CARACTERISTICAS DE PARARRAYOS

Tension Tens. Max. Sobretension


Nominal Operacin con onda Tensin residual para onda de 10 kA, 8/20 ms Sobretensiones de
Arrester Rating MCOV 1,2/50 ms Maniobra
(kV-rms) (kV-rms) kV-Crest 1,5 KA 3,0 KA 5 kA 10 kA 20 KA 40 KA KV
3.0 2.6 11.0 8.2 8.7 9.2 10.0 11.3 13.6 7.4
6.0 5.1 22.0 16.4 17.4 18.4 20.0 22.5 27.1 14.7
9.0 7.7 33.0 24.5 26.1 27.5 25.0 33.8 40.7 22.1
10.0 8.4 36.3 27.0 28.7 30.3 33.0 37.2 44.7 24.3
12.0 10.2 44.0 32.7 34.7 36.7 40.0 45.0 54.2 29.4
15.0 12.7 55.0 40.9 43.4 45.9 50.0 56.3 67.8 36.8
18.0 15.3 66.0 49.1 52.1 55.1 60.0 67.6 81.4 44.1
21.0 17.0 77.0 57.3 60.8 64.3 70.0 78.8 94.9 51.5
24.0 19.5 86.6 64.4 68.4 72.3 78.8 88.7 106.8 57.9
27.0 22.0 97.9 72.8 77.3 81.7 89.0 100.2 120.7 65.5
30.0 24.4 108.9 81.0 86.0 90.9 99.0 115.5 134.2 72.8
36.0 29.0 128.3 95.4 101.3 107.0 116.6 131.3 158.1 85.8
Fuente : Datos obtenidos de pararrayos Tipo AZL de McGraw-Edison
SELECCIN DE PARARRAYOS

CALCULO DEL PARARRAYOS PARA UN SISTEMA EN 22.9 KV


VALOR
TENSION NOMINAL DEL SISTEMA = Vn (kV) 22.9
TENSION MAXIMA DEL SISTEMA (entre fases) = Us (kV r.m.s). 25.0
TENSION MAXIMA DE LOS EQUIPOS = Um (kV r.m.s). AISLADO
FACTOR DE MAYOR VARIACION DE TENSION = Ft (pu). 1.05

FACTOR DE FALLA A TIERRA PARA UN SISTEMA CON NEUTRO RIGIDO A TIERRA (04 HILOS) = K (pu) 1.4

FACTOR DE FALLA A TIERRA PARA UN SISTEMA NEUTRO AISLADO (03 HILOS) = K (pu) 1.73
MAXIMA DURACION DE LA SOBRETENSION TEMPORARIA = t (seg). 10
FACTOR DE SOBRETENSION TEMPORAL PARA UNA FALLA DE 10 Seg. = Ktov 1.075
10 kA/Ur (valores que dependen del fabricante) 2.667
ALTITUD DE INSTALACION (m.sn.m.) 2600
NIVEL DE AISLAMIENTO DEL EQUIPAMIENTO = BIL (kVp) 125
NIVEL DE CONTAMINACION (mm/kV). 25
CORRIENTE NOMINAL DE DESCARGA REQUERIDA = In (kA). 10.00
DIAMETRO DEL RESITOR DE OM APROPIADO PARA In = 10 kA (mm) . 40.00
MAXIMA CORRIENTE DE CORTOCIRCUITO = In (kA). 20.00

CALCULO DEL MCOV

DESCRIPCION VALOR

TENSION MAXIMA DE OPERACIN PERMANENTE MINIMA REQUERIDA PARA UN SISTEMA CON NEUTRO
15.16
RIGIDO A TIERRA = MCOV (kV ef) = Uc min
TENSION MAXIMA DE OPERACIN PERMANENTE MINIMA REQUERIDA PARA UN SISTEMA CON NEUTRO
25.00
AISLADO = MCOV (kV ef) = Uc min

CALCULO DE LA TENSION NOMINAL DEL PARARRAYOS (Ur)

DESCRIPCION VALOR

TENSION NOMINAL DEL PARARRAYOS PARA UN SISTEMA CON NEUTRO RIGIDO A TIERRA = Ur1,min (kV ef) 18.94

TENSION NOMINAL DEL PARARRAYOS PARA UN SISTEMA CON NEUTRO RIGIDO A TIERRA = Ur2,min (kV ef) 18.80

TENSION NOMINAL DEL PARARRAYOS PARA UN SISTEMA AISLADO = Ur1, min (kV ef) 31.25
TENSION NOMINAL DEL PARARRAYOS SELECCIONADA PARA UN SISTEMA CON NEUTRO RIGIDO A
30.00
TIERRA = Ur = mx {Ur1, Ur2} redondeada al numero inmediato superior divisible por tres.
TENSION NOMINAL DEL PARARRAYOS SELECCIONADA PARA UN SISTEMA AISLADO = Ur = mx {Ur1, Ur2}
31.25
redondeada al numero inmediato superior divisible por tres.
TENSION MAXIMA DE OPERACIN PERMANENTE REDEFINIDA PARA UN SISTEMA CON NEUTRO RIGIDO A
24.00
TIERRA = MCOV (kV ef) = Uc
TENSION MAXIMA DE OPERACIN PERMANENTE REDEFINIDA PARA UN SISTEMA AISLADO = MCOV (kV ef)
25.00
= Uc

SOBRETENSIONES TEMPORARIAS PARA UN SISTEMA CON NEUTRO RIGIDO A TIERRA = UTOVP (kV) 20.21

SOBRETENSIONES TEMPORARIAS PARA UN SISTEMA AISLADO = UTOVP (kV) 20.21

SELECCIN DE LA CLASE DE DESCARGA DE LINEAS


(LA EXIGENCIA DE LOS DESCARGADORES AUMENTA AL IR DE LA CLASE UNO A LA CINCO)
DESCRIPCION VALOR

NIVEL DE PROTECCION AL IMPULSO ATMOSFERICO (10 kA, 8/20 us


) 80.01
NIVEL DE PROTECCION AL IMPULSO DE MANIOBRA (0,5 kA, 30/60 us
) 80.00
NIVEL DE PROTECCION AL IMPULSO ESCARPADO DE CORRIENTE ( 10 kA, 1/2 us
) 85.00
NIVEL BASICO DE AISLAMIENTO (BIL/10 kA, 8/20 us
) 1.56
DISTANCIA DISRUPTIVA (mm). 625.00
DISTANCIA DISRUPTIVA (mm). 625.00