TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

1. Location : 1110 KV / 6.9 KV Switch yard

Feeder Name : 6.3 MVA Trafo.

2. Equipment Details :

Make Crompton Greaves


Type 120 SFM-32B
SI.No 34008C
Rated Voltage 145 KV
TESTED BY WITNESSED BY
SHEET : 2 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

Rated Normal Current 1250


Frequency 50 Hz
Year 2011

3. General Inspection : OK

4. IR Test:

Measured Values (M)


Ref Applied Voltage (V)
R Y B
Pole to Pole 5 KV 517 717 515
TESTED BY WITNESSED BY
SHEET : 3 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

Pole to Pole 5 KV 558 720 520


Pole to Earth 5 KV 415 516 489

5. Contact Resistance Test:

Ref Applied Current (A) Measured Resistance( )


R 200 89.2
Y 200 80.3
B 200 96.9

TESTED BY WITNESSED BY
SHEET : 4 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

6. Time Interval Test:

Ref R Y B
Close 64 63 64
Open 23 24 24
Close-Open 22 22 21

TESTED BY WITNESSED BY
SHEET : 5 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

TESTED BY WITNESSED BY
SHEET : 6 OF: 6

TEST REPORT FOR CIRCUIT BREAKER PAGE :


DATE : 24.03.2016
Customer :
Project:

7. Operational Checks : (Whether Operational Checks OK / Not OK / Not Available)

1 Manual (close/open) OK
2 Breaker Mechanical open & close indication properly working OK
3 Breaker Spring Charging Indication properly working OK

8. Comments : Nil

9. Remarks : Breaker found healthy.

TESTED BY WITNESSED BY