Phase selection = 2 Nos.
Cts ratio 50:5 = 6 Nos
1 set of automatic trip battery unit of suitable rating operating at 24 V DC,
complete with necessary boost / trickle charging arrangements including
providing and fixing necessary control system component such as timer,
relays & contactors inclusive of DC meter etc as required for engine
driven pump. Set 1 313,621.00 313,621.00

BOQ - (FF) 4
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 2.2 Fabricating, supplying, erection, testing and commissioning of totally
enclosed cubicle type free standing, floor mounted, compartmentalised,
sectionalised, dust, damp and vermin proof, with suitable natural
ventilation arrangement, front and rear accessible, lockable power cum
control panel, fabricated from 1.6 / 2 mm thick MS sheet ( to give IP 54
protection ) spray painted with approved colour shade, heavy 4 strip
sleeved aluminium / aluminium alloy bus bar, bus bar supports,
interconnecting from busbars to outgoing switches / MCCBs including
earthing the board suitable to accomodate the following including
numbering etc., as required: For Terrace Pump

Cubical panel as described above with following:


Incoming section : 100 Amps MCCB, 3 pole with neutral link 25 KA, 415
V+ 1 No., Digital Voltmeter with phase selection push button = 1 No., 3
Phase indication lamps, instrument fuses and switches, 100 Amp Al. Bus
bar
Outgoing Section 900 LPM Pump:
63 A TP MCCB with neutral link 250 KA 415 V = 1 No.
On / Off indicating Lamp = 1 set.
Suitable fully automatic star delta starter for motor complete with single
phase preventer relay = 1 no.
Ammeter with Phase selection = 1 No.
CT Ratio 250 : 5 = 3 nos
Outgoing Section 180 LPM:
25 A TP MCCB with neutral link 250 KA 415 V = 1 No.
On / Off indicating Lamp = 1 set.
Suitable fully automatic star delta starter for motor complete with single
phase preventer relay = 1 no.
Ammeter with Phase selection = 1 No.
CT Ratio 250 : 5 = 3 nos Set 20 91,611.00 1,832,220.00
NS 2.3 Supplying and fixing of one number PVC insulated and PVC sheated
aluminium conductor cable of 1.1 KV grade of size on surface as required
complete with end terminations of aluminium lugs and brass compression
glands.
2.3.1 95 x 4 core Mtr. 100 928.00 92,800.00
2.3.2 16 x 4 core Mtr. 400 387.00 154,800.00

BOQ - (FF) 5
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 2.4 Providing and laying 2 x 1.5 sq mm PVC insulated and sheathed copper
conductor armoured cable for connecting between Pressure Switches to
Panel including fixing to walls and columns by GI saddles and steel
screws, and fixing by PVC ties and straps and end terminations with
aluminium lugs and brass compression glands complete as required. All
supports shall be at least 0.5 M intervals. Thimbles and ferrules shall be
provided at joints and terminations. Mtr. 290 122.00 35,380.00
NS 2.5 Fabricating and installing following sizes of perforated MS cable trays
including horizontal and vertical bends, reducers, tess, cross members
and other accessories as required and duly suspended from the ceiling
with MS suspenders and including painting etc. as required.

2.5.1 225 mm width x 50 mm depth x 1.6 mm thickness Mtr. 200 300.00 60,000.00
NS 2.6 Providing, installing, testing and commissioning of 4 station Pump
Repeater Panel with pilot lamp per pump and common piezo and accept
switches. Each 20 17,291.00 345,820.00
TOTAL OF ELECTRICALS WORK CARRIED OVER TO SUMMARY OF
FIRE FIGHTING & FIRE DETECTION WORKS 2,834,641.00

BOQ - (FF) 6
CHAPTER - 3 : PIPING AND ACCESSORIES (HYDRANT SYSTEM)
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 3.1 Providing, laying, testing and commissioning of MS pipe conforming to
IS:3589 including fittings like elbows, tees, flanges, tapers, nuts, bolts,
gaskets etc., fixing the pipe on pipe on the wall / ceiling with suitable
clamps and painting with two or more coats of synthetic paint of required
shade complete as required.
3.1.1 250 mm dia ( 6 mm wall thickness ) 20 2,516.00 50,320.00
3.1.2 200 mm dia ( 6 mm wall thickness ) 20 2,024.00 40,480.00
NS 3.2 Providing, laying, testing and commissioning of Class "C" heavy duty MS
pipe conforming to IS:1239 / 3589 including fittings like elbows, tees,
flanges, tapers, nuts, bolts, gaskets etc., fixing the pipe on pipe on the wall
/ ceiling with suitable clamps and painting with two or more coats of
synthetic paint of required shade complete as required.

3.2.1 150 mm dia Mtr. 4945 1,371.00 6,779,595.00


3.2.2 100 mm dia Mtr. 520 942.00 489,840.00
3.2.3 80 mm dia Mtr. 610 708.00 431,880.00
3.2.4 65 mm dia Mtr. 120 606.00 72,720.00
3.2.5 50 mm dia Mtr. 100 487.00 48,700.00
3.2.6 32 mm dia Mtr. 900 335.00 301,500.00
3.2.7 25 mm dia Mtr. 1000 284.00 284,000.00
NS 3.3 Providing, laying, testing and commissioning in trenches DOUBLE
FLANGED ductile iron pipes class K 9 PN 16 of following sizes
conforming to IS 8329-2000 (as amended up to date) and ISI marked with
FLANGED joints including the cost of standard specials such as tees,
bends, collars, trappers, caps, flanged tail pieces, blank flanges, etc
(heavy class) conforming to IS 9523-1980 (as amended up to date) and
ISI marked as required including flanged joint wherever required as per
manufacturers specification with neoprene gasket conforming to IS-1568,
MS nuts, bolts & washers and necessary excavation for trenches in any
type of soil, providing cement concrete blocks as supports, back filling &
disposal of surplus excavated soil. Each pipe shall have a concrete
pedestal of size 300 x 300 x 300 at each flange joint ( om either side of
joint ) and pipe shall be clamped to the pedestal through a collar piece.
Electrosteel / Lanco make

BOQ - (FF) 7
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 3.3.1 150 mm dia Mtr. 1200 4,304.00 5,164,800.00
NS 3.3.2 100 mm dia Mtr. 400 3,302.00 1,320,800.00
NS 3.3 Supplying and fixing single headed internal hydrant valve with
instantaneous stainless steel couplings of 63 mm dia with cast iron wheel,
ISI marked conforming to IS:5290 ( Type A ) with blank cap and chain as
required. Each 324 8,791.00 2,848,284.00
NS 3.4 Supplying and fixing 63 mm dia, 15 M long synthetic hose pipe with 63
mm dia male and female stainless steel couplings duly binded with GI
wire, rivets etc conforming to IS:636 ( Type B ) as required. Each 648 9,538.00 6,180,624.00
NS 3.5 Supplying and fixing 63 mm dia stainless steel branch pipe with 20 mm (
nominal internal diameter ) size gun metal conforming to IS:903, suitable
for instantaneous connection to interconnect hose pipe coupling as
required. Each 324 2,648.00 857,952.00
NS 3.6 Supplying and fixing First Aid Hose Reel with MS construction spray
painted in Post Office Red, conforming to IS:884 with upto date
amendments, complete with the following as required :
36 m long 25 mm ( nominal internal ) dia water hose Thermoplastic (
Textile reinforced ) Type 2 as per IS:12585.
25 mm ( nominal internal ) dia gun metal globe valve and nozzle.
Drum and brackets for fixing the equipments on wall.
Connections from Riser with 25 mm dia stop valve ( gun metal ) & MS
pipe. Set 242 14,000.00 3,388,000.00
NS 3.7 Supplying and fixing of hose cabinet of size 750 mm x 600 mm x 500 mm
made of 3 mm thick powder coated aluminium sheet with 5 mm thick
glazed glass doors including necessary locking arrangement suitable to
accommodate external hydrants, 2 nos 15 m long hose pipe, 1 no branch
pipe with 4 nos MS angle ( 40 x 40 x 8 ) supports grouted in floor and duly
powder coated with post office red external and white internal paint
complete in all respects, for external hydrant, as required.
Each 60 10,422.00 625,320.00
NS 3.8 Providing & fixing, testing and commissioning of double flanged sluice
valve of rating PN 1.6 with RISING spindle, bronze / gun metal seat, IS
marked complete with nuts, bolts, washers, gaskets, conforming to IS:780
of following sizes as required :
3.8.1 250,mm dia Each 2 62,075.00 124,150.00
3.8.2 200 mm dia ( 6 mm wall thickness ) Each 3 38,718.00 116,154.00
3.8.3 150 mm dia Each 112 24,790.00 2,776,480.00

BOQ - (FF) 8
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
3.8.4 100 mm dia Each 22 19,016.00 418,352.00
3.8.5 80 mm dia Each 19 12,732.00 241,908.00
3.8.6 65 mm dia Each 17 11,356.00 193,052.00
NS 3.9 Providing, installation, testing and commissioning of gun metal valves of
following sizes as required :
3.9.1 50 mm dia Each 78 4,593.00 358,254.00
NS 3.10 Providing, Installation, testing and commissioning of non return of
following sizes confirming to IS:5312 complete with rubber gaskets, GI
bolts, nuts, washers etc as required.
3.10.1 150 mm dia Each 43 17,728.00 762,304.00
3.10.2 65 mm dia Each 21 5,748.00 120,708.00
NS 3.11 Supplying and fixing air vessel made of 250 mm dia, 8 mm thick MS
sheet, 1200 mm in height with air release valve on top and flanged
connection to riser, drain arrangement with 25 mm dia gun metal wheel
valve, with required accessories, pressure guage and painting with
synthetic enamel paint of approved shade as required. Set 23 38,901.00 894,723.00
NS 3.12 Supplying and fixing 4 way Fire Brigade connection of cast iron body with
4 nos gun metal male instantaneous couplings complete with cap and
chain as required for 150 mm dia MS pipe connection, conforming top
IS:904 as required.
3.12.1 100 mm dia NRVs and BVs for 100 mm dia Down Commer / Riser Set 51 17,924.00 914,124.00
NS 3.13 Supplying, installing, testing and commissioning of gun metal suction
valve on tank with 4 mtr length 150 mm dia MS heavy pipe ( with all fittings
) and footvalve complete as required. Set 1 16,574.00 16,574.00
NS 3.14 Providing, installing, testing and commissioning of UL listed K80 pendant /
upright sprinkler head. Each 3000 442.00 1,326,000.00
NS 3.15 Providing, installing, testing and commissioning of UL listed K115 Sidewall
Extended Coverage Sprinkler Head Each 300 847.00 254,100.00

BOQ - (FF) 9
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 3.16 Providing and fixing, testing and commissioning of Installation Control
Valve of Cast Iron Body and brass / bronze working parts comprising of
water motor alarm, bronze seat clapper, and clapper arm, hydraulically
driven mechanical gong bell to sound continuous alarm when the
Sprinkler System activates, pressure guages, emergency releases,
strainer, pressure switch, cock valve and by pass, test control box, ball
valves, MS pipe of required sizes, flanges, orifice plate, retard chamber,
gasket etc of size 150 mm dia as required. Set 6 45,979.00 275,874.00
NS 3.17 Providing, intslling, testing and commissioning of 150 mm dia Flow Switch
Each 30 7,119.00 213,570.00
TOTAL OF PIPING AND ACCESSORIES (HYDRANT SYSTEM) WORK
CARRIED OVER TO SUMMARY OF FIRE FIGHTING & FIRE
DETECTION WORKS 37,891,142.00

BOQ - (FF) 10
CHAPTER - 4 : FIRE EXTINGUISHERS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Providing and fixing with brackets wall ounted Fire Extinguishers as per
details below ;
NS 4.1 9 litres water type fire extinguisher IS 15683 marked with internal plastic
lining and 60 gms CO2 cartridge, siphon tube, plunger (spring operated)
and discharge tube Each 8 3,774.00 30,192.00
NS 4.2 4 Kg ABC Extinguisher of stored pressure type with discahrge tube and
pressure guage complete IS 15683. marked with MAP90 powder
Each 364 2,979.00 1,084,356.00
NS 4.3 Supply of ISI marked Dry Chemical type portable Fire Extinguisher of 25
Kg capacity made of high pressure steel cylinder complete with discharge
tube, 1 M long high pressure wire braided discharge hose, discharge horn
fully charged with ABC powder and with 2 kg CO2 external cartridge,
plunger, two wheel trolley complete. Each 84 22,042.00 1,851,528.00
NS 4.4 CO2 Fire Extinguisher of 4.5 Kg capacity fitted with screw down type high
pressure control valve with 1.0 M long rubber braided discahrge hose with
horn. IS 15683 marked Each 20 6,500.00 130,000.00
NS 4.5 9 lts AFFF Extinguisher as per IS 15683 complete as required. Each 12 11,719.00 140,628.00
NS 4.6 Providing and installing of 10 kg Modular ceiling mounted Fire
Extinguisher with 10 KG DC powder and pressurised with sprinkler head
Each 24 8,243.00 197,832.00
NS 4.7 Providing & fixing wall mounted signages consisting of Zinc Sulphide
Photo Luminescent coatings on acrylic sheet. Signages shall be 15 cm x
30 cm and shall consist of Signage on half side and arrow on other half.
Signage shall be any of the following:Exit / Staircase / Extinguisher
location / Manual Call Box / Hydrant etc. Signage shall be as per drawing
Each 804 2,058.00 1,654,632.00
NS 4.8 Providing & fixing wall mounted Floor Plan Signages for emergency
eggress consisting of Building Floor Plan screen painted on Zinc Sulphide
Photo Luminescent coatings on acrylic sheet. Signages shall be 40 cm x
40 cm and shall consist of Floor Plan with location of staircases / exits and
arrow markings indicating escape paths. Each 180 6,559.00 1,180,620.00
TOTAL OF FIRE EXTINGUISHERS WORK CARRIED OVER TO
SUMMARY OF FIRE FIGHTING & FIRE DETECTION WORKS 6,269,788.00

BOQ - (FF) 11
CHAPTER - 5 : FIRE ALARM WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Providing, installing, testing and commissioning of the following
Addressable Detectors / Devices and Panels complete with junction boxes
complete as required.
NS 5.1 Intelligent Addressable Rate of Rise cum Fixed Temperature Heat
Detector with mounting base etc. complete as required. Each 360 3,855.00 1,387,800.00
NS 5.2 Intelligent Addressable Multi criteria detector with Photo Electric and Rate
of Rise type for both Smoke and heat applications, inbuilt Fault Isolator,
mounting base. Each 300 3,990.00 1,197,000.00
NS 5.3 Addressable Manual Call Box made of polycarbonate with plastic break
glass front and complete with Monitor Module. MCB shall be recessed in
wall with size of 75 x 120. The MCB shall have "IN CASE OF FIRE
BREAK GLASS" imprinted on the facia. Each 268 4,530.00 1,214,040.00
NS 5.4 Addressable Input Module for connecting to Flow Switch and other NO /
NC Each 48 3,990.00 191,520.00
NS 5.5 Output Module for tripping of AHU / Hooter / Srobe as required. Each 74 4,125.00 305,250.00
NS 5.6 Fault Isolator Unit Each 36 4,395.00 158,220.00
NS 5.7 UL/ EN 54/VdS listed strobe with base plate. Each 268 4,395.00 1,177,860.00
NS 5.8 Hooter cum Speaker with 6 Watt Amplifier and Line Matching
Transformer. Each 396 3,180.00 1,259,280.00
NS 5.9 Response Indicator Each 10 640.00 6,400.00
NS 5.10 Providing, installing, connecting, testing and commissioning of micro
processor based 16 bit Logic driven Networkable on Peer to Peer
Analogue Addessable 2 Loop ( each loop accessing 100 addressable
detectors ) Fire Alarm Control Panel. The Panel shall be able to give pin
point location of all Fire/Fault conditions of addressable units via the
address codes for each unit. The Panel shall also be able to automatically
switch off all Control Switches when ever any Alarm is triggered and
switch on Extractor Fans. The Panel shall be coupled to the PA System
and have sealed maintenance free batteries of 25 Ah capacity of 24 volts
capable of running for a minimum of 12 hours with battery charger,
rectifier, Loop cards, Keypad operation, L C D unit to indicate Fire / Fault
Signal of individual unit, built in built / external printer to log all incoming
data etc complete in all respects. Each 11 301,313.00 3,314,443.00

BOQ - (FF) 12
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 5.11 Providing, installing, testing and commissioning of PA System Operator
Console complete with 2 x 240 W ( RMS ) channel mixing Amplifiers with
1 channel, 1 no cardoid gooseneck micro phone, 1 no professional grade
cassette deck, a 10 zone Floor Selector Console, a Change over Panel for
connection to the Fire Alarm Panel, a Mains Panel and a Monitor Panel all
pre wired and rack mounted complete in all respects. PA System shall be
coupled to the Fire Alarm System.
Each 11 297,358.00 3,270,938.00
NS 5.12 Supplying and fixing of following sizes of MS steel conduit alongwith the
accessories in surface / recess including painting in case of surface
conduit, or cutting the wall and making good the same in case recessed
conduit as required. Exposed conduits shall be fixed by saddles with base
plate after every 500mm distance.
5.12.1 20 mm dia Mtr. 24800 293.00 7,266,400.00
NS 5.13 Supplying, Laying, Termination, Testing & Commisioning of Zero Halogen
Fire, 2 x 1.5 sq.mm,
5.13.1 2 x 1.5 sq mm Mtr. 27280 100.00 2,728,000.00
NS 5.14 Providing and fixing flexible 20 mm dia GI conduit including all necessary
supports, clamps, jointing pieces etc for cable from slab to detector.
Mtr. 400 120.00 48,000.00
NS 5.15 Providing and laying 50 mm dia HDPE pipe with all fittings and leak proof
joints 1.0 M below ground including excavation and backfilling complete
as required for connecting Fire Alarm System between Buildings.
Mtr. 1000 200.00 200,000.00
5.16 Providing and making Cable Pull Chamber of size 500 mmx 500 mm x
500 mm with 230 thick brickwork, internal cement slurry plaster, 100 mm
thick PCC foundation, cover of 100 mm thick RCC with plastic cover and
sleeve for 50 mm dia HDPE pipe entry. Job 20 3,000.00 60,000.00
NS 5.17 Providing and laying 2 x 1.5 sq mm PVC insulated and sheathed copper
conductor armoured cable for connecting between Networkable
Addressable Panels between different buildings. The cable shall be laid in
50 dia HDPE pipe laid below ground. Mtr. 5000 200.00 1,000,000.00
TOTAL OF FIRE ALARM SYSTEM WORK CARRIED OVER TO
SUMMARY OF FIRE FIGHTING & FIRE DETECTION WORKS 24,785,151.00

BOQ - (FF) 13
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF HVAC WORKS ( figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 HVAC WORKS 96,720.00 9,564,964.00
2 PRESSURIZATION WORK 537,950.00
3 VENTILATION WORKS 418,532.00 55,554,001.00
TOTAL OF HVAC WORKS CARRIED OVER TO GRAND
SUMMARY OF COST 515,252.00 65,656,915.00

BOQ - (HVAC) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - HVAC WORKS
CHAPTER - 1 : HVAC WORKS
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
1.1 VRF EQUIPMENT
NS 1.1.1 Outdoor and Indoor Unit
Supply, Installation, Testing and commissioning of variable refrigerant
volume system complete with 100% variable inverter compressors, air
cooled condenser with low noise fan having interconnected control
wiring and refrigerant piping housed in compact housing. The Minimum
COP should be 3.55 at 100% load at ARI Condition in cooling mode
only.
a) 20 HP Nos. 2 485,000.00 970,000.00
b) 26 HP Nos. 1 580,000.00 580,000.00
c) 30 HP Nos. 3 665,000.00 1,995,000.00
NS 1.1.2 Supply, Installation, Testing and Commissioning of Ductable Indoor
units consisting of DX coil section, Blower, Pre filter, Drain pan etc. of
following capacities
a) 8 TR High Static Nos. 4 154,000.00 616,000.00
b) 6.5 TR High Static Nos. 5 138,000.00 690,000.00
NS 1.1.3 Supply, Installation, Testing and Commissioning of Hiwall Indoor units
consisting of DX coil, Blower, pre filter, Drain pan etc. of following
capacity.
a) 2.0 TR Nos. 3 32,000.00 96,000.00
b) 1.6 TR Nos. 2 30,000.00 60,000.00
NS 1.1.4 Supply, Installation, testing and Commissioning of Floor Mounted Air
Handling unit consisting of 4/6 Row deep DX cooling coil, backward
curved centrifugal fan, prefilter section, Electronic Expansion valve kit
with controller, Drain pan etc. of following capacity

a) 16 TR, 6400 cfm, ESP 45 mm WC Nos. 2 245,000.00 490,000.00

BOQ - (HVAC) 2
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.1.5 Supply, Installation, Testing and Commissioning of Cassette Indoor
units consisting of DX coil, Blower, pre filter, Drain pan etc. of following
capacity.
a) 4 TR Nos. 4 54,000.00 216,000.00
b) 3.2 TR Nos. 1 50,000.00 50,000.00
c) 2.0 TR Nos. 2 48,000.00 96,000.00
d) 4 TR Round Flow Nos. 1 60,000.00 60,000.00
e) 2.6 TR Round Flow Nos. 2 56,000.00 112,000.00
NS 1.1.6 Supply and Installation of Cordless/ Corded Remotes Nos 24 2,650.00 63,600.00
NS 1.1.7 Y-Joints (VRV)
Supply, Installation, testing and commissioning of Y-joints of required
size for refrigerant piping as per manufacturer standards.
a) Y Joints Nos. 25 5,900.00 147,500.00
NS 1.1.8 T-Joints (VRV)
Supply, Installation, testing and commissioning of T-joints of required
size for refrigerant piping as per manufacturer standards.
a) T Joints Nos. 5 6,400.00 32,000.00
NS 1.1.9 Supply and Installation of Programmable Touch Screen Centralised
Controller to control all Indoor units and AHU. Set 1 150,000.00 150,000.00
1.2 ANCILLARY WORKS
NS 1.2.1 Copper Refrigerant Piping
Supply, installation, testing and commissioning of refrigerant copper
pipe work with (19mm/13mm thick) closed cell elastomeric nitrile rubber
tubular insulation between indoor & outdoor units as per specifications,
all piping inside the room shall be properly supported with MS slotted
angle, including cutting chases, hole in walls/slabs and making good the
walls/slabs etc.
a) Dia 6.4 mm OD Rm 70 400.00 28,000.00
b) Dia 9.5 mm OD Rm 55 500.00 27,500.00
c) Dia 12.7 mm OD Rm 55 670.00 36,850.00
d) Dia 15.9 mm OD Rm 100 770.00 77,000.00
e) Dia 19.1 mm OD Rm 130 960.00 124,800.00
f) Dia 22.2 mm OD Rm 55 1,100.00 60,500.00
g) Dia 28.6 mm OD Rm 65 1,450.00 94,250.00
h) Dia 34.9 mm OD Rm 20 1,750.00 35,000.00
i) Dia 41.3 mm OD Rm 10 1,950.00 19,500.00

BOQ - (HVAC) 3
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.2.2 Coverred Cable Trays for running exposed pipes
a) 300 mm x 40 x 40 x 1.6 mm thick Rm 25 1,080.00 27,000.00
b) 150 mm x 25 x 25 x 1.6 mm thick Rm 25 960.00 24,000.00
NS 1.2.3 Supply, installation, testing and commissioning of 2c x 1.5 sqmm control
cum transmission wiring/power/control cabling with PVC insulated, PVC
sheathed, multicore copper conductor control cable in suitable conduits
between indoor and outdoor units and its Rm 350 195.00 68,250.00
NS 1.2.4 Supply, installation, testing and commissioning of condensate drain
water piping with necessary clamps, supports, hangers and fitting such
as bend, tees, reducers etc. duly insulated with 6 mm thick chemically
cross-linked closed cell polyethylene foam
a) 25 mm Dia Rm 75 185.00 13,875.00
b) 32 mm Dia Rm 40 355.00 14,200.00
NS 1.2.5 Supply and filling of Refrigerant Gas for top up, R410 A Kgs 50 1,500.00 75,000.00
NS 1.2.6 Supply and fixing of MS Stand for Outdoor Units. Nos. 6 8,500.00 51,000.00
NS 1.2.7 Supply, installation, balancing and commissioning of factory fabricated
GSS sheet metal rectangular ducting complete with neoprene rubber
gaskets, elbows, splitter, vanes with Wire Rope Hangers & Supports
complete with end fixing in accordance with the approved shop
drawings and as required by the specifications
a) 20 G Sqmt 10 1,950.00 19,500.00
b) 22 G Sqmt 125 950.00 118,750.00
c) 24 G Sqmt 500 810.00 405,000.00
NS 1.2.8 Supply, installation, balancing and commissioning of fabricated at site
GSS sheet metal rectangular ducting complete with neoprene rubber
gaskets, elbows, splitter, vanes with Wire Rope Hangers & Supports
complete with end fixing in accordance with the approved shop
drawings and as required by the specifications
a) 20 G Sqmt 10 995.00 9,950.00
b) 22 G Sqmt 10 880.00 8,800.00
c) 24 G Sqmt 50 725.00 36,250.00
NS 1.2.9 Supply, fabrication, installation and testing the Flexible connections
constructed of fire resistance flexible double canvas sleeve.
Set 11 3,100.00 34,100.00

BOQ - (HVAC) 4
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.2.10 Supply and installation of External Thermal insulation.the material for
Duct insulation shall be closed cell Elastomeric Nitrile Rubber. Thermal
conductivity of the insulation material shall not exceed 0.038 W/moK
with protective coating on ducts as per the specifications:

a) 9 mm thick nitrile rubber insulation Sqmt 640 510.00 326,400.00


NS 1.2.11 Supply, installation and testing of Acoustic lining . Material shall be fibre
glass with 48 Kg/m3 density and all accessories as per specification:

a) 25 mm thick acoustic lining Sqmt 35 595.00 20,825.00


NS 1.2.12 Supply, installation, testing and balancing of powder coated square
diffusser in accordance with the approved shop drawings and
specifications. Sqmt 6 8,250.00 49,500.00
NS 1.2.13 Supply, installation and testing of GI volume control dampers within
ducts complete with suit-able links, levers and quadrants for manual
control of volume of air flow and for proper balancing of air distribution
system. Sqmt 1.5 5,850.00 8,775.00
NS 1.2.14 Supply, installation, testing and balancing of extruded powder coated
aluminium extruded grills as per site requirement. Sqmt 12 7,050.00 84,600.00
NS 1.2.15 Volume control MS Dampers to be provided in supply & Exhaust air
registers / terminals as per approved shop drawings. Sqmt 5 4,400.00 22,000.00
NS 1.2.16 Supplying, installing and testing of fresh/Exhaust air GI louvers with
bird screen complete as per spefifications and drawings.
Sqmt 5 7,780.00 38,900.00
NS 1.2.17 Supply, installation, testing and commissioning of fire dampers of at
least 90 minutes fire rating as per specification & approved shop
drawings, complete with actuator with spring return mechanism and
control panel, limit switch to shut off AHU blowers when the damper
closes.
a) Fire Dampers Sqmt 5 7,050.00 35,250.00
b) Actuators with spring return mechanism Nos. 22 14,000.00 308,000.00

BOQ - (HVAC) 5
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
1.3 ELECTRICAL WORKS
NS 1.3.1 For AHU (Up to 3.7 Kw Fan Motor)
32 A TPN MCB with 16-32 A Star Delta starter, overload relay, start
/ stop push buttons, phase indication lights with protection fuse, on / off /
trip indication lights with protection fuse, single phase preventer & auto
/ manual mode selector switch.
Set - 01
1.3.1.1 Controls & interlocking accessories as required. LOT Nos. 2 16,500.00 33,000.00
1.3.1.2 Weather proof Isolators for Outdoor units Set 6 9,000.00 54,000.00
NS 1.3.2 Power Cabling
1.3.2.1 Indoor Units
a) Providing and fixing flexible power cable of 3 core x 1.5 sqmm copper
between Indoor units and their power points RM 75 340.00 25,500.00
b) Providing and fixing flexible power cable of 3 core x 2.5 sqmm copper
between Indoor units and their power points RM 60 450.00 27,000.00
1.3.2.2 Outdoor Units
a) Providing and fixing flexible power cable of 4 core x 16 sqmm copper
between Outdoor units and their MCB RM 15 800.00 12,000.00
b) Providing and fixing flexible power cable of 4 core x 25 sqmm copper
between Outdoor units and their MCB RM 20 900.00 18,000.00
1.3.2.3 Earthing
a) Providing and fixing of GI earthing Wire 8 SWG RM 50 110.00 5,500.00

BOQ - (HVAC) 6
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.4 Supplying, installation , testing and comissioning of cubical type LT
panel suitable for 415Volts 3 phase 4wire 50 Hz AC supply system
having front surface area Sq.mtr (approx) fabricated in
compartmentalized design from CRCA sheet steel of 2 mm thick for
frame work and covers , 3 mmthick for gland plates including cleaning
and finishing complte with 7 tank process for power coating in approved
shade having --Amp capacity extensible type TPN aluminium alloy bus
bars of high conductivity DMC/SMC bus bars supports with short circuit
withstand capacity of 31 MVA for 1 second, bottom base channel of MS
section not less than 100mmx 50 mmx 5mm thick, fabrication shall be
done in transportable setctions, entire panel shall have a common
copper earthbar of size25 mm x 5 mm at the rear with 2 No earth stud
solid connections from main bus bars to switchgears with required size
of aluminium bus bars and control wiring with 2.5 Sq. mm PVCinsulated
copper conductor S/C cable alleys cable gland and plates in Top &
bottom half ,including providing following switchgars :-

I Incomer
a. 1 No. 400A, 4 pole MCCB operated Auto Transfer Switch having
braking capacity 70 KA fully interlocked with Microprocessor based O/L,
S/C and EF protection
b. CT's of ratio 400/5A , class 1 accuracy --1 set (1Set of 3nos.)
c. Digital type ammeter 0-400A with selector switch -- 1Set
d. Digital type voltmeter (0-500V) with selector switch and backup MCB -
1set
e. 3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB
, circuits as per standatd practice , auxiallry contact for positive
interlocking of the breakers as required .
II Bus Bars
4Pole aluminium bus bars of minimum of 500Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec

BOQ - (HVAC) 7
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
III Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
a. 3 No. 160A, TPN MCCB having braking capacity 35 KA with Thermal
Magnetic based protection each alongwith 3Nos. Phase indicating LED
lamps with 2 Amp backup MCB
b. 2 No. 100A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection each alongwith 3Nos. Phase indicating LED
lamps with 2 Amp backup MCB
c. 4 No. 63A, TPN MCB 10Ka Each 1 401,089.00 401,089.00
CABLE TRAYS
NS 1.5 Fabricating and installing following size of perforated M. S. cable trays
including horizontal and vertical bends, reducers, tees, cross members
and other accessories as required and duly suspended from the ceiling
with M. S. suspenders and including painting with powder coating etc as
required.
1.5.1 300mm width x 50mm depth x 1.6mm thickness Mtr 150 1,147.00 172,050.00
CABLES
NS 1.6 Supply of the following LT - XLPE 1100 Volts grade Al. Conductor
armoured cables. complete as required and as per tender
specifications.
1.6.1 3X35 sq.mm Mtr 200 447.00 89,400.00
9.1 1.7 Supply and making end termination with brass compression glands and
aluminium lugs for following sizes of PVC insulated & PVC sheathed /
XLPE aluminium conductor cable of 1.1 KV grade as required.

9.1.21 1.7.1 3.5x35 sq. mm. Each 6 270.00 1,620.00


EARTHING
5.4 1.8 Earthing wih GI Earth plate 600mmx600mmx6mm thick including Each
accessories and providinng masanory encliosure with cover plate
having locking arrangement and watering pipe etc. with charcoal or
coke and salt complete as rerquired. 4 4,490.00 17,960.00
5.11 1.9 Providing and fixing 25mm x 5mm G.I. strip in 40mm dia G.I. pipe from Mtr
earth electrode including connection with G.I.nut bolt spring, washer
excavation and re-filling as required. as required. 40 421.00 16,840.00

BOQ - (HVAC) 8
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
5.15 1.10 Providing and fixing 25mm x 5mm G.I. strip on surface or in recess for Mtr
connections etc. as required. 400 142.00 56,800.00
5.16 1.11 Providing and fixing 6 SWG dia GI wire on surface or in recess for loop
earthing as required. Mtr 100 35.00 3,500.00
TOTAL OF HVAC WORKS CARRIED OVER TO SUMMARY OF
HVAC WORKS 96,720.00 9,564,964.00

BOQ - (HVAC) 9
CHAPTER - 2 : PRESSURIZATION WORK
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
2.1 VENTILATION FANS
NS 2.1.1 Tube Axial Fan for Liftwell & Lift Lobby Pressurization
Supply, installation, testing & commissioning of floor mounted Tube Axial
flow fans with adjustable pitch blade, MS casing, cast aluminium alloy
impeller complete with TEFC Sq.Cage Induction motor suitable for 415
volts 10%, 50Hz 3 %, three phase A.C supply with support, mountings
and flexible connection, canopy (if required) etc. as per standard
specifications and drawings.
a) 6500 CFM (15 mm static pressure) Nos. 4 50,000.00 200,000.00
b) 9500 CFM (20 mm static pressure) Nos. 1 60,000.00 60,000.00
2.2 ANCILLARY WORKS
NS 2.2.1 Supply, installation, balancing and commissioning of fabricated at site
GSS sheet metal rectangular ducting complete with neoprene rubber
gaskets, elbows, splitter, vanes with Wire Rope Hangers & Supports
complete with end fixing in accordance with the approved shop drawings
and as required by the specifications
a) 20 G Sqmt 20 875.00 17,500.00
b) 22 G Sqmt 50 775.00 38,750.00
c) 24 G Sqmt 125 640.00 80,000.00
NS 2.2.2 Supply, installation, testing and balancing of extruded powder coated
aluminium extruded grills as per site requirement. Sqmt 2 6,200.00 12,400.00
NS 2.2.3 Volume control MS Dampers to be provided in supply & Exhaust air
registers / terminals as per approved shop drawings. Sqmt 10 3,850.00 38,500.00
NS 2.2.4 Supplying, installing and testing of fresh/Exhaust air GI louvers with bird
screen complete as per spefifications and drawings. Sqmt 1 6,800.00 6,800.00
2.3 ELECTRICAL WORKS
For Lift Lobby & Lift Well Pr. Fan (Up to 3.7 Kw Fan Motor)
NS 2.3.1 32 A TPN MCB with 16-32 A Star Delta starter, overload relay, start /
stop push buttons, phase indication lights with protection fuse, on / off /
trip indication lights with protection fuse, single phase preventer & auto /
manual mode selector switch.
Set - 01
Controls & interlocking accessories as required. LOT Nos. 5 14,500.00 72,500.00

BOQ - (HVAC) 10
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 2.3.2 Wiring for circuit/ submain wiring alongwith earth wire with the following
sizes of FR PVC insulated copper conductor, single core cable in surface/
recessed steel conduit as required.
a) 4 x 2.5 + 2 x 2.5 Sq.mm earth wire Rm 5 350.00 1,750.00
b) 4 x 4 + 2 x 4 Sq.mm earth wire Rm 10 425.00 4,250.00
c) 4 x 6 + 2 x 6 Sq.mm earth wire Rm 10 550.00 5,500.00
TOTAL OF PRESSURIZATION WORKS CARRIED OVER TO
SUMMARY OF HVAC WORKS 537,950.00

BOQ - (HVAC) 11
CHAPTER - 3 : VENTILATION WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
3.1 VENTILATION WORKS
3.1.1 Vane Axial Fan
Supply, installation, testing and commissioning of extract fans as per
standard specifications and drawings. Fan shall be with direct driven
vane axial fan. Fan and casing shall be suitable for smoke exhaust
application. Motor shall be mounted inside/outside so that it is not
exposed to smoke stream & thermally rated for 250 Deg C for 2 hour.
Motors shall be suitable for 415+10% volts, 50 cycles , 3 phase AC
supply and static pressure shall be as indicated.The fan shall be equipped
with mounting bracket & outlet core required at discharge.Fan shall be
with flexible fire proof connection at inlet and outlet.Cost of spring
isolators for the installation of the fans needs to be included. Fan capacity
based on static pressure which shall be given below :-
Note**
i) Third party certificate to be provided for motor fire rating.
ii) The SP of the fan should be checked by vendor and motor should be
selected accordingly prior to award of contract.
iii) Fans shall be AMCA Certified.
iv) Each Axial fan should be with tapper bush for easy servicing or
dismentling of impeller at the time of service.
v) All the impeller should be of LM-6 material pressure die casted.
vi) Each individual fan should be fire rated certify with the same motor to be
supplied.
vii) Noise level : not exceeding 80 db at 3.0m from fan.
viii) Duty : General Supply & Exhaust
NS a) Air Quantity : 18000 CFM
Static Pressure : 30 mm wg
Motor Rating : 10.0 HP Nos. 1 172,000.00 172,000.00
NS b) Air Quantity : 24000 CFM
Static Pressure : 30 mm wg
Motor Rating : 15.0 HP Nos. 1 222,500.00 222,500.00
NS c) Air Quantity : 30000 CFM
Static Pressure : 30 mm wg
Motor Rating : 15.0 HP Nos. 3 253,000.00 759,000.00

BOQ - (HVAC) 12
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS d) Air Quantity : 33000 CFM
Static Pressure : 30 mm wg
Motor Rating : 15.0 HP Nos. 12 253,000.00 3,036,000.00
NS e) Air Quantity : 37000 CFM
Static Pressure : 30 mm wg
Motor Rating : 20.0 HP Nos. 4 293,000.00 1,172,000.00
NS f) Air Quantity : 40000 CFM
Static Pressure : 30 mm wg
Motor Rating : 20.0 HP Nos. 11 305,000.00 3,355,000.00
3.1.2 Tube Axial Fan
Supply, installation, testing and commissioning of extract fans as per
standard specifications and drawings. Fan shall be with direct driven
Tube axial fan. Fan and casing shall be suitable for smoke exhaust
application.Motor shall be mounted inside/outside so that it is not exposed
to smoke stream & thermally rated for 250 Deg C for 2 hour. Motors shall
be suitable for 415+10% volts, 50 cycles , 3 phase AC supply and static
pressure shall be as indicated.The fan shall be equipped with mounting
bracket & outlet core required at discharge.Fan shall be with flexible fire
proof connection at inlet and outlet.Cost of spring isolators for the
installation of the fans needs to be included. Fan capacity based on static
pressure which shall be given below :-
Note**
i) Third party certificate to be provided for motor fire rating.
ii) The SP of the fan should be checked by vendor and motor should be
selected accordingly prior to award of contract.
iii) Fans shall be AMCA Certified.
iv) Each Axial fan should be with tapper bush for easy servicing or
dismentling of impeller at the time of service.
v) All the impeller should be of LM-6 material pressure die casted.
vi) Each individual fan should be fire rated certify with the same motor to be
supplied.
vii) Noise level : not exceeding 90 db at 3.0m from fan.
viii) Duty : Smoke Fire & Exhaust

BOQ - (HVAC) 13
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS a) Air Quantity : 18000 CFM
Static Pressure : 30 mm wg
Motor Rating : 10.0 HP Nos. 1 125,000.00 125,000.00
NS b) Air Quantity : 24000 CFM
Static Pressure : 30 mm wg
Motor Rating : 15.0 HP Nos. 1 165,000.00 165,000.00
NS c) Air Quantity : 30000 CFM
Static Pressure : 30 mm wg
Motor Rating : 15.0 HP Nos. 3 194,000.00 582,000.00
NS d) Air Quantity : 33000 CFM
Static Pressure : 30 mm wg
Motor Rating : 15.0 HP Nos. 12 194,000.00 2,328,000.00
NS e) Air Quantity : 37000 CFM
Static Pressure : 30 mm wg
Motor Rating : 20.0 HP Nos. 4 225,000.00 900,000.00
NS f) Air Quantity : 40000 CFM
Static Pressure : 30 mm wg
Motor Rating : 20.0 HP Nos. 11 225,000.00 2,475,000.00
3.2 ANCILLARY WORKS
NS 3.2.1 Supply, installation, balancing and commissioning of factory fabricated
GSS sheet metal rectangular ducting complete with neoprene rubber
gaskets, elbows, splitter, vanes with Wire Rope Hangers & Supports
complete with end fixing in accordance with the approved shop drawings
and as required by the specifications
a) 18 G Sqmt 550 1,120.00 616,000.00
b) 20 G Sqmt 5800 964.00 5,591,200.00
c) 22 G Sqmt 5000 834.00 4,170,000.00
d) 24 G Sqmt 5500 720.00 3,960,000.00
NS 3.2.2 Supply, installation, balancing and commissioning of fabricated at site
GSS sheet metal rectangular ducting complete with neoprene rubber
gaskets, elbows, splitter, vanes with Wire Rope Hangers & Supports
complete with end fixing in accordance with the approved shop drawings
and as required by the specifications
a) 18 G Sqmt 25 1,035.00 25,875.00
b) 20 G Sqmt 75 875.00 65,625.00
c) 22 G Sqmt 125 775.00 96,875.00
d) 24 G Sqmt 300 640.00 192,000.00

BOQ - (HVAC) 14
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 3.2.3 Supply, installation, testing and balancing of powder coated square
diffusser in accordance with the approved shop drawings and
specifications. Sqmt 25 7,200.00 180,000.00
NS 3.2.4 Supply, installation and testing of GI volume control dampers within ducts
complete with suit-able links, levers and quadrants for manual control of
volume of air flow and for proper balancing of air distribution system.
Sqmt 25 5,100.00 127,500.00
NS 3.2.5 Supply, installation, testing and balancing of extruded powder coated
aluminium extruded grills as per site requirement. Sqmt 220 6,200.00 1,364,000.00
NS 3.2.6 Volume control MS Dampers to be provided in supply & Exhaust air
registers / terminals as per approved shop drawings. Sqmt 78 3,850.00 300,300.00
NS 3.2.7 Supplying, installing and testing of fresh/Exhaust air GI louvers with bird
screen complete as per spefifications and drawings. Sqmt 160 6,800.00 1,088,000.00
NS 3.2.8 Supply, installation, testing and commissioning of fire dampers of at least
90 minutes fire rating as per specification & approved shop drawings,
complete with actuator with spring return mechanism and control panel,
limit switch to shut off AHU blowers when the damper closes.

a) Fire Dampers Sqmt 5 6,200.00 31,000.00


b) Actuators with spring return mechanism Nos. 1 12,500.00 12,500.00
3.3 ELECTRICAL WORKS
NS 3.3.1 VENTILATION MCC (LOWER & UPPER BASEMENT)
Incomer:
One (1) No. 100A TPN MCCB (25 KA).
3 Nos. phase indication lamps & 3 Nos. status indication lamps for
ON/OFF/TRIP with control SP MCB .
One (1) No. digital multifunction meter for measurement of voltage and
current (EFF-3259 of conzerv or equivalent) with selector push buttons
and one set of CTs of ratio 100A/5A, CL 1.0, 15VA.
Busbar :
160A TPN Al. Busbar of short circuit withstand capacity 35kA. Busbar
shall be insulated with heat shrinkable sleeves and shall be color coded.

Outgoing :
One (1) Nos. 63A TPN MCCB (25KA) - Spare

BOQ - (HVAC) 15
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Two (2) Nos. 40/63A TP MPCB suitable for 11-15 kW Star Delta Starter
with thermal range of 40A - 63A. Nos. 32 140,000.00 4,480,000.00
NS 3.3.2 Supplying, laying, testing & commissioning of following 1100 volt grade
XLPE insulation FRLS PVC insulated sheathed copper conductor
armoured cable as per specification in existing trenches, cable trays
ducts over bed of sand, clamped to wall with suitable clamps, including
fixing bolts, connecting testing and commissioning complete in all respect
as per drawing & specification.
a) 4 core 25 sq.mm Copper Rm 15 800.00 12,000.00
b) 4 core 16 sq.mm Copper Rm 15 700.00 10,500.00
c) 4 core 10 sq.mm Copper Rm 15 600.00 9,000.00
NS 3.3.3 Cable end termination of the following XLPE insulated FRLS PVC
sheathed Copper conductor armoured cables of 1100 volt grade including
supplying, fixing, testing & commissioning of Copper crimping lugs,
double compression glands with earthing complete in all respect as per
drawing & specification.
a) 4 core 25 sq.mm Copper Set 2 400.00 800.00
b) 4 core 16 sq.mm Copper Set 2 350.00 700.00
c) 4 core 10 sq.mm Copper Set 4 350.00 1,400.00
NS 3.3.4 Wiring for circuit/ submain wiring alongwith earth wire with the following
sizes of FR PVC insulated copper conductor, single core cable in surface/
recessed steel conduit as required.
a) 4 x 2.5 + 2 x 2.5 Sq.mm earth wire Rm 10 350.00 3,500.00
b) 4 x 4 + 2 x 4 Sq.mm earth wire Rm 10 425.00 4,250.00
c) 4 x 6 + 2 x 6 Sq.mm earth wire Rm 10 550.00 5,500.00
d) 4 x 10 + 2 x 10 Sq.mm earth wire Rm 150 850.00 127,500.00
e) 4 x 16 + 2 x 16 Sq.mm earth wire Rm 25 1,200.00 30,000.00
NS 3.3.5 Supply, installation, testing & commissioning of following sizes of GI
strip/wire clamped to walls, cable trays, bus ducts, cables, in recess
(including cost of digging & backfilling) or on surface etc for equipment/
System earthing complete as required including inter connection between
length at joints, all fixing accessories saddles, clamps, test joints etc.
and other fixing hardware material as required for proper installation.

a) 32 x 6 mm strip Rm 10 150.00 1,500.00


b) 25 x 3 mm strip Rm 20 120.00 2,400.00
c) 8 SWG Wire Rm 50 100.00 5,000.00

BOQ - (HVAC) 16
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Ventilation Panel 1-4 ( Located in Upper Basement) & Ventilation
Panel 5-8 ( Located in Lower Basement)
NS 3.4 Supplying, installation , testing and comissioning of cubical type LT panel
suitable for 415Volts 3 phase 4wire 50 Hz AC supply system having front
surface area Sq.mtr (approx) fabricated in compartmentalized design
from CRCA sheet steel of 2 mm thick for frame work and covers , 3
mmthick for gland plates including cleaning and finishing complte with 7
tank process for power coating in approved shade having --Amp capacity
extensible type TPN aluminium alloy bus bars of high conductivity
DMC/SMC bus bars supports with short circuit withstand capacity of 31
MVA for 1 second, bottom base channel of MS section not less than
100mmx 50 mmx 5mm thick, fabrication shall be done in transportable
setctions, entire panel shall have a common copper earthbar of size25
mm x 5 mm at the rear with 2 No earth stud solid connections from main
bus bars to switchgears with required size of aluminium bus bars and
control wiring with 2.5 Sq. mm PVCinsulated copper conductor S/C cable
alleys cable gland and plates in Top & bottom half ,including providing
following switchgars .(For other details & cable sizes ref. Ventilation & Fire
panel Single line diagram)

I. Incomer
2 No. 630-Amps. four pole electrically operaterd horizontal drawout type
air circuit breaker of fault breaking capacity 50Ka manually operated fitted
with interlocked door, automatic safety shutters, mechanical ON/OFF and
service/test/isolated position indicator and frame earthing contact
,confiming to IS 13947-2 1993 as amended upto date complete with
following accessories for each ACB
a. Independent manual spring clsing mechanism - 1 No.
b. Microprocessor release (EMI and EMC certified) for over current, earth
fault and short circuit protection- 1Set .
c. 0-630A Digital type Multifunction Meter with backup MCB -1set
d. 1 set of 3Nos.CT's of ratio 630/5/5A, 15A Class-1 accuracy and 15 VA
burden - 1 set
e. 3Nos. Phase indicating LED lamps with 2 Amp backup MCB, breaker
ON/OFF/Trip indication light with 2A MCB , test terminal block set, MCB ,
circuits as per standatd practice as required .
f. Shunt trip coil 220 Volt AC .

BOQ - (HVAC) 17
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
g. Auto/Manual switch for ACB for testing purpose.
II. (ii) Interlocking
Electrical through advance contacts in ACB (Incomer and bus coupler)
and mechanical (casstle key) interlocking should be provided to ensure
that only one supply is available at a time on each section of bus to
eleminate any possibility of accidentally approaching two supplies at one
bus section.
III. Bus Bars
a. 4Pole aluminium bus bars of minimum of 800Amp with heat shrinkable
coloured sleeves and including BMC/SMC bus bars supports at required
interval complete for cross section, side supports and their spacing etc.
for withstanding fault level of 31 MVA for 1 sec
b. Outgoings (MCCB's whereverspecified shall have rotary handle, shall
have double break, positive isolation current limiting, load line
reversability & horz. Cum vertical mounting feature)
10 No. 100A, TPN MCCB having braking capacity 25 KA with Thermal
Magnetic based protection each alongwith 3Nos. Phase indicating LED
lamps with 2 Amp backup MCB
4 No. 63A, TPN MCB 10Ka Each 8 992,972.00 7,943,776.00
CABLE TRAYS
NS 3.5 Fabricating and installing following size of perforated M. S. cable trays
including horizontal and vertical bends, reducers, tees, cross members
and other accessories as required and duly suspended from the ceiling
with M. S. suspenders and including painting with powder coating etc as
required.
3.5.1 300mm width x 50mm depth x 1.6mm thickness Mtr 300 1,147.00 344,100.00
3.5.2 450mm width x 50mm depth x 2.0mm thickness Mtr 300 1,695.00 508,500.00
3.5.3 600mm width x 50mm depth x 2.00mm thickness Mtr 600 2,168.00 1,300,800.00
CABLES
NS 3.6 Supply of the following LT - XLPE 1100 Volts grade Al. Conductor
armoured cables. complete as required and as per tender specifications.

3.6.1 3X25 sq.mm Mtr 3200 314.00 1,004,800.00


3.6.2 3.5x300 sq.mm Mtr 2400 2,769.00 6,645,600.00

BOQ - (HVAC) 18
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
9.1 3.7 Supply and making end termination with brass compression glands and
aluminium lugs for following sizes of PVC insulated & PVC sheathed /
XLPE aluminium conductor cable of 1.1 KV grade as required.
9.1.9 3.7.1 3x25 sq. mm. Each 128 195.00 24,960.00
9.1.30 3.7.2 3.5x300 sq. mm. Each 32 1,086.00 34,752.00
EARTHING
5.4 3.8 Earthing wih GI Earth plate 600mmx600mmx6mm thick including Each
accessories and providinng masanory encliosure with cover plate having
locking arrangement and watering pipe etc. with charcoal or coke and salt
complete as rerquired. 8 4,490.00 35,920.00
5.11 3.9 Providing and fixing 25mm x 5mm G.I. strip in 40mm dia G.I. pipe from Mtr
earth electrode including connection with G.I.nut bolt spring, washer
excavation and re-filling as required. as required. 100 421.00 42,100.00
5.15 3.10 Providing and fixing 25mm x 5mm G.I. strip on surface or in recess for Mtr
connections etc. as required. 400 142.00 56,800.00
5.16 3.11 Providing and fixing 6 SWG dia GI wire on surface or in recess for loop
earthing as required. Mtr 6400 35.00 224,000.00
TOTAL OF VENTILATION WORKS CARRIED OVER TO SUMMARY
OF HVAC WORKS 418,532.00 55,554,001.00

BOQ - (HVAC) 19
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF ELEVATOR WORKS (figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 Elevator Works 118,065,033.00
TOTAL OF ELEVATOR WORKS CARRIED OVER TO GRAND
SUMMARY OF COSTS 118,065,033.00

BOQ - (ELEV) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - ELEVATOR WORKS
CHAPTER - 1 : SUPPLY AND INSTALLATION OF ELEVATORS
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
ELEVATOR WORK
NS 1.1 Supply, installation, testing, commissioning and maintenance of machine
room less passenger lifts conforming to the specifications and relevant
Indian Standards suitable for operation on 415 volts, 3 phase, 50 cycle,
A.C power supply with neccesary ARD system. The work shall include
among all other things as detailed in the specification, necessary
scaffolding, all steel works and other builder works, safety device for car
and counterweight as required for satisfactory working all complete as
specified and described (The maintenance period for the lift shall be 12
month for the date of commissioning and handing over the same).

PASSENGER ELEVATORS
a) CENTRE OF EXCELLENCE
I) Elevator Type 2 (13 Passenger Elevator) Ground floor to 3rd floor -
16.8m approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 1 2,902,083.00 2,902,083.00
b) COMMUNITY FACILITY
I) Elevator Type 1 (Passenger Elevator) Ground floor to 5th floor - 18 m
approximately
Capacity - 8 passengers - 544 Kgs.
Speed - 1 MPS Each 1 2,643,588.00 2,643,588.00
c) HOSTEL FOR SOs & SAs
I) Elevator Type 2 (Passenger Elevator) Ground floor to 4th floor - 15.75m
approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 4 2,989,772.00 11,959,088.00
d) TRANSIT ACCOMMODATION FOR SO's&SA's
I) Elevator Type 1 (Passenger Elevator) Ground floor to 5th floor - 18.9 m
approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 2 3,091,349.00 6,182,698.00

BOQ - (ELEV) 2
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
e) TRANSIT ACCOMMODATION FOR GO's
I) Elevator Type1 (Passenger Elevator) Ground floor to 4th floor - 15.75m
approximately
Capacity - 8 passengers - 544 Kgs.
Speed - 1 MPS Each 1 2,804,372.00 2,804,372.00
f) TYPE II
I) Elevator Type 2 (Passenger Elevator) 2 Basements+Ground floor to 8th
floor -37.35 m approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 12 3,950,841.00 47,410,092.00
g) TYPE III
I) Elevator Type 2 (Passenger Elevator) 2 Basements+ Stilt floor to 8th
floor -37.35 m approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 4 3,950,841.00 15,803,364.00
h) TYPE IV
I) Elevator Type 2 (Passenger Elevator) Stilt floor to 7th floor - 25.2 m
approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 1 3,604,276.00 3,604,276.00
i) TYPE V
I) Elevator Type 2 (Passenger Elevator) Stilt floor to 7th floor - 25.2 m
approximately
Capacity -13 passengers - 844 Kgs.
Speed - 1 MPS Each 1 3,604,276.00 3,604,276.00

GOODS LIFT
a) CENTRE OF EXCELLANCE
I) Elevator Type 3 (Goods lift) Ground floor to 3rd floor - 16.8m
approximately
Capacity - 2000Kgs.
Speed - 0.5 MPS Each 1 5,226,518.00 5,226,518.00
b) COMMUNITY FACILITY
I) Elevator Type 3 (Goods lift) Ground floor to 5th floor - 18 m
approximately
Capacity - 2000Kgs.
Speed - 0.5 MPS Each 1 5,397,320.00 5,397,320.00

BOQ - (ELEV) 3
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
h) TYPE IV
I) Elevator Type 3 (Goods lift) Stilt floor to 7th floor - 25.2 m
approximately
Capacity - 2000Kgs.
Speed - 0.5 MPS Each 1 6,019,590.00 6,019,590.00
i) TYPE V
I) Elevator Type 3 (Goods lift) Stilt floor to 7th floor - 25.2 m approximately

Capacity - 2000Kgs.
Speed - 0.5 MPS Each 1 4,507,768.00 4,507,768.00
TOTAL OF SUPPLY AND INSTALLATION OF ELEVATORS WORK
CARRIED OVER TO SUMMARY OF ELEVATOR WORKS 118,065,033.00

BOQ - (ELEV) 4
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF CCTV WORKS (figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 CCTV WORKS 17,928,882.00

TOTAL OF WORKS CARRIED OVER TO GRAND


SUMMARY OF COSTS 17,928,882.00

BOQ - (CCTV)SUM 1
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - CCTV WORKS
CHAPTER - 1 :CCTV WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
Providing, installing, testing and commissioning of the following CC TV
components as below :
NS 1.1 Mini Dome Camera - 1.3MP, Vandal proof, IP66, 1/3'' CMOS, 1280x960:
25fps(P)/30fps(N), 0.01lux/f1.2, 4mm/f1.8 lens, Electronic Day/Night,
H.264/MJPEG/MPEG4,Dual-Stream, Motion Detection, Watermark
DC12V/PoE, TCP/IP, HTTP, DHCP, DNS, DDNS, RTP/RTSP, PPPoE,
SMTP, NTP
(SNMP, HTTPS, FTP, SIP, SRTP, 802.1X, IPv6 optional)
Each 82 3,588.00 294,216.00
NS 1.2 IR Bullet Camera -1/3" Progressive CMOS, 1280x960: 25fps(P)
/30fps(N), 0.01lux/F1.2, 2.7 - 9mm/F1.2 lens,IP66, ICR and 30M IR
range, H.264/ MJPEG/ MPEG4, Dual-Stream, Motion
Detection,Watermark,PoE,support SD/SDHC Card
DC12V/PoE, IP66,
TCP/IP,HTTP,DHCP,DNS,DDNS,RTP/RTSP,PPPoE,SMTP,NTP Each 30 17,249.00 517,470.00
NS 1.3 IR IP High Speed Dome (PTZ) - NEW (Weather proof) PAL:
752(H)582(V), NTSC: 768(H)494(V), 1/4" Sony Super HAD CCD,
Color: 540TVL, 0.2Lux/F1.6, B/W: 570TVL, 0.02Lux/F1.6, 0Lux with IR,
ICR, Optical Zoom: 36x, Digital Zoom: 16x Focus: 3.4- 122.4mm,
SNR>50db,Tilt Range:-10~90(Auto Flip), 80m IR Range,IP66, Electronic
shutter: 1/50(1/60)-1/10000s, 24 VAC Each 20 17,249.00 344,980.00
NS 1.4 Indoor High Speed Dome Camera (PTZ) - IP High Speed Dome
(Outdoor/Indoor) Wide Dynamic Range
PAL:752(H)582(V),NTSC:768(H)494(V), 1/4" Sony EXVIEW HAD CCD,
ICR, Color: 540 TVL, 0.7 Lux / F1.4, B/W: 570 TVL, 0.01 Lux / F1.4,
Optical zoom:18x, Digital zoom: 12x, Wide Dynamic Range: 128x, Focus:
4.1-73.8mm, SNR>50 dB,Tilt Range:-5~185(Auto Mirror), Electronic
shutter:1/3(1/4)-1/10,000s, 24 VAC(12 VDC Optional)
Each 4 18,945.00 75,780.00
NS 1.5 16 channel DVR with 16 TB Hard Disk and Power Suupply Unit complete
Each 26 17,924.00 466,024.00
NS 1.6 42: LCD colour monitor Each 26 56,000.00 1,456,000.00

BOQ - (CCTV) 2
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 1.7 Supplying and fixing of following sizes of MS steel conduit alongwith the
accessories in surface / recess including painting in case of surface
conduit, or cutting the wall and making good the same in case recessed
conduit as required. Exposed conduits shall be fixed by saddles with base
plate after every 500mm distance.
1.7.1 20 mm dia Mtr. 26400 293.00 7,735,200.00
NS 1.8 Supplying, Laying, Termination, Testing & Commisioning of Zero Halogen
Fire, 2 x 1.5 sq.mm,
1.8.1 2 x 1.5 sq mm Mtr. 24940 100.00 2,494,000.00
NS 1.9
Providing, laying, testing and commissioning of twin twisted CAT 6 cable
Mtr. 27434 118.00 3,237,212.00
NS 1.10 Providing and fixing flexible 20 mm dia GI conduit including all necessary
supports, clamps, jointing pieces etc for cable from slab to detector.
Mtr. 400 120.00 48,000.00
NS 1.11 Providing and laying 50 mm dia HDPE pipe with all fittings and leak proof
joints 1.0 M below ground including excavation and backfilling complete
as required for connecting Fire Alarm System between Buildings.
Mtr. 1000 200.00 200,000.00
NS 1.12 Providing and making Cable Pull Chamber of size 500 mmx 500 mm x
500 mm with 230 thick brickwork, internal cement slurry plaster, 100 mm
thick PCC foundation, cover of 100 mm thick RCC with plastic cover and
sleeve for 50 mm dia HDPE pipe entry. Job 20 3,000.00 60,000.00
NS 1.13 Providing and laying 2 x 1.5 sq mm PVC insulated and sheathed copper
conductor armoured cable for connecting between Networkable
Addressable Panels between different buildings. The cable shall be laid in
50 dia HDPE pipe laid below ground. Mtr. 5000 200.00 1,000,000.00
TOTAL OF CCTV WORKS CARRIED OVER TO SUMMARY OF CCTV
WORKS 17,928,882.00

BOQ - (CCTV) 3
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF ACOUSTICAL WORKS ( figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 ACOUSTICAL TREATMENT - CEILING AND WALL PANELING 5,659,080.00
2 STAGE & HALL FURNISHING 1,626,130.00
3 STAGE LIGHTING SYSTEM 3,898,320.00
4 AUDIO SYSTEM 2,623,592.00
5 VIDEO PROJECTION SYSTEM 1,634,060.00
6 LIGHTING SYSTEM 383,000.00
TOTAL OF ACOUSTICAL WORKS CARRIED OVER TO GRAND
SUMMARY OF COSTS 15,824,182.00

BOQ - (ACUS) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - ACOUSTICAL WORKS
CHAPTER - 1 : ACOUSTICAL TREATMENT - CEILING & WALL PANELING
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
CEILING:
NS 1.1 ACOUSTICAL DESIGN CEILING:
Providing and fixing at all heights false ceiling with pre fabricated
acoustical ceiling panels (Akoustike 35mm) as per approved design and
colour. The panel comprises of Perforated panel with 25mm acoustic wool
duly placed and Fabric finish in approved shade and quality of fabric. The
Acoustic Panels shall be placed in 24mm T grid ceiling framework as per
design with gypsum border on all sides as per design and drawing layout.
The work includes working at all heights as per site and nothing extra shall
be paid for light fitting or AC grill fittings.
MAKE: IBS-Acoustike panel (35mm)/ Ecophon ceiling panels/ Utone
(35mm) panels. sqm 308 2,840.00 874,720.00
NS 1.2 Fabric stretched Acoustic wall panelling system:
Providing and laying Fabric Stretched Acoustic wall panelling system on
GI and ply batton Frame work as per design with fabric stretch grippers
with glass wool/ rockwool of 48kg/cum; 50mm thick ; and duly covered
with a top layer of 25mm IBS Acoustic Sheet Wool duly compressed to
10mm within framework to achive average NRC (Noise Reduction co-
efficient) of 0.85 0.90, Edge finish of square/ half round type with shape
and size as per approved design. Approved fabric to be installed on 12mm
cove, mid and edge grippers in desired shape and size as per detailed
drawing. The rate quoted should include for supplying & fixing the
grippers, base frame of GI and ply battons as per detailed drawings,
supplying and fixing the glass wool, Decron and fixing of the approved
fabric as per design layout.
MAKE: IBS-FSS Wall paneling/ Ecophon wall panels/ Armstrong wall
panels.
sqm 336 4,200.00 1,411,200.00

BOQ - (ACUS) 2
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.3 Wall Treatment side/rear walls Lower Levels: Providing and fixing Wood
finished MDF based panels with lineal perforations to be fixed on
walls.The panels shall be with melamine laminate finish of size 2430mm x
128mm x15mm wirh 4mm slats at 28 mm pitch, Toungue and Groove
edges for seamless mounting having density of 800kg/m3 . The back of
the panels are perforated with 10mm diameter circular holes with a
nonwoven fabric covering of 0.2mm for providing Sound absorption via
the acoustic impedance method.Panel is to be fixed on GI framework as
recommended by the manufacturer with screw fixed horizontal / vertical to
wall at every 600mm c/c with centre & edge bracket in tongue & groove
system on GI framework. The cavity of framework should be inserted with
50mm thick fibre glass resin bonded insulation of density 24kg/cum.
sqm 185 4,950.00 914,760.00
NS 1.4 Providing & fixing 100mm high polished wooden skirting. mtr 100 350.00 35,000.00
FLOORING:
NS 1.5 STAGE FLOORING:
Providing and fixing 65x15 th. 2nd class Teak wood planks flooring with
Tongue and Groove joints (concealed screwing) over 50x50mm section
Sal wood framing @ 600mm c/c in both directions with 12mm thick
commercial ply.The framing to be filled with 50mm th. fibre glass resin
bonded insulation of density 24kg/cum. Melamine polishing of teakwood
on exposed surface: In horizontal/vertical plane (Rate for flooring shall
include providing additional framework required for housing microphone
and power outlet junction boxes including providing and fixing hinged
15mm thick teakwood cover for the junction boxes. sqm 112 9,200.00 1,030,400.00
NS 1.6 Providing and fixing 26 oz. loop pile carpet with precision tufted loop piles
and underlay of 8mm thick PU foam fixed to existing levelled floor with
synthetic adhesives as approved by the manufacturer.
Appvd. Make: Capital Carpet, Floortex, Unitex sqm 350 2,980.00 1,043,000.00

BOQ - (ACUS) 3
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 1.7 SPD DOORS: Providing and fixing Sound Proof doors (SPD) as per size.
The doors should be made up of 50 x 50mm hard wood frame with equal
partitions filled with 48kg/ cu. meter density rockwool. The frame is
laminated with 8mm ply/ mdf on both sides. the audi side (inside)
framework should be insulated with Tecsound 50 (spain) completely
covered with another sheet of 6mm mdf/ply. SPD door as well as door
frame work should be strictly as per sound proofing design with double
layer (Z) formation for sound insulation of minimum 40db. 1mm laminate
to be pasted for final finish on the door as per selected shade. Appropriate
long handles, fasteneres etc. to be fitted as required. Door closer is not
recommended. sqm 20 17,500.00 350,000.00
TOTAL OF ACOUSTICAL TREATMENT - CEILING & WALL
PANELINGCARRIED OVER TO SUMMARY OF ACOUSTICAL WORKS
5,659,080.00

BOQ - (ACUS) 4
CHAPTER - 2 :STAGE & HALL FURNISHING
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
MAIN CURTAIN
NS 2.1 P/F of Stage MAIN curtain made out of crushed/ velvet/ mercury or as
approved curtain cloth with horizontal sliding arrangement complete with
Aluminium Cyrtain Track, Ceiling or wall mount brackets, sliding
arrangement & motorised operation complete with runners and master
runners, Rf remote with 3 nos push buttons for forward, reverse and stop
positions. The curtain should be draped to half area when in closed
position. Minimum overlap at centre should be 900mm and should be
stitched in double gathering.
The motorized curtain mechanism is operated with 2 nos. of Curtain track
motors; one at each end/ track; with inbuilt limit switch system, torque
limiter to protect against unwanted interruption and soft start system.

Size:- 50' x 20' each 1 274,800.00 274,800.00


NS 2.2 Middle Curtain aqnd Rear curtain in black matt satin/ crushed/ velvet
curtain cloth with horizontal sliding arrangement complete with Aluminium
Cyrtain Track, Ceiling or wall mount brackets, sliding arrangement &
motorised operation complete with runners and master runners, Rf remote
with 3 nos push buttons for forward, reverse and stop positions. The
curtain should be draped to half area when in closed position. Minimum
overlap at centre should be 900mm and should be stitched in double
gathering.
The motorized curtain mechanism is operated with 2 nos. of Curtain track
motors; one at each end/ track; with inbuilt limit switch system, torque
limiter to protect against unwanted interruption and soft start system.

Size: 40' x 20' each 2 234,115.00 468,230.00


NS 2.3 CYCLORAMA :- Providing and fixing cyclorama curtain cum screen in
High Gain WHITE MATT projection screen material duly stretched on MS
pipe frame. The screen to be fixed on tubular frame made out of 35mm
dia MS pipe or on wall frame as suitable and approved.
Size:- 28' X 18' each 1 237,000.00 237,000.00
NS 2.4 Stage Wings: Providing and fixing cloth wings made out of black glazed
cotton cloth fixed on 32mm dia Pivoted bar and stretched with bottom
weight. each 6 23,500.00 141,000.00

BOQ - (ACUS) 5
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 2.5 FRILLS :- Providing and fixing light bar and stage frills made out of double
gathering glazed cotton cloth to be installed above the stage on 28mm dia
GI pipe or GI channel each 6 20,400.00 122,400.00
NS 2.6 Stage Personium Wall:
MS Rectangular Pipe Frame Structure: MS Pipe size : 50mmx 25 mm x 16
G Structure Size : 1200 mm width x stage Height approx 5000m.
Structure to be made using rectangular Pipe frame at 900 x 900 c/c.
6mm commercial ply to be fixed on the front side of the frame.
sqm 50 3,160.00 158,000.00
NS 2.7 Stage MS Suspension grid: Providing and fixing MS angle rafters above
acting area of stage at 1200x600mm centers, 2 x 40x40x5mm thick. MS
angle runners & 25x12x12mm thick studs as MS spacers fixed @
600mmc/c sandwiched between the MS angle runners so as to maintain
12mm gap between MS angle . The grid so formed to be suspended from
bottom of roof structure by means of 50 x 5mm thick. MS flat suspenders,
fixed with MS cleats & dash fasteners at RCC slab & nuts & bolts at
1200mm centers to the grid. Painting MS suspension grid & suspenders
with 2 coats of redoxide primer and 2 or more coats of enamel paint of
approved shade. sqm 70 3,210.00 224,700.00
TOTAL OF STAGE & HALL FURNISHING CARRIED OVER TO
SUMMARY OF ACOUSTICAL WORKS 1,626,130.00

BOQ - (ACUS) 6
CHAPTER - 3 :STAGE LIGHTING SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
STAGE LIGHTING FOR AUDITORIUM
I FOH LIGHTING BAR
NS 3.1 Supply, installation, testing and commissioning of 575/750W Profile Light
with 575/750W Halogen Lamp, G 9.5 Socket, and Manufacturer rated
lamp life is 250 Hours, IP 20 Casting aluminium housing, in conformity
with the CE Standard and ROHS directive.
Make: STAN/ MARTIN / CLAY PAKEY Each 6 31,500.00 189,000.00
NS 3.2 Supply, installation, testing and commissioning of LED PAR Light with 54
x 1W high quality LEDs, 100-120V and 200-240V AC, 50/60Hz
(200W@220V), RGBW colour mixting; linearly adjustable colour
temperature, 0-100% linearly adjustable dimmer, Strobe 0~20 F.P.S, DMX
mode, display setting status, operation mode can be transmitted by
synchronous control.
Make: MARTIN / Stan / Imported Eqv. Each 16 13,150.00 210,400.00
II Ist Lighting BAR
NS 3.3 Supply, installation, testing and commissioning of 1000W Halogen
Fresnel light consisting of 1000W Halogen Bipin T-11 lamp, 150mm dia
imported fresenel lens, Imported socket, bottom sliding knob, yoke, colour
frame & suitable clamp.
Make: IBS/ canara / TDH Each 4 12,900.00 51,600.00
NS 3.4 Supply, installation, testing and commissioning of 575/750W Profile Light
with 575/750W Halogen Lamp, G 9.5 Socket, and Manufacturer rated
lamp life is 250 Hours, IP 20 Casting aluminium housing, in conformity
with the CE Standard and ROHS directive.
Make: IBS / STAN/ Equivalent Each 4 31,500.00 126,000.00
NS 3.5 Supply, installation, testing and commissioning of 1000 W Halogen light
with mash & barndoor consisting of 2nos. single contact compressible
holders, yoke, 1000W halogen tube & suitable clamp.
Make: Modern Stage Service / IBS/ canara Each 2 1,400.00 2,800.00
NS 3.6 SITC of 1000W Planoconvex Spot Light complete with 1000W Halogen
Bipin T-11 lamp, G-38 base socket, spherical anodised reflector, 200 mm
dia Planoconvex lens, rear sliding knob, yoke, colour frame & suitable
clamp.
Make: IBS / canara/ CSE Each 3 13,500.00 40,500.00

BOQ - (ACUS) 7
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
III 2nd Lighting BAR
NS 3.7 Supply, installation, testing and commissioning of 1000 W Halogen light
with mash & barndoor consisting of 2nos. single contact compressible
holders, yoke, 1000W halogen tube & suitable clamp.
Make: IBS/ canara / CSE Each 2 1,400.00 2,800.00
NS 3.8 Supply, installation, testing and commissioning of 575/750W Profile Light
with 575/750W Halogen Lamp, G 9.5 Socket, and Manufacturer rated
lamp life is 250 Hours, IP 20 Casting aluminium housing, in conformity
with the CE Standard and ROHS directive.
Make: IBS / STAN/ Equivalent Each 4 31,500.00 126,000.00
NS 3.9 Supply, installation, testing and commissioning of 1000W Halogen
Fresnel light consisting of 1000W Halogen Bipin T-11 lamp, 150mm dia
imported fresenel lens, Imported socket, bottom sliding knob, yoke, colour
frame & suitable clamp.
Make: IBS / canara / CSE Each 3 12,900.00 38,700.00
NS 3.10 SITC of 1000W Planoconvex Spot Light complete with 1000W Halogen
Bipin T-11 lamp, G-38 base socket, spherical anodised reflector, 200 mm
dia Planoconvex lens, rear sliding knob, yoke, colour frame & suitable
clamp.
Make: IBS / canara/ CSE Each 3 13,500.00 40,500.00
IV 3rd Lighting BAR -
NS 3.11 Supply, installation, testing and commissioning of 1000 W Halogen light
with mash & barndoor consisting of 2nos. single contact compressible
holders, yoke, 1000W halogen tube & suitable clamp.
Make: IBS/ canara / CSE Each 2 1,400.00 2,800.00
NS 3.12 Supply, installation, testing and commissioning of 575/750W Profile Light
with 575/750W Halogen Lamp, G 9.5 Socket, and Manufacturer rated
lamp life is 250 Hours, IP 20 Casting aluminium housing, in conformity
with the CE Standard and ROHS directive.
Make: IBS / STAN/ Equivalent Each 3 31,500.00 94,500.00
NS 3.13 Supply, installation, testing and commissioning of 1000W Halogen
Fresnel light consisting of 1000W Halogen Bipin T-11 lamp, 150mm dia
imported fresenel lens, Imported socket, bottom sliding knob, yoke, colour
frame & suitable clamp.
Make: IBS / canara / CSE Each 3 12,900.00 38,700.00

BOQ - (ACUS) 8
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 3.14 SITC of 1000W Planoconvex Spot Light complete with 1000W Halogen
Bipin T-11 lamp, G-38 base socket, spherical anodised reflector, 200 mm
dia Planoconvex lens, rear sliding knob, yoke, colour frame & suitable
clamp.
Make: IBS / canara/ CSE Each 3 13,500.00 40,500.00
Cyclorama Lighting BAR
NS 3.15 9 LED Matrix Moving Head: 9 pcs., 10W RGBW moving head LED light
with RGBW infinite Color Mixing, multiple built in programs; 0-100% Linear
Dimming System having nd strobe and 20 DMX channels; operating at
110-240V/ 50-60Hz; power 150W.
Make: IBS / Stan / Imported Eqv. Each 12 39,585.00 475,020.00
Side Light Ladder
NS 3.16 Supply, installation, testing and commissioning of M.S. Pipe Ladders to
be provided on sides of the Stage to be fixed on the existing GI pipe or top
grid. Made of 50mm x 25mm MS pipe of following Size: - 1200 x 600
Each 6 5,800.00 34,800.00
NS 3.17 Supply, installation, testing and commissioning of LED PAR Light with 54
x 1W high quality LEDs, 100-120V and 200-240V AC, 50/60Hz
(200W@220V), RGBW colour mixting; linearly adjustable colour
temperature, 0-100% linearly adjustable dimmer, Strobe 0~20 F.P.S, DMX
mode, display setting status, operation mode can be transmitted by
synchronous control.
Make: IBS / Stan / Imported Eqv. Each 12 13,150.00 157,800.00
V SPECIAL EFFECT LIGHT
NS 3.18 MOVING HEAD SHARPY 10R: Moving Head Sharpy Beam 10R Light with
Lamp YODN 280WR10, Color Temperature 8500K, electronic ballast; 14
color + blank colour wheel; 17 fixed gobos + blank gobo; rotation 16 face
prism, bilateral rotation; high precision optical lens; adjustable wash
effects angle; 0-100% linear adjustment; parallel beam angle 0 - 3.8
degree; double lens strobe; standard DMX 512, Automatic and master /
slave mode operatio/50-60Hz.
Make: IBS / Stan / Imported Eqv. Each 4 136,700.00 546,800.00

BOQ - (ACUS) 9
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 3.19 Supply, installation, testing and commissioning of 6 Channel DMX Splitter
for ensure maximum safety and DMX Signal distribution . The DMX splitter
provided on DMX input and Six Buffered output. The conections are thru 3
pin or 5 pin XLR Connectors.
Make: Modern Stage Service / IBS/ CSE / TDH Each 2 18,600.00 37,200.00
NS 3.20 Electronic dimmer with Patch Panel; wall mount type 12ch x 4kw Auto
sensing of supply voltage (140-260VAC) Automatic supply frequecy
tacking 40-60HZ, Liner dimming High quality RF noise supperssion,Radio
frequency curve,Neon'Load present'indicators interference suppression
to better than BS-800 guidelines,12 channels-99.5% duty circle,Singl,Dual
or three operation,phase monitoring Neon,Control signal monitring LEDs.0-
10 Volt control input by one 8-pin Din socket,Soft start function at power
up, lamp pre-heat level selector for longer lamp life, individual channel test
controls,individual channel blown fuse indicators,Individual channel status
blown fuse indicators,Individual channel status indicators.
Make: IBS/ TDH/ CSE
Each 2 146,450.00 292,900.00
NS 3.21 Providing/ fixing STAGE1024 *Controller *1024DMX Channel;, 2x512
Channel *Control 96 Intellegent Lights With Upto 40 Channel Each;
consisting of sub masters, separate pages manual controls with 2 sub
masters, 1 master fader , blinker switches, effects control, DMX output
and soft patch to 512 DMX channels, LCD menus , HTP control,
Provision for Controlling intelligent lights etc.
Make AVOLITE/ STAN / Imported Eqv. Each 1 145,000.00 145,000.00
NS 3.22 Supply, installation, testing and commissioning Inter connection wiring for
Dimmer to Control Room with required connectors. job 1 20,000.00 20,000.00
NS 3.23 Supply, installation, testing and commissioning Light Point Wiring from
Patch Panel to be provided near stage to various stage light fixtures with
1.5 Sq.mm 3 Core PVC Insulated and PVC Sheathed Cable including
Cable Tray of suitable size for laying these wires on the tray including 20
amps connectors at top. Each 30 2,800.00 84,000.00
NS 3.24 Supply, installation, testing and commissioning DMX Point Wiring Each 40 3,000.00 120,000.00

BOQ - (ACUS) 10
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 3.25 Supplying, Installation, Testing & Commissioning of Stage light bars in
respective position duly fixed with MS angles and fastners. Bar of GI PIPE,
50mm B class jindal Hisar). Duly supported from ceiling with MS angles
and connectors as per the Bar position to be provided at 250mm
c/c.Lights with clamps will be hung on the bars and wiring will be done in
the sockets, complete etc. as required. Nos. 40 24,500.00 980,000.00
TOTAL OF STAGE LIGHTING SYSTEM CARRIED OVER TO
SUMMARY OF ACOUSTICAL WORKS 3,898,320.00

BOQ - (ACUS) 11
CHAPTER - 4 : AUDIO SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
Front Line Array Loudspeaker System (L, C & R) :
NS 4.1 FOH Loudspeaker left & right : Full-range loudspeaker designed for
permanent installations and portable sound reinforcement, for both indoor
and outdoor applications with frequency response of 60Hz to 15kHz; Cont
power: 240W @ 8 Ohms; Nominal dispersion of 120H X 100V; Sensitivity
of 91 dB; Max SPL of 116 dB SPL; inbuilt drivers with Rugged enclosure
with powder coated steel grille. Nos. 6 118,650.00 711,900.00
NS 4.2 Brackets/Hanging Arrangment : Mounting arrangement for the flying
above speakers. Nos. 3 5,800.00 17,400.00
NS 4.3 Delay Loudspeaker left & right : Full-range loudspeaker designed for
permanent installations and portable sound reinforcement, for both indoor
and outdoor applications with frequency response of 60Hz to 15kHz; Cont
power: 240W @ 8 Ohms; Nominal dispersion of 120H X 100V; Sensitivity
of 91 dB; Max SPL of 116 dB SPL; inbuilt drivers with Rugged enclosure
with powder coated steel grille. Nos. 2 118,650.00 237,300.00
NS 4.4 Brackets/Hanging Arrangment : Mounting arrangement for the flying
above speakers. Nos. 2 5,800.00 11,600.00
NS 4.5 SUBWOOFER:18" subwoofer, 38Hz-300Hz (-10db); dbx controller;
impedence of 4 ohms; 127dB SPL; 350W (1400W peak) power rating. Nos. 2 59,450.00 118,900.00
NS 4.6 Amplifier: Class AB professional power amplifier with 2 X 300 Watt @ 4
Ohms; 2 X 150 Watt @ 8 Ohms; 600 Watt @ 8 Ohm Bridged; Frequency
response 20 Hz to 20kHz; THD <0.5%; Damping factor > 200; S/N ratio >
100 dB; Front panel signal / clip / protect LED indicators; 4 audio input 4-
pole removable connectors. Nos. 1 38,650.00 38,650.00
NS 4.7 Amplifier: Class H Dual Channel Professional power amplifier with
frequency response of 20 Hz to 20kHz; Power rating as: 450 W @ 4
Ohms; 330 Watt @ 8 Ohms; 900 Watt @ 8 Ohm Bridged; THD<0.5%;
Damping factor > 200; Front panel signal / clip / protect LED indicators;
Extensive protective circuits ensure high reliability and operating safety.
Nos. 4 48,630.00 194,520.00

BOQ - (ACUS) 12
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 4.8 Amplifier: Class H Dual Channel Professional power amplifier with
frequency response of 20 Hz to 20kHz; Power rating as: 1100 W @ 4
Ohms; 700 Watt @ 8 Ohms; 2200 Watt @ 8 Ohm Bridged; THD<0.5%;
Damping factor > 200; Front panel signal / clip / protect LED indicators;
Extensive protective circuits ensure high reliability and operating safety.
Nos. 2 58,740.00 117,480.00
NS 4.9 Floor Monitor: SITC of two way stage monitor; 60Hz-16kHz (-10db); dual
angle pole socket; impedence of 8 ohms; 129db SPL; 90 x 50
dispersion; 250W (1000W peak)power rating. Nos. 4 39,450.00 157,800.00
NS 4.10 Processor: 4 in 12 out Digital Loudspeaker Processor, with inbuilt DSP
features like Input Equalisation, Router, Band Pass filter, Output
Equalizer, Delay, Limiters etc Nos. 1 251,790.00 251,790.00
NS 4.11 SITC of programmable gooseneck microphone with RED status ring of
neck, cardiod polar pattern, integrated on/off switch, bass roll off filter
complete with standard accessories as per tender specifications.
Nos. 2 22,450.00 44,900.00
NS 4.12 Wireless handheld microphone: Cardioid dynamic capsule system with
frequency response of 80Hz-16kHz; Max SPL of 149 dB SPL; Excellent
feedback rejection; illuminated mute button; 10 hours of operation; 12
Presets; Total harmonic distortion(THD-N) is < 1%; Signal to noise ratio is
> 103 dB; Switching bandwidth of 24MHz; Synchronization via RF remote
channel. Nos. 3 32,460.00 97,380.00
NS 4.13 Wired handheld microphone: Microphone with frequency response of
40Hz-16kHz; Cardioid pick-up pattern; Exceptional feedback rejection;
Isolation from incidental noise. Nos. 4 6,890.00 27,560.00
NS 4.14 Wired Instrumental microphone: Supply , installation , testing and
commissioning of wired Instrumental microphone as per the tender
specifications. Nos. 6 7,650.00 45,900.00
NS 4.15 Wireless Lapel Microphone: Frequency response: mic: 100 - 16000 Hz,
Line: 60 - 16000 Hz; Presets: 12; THD: <1%; S/N Ratio: > 103 dB(A).
Nos. 4 28,363.00 113,452.00
NS 4.16 Mike Stands Nos. 6 3,850.00 23,100.00

BOQ - (ACUS) 13
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 4.17 Mixing Console: Mixing Console with 18 MIC/LINE inputs, 4 STEREO
inputs; 4 STEREO AUX returnsl; 20Hz to 20kHz frequency response;
THD+N 0.03%; S/N Ratio 114 dB; 3-band EQ with swappable MID
Frequency on microphone channels; 4-band fixed EQ on stereo line
channels; 4-GROUP MIX; 24-bit DSP effects for 100 presets (10 presets,
10 variations). Nos. 1 85,460.00 85,460.00
NS 4.18 DVD Cum USB Player : Portable DVD Player with 18cm/ 7" LCD 3hr
playtime USB . Nos. 1 8,000.00 8,000.00
NS 4.19 Connectors : UL Listed Connectors. Nos. 1 25,000.00 25,000.00
NS 4.20 Microphone Cable: 2 core PVC insulated Cu conduction sheilded
microphone cable cable. Mtr. 800 130.00 104,000.00
NS 4.21 Speaker Cable: 2 core 2.5 sq mm PVC insulated Cu conduction
loudspeaker cable. Mtr. 500 140.00 70,000.00
NS 4.22 Rack: Equipment Rack for housing all rack mountable equipments with
internal wiring, front glass door; Heat dessipation fans; Movement wheels,
Power distribution units etc. Nos. 1 46,500.00 46,500.00
NS 4.23 Installation, testing, commissioning job 1 75,000.00 75,000.00
TOTAL OF SOUND REINFORCEMENT SYSTEM CARRIED OVER TO
SUMMARY OF ACOUSTICAL WORKS 2,623,592.00

BOQ - (ACUS) 14
CHAPTER - 5 : VIDEO PROJECTION SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
Video Projection and Presentation System
NS 5.1 Projector : 1DLP 0.67" DMD projector with 6050 ANSI Lumens ,
Resolution 1920 x 1200 WUXGA; Contrast ratio : 4800:1 (dynamic
contrast enabled) ; full on/off ; Inputs : 1x HDMI ; 1x DVI-D ; 1x
DisplayPort 1x HD15 ; 1x composite video ; 1x S-Video ; Component
video ; 1x USB (type B mini) - display over USB ; 1x USB (type A) - image
viewer or Wi-fi dongle (optional) ; 1x RJ45with Standard Zoom Lens
(Range for the given lens is from 4.5m - 5.6m) fcomplete with all
standard accessories. Nos. 1 836,450.00 836,450.00
NS 5.2 Ceiling Mount Kit : Fixed Projector mounting Kit for above Projector
Complete with all standard accessories . Nos. 1 4,800.00 4,800.00
NS 5.3 Motorized Projection screen with 170 " Diagonal ; Aspect Ratio
(16:10) ; Height & Width (12.02ft x 7.51ft) complete with all standard
accessories . Nos. 1 78,400.00 78,400.00
NS 5.4 Wall Plate : Customized Wall Plate with 1 HDMI , I VGA and 1 Audio
Input Complete with all standard accessories. Nos. 1 12,500.00 12,500.00
NS 5.5 Multiformat Presentation Point : Inputs- 1 x HDMI, 1 X 1 VGA on a
15pin HD (F) connector ; 1 X unbalanced stereo audio ; Outputs - 1 X
HDBaseT ; 1 X unbalanced stereo audio ; Control - 1X RS232 & 1 x
RJ45 Ethernet ; Control for Remote switches for input switching and
volume control ; HDCP & EDID Compliance ; Max Data Rate : 10.2Gbps
(3.4Gbps per graphic channel) complete with standard accessories.
Nos. 2 110,200.00 220,400.00
NS 5.6 Presentation switcher with 4 HDMI Input ; 2 VGA Input ; 6 Stereo
Audio Input with 1 Mic Input ; 1 HDMI Output , 1 HD-BaseT Output & 1
Stereo Audio Output ; Video Latency: Less than 2 frames ; RS232
(control and data), Ethernet (OSD and Web pages). Nos. 1 126,780.00 126,780.00
NS 5.7 HD Base-T Twisted Pair Reciever for HDMI ;Bidirectional RS232 and
IR Signal over Sheilded Twisted Pair Cable ; HDCP & HDTV Compliant ;
System Range - 70m (230ft) @1080p, 40m (130ft) @4K complete with all
standard accessories Nos. 3 24,560.00 73,680.00

BOQ - (ACUS) 15
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
NS 5.8 Master Room controller: Ports: 4 RS232, RS485, 4 GPI/O and
KNET on terminal block connectors; 1 Ethernet on an RJ45
connector; 1 infrared builtin receiver, 2 infrared on 3.5mm mini jacks; 1
USB for programming ; Outputs: 4 infrared, 8 relays (36V AC or DC, 2A,
60V AC maximum on noninductive load); LED Indicators.
Nos. 1 74,520.00 74,520.00
NS 5.9 High Voltage Relay Interface : 8 channels of power switching ;
Supports 120 to 240 Volt 50/60 Hz ; Override input. Nos. 1 30,100.00 30,100.00
NS 5.10 TouchPanel : Wireless Touch Panel with control software and docking
station complete with standard accessories . Nos. 1 116,500.00 116,500.00
NS 5.11 Ethernet Switch : 8 Port Ethernet Switch complete with standard
accessories. Nos. 1 14,680.00 14,680.00
NS 5.12 Wireless Router complete with standard accessories. Nos. 1 6,500.00 6,500.00
NS 5.13 1.8 Meter HDMI-HDMI Cable. Nos. 5 2,850.00 14,250.00
NS 5.14 1.8 Meter VGA-VGA Cable. Nos. 2 3,250.00 6,500.00
NS 5.15 Cat 6 Shielded Twisted pair Cable. Mtrs. 200 90.00 18,000.00
TOTAL OF VIDEO PROJECTION SYSTEM CARRIED OVER TO
SUMMARY OF ACOUSTICAL WORKS 1,634,060.00

BOQ - (ACUS) 16
CHAPTER - 6 : LIGHTINIG SYSTEM
DSR - RATE (RS.) AMOUNT(RS.)
2014/ SL. NO. DESCRIPTION OF ITEM UNIT QTY
NS DSR NS DSR ITEMS NS ITEMS
Video Projection and Presentation System
NS 6.1 Flexible LED strip in transparent enclosure, end strip is scoldered with
connecting leads for power supply complete with Amplifier unit, Master
controller, fixing clip etc. (Make - Bajaj / Philips / Insta power / Eqv.) metre 500 150.00 75,000.00
NS 6.2 Recessed wall mounting 1 watt LED step light Luminaire with die cast
aluminium housing with reflector, driver unit etc. (Make - Bajaj / Philips /
Regent/ eqv.) each 60 750.00 45,000.00
NS 6.3 Single colour LED accent lighting suitable for staircase steps with silver
grey finish extruded aluminium housing with toughened glass diffuser
complete with driver unit etc. (Make & Sample should get approved by
Architect) each 120 950.00 114,000.00
NS 6.4 Recessed mounted 7x3 watt LED spot light Luminaire with cast aluminium
housing with swivel arrangement complete with driver unit etc. (Make -
Bajaj / Philips / WIPRO/ REGENT each 60 1,850.00 111,000.00
NS 6.5 Supplying & fixing of LED lit signages of super bright green colour, Exit
sign is written on etched acrylic sheet (Make - Bajaj / Philips / Insta power
/ Regent) each 20 1,900.00 38,000.00
TOTAL OF LIGHTING SYSTEM CARRIED OVER TO SUMMARY OF
ACOUSTICAL WORKS 383,000.00

BOQ - (ACUS) 17
RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA

SUMMARY OF SITE DEVELOPMENT WORKS (figures in Rs.)

Cost of work
Sl. No. Chapter Description/ Head of work
Scheduled Items Non Scheduled items
1 SITE DEVELOPMENT & LANDSCAPE WORKS 77,334,258.40 22,441,907.09
BOUNDARY WALL & GATE ALONG NURSERY SCHOOL &
2 1,727,973.65
MAIN ENTRY
3 BOUNDARY ALONG TECHNICAL SECTOR 3,161,589.65
TOTAL OF SITE DEVELOPMENT WORKS CARRIED
OVER TO GRAND SUMMARY OF COST 82,223,821.70 22,441,907.09

BOQ - (SD) SUM 1


RESIDENTIAL CUM TRAINING COMPLEX FOR SPECIAL PROTECTION GROUP (SPG) AT DWARKA
BILL OF QUANTITY - SITE DEVELOPMENT WORKS
CHAPTER - 1 : SITE DEVELOPMENT & LANDSCAPE WORKS
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.31 1.1 Clearing jungle including uprooting of rank vegetation, grass, brush
wood, trees and saplings of girth upto 30 cm measured at a height of
1m above ground level and removal of rubbish upto a distance of 50 m
outside the periphery of the area cleared. 100sqm 948 642.00 608,616.00
2.1 1.2 Earth work in surface excavation not exceeding 30 cm in depth but
exceeding 1.5 m in width as well as 10 sqm on plan including disposal
of excavated earth upto 50 m and lift upto 1.5 m, disposed soil to be
levelled and neatly dressed :
2.1.1 1.2.1 All kinds of soil 100sqm 435 5,044.15 2,194,205.25
2.6 1.3 Earthwork in excavation by mechanical means (hydraulic
excavator)/manual means over areas (exceeding 30cm in depth, 1.5m
in width as well as 10sqm on plan) including disposal of excavated
earth, lead upto 50m and lift upto 1.5m, disposed earth to be levelled
and neatly dressed:
2.6.1 1.3.1 All kinds of soil cum 19232 155.60 2,992,499.20
2.8 1.4 Earth work in excavation by mechanical means (hydraulic excavator)/
manual means in foundation trenches or drains (not exceeding 1.5m in
width or 10sqm on plan) including dressing of sides and ramming of
bottoms, lift upto 1.5m, including getting out the excavated soil and
diposal of surplus excavated soil as directed, within a lead of 50 m:
2.8.1 1.4.1 All Kinds of soil . cum 1445 157.50 227,587.50
2.25 1.5 Filling available excavated earth (excluding rock) in trenches, plinth,
sides of foundations etc. in layers not exceeding 20cm in depth:
consolidating each deposited layer by ramming and watering, lead up
to 50 m and lift upto 1.5 m cum 646 112.40 72,610.40
NS 1.6 Filling available excavated earth (excluding rock) in in layer not
exceeding 20cm in depth: consolidating each deposited layer by
ramming and watering, lead up to 500 m and lift upto 1.5 m cum 18400 112.40 2,068,160.00
2.27 1.7 Supplying and filling, in plinthwith Jamuna sand under floors including,
watering, ramming consolidating and dressing complete.
cum 848 910.25 771,892.00

BOQ - SD 2
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
4.1 1.8 Providing and laying in position cement concrete of specified grade
excluding the cost of centering and shuttering - All work upto plinth
level.
4.1.4 1.8.1 1:2:4 (1 Cement : 2 coarse sand : 4 graded stone aggregate 40 mm
nominal size) cum 110 5,335.25 586,877.50
4.1.6 1.8.2 1:3:6 (1 Cement:3 coarse sand: 6 graded stone aggregate 40 mm
nominal size) cum 681 4,672.50 3,181,972.50
4.6 1.9 Providing and fixing at or near ground level precast cement concrete in
kerbs, edgings etc. as per approved pattern and setting in position with
cement mortar 1:3 (1 Cement : 3 coarse sand) including the cost of
required centering, shuttering and finishing smooth with 6mm thick
cement plaster 1:3 (1 cement : 3 fine sand) on exposed surfaces
complete.
4.6.1 1.9.1 1:2:4 ( 1 cement : 2 coarse sand : 4 graded stone aggregate 20mm
nominal size). cum 429 5,714.95 2,451,713.55
16.42 1.10 Cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone
aggregate 40 mm nominal size) in pavements, laid to required slope
and camber in panels as required including consolidation finishing and
tamping complete. cum 90 5,450.45 490,540.50
6.1 1.11 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in foundation and plinth in:
6.1.2 1.11.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 17 4,677.25 79,513.25
6.4 1.12 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level in
all shapes and sizes in :
6.4.2 1.12.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 19 5,426.15 103,096.85
16.68 1.13 Providing and laying 60mm thick factory made cement concrete
interlocking paver block of M -30 grade made by block making machine
with strong vibratory compaction, of approved size, design & shape,
laid in required colour and pattern over and including 50mm thick
compacted bed of coarse sand, filling the joints with fine sand etc. all
complete as per the direction of Engineer-in-charge.
sqm 2500 602.20 1,505,500.00
NS 1.14 Providing and laying Grass paver tile 100 mm thick of approved
colour and pattern, M-30 grade, over bed of fine sand( average 50mm)
laid to proper slope including filling the joints with fine sand etc.
complete and as directed by Engineer-in-charge. sqm 7294 969.00 7,067,886.00

BOQ - SD 3
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
11.3 1.15 Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded
stone aggregate) finished with a floating coat of neat cement, including
cement slurry, but excluding the cost of nosing of steps etc. complete.

11.3.1 1.15.1 40 mm thick with 20 mm nominal size stone aggregate sqm 902 353.35 318,721.70
11.28 1.16 40 mm thick fine dressed stone flooring over 20 mm (average) thick
base of cement mortar 1:5 ( 1cement : 5 coarse sand) with joints
finished flush.
11.28.1 1.16.1 Red sand stone sqm 3300 582.80 1,923,240.00
11.28.2 1.16.2 White sand stone sqm 2900 608.35 1,764,215.00
11.27 1.17 Stone work (machine cut edges) for wall lining etc. (veneer work) upto
10 metre height, backing filled with a grout of average 12 mm thick
cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in
white cement mortar 1:2 (1 white cement : 2 stone dust) with an
admixture of pigment matching the stone shade : (To be secured to the
backing and the sides by means of cramps and pins which shall be
paid for separately) : sqm 244 1,191.25 290,665.00
7.23 1.18 Stone work (machine cut edges) for wall lining etc. (veneer work) upto
10 metre height, backing filled with a grout of average 12 mm thick
cement mortar 1:3 (1 cement : 3 coarse sand) including pointing in
white cement mortar 1:2 (1 white cement : 2 stone dust) with an
admixture of pigment matching the stone shade : (To be secured to the
backing and the sides by means of cramps and pins which shall be
paid for separately) :
7.23.1 1.18.1 Red sand stone - exposed face fine dressed with rough backing.
7.23.1.5 1.18.1.1 30 mm thick sqm 46 2,172.00 99,912.00

BOQ - SD 4
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
7.23.3 1.18.2 White sand stone - exposed face fine dressed with rough backing
7.23.3.5 1.18.2.1 30 mm thick sqm 27 2,195.20 59,270.40
16.3 1.19 Supplying and stacking at site.
16.3.1 1.19.1 90 mm to 45 mm size stone aggregate cum 12472 1,310.45 16,343,932.40
16.3.3 1.19.2 53 mm to 22.4 mm size stone aggregate cum 3697 1,354.00 5,005,738.00
16.3.6 1.19.3 Stone screening 13.2 mm nominal size (Type A) cum 1343 1,558.15 2,092,595.45
16.3.7 1.19.4 Stone screening 11.2 mm nominal size (Type B) cum 675 1,471.00 992,925.00
16.3.10 1.19.5 Moorum cum 3390 646.35 2,191,126.50
16.4 1.20 Laying spreading and compacting stone aggregate of specified sizes to
WBM specifications including spreading in uniform thickness, hand
picking , rolling with 3 wheeled road / vibratory roller 8-10 tonne in
stages to proper grade and camber, applying and brooming requisite
type of screening / binding material to fill up interstices of coarse
aggregate watering and compacting to the required density .
Cum 48066 425.05 20,430,453.30
16.35 1.21 2.5 cm premix carpet surfacing with 3 cum of stone chippings 10 mm
nominal size per 100 sqm and bitumen emulsion (medium setting min.
65% bitumen contents) complying with IS : 8887, using 96 kg per cum
of chippings of road surface, including consolidation with road roller
etc. complete. sqm 26789 200.60 5,373,873.40
16.48 1.22 Painting road surface marking with adequate nos of coats to give
uniform finish with ready mixed road marking paint conforming to IS :
164, on bituminous surface in white/yellow shade, including cleaning
the surface of all dirt, scales, oil, grease and foreign material etc.
complete.
16.48.1 1.22.1 New work (Two or more coats) sqm 26789 122.15 3,272,276.35
16.92 1.23 Providing and fixing 10x10x7.50 cm Granite stone block hand cut and
chisel dressed on top, for paving in floors, drains etc. laid over 20mm
thick base mortar 1:4 (1cement:4 coarse sand) with joints 10mm wide
filled with same mortar including ruled pointing etc. complete as per
direction of engineer-in charge. sqm 1300 1,375.20 1,787,760.00

BOQ - SD 5
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
11.53 1.24 Providing and fixing Glass mossaic tiles at finished plain wall surface of
size 20 mm x 20 mm x 4 mm in all colour, design , fixing in customize
design as per direction of Engineer-in- Charge. The glass mosaic tiles
to be fixed on the wall surface with the help of approved adhesive
applied at the rate of 2.5 kg per sqm and grouting of the same. The
rate is inclusive of all operation, material and required pattern approved
by Engineer-in-Charge: sqm 69 1,752.60 120,929.40
NS 1.25 Supplying Garden Seats of Hard wood slats fixed to wrought iron
frame as per enclosed drawing each 10 11400.00 114000.00
NS 1.26 Supplying and stacking sludge at site including royalty and carriage up
to 1 km (sludge measured in stacks will be reduced by 8% for
payment). cum 714 248.77 177,620.35
NS 1.27 Digging holes in ordinary soil and refilling the same with the excavated
earth, mixed with manure or sludge in the ratio of 2:1 by volume (2
parts of stacked volume of earth after reduction by 20% : 1 part of
stacked volume of manure after reduction by 8%), flooding with water,
dressing including removal of rubbish and surplus earth, if any with all
leads and lifts (cost of manure, sludge or extra good earth if needed to
be paid for separately)
1.27.1 Hole 1.2 m dia and 1.2 m deep each 1215 220.38 267,756.84
NS 1.28 Spreading of sludge, dump manure and / or good earth in required
thickness as par direction of officer-in-charge (Cost of sludge, dump
manure and / or good earth to be paid separately). cum 1329 26.16 34,761.32
NS 1.29 Mixing earth and sludge or manure in the required proportion specified
or directed by the officer-in-charge. cum 192 17.94 3,444.48
NS 1.30 Filling mixture of earth and sludge or manure in the desired proportion
in trenches, flooding with water and levelling (cost of supllying earth
and sludge or manure and mixing excluded) cum 192 8.94 1,717.25
NS 1.31 Grassing with selection No.1 grass including watering and
maintenance of the lawn for 30 days or more till the grass forms a thick
lawn, free from weeds and fit for mowing including supplying good
earth, if needed (the good earth shall be paid for separately). 116,361.70
1.31.1 In rows 5 cm apart in both directions 100sqm 133 874.90 33,643.27
1.31.2 With grass Turf 100sqm 51 659.67 33,643.27

BOQ - SD 6
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 1.32 Supply and plantation of ground covers/ Hedges with soft cuttings
(including supply of required numbers of developed potted plants),
prepration of cuttings, prepration of ground, supply, spreading and
mixing of manure, fine derssing the ground and then planting the
cuttings with watering, etc complete as per direction of officer-in-
charge.
1.32.1 Golden Duranta sqm 1630 270.00 440,100.00
1.32.2 Erantheium sqm 1630 270.00 440,100.00
1.32.3 Tecoma Capeusis sqm 1630 270.00 440,100.00
1.32.4 Latana Depressa sqm 820 270.00 221,400.00
1.32.5 Latana Sellowania sqm 820 270.00 221,400.00
1.32.6 Jet Plant sqm 820 270.00 221,400.00
1.32.7 Levandra sqm 820 270.00 221,400.00
NS 1.33 Preparation of beds for hedging and shrubbery by excavating 60 cm
deep and trenching the excavated base to a further depth of 30 cm,
refilling the excavated earth after breaking clods and mixing with
sludge or manure in the ratio of 8:1 (8 parts of stacked volume of earth
after reduction by 20% : one part of stacked volume of sludge or
manure after reduction by 8%), flooding with water, filling with earth if
necessary, watering and finally fine dressing, leveling etc.
including stacking and disposal of materials declared unserviceable
and surplus earth by spreading and leveling as directed, within a
lead of 50 m, lift up to 1.5 m complete (cost of sludge, manure or
extra earth to be paid for separately).

cum 14963 109.41 1,637,071.90


NS 1.34 Supplying best quality healthy shrubs of species specified as decided
by Engineer - in - Charge, inclusive of cultivation of shrubs beds to 750
mm depth. All plants to be approved before planting inclusive of
maintenance as specified for 3 months after planting
1.34.1 Hibiscus No 2106 377.45 794,909.70
1.34.2 Hamelia No 4213 251.00 1,057,463.00
1.34.3 Ficus Panda No 8425 346.00 2,915,050.00
1.34.4 Tecoma Ghori Chordi No 4213 251.00 1,057,463.00
1.34.5 Boungainvillea No 2106 535.00 1,126,710.00

BOQ - SD 7
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
NS 1.35 Supplying and planting best quality poly bag grown healthy Treess min.
1500mm tall of species specified, inclusive of cultivation of shrubs
beds to 750 mm depth. All plants to be approved before planting
inclusive of maintenance as specified for one year after planting

1.35.1 Delonix regia (Gulmohar) (ht-7' - 8') No 188 163.00 30,644.00


1.35.2 Anthocephallus (Cadamb) (ht-7' - 8') No 13 232.00 3,016.00
1.35.3 Azatirachta Indica (Neem) No 177 163.00 28,851.00
1.35.4 Polyalthia Longifolia (Ashoka) No 50 180.00 9,000.00
1.35.5 Ficus Bengamina No 214 267.00 57,138.00
1.35.6 Erythrina Indica No 56 174.00 9,744.00
1.35.7 Plumeria Alba No 198 441.00 87,318.00
1.35.8 Cassia Fistula No 50 163.00 8,150.00
1.35.9 Roystonea Palm No 10 1,050.00 10,500.00
1.35.10 Date Palm No 10 965.00 9,650.00
NS 1.36 Providing & fixing paly equipments in Nursery Scool & Totlot of
PICANO or any other make approved by Engineer - In- Charge
1.36.1 SWING & SLIDE 2750X2600X1900 MM No 5 226,530.00 1,132,650.00
1.36.2 CAMEL 1800X600X1000 MM No 5 49,580.00 247,900.00
1.36.3 PLAY HORSE 1500X300X560 MM No 2 18,875.00 37,750.00
1.36.4 TUNNEL 2200X1000X1100 MM No. 1 56,034.00 56,034.00
TOTAL OF SITE DEVELOPMENT & LANDSCAPE WORKS
CARRIED OVER TO SUMMARY OF COSTS 77,334,258.40 22,441,907.09

BOQ - SD 8
CHAPTER - 2 : BOUNDARY WALL & GATE ALONG NURSERY SCHOOL & MAIN ENTRY
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.8 2.1 Earth work in excavation by mechanical means (hydraulic
excavator)/manual means in foundation trenches or drains (not exceeding
1.5m in width or 10sqm on plan) including dressing of sides and ramming
of bottoms lift upto 1.5m, including getting out the excavated soil and
disposal of surplus excavated soil as directed, within a lead of 50 m:

2.8.1 2.1.1 All kinds of soil. cum 115 157.50 18,112.50


2.25 2.2 Filling available excavated earth (excluding rock) in trenches, plinth, sides
of foundations etc. in layer not exceeding 20cm in depth, consolidating
each deposited layer by ramming and watering, lead up to 50 m and lift
upto 1.5 m cum 50 112.40 5,620.00
4.1 2.3 Providing and laying in position cement concrete of specified grade
excluding the cost of centring and shuttering - All work upto plinth level.
4.1.5 2.3.1 1:4:8(1cement :4coarse sand :8graded stones aggregate 40 mm nominal
size). cum 1 4,834.30 4,834.30
4.1.8 2.3.2 1:3:6(1cement :3coarse sand :6graded stones aggregate 20 mm nominal
size). cum 20 4,301.15 86,023.00
5.1 2.4 Providing and laying in position specifid grade of reinforced cement
concrete excluding the cost of centring, shuttering, finishing and
reinforcement - All work upto plinth level.
5.1.3 2.4.1 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm
nominal size) cum 6 5,725.90 34,355.40
5.2 2.5 Reinforced cement concrete work in walls (any thickness) including
attached pilasters,buttresses, plinth and string courses, fillets, columns,
pillars, piers, abutments, posts and struts etc upto floor five level,
excluding the cost of centering, shuttering and finishing and reinforcement

5.2.3 2.5.1 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm


nominal size) cum 0.5 6,570.00 3,285.00
5.9 2.6 Centring and shuttering including strutting, propping etc.and removal of
form work for :
5.9.1 2.6.1 Foundations, footings, bases of columns SqM 15 196.45 2,946.75
5.9.6 2.6.2 Columns, Pillars, Piers, Abutments, Posts and Struts SqM 45 453.35 20,400.75

BOQ - SD 9
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
6.1 2.7 Brick work F.P.S. bricks of class designation 75 in foundation and plinth in
:
6.1.2 2.7.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 80 4,677.25 374,180.00
6.4 2.8 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level in all
shapes and sizes in :

6.4.2 2.8.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 2 5,426.15 10,852.30
4.10 2.9 Providing and laying damp - proof course 40 mm thick with cement
concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 12.5
mm nominal size) Sqm 70 257.80 18,046.00
4.12 2.10 Extra for providing and mixing water proofing material in cement concrete per bag
work @ 1 Kg per 50kg of cement. of 50kg.
of
cement
used in
the mix 3 48.15 144.45
4.13 2.11 Applying a coat of residual petroleum bitumen of grade of VG-10 of
approved quality using 1.7 kg per square metre on damp proof course
after cleaning the surface with brushes and finally with a piece of cloth
lightly soaked in kerosene oil. sqm 70 132.00 9,240.00
10.25 2.12 Steel work welded in built up sections/framed work including cutting
hoisting, fixing in position and applying a priming coat of approved steel
primer using structural steel etc.as required.
10.25.2 2.12.1 In gratings, frames, guard bar, ladders, railings, brackets, gates & similar
works. kg 8500 90.10 765,850.00
13.62 2.13 Painting with synthetic enamel paint of approved brand and manufacture
of required colour to give an even shade:
13.62.1 2.13.1 Two or more coats on new work over an under coat of suitable shade with
ordinary paint of approved brand and manufacture. SqM 325 106.25 34,531.25

BOQ - SD 10
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
4.2 2.14 Providing and laying cement concrete in retaining walls, return walls,
walls (any thickness) including attached pilasters, columns, piers,
abutments, pillars, posts, struts, buttresses, string or lacing courses,
parapets, coping, bed blocks, anchor blocks, plain window sills, fillets etc,
upto floor five level, excluding the cost of centering, shuttering and
finishing
4.2.3 2.14.1 1:2:4 (1 Cement : 2 coarse sand :4 graded stone aggregate 20 mm
nominal size) cum 6 6,450.00 38,700.00
5.22 2.15 Reinforcement for R.C.C. work including straightening, cutting, bending,
placing in position and binding all complete upto plinth
5.22.6 2.15.1 Thermo-Mechanically Treated bars Kg 530 68.10 36,093.00
5.22A 2.16 Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete above plinth level.

5.22A.6 2.16.1 Thermo-Mechanically Treated bars Kg 52 68.10 3,541.20


13.3 2.17 20 mm cement plaster of mix

13.3.1 2.17.1 1:4 (1 cement : 4 fine sand) sqm 335 228.10 76,413.50
13.47 2.18 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone
additives of required shade
13.47.1 2.18.1 New work (Two or more coats applied @ 1.43 ltr/10 sqm. over and
including priming coat of exterior primer applied @ 2.20 kg/10 sqm). sqm 335 94.95 31,808.25
7.32 2.19 Stone work, plain in copings, cornices, string courses and plinth courses,
upto 75 mm thick in Cement mortar 1:6 (1 cement : 6 coarse sand),
including pointing with white cement mortar 1:2 (1 white cement : 2 stone
dust) with an admixture of pigment matching the stone shade.

7.32.1 2.19.1 Red sand stone cum 4 38,249.00 152,996.00


TOTAL OF BOUNDARY WALL & GATE ALONG NURSERY SCHOOL
& MAIN ENTRY CARRIED OVER TO SUMMARY OF SITE
DEVELOPMENT WORKS 1,727,973.65 -

BOQ - SD 11
CHAPTER- 3 : BOUNDARY ALONG TECHNICAL SECTOR
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
2.6 3.1 Earthwork in excavation by mechanical means (hydraulic
excavator)/manual means over areas (exceeding 30cm in depth, 1.5m in
width as well as 10sqm on plan) including disposal of excavated earth
lead upto 50m and lift upto 1.5m, disposed earth to be levelled and neatly
dressed :
2.6.1 3.1.1 All kinds of soil cum 1460 155.60 227,176.00
2.26 3.2 Extra for every additional lift of 1.5 m or part thereof in excavation /
banking excavated or stacked materials .
2.26.1 3.2.1 All Kinds of soil cum 365 46.25 16,881.25
2.25 3.3 Filling available excavated earth (excluding rock) in trenches, plinth, sides
of foundations etc. in layer not exceeding 20cm in depth, consolidating
each deposited layer by ramming and watering, lead up to 50 m and lift
upto 1.5 m cum 1350 112.40 151,740.00
4.1 3.4 Providing and laying in position cement concrete of specified grade
excluding the cost of centring and shuttering - All work upto plinth level.
4.1.5 3.4.1 1:4:8(1cement :4coarse sand :8graded stones aggregate 40 mm nominal
size). cum 26 4,834.30 125,691.80
5.33 3.5 Providing and laying in position machine batched and machine mixed
design mix M-25 grade cement concrete for reinforced cement concrete
work,using cement content as par approved design mix, including
pumping of concrete to site of laying but excluding the cost of centring,
shuttering, finishing and reinforcement. including admixtures in
recommended proportions. as per IS 9103 to accelerate, retard setting of
concrete improve workability without impairing strength and durability as
per direction of Engineer-in-Charge.
(Note:-cement concrete considered in this item is @ 330 kg/cum.
Excess/less cement used as per design mix. is payable/recoverable
separately)

5.33.1 3.5.1 All works upto plinth level. cum 90 6,296.15 566,653.50
5.33.2 3.5.2 All works above plinth level upto floor V level. cum 5 7,014.55 35,072.75
5.35 3.6 Add for using extra cement in the items of design mix over and above the
specified cement content therein quintal 65 742.75 48,278.75

BOQ - SD 12
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
5.9 3.7 Centring and shuttering including strutting, propping etc.and removal of
form work for :
5.9.1 3.7.1 Foundations, footings, bases of columns SqM 165 196.45 32,414.25
5.9.6 3.7.2 Columns, Pillars, Piers, Abutments, Posts and Struts SqM 335 453.35 151,872.25
5.9.5 3.7.3 Lintels, beams, plinth beams, girders, bressumers and cantilevers. sqm 113 332.15 37,532.95
6.1 3.8 Brick work F.P.S. bricks of class designation 75 in foundation and plinth in
:
6.1.2 3.8.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 60 4,677.25 280,635.00
6.4 3.9 Brick work with common burnt clay F.P.S. (non modular) bricks of class
designation 7.5 in superstructure above plinth level up to floor V level in all
shapes and sizes in :

6.4.2 3.9.1 Cement mortar 1:6 (1 cement : 6 coarse sand) cum 20 5,426.15 108,523.00
10.25 3.10 Steel work welded in built up sections/framed work including cutting
hoisting, fixing in position and applying a priming coat of approved steel
primer using structural steel etc.as required.
10.25.2 3.10.1 In gratings, frames, guard bar, ladders, railings, brackets, gates & similar
works. kg 410 90.10 36,941.00
13.62 3.11 Painting with synthetic enamel paint of approved brand and manufacture
of required colour to give an even shade:
13.62.1 3.11.1 Two or more coats on new work over an under coat of suitable shade with
ordinary paint of approved brand and manufacture. SqM 18 106.25 1,912.50
4.2 3.12 Providing and laying cement concrete in retaining walls, return walls,
walls (any thickness) including attached pilasters, columns, piers,
abutments, pillars, posts, struts, buttresses, string or lacing courses,
parapets, coping, bed blocks, anchor blocks, plain window sills, fillets etc,
upto floor five level, excluding the cost of centering, shuttering and
finishing
4.2.3 3.12.1 1:2:4 (1 Cement : 2 coarse sand :4 graded stone aggregate 20 mm
nominal size) cum 1 6,450.00 6,450.00
5.22 3.13 Reinforcement for R.C.C. work including straightening, cutting, bending,
placing in position and binding all complete upto plinth
5.22.6 3.13.1 Thermo-Mechanically Treated bars Kg 13800 68.10 939,780.00
5.22A 3.14 Steel reinforcement for R.C.C. work including straightening, cutting,
bending, placing in position and binding all complete above plinth level.

5.22A.6 3.14.1 Thermo-Mechanically Treated bars Kg 915 68.10 62,311.50

BOQ - SD 13
DSR - RATE (RS.) AMOUNT(RS.)
SL.
2014/ DESCRIPTION OF ITEM UNIT QTY
NO. DSR NS DSR ITEMS NS ITEMS
NS
13.3 3.15 20 mm cement plaster of mix

13.3.1 3.15.1 1:4 (1 cement : 4 fine sand) sqm 760 228.10 173,356.00
13.47 3.16 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone
additives of required shade
13.47.1 3.16.1 New work (Two or more coats applied @ 1.43 ltr/10 sqm. over and
including priming coat of exterior primer applied @ 2.20 kg/10 sqm). sqm 760 94.95 72,162.00
5.12 3.17 Providing, hoisting and fixing up to floor five level precast reinforced
cement concrete work in string courses, bands, copings, bed plates,
anchor blocks, plain window sills and the like, including the cost of
required centering, shuttering but excluding cost of reinforcement, with
1:2:4 (1 cement: 2 coarse sand: 4 graded stone aggregate 20 mm nominal
size). cum 5 6,447.95 32,239.75
16.53 3.18 Providing and fixing concertina coil fencing with punched tape concertina
coil 600 mm dia 10 metre openable length ( total length 90 m), having 50
nos rounds per 6 metre length, upto 3 m height of wall with existing angle
iron Y shaped placed 2.4 m or 3.00 m apart and with 9 horizontal R.B.T.
reinforced barbed wire, stud tied with G.I. staples and G.I. clips to retain
horizontal, including necessary bolts or G.I. barbed wire tied to angle iron,
all complete as per direction of Engineer-in-charge, with reinforced barbed
tape(R.B.T.) / Spring core (2.5mm thick) wire of high tensile strength of
165 kg/ sq.mm with tape (0.52 mm thick) and weight 43.478 gm/ metre
(cost of M.S. angle, C.C. blocks shall be paid separately)
metre 188 287.05 53,965.40
TOTAL OF BOUNDARY ALONG TECHNICAL SECTOR CARRIED
OVER TO SUMMARY OF SITE DEVELOPMENT WORKS 3,161,589.65 -

BOQ - SD 14