SINAMICS G120

s Control Unit CU230P-2


Control Unit CU240B/E-2

Product information 10/2017

Supplement for commissioning a reluctance motor


The following information is missing in Chapter 5 (Commissioning) of the Operating
Instructions, Edition 09/2017:
It is only possible to operate a reluctance motor with encoderless vector control.
To commission the converter with reluctance motor, in quick commissioning you must select
one of the following application classes:
"Dynamic Drive Control"
"Expert" with the "Encoderless vector control" control mode
When selecting application class "Standard Drive Control" or control mode "V/f control" it
is not permissible during quick commissioning to configure a reluctance motor.

Supplement to display the "RDY" LED


In Chapter A.1.1 (New and extended functions, firmware version 4.7 SP9) of the Operating
Instructions, Edition 09/2017 the following information is missing:
The converter indicates the "PROFIenergy-Pause" state as follows:
LED RDY "green on": 0.5 s
LED RDY off: 3 s

Incorrect information about a Power Module


The following incorrect information is provided in Chapter A.1.1 (New and extended functions,
firmware version 4.7 SP9) of the Operating Instructions, Edition 09/2017.
[3] Support of the PM240-2 Power module, 3 AC 500 V 690 V, frame size
FSD with reduced power 3 kW 7.5 kW.
Correction:
The Power Module mentioned above does not belong to the SINAMICS G120 converter
family.
SINAMICS G120
s Control Unit CU230P-2
Control Unit CU240B/E-2

Produktinformation 10/2017

Ergnzung zur Inbetriebnahme eines Reluktanzmotors


In Kapitel 5 (Inbetriebnehmen) der Betriebsanleitung, Ausgabe 09/2017, fehlt folgende
Information:
Der Betrieb eines Reluktanzmotors ist nur mit geberloser Vektorregelung mglich.
Um den Umrichter mit Reluktanzmotor in Betrieb nehmen zu knnen, mssen Sie daher in
der Schnellinbetriebnahme eine der folgenden Applikationsklassen whlen:
Dynamic Drive Control
Expert mit der Regelungsart Geberlose Vektorregelung
Bei Wahl der Applikationsklasse Standard Drive Control oder der Regelungsart
U/f-Steuerung ist es whrend der Schnellinbetriebnahme nicht mglich, einen
Reluktanzmotor zu konfigurieren.

Ergnzung zur Anzeige der LED RDY


In Kapitel A.1.1 (Neue und erweiterte Funktionen, Firmware Version 4.7 SP9) der
Betriebsanleitung, Ausgabe 09/2017, fehlt folgende Information:
Der Umrichter zeigt den Zustand "PROFIenergy-Pause" folgendermaen an:
LED RDY "grn ein": 0,5 s
LED RDY aus: 3 s

Falsche Information zu einem Power Module


In Kapitel A.1.1 (Neue und erweiterte Funktionen, Firmware Version 4.7 SP9) der
Betriebsanleitung, Ausgabe 09/2017, steht folgende fehlerhafte Information:
[3] Untersttzung des Power Module PM240-2, 3 AC 500 V 690 V, Baugre
FSD mit reduzierter Leistung 3 kW 7,5 kW.
Richtigstellung:
Das obige Power Module ist kein Bestandteil der Umrichterfamilie SINAMICS G120.
SINAMICS G120
s Control Unit CU230P-2
Control Unit CU240B/E-2

Information produit 10/2017

Informations complmentaires concernant la mise en service d'un moteur rluctance


Dans le chapitre 5 (Mise en service) des Instructions de service, dition 09/2017, il manque
l'information suivante :
Le fonctionnement d'un moteur rluctance n'est possible qu'en mode rgulation vectorielle
sans capteur.
Pour la mise en service du variateur avec un moteur rluctance, il convient alors de
slectionner, dans la mise en service rapide, l'une des classes d'applications suivantes :
"Dynamic Drive Control"
"Expert" avec le type de rgulation "Rgulation vectorielle sans capteur"
En slectionnant la classe d'applications "Standard Drive Control" ou le mode de rgulation
"Commande U/f", il est impossible de configurer un moteur rluctance pendant la mise en
service rapide.

Informations complmentaires concernant l'affichage de la LED "RDY"


Dans le chapitre A.1.1 (Fonctions nouvelles et tendues, firmware version 4.7 SP9) des
Instructions de service, dition 09/2017, il manque l'information suivante :
Le variateur affiche l'tat "Pause PROFIenergy" de la manire suivante :
LED RDY "allume verte" : 0,5 s
LED RDY teinte : 3 s

Informations incorrectes concernant un Power Module


Le chapitre A.1.1 (Fonctions nouvelles et tendues, firmware version 4.7 SP9) des
Instructions de service, dition 09/2017, comporte l'information errone suivante :
[3] Prise en charge du Power Module PM240-2, 3ph. 500 V 690 V, taille
FSD avec puissance rduite 3 kW 7,5 kW.
Correction :
Le Power Module mentionn ci-dessus ne fait pas partie de la famille des variateurs
SINAMICS G120.
SINAMICS G120
s Control Unit CU230P-2
Control Unit CU240B/E-2

Informazione sul prodotto 10/2017

Integrazione per la messa in servizio di un motore a riluttanza


Nel capitolo 5 (Messa in servizio) delle Istruzioni operative, edizione 09/2017, manca la
seguente informazione:
Un motore a riluttanza pu essere fatto funzionare solo con regolazione vettoriale senza
encoder.
Per mettere in funzione il convertitore con un motore a riluttanza si deve pertanto scegliere
nella messa in servizio rapida una delle seguenti classi di applicazione:
"Dynamic Drive Control"
"Esperti" con il tipo di regolazione "Regolazione vettoriale senza encoder"
Selezionando la classe di applicazione "Standard Drive Control" o il tipo di regolazione
"Controllo U/f", durante la messa in servizio rapida non sar possibile configurare un motore
a riluttanza.

Integrazione per la segnalazione del LED "RDY"


Nel capitolo A.1.1 (Funzioni nuove e ampliate, versione firmware 4.7 SP9) delle Istruzioni
operative, edizione 09/2017, manca la seguente informazione:
Il convertitore visualizza lo stato "Pausa PROFIenergy" nel modo seguente:
LED RDY "Verde acceso": 0,5 s
LED RDY spento: 3 s

Informazione errata relativa a un Power Module


Nel capitolo A.1.1 (Funzioni nuove e ampliate, versione firmware 4.7 SP9) delle Istruzioni
operative, edizione 09/2017, si trova la seguente informazione errata:
[3] Supporto del Power Module PM240-2, 3 AC 500 V 690 V, grandezza costruttiva FSD
con potenza ridotta 3 kW 7,5 kW

Correzione:
Il Power Module citato sopra non fa parte della famiglia di convertitori SINAMICS G120.
SINAMICS G120
s Control Unit CU230P-2
Control Unit CU240B/E-2

Informacin de producto 10/2017

Informacin adicional sobre la puesta en marcha de un motor de reluctancia


En el captulo 5 (puesta en marcha) de las instrucciones de servicio, edicin 09/2017, falta la
informacin siguiente:
Los motores de reluctancia solo se pueden utilizar con regulacin vectorial sin encder.
Por eso, para poner en marcha el convertidor con un motor de reluctancia, se debe
seleccionar una de las clases de aplicacin siguientes en la puesta en marcha rpida:
"Dynamic Drive Control"
"Experto" con el tipo de regulacin "Regulacin vectorial sin encder"
Si se selecciona la clase de aplicacin "Standard Drive Control" o el modo de regulacin
"control por U/f", no es posible configurar un motor de reluctancia durante la puesta en
marcha rpida.

Informacin adicional sobre la indicacin del LED "RDY"


En el captulo A.1.1 (funciones nuevas y ampliadas, versin de firmware 4.7 SP9) de las
instrucciones de servicio, edicin 09/2017, falta la informacin siguiente:
El convertidor indica el estado "Pausa PROFIenergy" del siguiente modo:
LED RDY "encendido en verde": 0,5 s
LED RDY apagado: 3 s

Informacin incorrecta sobre un Power Module


En el captulo A.1.1 (funciones nuevas y ampliadas, versin de firmware 4.7 SP9) de las
instrucciones de servicio, edicin 09/2017, aparece la siguiente informacin incorrecta:
[3] Soporte del Power Module PM240-2, 3 AC 500 V690 V, tamao
FSD con potencia reducida 3 kW7,5 kW.
Correccin:
El Power Module mencionado no forma parte de la gama de convertidores SINAMICS G120.
SINAMICS G120
s Control Unit CU230P-2
Control Unit CU240B/E-2

10/2017

2017/09 5


Dynamic Drive Control
Expert

Standard Drive ControlV/f


LEDRDY
2017/09 A.1.1 4.7 SP9

PROFIenergy
LED RDY0.5 s
LED RDY 3 s

2017/09 A.1.1 4.7 SP9

[3] PM240-23 AC 500 V 690 V


FSD 3 kW 7.5 kW

SINAMICS G120

Вам также может понравиться