Type : A318/A319/A320/A321 Selected applicability : ALL


Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

** ON A/C ALL

21-20 - DISTRIBUTION

21-20-00 - DISTRIBUTION

21-20-00 PB 001 CONF 00 - DISTRIBUTION - DESCRIPTION AND OPERATION

1. General
The distribution system delivers conditioned air to the pressurized fuselage.
2. System Description

** ON A/C 201-250
The air distribution system has the subsequent subsystems:
cabin air distribution and recirculation (Ref. AMM D/O 21-21-00-00) ,
cockpit air ventilation (Ref. AMM D/O 21-21-00-00) ,
lavatory/galley ventilation (Ref. AMM D/O 21-23-00-00) ,
individual air distribution (Ref. AMM D/O 21-24-00-00) ,
avionics equipment ventilation (Ref. AMM D/O 21-26-00-00) ,

** ON A/C 001-014, 016-200


The air distribution system has the subsequent subsystems:
cabin air distribution and recirculation (Ref. AMM D/O 21-21-00-00) ,
cockpit air ventilation (Ref. AMM D/O 21-21-00-00) ,
lavatory/galley ventilation (Ref. AMM D/O 21-23-00-00) ,
individual air distribution (Ref. AMM D/O 21-24-00-00) ,
avionics equipment ventilation (Ref. AMM D/O 21-26-00-00) ,
cargo compartment ventilation (Ref. AMM D/O 21-28-00-00) .

** ON A/C ALL
A. Cabin Air Distribution and Recirculation
The cabin air distribution system supplies conditioned air to the cabin and to the cockpit. Cockpit and cabin
main supply ducts come from the mixer unit, which is central element of the distribution system.
In the mixer unit the fresh air from the air conditioning packs is mixed with a part of the exhaust air of the
cabin and the underfloor area. This recirculated air is drawn by recirculation fans through recirculation filters
to the mixer unit.
B. Cockpit Air Ventilation
The cockpit-air ventilation system supplies temperature controlled and conditioned air to the cockpit. The
airflow comes from the cabin air distribution system from the mixer unit in a separate duct. The air flows
from air outlets and individual air outlets into the cockpit.
C. Lavatory/Galley Ventilation
The lavatory/galley ventilation system supplies the lavatories and galleys with sufficient temperature
controlled and conditioned air. Air flows from the cabin into the lavatories and galleys. Air also flows into the
lavatories from the cabin air distribution and recirculation system through individual air outlets.
The air flows from the lavatories and galleys into an extraction duct in the area of the outflow valve and then
out of the aircraft. An extraction fan gives the necessary airflow.
D. Individual Air Distribution
The individual air distribution system supplies temperature controlled and conditioned air from the cabin
distribution and recirculation system to each passenger through individual air outlets.
E. Avionics-Equipment Ventilation System

Print Date: December 23, 2016 Page 1 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

The avionics equipment ventilation system makes sure that the avionics racks have a good flow of air
for cooling. It operates in different configurations. These configurations are dependent on the ambient
temperature, whether the aircraft is on ground, in flight or a system failure exists.

** ON A/C 001-014, 016-200


F. Cargo Compartment Ventilation
Cabin air is drawn into the cargo compartment through ducts which are installed in the lower fuselage.
Outlets along the compartment left-hand sidewall direct the air towards the cargo floor area. The air is
extracted from the compartment through outlets which are located near the compartment ceiling. An
extraction fan gives the necessary air flow.

** ON A/C ALL

21-20-00 PB 201 CONF 00 - DISTRIBUTION - MAINTENANCE PRACTICES

TASK 21-20-00-010-001-A
Removal of the Air-Conditioning Distribution Ducts

WARNING: MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE
MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.

1. Reason for the Job


Self explanatory
2 Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment

REFERENCE QTY DESIGNATION


No specific AR ACCESS PLATFORM 2M (6 FT)
No specific AR SAFETY CLIP - CIRCUIT BREAKER

B. Work Zones and Access Panels

ZONE/ACCESS ZONE DESCRIPTION


811, 824,
825, 826

C. Referenced Information

REFERENCE DESIGNATION
24-41-00-861-002-A Energize the Aircraft Electrical Circuits from the External Power
24-41-00-861-002-A-01 Energize the Aircraft Electrical Circuits from the APU
24-41-00-861-002-A-02 Energize the Aircraft Electrical Circuits from Engine 1(2)
25-13-41-000-001-A Removal of the Ceiling Panels
25-23-42-000-001-A Removal of the Ceiling Panels - Forward Utility Area
25-23-43-000-001-A Removal of the Upper Sidewall Panel(s)
25-23-44-000-001-A Removal of the Lower Sidewall-Panels (Dado Panels)
25-41-41-000-001-A Removal of the Lavatory A
25-54-12-000-001-A Removal of the Forward Cargo-Compartment Partition FR34
25-54-12-000-002-A Removal of the Ceiling Panels in the Forward Cargo-Compartment

Print Date: December 23, 2016 Page 2 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

REFERENCE DESIGNATION
25-54-12-000-003-A Removal of the Sidewall Panels in the Forward Cargo-Compartment
25-55-11-000-001-A Removal of the Aft Cargo-Compartment Partition FR47
25-55-11-000-002-A Removal of the Ceiling Panels in the Aft Cargo-Compartment - FR47/
FR59
25-55-11-000-003-A Removal of the Sidewall Panels in the Aft Cargo-Compartment - FR47/
FR59
25-55-12-000-001-A Removal of the Aft Cargo-Compartment Partition FR65
25-55-12-000-002-A Removal of the Ceiling Panels in the Aft Cargo Compartment - FR59/
FR65
25-55-12-000-003-A Removal of the Sidewall Panels in the Aft Cargo Compartment - FR59/
FR65
52-30-00-860-001-A Open the FWD or Aft Cargo-Compartment Door with the Yellow Elec-
tric Pump
52-41-00-010-002-A Open the Avionics Compartment Doors for Access
53-12-13-000-001-A Removal of the avionics compartment floor panels
53-32-12-000-002-A Removal of the Cabin Floor Panels
06-41-53-00 FUSELAGE - DESCRIPTION AND OPERATION
21-21-00-00 AIR DISTRIBUTION AND RECIRCULATION - DESCRIPTION AND
OPERATION
Distribution Ducts Location SHEET 1
Examples of Distribution Duct Connections SHEET 1
Examples of Distribution Duct Attachment Methods SHEET 1

Print Date: December 23, 2016 Page 3 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

RISER DUCTS

FWD CARGO COMPARTMENT


VENTILATION DUCTS

SUPPLY DUCTS

COCKPIT RISER DUCT

FWD CABIN AND CARGO


COMPARTMENT AREA

RISER DUCTS

SUPPLY DUCTS

WING BOX AREA

RISER DUCTS

SUPPLY DUCTS

AFT CARGO COMPARTMENT


VENTILATION DUCTS
AFT CABIN AND CARGO
COMPARTMENT AREA N_MM_212000_2_AAM0_01_01

Figure 21-20-00-991-00100-00-A / SHEET 1/1 - Distribution Ducts Location


** ON A/C ALL

Print Date: December 23, 2016 Page 4 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

4 5
1
2 6
3

2
1

1
1 2
7
2
9
10

1
2 'A'

2
1

'A'

'A'= APROX AREA FOR POSITION


OF CLAMP LOCK FOR OVAL
SHAPED DUCT CONNECTIONS

N_MM_212000_2_ABM0_01_00

Figure 21-20-00-991-00200-00-A / SHEET 1/1 - Examples of Distribution Duct Connections


** ON A/C ALL

Print Date: December 23, 2016 Page 5 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

20

20 21

21

22

21
20

23

25

'A'

24
21

20

'A'

'A'= APROX AREA FOR POSITION


OF CLAMP LOCK FOR OVAL
SHAPED DUCT CONNECTIONS
N_MM_212000_2_ACM0_01_00

Figure 21-20-00-991-00300-00-A / SHEET 1/1 - Examples of Distribution Duct Attachment Methods


** ON A/C ALL

Print Date: December 23, 2016 Page 6 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

3. Job Set-up
Subtask 21-20-00-861-050-A
A. Energize the aircraft electrical circuits (Ref. AMM TASK 24-41-00-861-002) .
Subtask 21-20-00-865-050-A
B. Open, safety and tag this(these) circuit breaker(s):

PANEL DESIGNATION FIN LOCATION


122VU AIR COND/RECIRC FAN/R/SPLY 3HG W18
122VU AIR COND/RECIRC FAN/L/SPLY 1HG X18
Subtask 21-20-00-941-050-A
C. Safety Precautions
(1) On the panel 30VU:
(a) Make sure that:
the APU BLEED pushbutton switch is in the off position (the ON legend is off) and,
the ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF
legends are on).
(b) Put a warning notice in position to tell persons not to operate these pushbutton switches.
(2) On the HP and the LP ground connector put a warning notice in position to tell persons not to supply
the ground air.
Subtask 21-20-00-010-050-A
D. Get Access
(1) For the cockpit area supply and ventilation ducts:
(a) Get access to the cockpit.
(b) For the location of the ventilation ducts in the cockpit, refer to (Ref. AMM D/O 21-21-00-00) .
(c) For the location of the applicable cockpit panel, refer to (Ref. AMM D/O 06-41-53-00) .
(d) Remove the access panels as necessary (Ref. AMM TASK 25-13-41-000-001) .
(2) For the cockpit riser duct on the LH side at FR13:
(a) Remove the lavatory (Ref. AMM TASK 25-41-41-000-001) .
(b) Remove the ceiling panel 221AC as necessary (Ref. AMM TASK 25-23-42-000-001) .
(3) For the supply and ventilation ducts in the avionics compartment:
(a) Put an ACCESS PLATFORM 2M (6 FT) in position at access door 824 and access door 811.
(b) Open the access door 824 and 811 (Ref. AMM TASK 52-41-00-010-002) .
(c) For the location of the applicable access panel, refer to (Ref. AMM D/O 06-41-53-00) .
(d) Remove the access panels as necessary (Ref. AMM TASK 53-12-13-000-001) .
(4) For the cabin area supply and the cargo-compartment ventilation ducts in the FWD cargo
compartment area:
(Ref. Fig. Distribution Ducts Location SHEET 1)
(a) Put the ACCESS PLATFORM 2M (6 FT) in position at the FWD cargo-compartment door 825.
(b) Open the FWD cargo-compartment door 825 (Ref. AMM TASK 52-30-00-860-001) .
(c) Remove the access panels as necessary (Ref. AMM TASK 25-54-12-000-001) ,
(Ref. AMM TASK 25-54-12-000-002) or (Ref. AMM TASK 25-54-12-000-003) .

Print Date: December 23, 2016 Page 7 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

(5) For the cabin area supply ducts in the MID cabin and the wing box area:
(a) Remove the cabin floor panels as necessary (Ref. AMM TASK 53-32-12-000-002) .
(6) For the cabin area supply and the cargo-compartment ventilation ducts in the AFT cargo
compartment area:
(a) Put the ACCESS PLATFORM 2M (6 FT) in position at the AFT cargo-compartment door 826.
(b) Open the AFT cargo-compartment door 826 (Ref. AMM TASK 52-30-00-860-001) .
(c) Remove the access panels as necessary (Ref. AMM TASK 25-55-11-000-001) ,
(Ref. AMM TASK 25-55-11-000-002) , (Ref. AMM TASK 25-55-11-000-003) ,
(Ref. AMM TASK 25-55-12-000-001) , (Ref. AMM TASK 25-55-12-000-002) or
(Ref. AMM TASK 25-55-12-000-003) .
(7) For the riser ducts in the cabin area:
(a) Remove the upper and the lower sidewall panels as necessary (Ref. AMM TASK 25-23-44-000-
001) and (Ref. AMM TASK 25-23-43-000-001) .
4. Procedure
Subtask 21-20-00-020-050-A
A. Removal of an Air-Conditioning Distribution Duct
(1) Applicable on duct connection method:
(Ref. Fig. Examples of Distribution Duct Connections SHEET 1)
(a) Remove the clamps (2) and the bellows (3) or,
(b) Remove the nuts (4), the screws (6) and the seal (5) or,
(c) Remove the clamp (2) and the hose (10) or,
(d) Remove the clamps (2) and the sleeve (8).
(2) Applicable on duct attachment method:
(Ref. Fig. Examples of Distribution Duct Attachment Methods SHEET 1)
(a) Remove the screws (20), the washers (21) and the duct (1).
(b) Remove the clamp (22) and the duct (1).
(3) Where applicable make identification marks on the restrictors (9) and their positions in the duct (1).

NOTE: This will assist in the correct position of the restrictors on installation.

(4) Put protective covers on the open ends of the ducts and the related connections.

TASK 21-20-00-410-001-A
Installation of the Air-Conditioning Distribution Ducts

WARNING: MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE
MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.

1. Reason for the Job


Self explanatory
2 Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment

Print Date: December 23, 2016 Page 8 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

REFERENCE QTY DESIGNATION


No specific 2 ACCESS PLATFORM 2M (6 FT)

B. Consumable Materials

REFERENCE DESIGNATION
(Material No. 05RAJ9) Adhesive Film Tape-- Film PTFE -
(Material No. 05TGA1) Adhesive Tape-Insulation Blanket - -

C. Work Zones and Access Panels

ZONE/ACCESS ZONE DESCRIPTION


811, 824,
825, 826

D. Referenced Information

REFERENCE DESIGNATION
12-33-21-618-001-A Pre-conditioning through the LP Ground Connection
12-33-21-618-001-A-01 Pre-conditioning through the HP Ground Connection
12-33-21-618-001-A-02 Pre-conditioning with the APU
24-41-00-861-002-A Energize the Aircraft Electrical Circuits from the External Power
24-41-00-861-002-A-01 Energize the Aircraft Electrical Circuits from the APU
24-41-00-861-002-A-02 Energize the Aircraft Electrical Circuits from Engine 1(2)
24-41-00-862-002-A De-energize the Aircraft Electrical Circuits Supplied from the External
Power
24-41-00-862-002-A-01 De-energize the Aircraft Electrical Circuits Supplied from the APU
24-41-00-862-002-A-02 De-energize the Aircraft Electrical Circuits Supplied from the Engine
1(2)
25-13-41-000-001-A Removal of the Ceiling Panels
25-13-41-400-001-A Installation of the Ceiling Panels
25-23-42-000-001-A Removal of the Ceiling Panels - Forward Utility Area
25-23-42-400-001-A Installation of the Ceiling Panels - Forward Utility Area
25-23-43-000-001-A Removal of the Upper Sidewall Panel(s)
25-23-43-400-001-A Installation of the Upper Sidewall Panel(s)
25-23-44-000-001-A Removal of the Lower Sidewall-Panels (Dado Panels)
25-23-44-400-001-A Installation of the Lower Sidewall-Panels (Dado Panels)
25-41-41-000-001-A Removal of the Lavatory A
25-41-41-400-001-A Installation of the Lavatory A
25-54-12-000-001-A Removal of the Forward Cargo-Compartment Partition FR34
25-54-12-000-002-A Removal of the Ceiling Panels in the Forward Cargo-Compartment
25-54-12-000-003-A Removal of the Sidewall Panels in the Forward Cargo-Compartment
25-54-12-400-001-A Installation of the Forward Cargo-Compartment Partition FR34
25-54-12-400-002-A Installation of the Ceiling Panels in the Forward Cargo-Compartment
25-54-12-400-003-A Installation of the Sidewall Panels in the Forward Cargo- Compartment
25-55-11-000-001-A Removal of the Aft Cargo-Compartment Partition FR47
25-55-11-000-002-A Removal of the Ceiling Panels in the Aft Cargo-Compartment - FR47/
FR59
25-55-11-000-003-A Removal of the Sidewall Panels in the Aft Cargo-Compartment - FR47/
FR59

Print Date: December 23, 2016 Page 9 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

REFERENCE DESIGNATION
25-55-11-400-001-A Installation of the Aft Cargo-Compartment Partition FR47
25-55-11-400-002-A Installation of the Ceiling Panels in the Aft Cargo-Compartment - FR47/
FR59
25-55-11-400-003-A Installation of the Sidewall Panels in the Aft Cargo-Compartment -
FR47/FR59
25-55-12-000-001-A Removal of the Aft Cargo-Compartment Partition FR65
25-55-12-000-002-A Removal of the Ceiling Panels in the Aft Cargo Compartment - FR59/
FR65
25-55-12-000-003-A Removal of the Sidewall Panels in the Aft Cargo Compartment - FR59/
FR65
25-55-12-400-001-A Installation of the Aft Cargo-Compartment Partition FR65
25-55-12-400-002-A Installation of the Ceiling Panels in the Aft Cargo Compartment - FR59/
FR65
25-55-12-400-003-A Installation of the Sidewall Panels in the Aft Cargo Compartment -
FR59/FR65
52-30-00-860-001-A Open the FWD or Aft Cargo-Compartment Door with the Yellow Elec-
tric Pump
52-30-00-860-002-A Close the FWD or Aft Cargo-Compartment Door with the Yellow Elec-
tric Pump
52-41-00-010-002-A Open the Avionics Compartment Doors for Access
52-41-00-410-002-A Close the Avionics Compartment Doors after Access
53-12-13-400-001-A Installation of the avionics compartment floor panels
53-32-12-000-002-A Removal of the Cabin Floor Panels
53-32-12-400-002-A Installation of the Cabin Floor Panels
Distribution Ducts Location SHEET 1
Examples of Distribution Duct Connections SHEET 1
Examples of Distribution Duct Attachment Methods SHEET 1

3. Job Set-up
Subtask 21-20-00-860-050-A
A. Aircraft Maintenance Configuration
(1) Make sure that:
(a) The aircraft electrical circuits are energized (Ref. AMM TASK 24-41-00-861-002) .
(b) On the panel 30VU:
1 The APU BLEED pushbutton switch is in the off position (the ON legend is off).
2 The ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the
OFF legends are on).
3 The warning notice to tell persons not to operate these pushbutton switches is in position.
(c) On the HP and the LP ground connector the warning notice to tell persons not to supply the
ground air is in position.
(d) For the cockpit area supply and ventilation ducts:
the access panels are removed as necessary (Ref. AMM TASK 25-13-41-000-001) .
(e) For the cockpit riser duct on the LH side at FR13:
the lavatory is removed (Ref. AMM TASK 25-41-41-000-001) .
the ceiling panel 221AC is removed as necessary (Ref. AMM TASK 25-23-42-000-001) .
(f) For the supply and ventilation ducts in the avionics compartment:

Print Date: December 23, 2016 Page 10 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

the ACCESS PLATFORM 2M (6 FT) is in position at access door 824 and 811, as necessay.
the access doors 824 and 811 are open (Ref. AMM TASK 52-41-00-010-002) .
(g) For the cabin area supply and the cargo-compartment ventilation ducts in the FWD cargo
compartment area:
(Ref. Fig. Distribution Ducts Location SHEET 1)
the ACCESS PLATFORM 2M (6 FT) is in position at the FWD cargo-compartment door 825,
the FWD cargo-compartment door 825 is open (Ref. AMM TASK 52-30-00-860-001) ,
the access panels are removed as necessary (Ref. AMM TASK 25-54-12-000-001) ,
(Ref. AMM TASK 25-54-12-000-002) or (Ref. AMM TASK 25-54-12-000-003) .
(h) For the cabin area supply ducts in the MID cabin and the wing box area:
the cabin floor panels are removed as necessary (Ref. AMM TASK 53-32-12-000-002) .
(i) For the cabin area supply and the cargo-compartment ventilation ducts in the AFT cargo
compartment:
the ACCESS PLATFORM 2M (6 FT) is in position at the AFT cargo-compartment door 826,
the AFT cargo-compartment door 826 is open (Ref. AMM TASK 52-30-00-860-001) ,
the access panels are removed as necessary (Ref. AMM TASK 25-55-11-000-
001) , (Ref. AMM TASK 25-55-11-000-002) , (Ref. AMM TASK 25-55-11-000-003) ,
(Ref. AMM TASK 25-55-12-000-001) , (Ref. AMM TASK 25-55-12-000-002) or
(Ref. AMM TASK 25-55-12-000-003) .
(j) For the riser ducts in the cabin area:
the upper and the lower sidewall panels are removed as necessary (Ref. AMM TASK 25-23-
44-000-001) and (Ref. AMM TASK 25-23-43-000-001) .
Subtask 21-20-00-865-051-A
B. Make sure that this(these) circuit breaker(s) is(are) open, safetied and tagged:

PANEL DESIGNATION FIN LOCATION


122VU AIR COND/RECIRC FAN/R/SPLY 3HG W18
122VU AIR COND/RECIRC FAN/L/SPLY 1HG X18
4. Procedure
Subtask 21-20-00-560-050-A
A. Preparation of the Replacement Air-Conditioning Distribution Duct
(1) Where applicable remove the attached components, for example drain hose, blanking caps,
restrictors etc. from the removed duct.

NOTE: Identify the respective positions of the restrictors on the removed duct. The restrictors must
be installed in the identical positions on the replacement duct. The position of the restrictors is
not usually interchangeable.

(2) Install the removed components in their correct respective positions on the replacement duct.
Subtask 21-20-00-420-050-A
B. Installation of an Air-Conditioning Distribution Duct
(1) Remove the protective covers from the ends of the ducts and the related connections.
(2) Where applicable make sure that:
(Ref. Fig. Examples of Distribution Duct Connections SHEET 1)
(a) The blanking caps (7) and the clamps (2) are correctly installed.
(b) The restrictors (9) are correctly installed in the duct (1).

Print Date: December 23, 2016 Page 11 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

NOTE: The restrictors (9) must be installed in the original position in the duct. The position of the
restrictors is not usually interchangeable.

(Ref. Fig. Examples of Distribution Duct Attachment Methods SHEET 1)


(3) Put the duct (1) in position and, applicable upon duct attachment method:
(a) Install the washers (21) and the screws (20) or,
(b) Put the clamps (25) in position and install the washers (21) and the screws (20) or,
(c) Put the clamps (22) in position on the brackets (23),
make sure that the clamps (22) are correctly installed on the brackets (23),
tighten the clamps (22).

NOTE: On oval shaped ducts make sure that the clamp lock is in the correct position on the duct
ellipse. On the cabin riser ducts make sure that, where possible, the clamp lock is posi-
tioned on the outboard side of the duct. This will help to give sufficient clearance when
you install the sidewall panels.

(4) Applicable upon the type of duct connection,


(Ref. Fig. Examples of Distribution Duct Connections SHEET 1)

NOTE: On oval shaped ducts make sure that the clamp lock is in the correct position on the duct el-
lipse. On duct end connections with one coloured marking on only one duct end you must
make sure that the ends of the bellows, sleeve or hose cover the coloured marking. On duct
end connections with one coloured marking on each duct end you must make sure that the
ends of the bellows, sleeve or hose are between the coloured markings. On the cabin riser
ducts make sure that, where possible, the clamp lock is positioned on the outboard side of the
duct. This will help to give sufficient clearance when you install the sidewall panels.

(a) Put the hose (10) and the clamp (2) in position on the duct (1) and tighten the clamp (2) or,
(b) Put the seal (5) in position between the ducts (1) and install the screws (6) and the nuts (4).
(c) Put the bellows (3) and the clamps (2) in position on the duct (1) and tighten the clamps (2) or,
(d) Put the sleeve (8) and the clamps (2) in position on the duct (1) and tighten the clamps (2).
(5) If previously installed:
(a) Apply rub coat on the duct as protection:
cut a piece of the tape Adhesive Film Tape-- Film PTFE - (Material No. 05RAJ9) and put it in
position on the duct.
wind 2 layers of tape Adhesive Tape-Insulation Blanket - - (Material No. 05TGA1) around the
duct.
Subtask 21-20-00-865-052-A
C. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):

PANEL DESIGNATION FIN LOCATION


122VU AIR COND/RECIRC FAN/R/SPLY 3HG W18
122VU AIR COND/RECIRC FAN/L/SPLY 1HG X18
Subtask 21-20-00-710-050-A
D. Leak Check of the Air-Conditioning Distribution Ducts
(1) Do the pre-conditioning through the LP ground connection (Ref. AMM TASK 12-33-21-618-001) .
(2) Do a check for leaks at the duct connections.

Print Date: December 23, 2016 Page 12 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

NOTE: Leaks are not allowed.

(3) Stop the pre-conditioning through the LP ground connection (Ref. AMM TASK 12-33-21-618-001) .
5. Close-up
Subtask 21-20-00-410-050-A
A. Close Access
(1) For the cockpit area supply and ventilation ducts:
(a) Install the access panels as necessary (Ref. AMM TASK 25-13-41-400-001) .
(2) For the cockpit riser duct on the LH side at FR13:
(a) Install the ceiling panel 221AC as necessary (Ref. AMM TASK 25-23-42-400-001) .
(b) Install the lavatory (Ref. AMM TASK 25-41-41-400-001) .
(3) For the supply and ventilation ducts in the avionics compartment:
(a) Install the access panels as necessary (Ref. AMM TASK 53-12-13-400-001) .
(b) Close the access doors 824, 811 (Ref. AMM TASK 52-41-00-410-002) .
(c) Remove the ACCESS PLATFORM 2M (6 FT).
(4) Make sure that the work area is clean and clear of tools and other items.
(5) For the cabin area supply and the cargo-compartment ventilation ducts in the FWD cargo
compartment area:
(Ref. Fig. Distribution Ducts Location SHEET 1)
(a) Install the access panels as necessary (Ref. AMM TASK 25-54-12-400-001) ,
(Ref. AMM TASK 25-54-12-400-002) or (Ref. AMM TASK 25-54-12-400-003) .
(b) Close the FWD cargo-compartment door 825 (Ref. AMM TASK 52-30-00-860-002) .
(c) Remove the ACCESS PLATFORM 2M (6 FT).
(6) For the cabin area supply ducts in the MID cabin and the wing box area:
(a) Install the cabin floor panels as necessary (Ref. AMM TASK 53-32-12-400-002) .
(7) For the riser ducts in the cabin area:
(a) Install the upper and the lower sidewall panels as necessary (Ref. AMM TASK 25-23-43-400-
001) and (Ref. AMM TASK 25-23-44-400-001) .
(8) For the cabin area supply and the cargo-compartment ventilation ducts in the AFT cargo
compartment area:
(a) Install the access panels as necessary (Ref. AMM TASK 25-55-11-400-001) ,
(Ref. AMM TASK 25-55-11-400-002) , (Ref. AMM TASK 25-55-11-400-003) ,
(Ref. AMM TASK 25-55-12-400-001) , (Ref. AMM TASK 25-55-12-400-002) or
(Ref. AMM TASK 25-55-12-400-003) .
(b) Close the AFT cargo-compartment door 826 (Ref. AMM TASK 52-30-00-860-002) .
(c) Remove the ACCESS PLATFORM 2M (6 FT).
(9) Remove the warning notice(s).
Subtask 21-20-00-862-050-A
B. De-energize the aircraft electrical circuits (Ref. AMM TASK 24-41-00-862-002)
Figure 21-20-00-991-00100-00-A / SHEET 1/1 - Distribution Ducts Location
Figure 21-20-00-991-00200-00-A / SHEET 1/1 - Examples of Distribution Duct Connections
Figure 21-20-00-991-00300-00-A / SHEET 1/1 - Examples of Distribution Duct Attachment Methods

Print Date: December 23, 2016 Page 13 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

21-20-00 PB 601 CONF 00 - DISTRIBUTION - INSPECTION/CHECK

TASK 21-20-00-210-001-A
General Visual Inspection of the Riser Ducts in the Passenger Compartment

WARNING: MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE
MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.

1. Reason for the Job


Refer to the MPD TASK: 212100-02
GENERAL VISUAL INSPECTION OF RISER DUCTS IN THE PASSENGER COMPARTMENT
2 Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment

REFERENCE QTY DESIGNATION


No specific AR SAFETY CLIP - CIRCUIT BREAKER

B. Work Zones and Access Panels

ZONE/ACCESS ZONE DESCRIPTION


230 FWD PASSENGER COMPARTMENT
240 MID PASSENGER COMPARTMENT
250 AFT PASSENGER COMPARTMENT

C. Referenced Information

REFERENCE DESIGNATION
21-20-00-010-001-A Removal of the Air-Conditioning Distribution Ducts
21-20-00-410-001-A Installation of the Air-Conditioning Distribution Ducts
25-23-41-000-001-A Removal of the Ceiling Panels
25-23-41-400-001-A Installation of the Ceiling Panels
25-23-43-000-001-A Removal of the Upper Sidewall Panel(s)
25-23-43-400-001-A Installation of the Upper Sidewall Panel(s)
25-23-44-000-001-A Removal of the Lower Sidewall-Panels (Dado Panels)
25-23-44-400-001-A Installation of the Lower Sidewall-Panels (Dado Panels)
25-23-48-000-001-A Removal of the Cove Light Panels
25-23-48-400-001-A Installation of the Cove Light Panels
Riser Ducts - General Component Location SHEET 1

Print Date: December 23, 2016 Page 14 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

FWD CABIN AREA


RISER
DUCTS

MID CABIN AREA

RISER
DUCTS

AFT CABIN AREA

RISER
DUCTS

N_MM_212000_6_AAM0_01_00

Figure 21-20-00-991-00400-00-A / SHEET 1/1 - Riser Ducts - General Component Location


** ON A/C ALL

Print Date: December 23, 2016 Page 15 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

3. Job Set-up
Subtask 21-20-00-010-055-A
A. Get Access
(1) Remove, when installed, the passenger compartment seats (refer to AMM chapter 25-21).
(2) Remove the ceiling panels (Ref. AMM TASK 25-23-41-000-001) .

** ON A/C 101-200
Subtask 21-20-00-010-056-A
B. Get Access
(1) Remove, when installed,
(a) the forward lavatory/ies (refer to AMM chapter 25-41),
(b) the middle lavatory (refer to AMM chapter 25-42) and,
(c) the aft lavatory/ies (refer to AMM chapter 25-43).
Subtask 21-20-00-010-057-B
C. Get Access
(1) Remove, when installed,
(a) the forward galley units (refer to AMM chapter 25-31),
(b) the middle galley units (refer to AMM chapter 25-32) and,
(c) the aft galley units (refer to AMM chapter 25-33).
Subtask 21-20-00-010-051-B
D. Get Access
(1) Remove,
(a) the lower sidewall panels between frames C21 to C35, C35.3 to C47.2 and C48 to C66
(Ref. AMM TASK 25-23-44-000-001) ,
(b) the upper sidewall panels between frames C21 to C35, C35.3 to C38, C40 to C47.2 and C48 to
C66 (Ref. AMM TASK 25-23-43-000-001) and,
(c) the cove light panels between frames C21 to C35, C35.3 to C38, C40 to C47.2 and C48 to C66
(Ref. AMM TASK 25-23-48-000-001) .

** ON A/C 001-014, 016-100, 201-250


Subtask 21-20-00-010-056-B
B. Get Access
(1) Remove, when installed,
(a) the forward lavatory/ies (refer to AMM chapter 25-41) and,
(b) the aft lavatory/ies (refer to AMM chapter 25-43).
Subtask 21-20-00-010-057-A
C. Get Access
(1) Remove, when installed,
(a) the forward galley units (refer to AMM chapter 25-31),
(b) the aft galley units (refer to AMM chapter 25-33).

Print Date: December 23, 2016 Page 16 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

Subtask 21-20-00-010-051-A
D. Get Access
(1) Remove,
(a) the lower sidewall panels between frames C21 to C37, C39 to C40 and C41 to C66
(Ref. AMM TASK 25-23-44-000-001) ,
(b) the upper sidewall panels between frames C21 to C37, C39 to C40 and C41 to C66
(Ref. AMM TASK 25-23-43-000-001) and,
(c) the cove light panels between frames C21 to C65 (Ref. AMM TASK 25-23-48-000-001) .

** ON A/C ALL
Subtask 21-20-00-865-053-A
E. Open, safety and tag this(these) circuit breaker(s):

PANEL DESIGNATION FIN LOCATION


122VU AIR COND/RECIRC FAN/R/SPLY 3HG W18
122VU AIR COND/RECIRC FAN/L/SPLY 1HG X18
Subtask 21-20-00-860-053-A
F. Safety Precautions
(1) On the panel 30VU:
(a) Make sure that:
the APU BLEED pushbutton switch is in the off position (the ON legend is off) and,
the ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF
legends are on).
(b) Put a warning notice in position to tell persons not to operate these pushbutton switches.
(2) On the HP and the LP ground connector put a warning notice in position to tell persons not to supply
the ground air.
4. Procedure
Subtask 21-20-00-210-050-B
A. Inspection
(Ref. Fig. Riser Ducts - General Component Location SHEET 1)
(1) Do a general visual inspection of the riser ducts for:
breakages, cracks and delamination of the composite material,
security of installation of the duct system and,
correct installation and general condition of the duct connections.
(a) Replace any worn, delaminated or damaged components and safety any loose installation (refer
to examples in)
(Ref. AMM TASK 21-20-00-010-001) and,
(Ref. AMM TASK 21-20-00-410-001)
(2) Do a visual inspection of the insulation of the riser ducts for:
damages.
(a) Repair small damages of the insulation:
Apply wear protection to the insulation (Ref. Duct Fuel Pipe Repair Manual - DFPRM 51-12-
00),
(b) If necessary, replace any damaged components.

Print Date: December 23, 2016 Page 17 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

Subtask 21-20-00-865-055-A
B. Remove the safety clip(s) and the tag(s) and close this(these) circuit breaker(s):

PANEL DESIGNATION FIN LOCATION


122VU AIR COND/RECIRC FAN/R/SPLY 3HG W18
122VU AIR COND/RECIRC FAN/L/SPLY 1HG X18
5. Close-up

** ON A/C 001-014, 016-100, 201-250


Subtask 21-20-00-410-051-A
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install,
(a) the cove light panels between frames C21 to C65 (Ref. AMM TASK 25-23-48-400-001) ,
(b) the upper sidewall panels between frames C21 to C37, C39 to C40 and C41 to C66
(Ref. AMM TASK 25-23-43-400-001) and,
(c) the lower sidewall panels between frames C21 to C37, C39 to C40 and C41 to C66
(Ref. AMM TASK 25-23-44-400-001) .
Subtask 21-20-00-410-055-A
B. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install, when removed,
(a) the forward galley units (refer to AMM chapter 25-31),
(b) the aft galley units (refer to AMM chapter 25-33).
Subtask 21-20-00-410-056-B
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install, when removed,
(a) the forward lavatory/ies (refer to AMM chapter 25-41),
(b) the aft lavatory/ies (refer to AMM chapter 25-43).

** ON A/C 101-200
Subtask 21-20-00-410-051-B
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install,
(a) the cove light panels between frames C21 to C35, C35.3 to C47.2 and C47.5 to C66
(Ref. AMM TASK 25-23-48-400-001) ,
(b) the upper sidewall panels between frames C21 to C35, C35.3 to C38, C40 to C47.2 and C48 to
C66 (Ref. AMM TASK 25-23-43-400-001) and,
(c) the lower sidewall panels between frames C21 to C35, C35.3 to C47.2 and C48 to C66
(Ref. AMM TASK 25-23-44-400-001) .

Print Date: December 23, 2016 Page 18 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

Subtask 21-20-00-410-055-B
B. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install, when removed,
(a) the forward galley units (refer to AMM chapter 25-31),
(b) the middle galley units (refer to AMM chapter 25-32) and,
(c) the aft galley units (refer to AMM chapter 25-33).
Subtask 21-20-00-410-056-A
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install, when removed,
(a) the forward lavatory/ies (refer to AMM chapter 25-41),
(b) the middle lavatory (refer to AMM 25-42) and,
(c) the aft lavatory/ies (refer to AMM chapter 25-43).

** ON A/C ALL
Subtask 21-20-00-410-057-A
D. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install, when removed, the passenger compartment seats (refer to AMM chapter 25-21).
(3) Install the ceiling panels (Ref. AMM TASK 25-23-41-400-001) .
Subtask 21-20-00-941-051-A
E. Remove the warning notice(s).

TASK 21-20-00-210-002-A
General Visual Inspection of Lavatory and Galley Ventilation Ducting (Zones 220 to 260)

WARNING: MAKE SURE THAT AIR IS NOT SUPPLIED TO THE AIR CONDITIONING SYSTEM FROM THE
MAIN ENGINE, THE APU OR A GROUND SOURCE.
HOT COMPRESSED AIR CAN CAUSE INJURY TO PERSONNEL.

1. Reason for the Job


Refer to the MPD TASK: 212300-01
GENERAL VISUAL INSPECTION OF LAVATORY AND GALLEY VENTILATION DUCTING IN ZONES 210
THROUGH 260
2 Job Set-up Information
A. Fixtures, Tools, Test and Support Equipment

REFERENCE QTY DESIGNATION


No specific AR SAFETY CLIP - CIRCUIT BREAKER

B. Work Zones and Access Panels

Print Date: December 23, 2016 Page 19 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

ZONE/ACCESS ZONE DESCRIPTION


220 FWD CAB UTILITY AREAS
260 AFT CABIN UTILITY AREA
251AX, 251BX,
251CX

C. Referenced Information

REFERENCE DESIGNATION
21-20-00-010-001-A Removal of the Air-Conditioning Distribution Ducts
21-20-00-410-001-A Installation of the Air-Conditioning Distribution Ducts
21-23-00-720-001-A Functional Test of the Galley/Lavatory Air Extraction Duct
25-23-41-000-001-A Removal of the Ceiling Panels
25-23-41-400-001-A Installation of the Ceiling Panels
25-23-43-000-001-A Removal of the Upper Sidewall Panel(s)
25-23-43-400-001-A Installation of the Upper Sidewall Panel(s)
25-23-44-000-001-A Removal of the Lower Sidewall-Panels (Dado Panels)
25-23-44-400-001-A Installation of the Lower Sidewall-Panels (Dado Panels)
25-23-48-000-001-A Removal of the Cove Light Panels
25-23-48-400-001-A Installation of the Cove Light Panels

3. Job Set-up
Subtask 21-20-00-010-053-A
A. Get Access
(1) Remove the cabin ceiling panels between frames C16 and C65 (Ref. AMM TASK 25-23-41-000-
001) .
Subtask 21-20-00-010-052-A
B. Get Access
(1) Remove, if installed, the aft lavatory/ies (refer to AMM chapter 25-43).
Subtask 21-20-00-010-054-A
C. Get Access
(1) Remove,
(a) the lower sidewall panel 251AX between frames C63 and C65 (Ref. AMM TASK 25-23-44-000-
001) ,
(b) the upper sidewall panel 251BX between frames C63 and C65 (Ref. AMM TASK 25-23-43-000-
001) and,
(c) the cove light panel 251CX between frames C63 and C65 (Ref. AMM TASK 25-23-48-000-001) .
Subtask 21-20-00-865-054-A
D. Open, safety and tag this(these) circuit breaker(s):

PANEL DESIGNATION FIN LOCATION


122VU AIR COND/RECIRC FAN/R/SPLY 3HG W18
122VU AIR COND/RECIRC FAN/L/SPLY 1HG X18
Subtask 21-20-00-860-054-A
E. Safety Precautions

Print Date: December 23, 2016 Page 20 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

(1) On the panel 30VU:


(a) Make sure that:
the APU BLEED pushbutton switch is in the off position (the ON legend is off) and,
the ENG 1 BLEED and the ENG 2 BLEED pushbutton switches are in the off position (the OFF
legends are on).
(b) Put a warning notice in position to tell persons not to operate these pushbutton switches.
(2) On the HP and the LP ground connector put a warning notice in position to tell persons not to supply
the ground air.
4. Procedure
Subtask 21-20-00-210-051-A
A. Inspection
(1) Do a general visual inspection of the of the ventilation ducts for:
breakages, cracks and delamination of the composite material,
security of installation of the duct system and,
correct installation and general condition of the duct connections.
on unused connection points make sure that the blanking caps are in a good condition and are
secure.
(2) Replace any worn, delaminated or damaged components and secure any loose installation (refer to
examples in)
(Ref. AMM TASK 21-20-00-010-001) and,
(Ref. AMM TASK 21-20-00-410-001)

NOTE: If you replace any compoments in the system you must do the functional test of the galley/lav-
atory air extraction duct (Ref. AMM TASK 21-23-00-720-001) .

5. Close-up
Subtask 21-20-00-410-054-A
A. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install,
(a) the lower sidewall panel 251AX between frames C63 and C65 (Ref. AMM TASK 25-23-44-400-
001) ,
(b) the upper sidewall panel 251BX between frames C63 and C65 (Ref. AMM TASK 25-23-43-400-
001) and,
(c) the cove light panel 251CX between frames C63 and C65 (Ref. AMM TASK 25-23-48-400-001) .
Subtask 21-20-00-410-052-A
B. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install, if removed, the aft lavatory/ies (refer to AMM chapter 25-43).
Subtask 21-20-00-410-053-A
C. Close Access
(1) Make sure that the work area is clean and clear of tools and other items.
(2) Install the cabin ceiling panels between C16 and C65 (Ref. AMM TASK 25-23-41-400-001) .
Subtask 21-20-00-941-052-A

Print Date: December 23, 2016 Page 21 of 22


AIRBUS S.A.S. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
Customer : SVA Manual : AMM
Type : A318/A319/A320/A321 Selected applicability : ALL
Rev. Date : Nov 01, 2016
21-20 - DISTRIBUTION

D. Remove the warning notice(s).


Figure 21-20-00-991-00400-00-A / SHEET 1/1 - Riser Ducts - General Component Location

End of document

Print Date: December 23, 2016 Page 22 of 22