Conductores de cobre con aislante THHN a 75C con factor de carga 100%
V=3,5% Capacidad
AWG o Cos R (/m) X(/m) de corriente
MCM
1 0.95 0.9 0.85 0.8 en Ampere
4 1484 1487 1535 1594 1663 1.02E-03 1.57E-04 91
N 2 2430 2373 2421 2492 2578 6.23E-04 1.48E-04 121
N 2/0 4616 4258 4245 4288 4363 3.28E-04 1.41E-04 188
N 4/0 7459 6443 6268 6214 6221 2.03E-04 1.35E-04 246
N 250 8855 7401 7117 6995 6952 1.71E-04 1.35E-04 280
350 12113 9484 8928 8639 8478 1.25E-04 1.31E-04 342
N 500 17013 12161 11142 10583 10231 8.90E-05 1.28E-04 421
Conductores de cobre con aislante THHN a 75C con factor de carga 100%
K Capacidad
AWG o Cos R (/m) X(/m) de corriente
MCM
1 0.95 0.9 0.85 0.8 en Ampere
4 0.002357618 0.002353031 0.00228004 0.002195145 0.002103828 1.02E-03 1.57E-04 91
N 2 0.001439996 0.001474796 0.001445112 0.001404208 0.001357249 6.23E-04 1.48E-04 121
N 2/0 0.000758136 0.000821977 0.000824385 0.000816103 0.000802053 3.28E-04 1.41E-04 188
N 4/0 0.000469212 0.00054317 0.000558308 0.000563212 0.000562592 2.03E-04 1.35E-04 246
N 250 0.000395248 0.000472904 0.00049174 0.000500342 0.000503421 1.71E-04 1.35E-04 280
350 0.000288924 0.000369009 0.000392019 0.000405096 0.000412814 1.25E-04 1.31E-04 342
N 500 0.000205714 0.000287795 0.000314107 0.000330715 0.000342086 8.90E-05 1.28E-04 421
Conductores de aluminio con aislante THHN a 75C con factor de carga 100%
V=3,5% Capacidad
AWG o Cos R (/m) X(/m) de corriente
MCM
1 0.95 0.9 0.85 0.8 en Ampere
4 906 925 963 1008 1058 1.67E-03 1.57E-04 71
N 2 1442 1450 1499 1560 1630 1.05E-03 1.48E-04 95
N 2/0 2884 2789 2835 2909 3000 5.25E-04 1.41E-04 147
N 4/0 4616 4280 4276 4327 4409 3.28E-04 1.35E-04 193
N 250 5427 4929 4885 4912 4977 2.79E-04 1.35E-04 219
350 7571 6557 6386 6335 6346 2.00E-04 1.31E-04 268
N 500 10739 8706 8288 8085 7986 1.41E-04 1.28E-04 331
Conductores de aluminio con aislante THHN a 75C con factor de carga 100%
K Capacidad
AWG o Cos R (/m) X(/m) de corriente
MCM
1 0.95 0.9 0.85 0.8 en Ampere
4 3.86E-03 0.003780333 0.003632199 0.003472182 0.003305751 1.67E-03 1.57E-04 71
N 2 2.43E-03 0.002412428 0.002333376 0.002243121 0.00214682 1.05E-03 1.48E-04 95
N 2/0 1.21E-03 0.00125457 0.001234191 0.00120314 0.001166328 5.25E-04 1.41E-04 147
N 4/0 7.58E-04 0.000817663 0.000818337 0.000808792 0.000793732 3.28E-04 1.35E-04 193
N 250 6.45E-04 0.000710068 0.000716404 0.000712522 0.000703125 2.79E-04 1.35E-04 219
350 4.62E-04 0.000533711 0.000548034 0.000552442 0.000551498 2.00E-04 1.31E-04 268
N 500 3.26E-04 0.000401992 0.000422277 0.000432873 0.00043824 1.41E-04 1.28E-04 331
Conductores de cobre con aislante THHN a 75C con factor de carga 100%
V=3,5% Capacidad
AWG o Cos R (/m) X(/m) de corriente
MCM
1 0.95 0.9 0.85 0.8 en Ampere
4 1976 1980 2043 2122 2214 1.02E-03 1.57E-04 91
N 2 3235 3159 3224 3318 3433 6.23E-04 1.48E-04 121
N 2/0 6146 5668 5652 5709 5809 3.28E-04 1.41E-04 188
N 4/0 9931 8578 8346 8273 8282 2.03E-04 1.35E-04 246
N 250 11789 9853 9476 9313 9256 1.71E-04 1.35E-04 280
350 16127 12627 11886 11503 11287 1.25E-04 1.31E-04 342
N 500 28474 18986 17077 16020 15339 7.08E-05 1.25E-04 430
Conductores de cobre con aislante THHN a 75C con factor de carga 100%
K Capacidad
AWG o Cos R (/m) X(/m) de corriente
MCM
1 0.95 0.9 0.85 0.8 en Ampere
4 1.77E-03 0.001767401 0.00171256 0.001648793 0.001580208 1.02E-03 1.57E-04 91
N 2 1.08E-03 0.001107748 0.001085437 0.001054712 0.001019444 6.23E-04 1.48E-04 121
N 2/0 5.69E-04 0.000617408 0.000619202 0.00061298 0.000602431 3.28E-04 1.41E-04 188
N 4/0 3.52E-04 0.000407993 0.000419349 0.000423031 0.000422569 2.03E-04 1.35E-04 246
N 250 2.97E-04 0.000355215 0.000369349 0.000375809 0.000378125 1.71E-04 1.35E-04 280
350 2.17E-04 0.000277178 0.000294447 0.000304268 0.000310069 1.25E-04 1.31E-04 342
N 500 1.23E-04 0.000184338 0.000204947 0.000218469 0.000228167 7.08E-05 1.25E-04 430
Caida de tension en Media Tension (13,8Kv)